Building Codes and Inspections/Questions Answered by Expert Fred Weldin

SubjectDate Asked
Primary AC drain3/17/2012
  Q: Does the plumbing code allow the use of an auxiliary AC condensation pump as the primary in new ...
  A: Elaine: First, the "cutoff" should be in the pump housing, higher than the switch that operates the ...
Primary AC drain3/15/2012
  Q: Does the plumbing code allow the use of an auxiliary AC condensation pump as the primary in new ...
  A: Elaine: The Mechanical Code does not specifically prohibit condensate pumps, but it does require ...
LP furnace in Garage11/16/2011
  Q: Fred You had answered a question some time ago about a gas furnace in a garage. To expand on that ...
  A: Wayne: A closet is not required, but protection from the vehicle(s) is. If there's no protection ...
Asbestos Abatement and Insulation Career advice11/15/2011
  Q: I'm not sure if you can help me but its worth a shot here, and really I just need ...
  A: Dave: I'm not involved with asbestos abatement, but I spoke with a friend who's an Industrial ...
Altering Foundation10/9/2011
  Q: I have a customer that, while I stopped the job due to conflicts with contracted work, hired an ...
  A: I don't do structural/architectural. However, I have worked as a contractor, and interfaced with ...
vent fan7/7/2011
  Q: does my vent fan in the bathroom have to run from the outside?
  A: TD: Yes (I assume you mean "to the outside"). Furthermore, many jurisdictions require round metal ...
Gas fired hot water heater flue7/1/2011
  Q: i live in mexico and am building a wood frame house. Im going to install a rheem 152ltr gas fired ...
  A: Ryan: Forgive me, but I was trying to be polite. Please look at this from my perspective: Here's a ...
stoves& vent a hood12/31/2010
  Q: We are installing a new kitchen in are organization, what are the codes for installing new vent a ...
  A: Ray: NFPA 96 is the national Standard. You'll need a LOT: Suppression, hood exhaust, automatic gas ...
Tennat sleeping in the furnace room12/27/2010
  Q: My father passed away and I have been able to rent out his house. I plan to sell as soon as there's ...
  A: Vicky: Fred
international mechancial code hanging furance11/4/2010
  Q: I just built a 23,000 foot building with 18 foot ceilings 1200 foot bays I hung heil air handler ...
  A: Gary: I signed on here to help homeowners with problems, and I do that for free. Contact me through ...
direct vent water heater11/1/2010
  Q: are direct vent water heater legal to install in a garage for the city of los angeles. i h have 2 ...
  A: Joe: I signed on here to help homeowners with problems. I can't envision a home with three water ...
asbestos in heating of a tract house9/7/2010
  Q: The house was built in 1969 in a tract of Camarillo, CA. The furnace was replaced in the 2000 to ...
  A: Eileen: Fred
boiler room ventilation8/10/2010
  Q: I’m currently having my basement renovated and a new steam boiler put in. The contractor will frame ...
  A: Alex: Forgive me, but what are you doing heating with steam in this day and age? It's the least ...
water heater/boiler7/28/2010
  Q: the home i live in is VERY old and the boiler is pretty old with some exposed wires and the water ...
  A: Samantha: Hard to say. It would be OK so long as the appliances (to include all controls and access ...
gas hot water tank6/4/2010
  Q: how much clearance do you need around a gas hot water tank mine is in a little closet it is 50, 000 ...
  A: Jay: Good question! Fred
plumbing5/14/2010
  Q: Is it legal to drill a 3/4 hole in a 4 copper pipe and to sweat a 3/4 line to that hole instead of ...
  A: Rich: Fred
Bathroom venting3/10/2010
  Q: what are the codes for residential bathroom exhaust vent material. Is vinyl flex still allowed.
  A: Patrick: The toilet exhaust is a duct like any other in the home. Only approved materials are ...
gas water heater and furnace3/1/2010
  Q: My home has the gas furnace and the gas water heater in the same utility room (5' x 5') with a ...
  A: Addison: Fred
gas water heater venting2/18/2010
  Q: I have a 40 gal gas fired Rheem water heater, 5 yrs old. It is currently vented with 3 inch dia ...
  A: Adam: Fred
help1/28/2010
  Q: fred, i recently purchased a 90+% gas furnace that has a concentric direct vent. i'm thinking of ...
  A: Shaun: Fred
Fart Fan Duct Code10/27/2009
  Q: Fredericksburg, VA: Rebuilding a house struck by fire. The fart fan is 3", hard pipe running to a ...
  A: Roger: Fred
gas h2o htr install8/17/2009
  Q: 1. I have a gas (LP) tankless water heater to install. I have no problem with the install itself but ...
  A: Don: I respect your expertise, but this is specialized: Are you equipped to measure manifold ...
gas h2o htr install8/17/2009
  Q: 1. I have a gas (LP) tankless water heater to install. I have no problem with the install itself but ...
  A: Don: I must advise against DIY gas water heater installation; too much can go wrong, and the risks ...
residential codes re windows8/16/2009
  Q: a friend of mine that lives out by dekalb was shopping for new windows for his house, one of the ...
  A: Debbie: I was told the same thing when I built a house in 1993. Just looked through the 2003 IRC, ...
Vent for gas stove?5/18/2009
  Q: Does a residential gas stove require some sort of venting system? The builder of our new home ...
  A: Michael: You must be like me: Our kitchen is only there for resale. Seriously, we don't do much ...
Hot Water Heater Exhaust5/13/2009
  Q: My hot water tank sits on the opposite side of my homes basement from where the water demand is in ...
  A: Doug: I like your idea, it'll save you some money on gas. Tjernlund is one manufacturer offering a ...
Installing High Eff. Gas HWH with power vent in crawl space4/23/2009
  Q: Is it legal to install a high efficincy power vent gas hot water heater in a crawl space. Note the ...
  A: Dave: This goes to access: You must have a 22" wide, 30" high passageway that's no longer than 20 ...
Mechanical issues...7/21/2008
  Q: Weldin, I'm buying a new home in Houston, TX. Before sheetrock was installed, I saw some air ducts ...
  A: Duke:You'll have to go to your builder (you might also try the local mechanical Inspector); the ...
Mechanical issues...7/17/2008
  Q: Weldin, I'm buying a new home in Houston, TX. Before sheetrock was installed, I saw some air ducts ...
  A: Duke: Which came first, the duct or the wiring? I don't know of any Code requirement that would ...
gas furnace in the garage6/11/2008
  Q: I am about to by a new house and the home inspector I highered had some problems with the gas ...
  A: Tamara: There must be a tightly sealed return duct from the furnace to the return grille in the ...
Fuel gas line to the garage6/8/2008
  Q: I'm planning to install a gas heater in the garage in the future. For now we are re-doing the back ...
  A: Michael: You're going to need a contractor at some point, so it might be good to get one involved ...
followup email6/2/2008
  Q: how many air ducts needed per room Question We have just replaced 1 unit last summer that serves ...
  A: Michelle: Still working on askweldin, spent some time today. Using Yahoo hosting/composing. It'll ...
Gas Hot Water - in Hall Closet - vent options6/2/2008
  Q: We just purchased a 14 year old home and replaced the old gas hot water heater with a new Bradford ...
  A: Erin: It is a concern, but the REAL unsafe condition occurs when there's another gas appliance or ...
Ventilation of hot water heater closet5/30/2008
  Q: Fred, I have a one story house on a slab where the 40 galllon gas hot water heater is in a closet. ...
  A: George: One opening into the attic is permitted. Free Area must be at least 14 sq. inches; if you ...
Gas Hot Water - in Hall Closet - vent options5/30/2008
  Q: We just purchased a 14 year old home and replaced the old gas hot water heater with a new Bradford ...
  A: Erin: The openings must be within 12" of the floor and within 12" of the ceiling. Minimum size of ...
gas furnace venting5/20/2008
  Q: have an old gas furnace to replace in my home has single wall flue pipe can the new furnaces 80% be ...
  A: Bobby: Usually, see Installation Instructions for your make and model. I'm surprised you're even ...
Closet for hot water heater in garage5/13/2008
  Q: I am installing a closet around my hot water heater in my garage. I am trying to find out the ...
  A: Tommy: No luck: The outdoor opening must be high either way (single opening or indoor/outdoor ...
Closet for hot water heater in garage5/13/2008
  Q: I am installing a closet around my hot water heater in my garage. I am trying to find out the ...
  A: Tommy:One opening required (we're using the "One-permanent-opening method" under 2006 International ...
GAS HEAT VENTILATION4/25/2008
  Q: I HAVE PROPANE HEAT IN MY RAISED RANCH WITH THE HEATER BEING IN THE CLOSET OF THE LOWER LEVEL. I ...
  A: Erik: There's no provision in the 2006 International Fuel Gas Code for louvered doors. You'll have ...
Closet for hot water heater in garage4/23/2008
  Q: I am installing a closet around my hot water heater in my garage. I am trying to find out the ...
  A: Tommy: Send me a follow up. Is it a gas water heater? Oil? Electric? That makes a difference. If ...
Residential Gas Line4/10/2008
  Q: Would a low pressure residential gas line be considered defective if a test gauge left on for a week ...
  A: Tim: I have no experience testing gas lines at 40X operating pressure, but I do know the huge ...
Residential Gas Line4/8/2008
  Q: Would a low pressure residential gas line be considered defective if a test gauge left on for a week ...
  A: Tim: The test pressure must be at least 3 psig (about eight times working pressure), test duration ...
a/c condensate drain3/14/2008
  Q: I keep getting mixed information on air conditioning condensate drain legalities. I live in Fort ...
  A: Charles: I can tell you what the code says, but your local plumbing inspector is the only one who ...
exhaust line3/3/2008
  Q: I own a condominium unit in a 4 story building in Chicago. The first floor is composed of 3 ...
  A: Mark: I assume it's a kitchen hood exhaust duct. That's governed by NFPA 96, which requires a wall ...
flue pipe2/22/2008
  Q: Do you have to screw section together if less than 2ft from 90 to chimney?
  A: Ron: I assume you're working with round single wall metal duct. If so, this becomes a duct ...

All Questions in This Category

Building Codes and Inspections

All Answers


Answers by Expert:


Ask Experts

Volunteer


Fred Weldin

Top Expert on this page

Expertise

All aspects of International Mechanical Code, International Energy Conservation Code and International Fuel Gas Code.

Experience

I now troubleshoot existing H&AC installations and design H&AC systems and oversee their installations. I have 23 years experience as a H&AC contractor, and I've worked with the tools as a plumber-pipefitter. I'm certified by ICC as a Commercial Mechanical Inspector.

Organizations
ASHRAE, ICC, NSPE.

Education/Credentials
B of ME, numerous factory schools (York, Honeywell, etc.) and Code seminars.

©2012 About.com, a part of The New York Times Company. All rights reserved.