Question
I am planning on installing a wood stove in my basement. I am hopeing to purchase the type that has a built in blower that I can tie into the return air plenum of my furnace. My house was built in the sixties and has a masonary chimney thats lined with clay. I have inspected the liner as best as I can and it looks to be in good shape. I also did a smoke test by burning a bunch of paper and cardboard in the access opening at the floor in my basement and did not smell smoke anywhere in the house including the attick. The stack on the wood burner im looking at is six inch and the clay liner in 8" x 8". There is also an exhaust from my natural gas furnace tied into the chimney. I was hoping to core a hole into the chimney in the basement and tie the stack in above where my furnace stack ties in. I have the acceptable clearences from any combustible source where I plan to tie in. I do not plan on running the furnace and the woodburner at the same time so there shouldnt be any issues with to much being vented out at the same time. My question is, is it safe to use that chimney with the clay liner to vent my wood stove or should I install a stainless steel liner? Also how would you recommend tieing the metal stack from my woodburner into the masonary chimney. Would appreciate any info

Answer
Hi Mike,

You can NOT use the same flue to vent a wood burning stove and a furnace.

If you wish to install a wood burning furnace and tie it into your existing duct work, you will need to install a separate chimney system.

Alternatively, you could install a new flue for the furnace and use this flue system AFTER a LEVEL 2 Inspection is completed by a CSIA Certified Chimney Sweep.  A Level 2 inspection involves checking EACH joint on the interior of the flue with a video camera or other means.  EACH joint must be checked when changing fuels in a flue.  If the flue is interior, you must have 2" clearance to all combustibles from the chimney.  If the flue is exterior, you must have 1" clearance to all combustibles from the chimney.

If the flue is defective (broken flue tiles or voids between flue tiles) you will need a UL Listed lining system installed.  A UL Lining system typically, for solid fuel, requires insulation to be installed and for the lining system to be no less in diameter than the outlet of the appliance.  With an 8" x 8" existing flue liner, this will be impossible to achieve, so I would recommend that you simply install a separate, new flue system for this appliance.

I recommend you contact a local CSIA Certified Chimney Sweep to do some on-site diagnosis of your situation and to give you some specific advisement.

You can find a CSIA Certified Chimney Sweep at www.csia.org.

Thanks for using AllExperts.Com and good luck with your project.

Sincerely,
A. Bart Ogden, President
Home Safe Hearth %26 Chimney, Inc.
Wichita, KS
Voice 316-265-9828
Fax 316-265-9890
www.HomeSafeKS.com

CSIA Certified Chimney Sweep #2653
CSIA Certified Dryer Exhaust Technician #10
NFI Certified Wood Specialist
NFI Certified Gas Specialist
NFI Certified Pellet Specialist
NFI Master Hearth Professional
NCSG Technical Advisory Council Member

Advice given is general in nature. Local laws and ordinances may govern and/or supersede the information and recommendations provided. Final determinations are the responsibility of a local professional with first-hand knowledge of the situation, and the AHJ.

Note: Dissemination, distribution or copying of any part of this email or its attachments is prohibited without the expressed permission of the sender.  

Chimney & Fireplaces

All Answers


Answers by Expert:


Ask Experts

Volunteer


Bart Ogden

Expertise

I can answer questions related to chimney and fireplace cleaning, construction and repair as well as questions related to the performance of chimneys and fireplaces. I can also answer questions related to clothes dryer vent cleaning and repair. Additionally, I can field questions related to masonry repair.

Experience


Experience in the area:
28 years experience in the chimney service/installation/repair field
President, Home Safe Hearth & Chimney, Inc. Wichita, Kansas

Professional Organizations:
Member, National Chimney Sweep Guild (NCSG)
Member, Hearth, Patio & Barbecue Association (HPBA)
Member, Kansas Guild of Professional Chimney Sweeps (KGPCS)
Member, Midwest Chimney Safety Council (MCSC)
Member, Kansas Association of Real Estate Inspectors (KAREI)
Past At-Large Director of the National Chimney Sweep Guild
Past At-Large Director of the Chimney Safety Institute of America
Past Secretary, National Chimney Sweep Guild
Past Secretary, Chimney Safety Institute of America
Member, National Chimney Sweep Guild Technical Advisory Council
Member, Chimney Safety Institute of America Certification Committee
Past Chairman, CSIA Chimney Safety Education Brochures Committee
Past Chairman, NCSG Nomination Committee

Publications:
SWEEPING Magazine, The Journal of Chimney & Venting Technoloty, A Publication of the National Chimney Sweep Guild
SNEWS, The Chimney Sweep News
THE KANSAS SWEEP, The Voice of the KS Guild of Professional Chimney Sweeps

Education/Credentials:
BA, Wichita State University
C.S.I.A. Certified Chimney Sweep
C.S.I.A. Certified Dryer Exhaust Technician
N.F.I. Woodburning Specialist
N.F.I. Gas Specialist
Chimney Diagnosis & Documentation Seminar
Ahren's Masonry Restoration School Graduate
Advanced Gas Certification
Master Gas Certification
Licensed Mechanical Contractor
Pellet Appliance Specialist
Venting Design Specialist
Dale Carnegie Course Graduate

Awards and Honors:
Superior Dealer Award, Ventinox Chimney Lining Systems

©2012 About.com, a part of The New York Times Company. All rights reserved.