Question
We recently installed a new Xtrordinair fireplace (36CFR)and noticed that after about 30 minutes of use, the marble surround at the top center of the fireplace box is scorched. We immediately turned it off.  Any ideas what could cause this. Thank you for your help.

Answer
Rocky,

The manufacture requires that the unit be surrounded with cement board first, drywall second and any noncombustible material provided it doesn't protrude more than 3/4" inches from the glass. If your marble is protruding more than 3/4" inches from the glass, that's why it's scorched. If a mastic was used to adhere the marble to the drywall, you can expect a foul odor and toxic fumes to be the next issue. If the marble doesn't protrude more than 3/4" inches from the glass, contact the manufacture. Cut and paste the link below to see if your unit was involved in this recall as well. Good luck.

http://www.travisproducts.com/Notice/Safety_Notice.html

Chimney & Fireplaces

All Answers


Answers by Expert:


Ask Experts

Volunteer


Randy Brooks

Expertise

Inspection of Masonry, Pre-cast Tilt-up, and Factory Built Fireplaces as well as Free Standing & Insert, Gas, and Wood Appliances. We also provide Hearth Fire Loss Investigations, Litigation Support, Consulting Services, Flue Sweeping, Installation and Repair. Additionally, I’ve been a chimney sweep for 23 years, service and install hearth appliances as well as being recognized by the Superior Court of California as an expert witness.

Experience

Brooks Chimney Sweeping Since 1989 Ojai, CA Owner / President www.brooks-hearth.com

Organizations
NCSG, MEMBER,(National Chimney Sweep Guild), Member since 1990, Board of Directors representing Region 6, (CA, NV, AZ, UT, OR, WA, ID, WY, MT, AK and HI,) 2004-2011, ethics committee chair, 2004-2005, executive committee member, Vice President, 2006-2008, President, 2008-2011. CSIA, BOD (Chimney Safety Institute of America,) Board of Directors, ethics committee chair, 2004-2005, executive committee member, Secretary, 2005-2006, Vice President, 2006-2008, President, 2008-2011. HPBA, MEMBER, (Hearth, Patio, & BBQ Association,) since 2002. NFPA Member, (National Fire Protection Association) Since 2009. Technical Committee member for the 211 Standard.

Education/Credentials
California State Licensed Contractor, C61-D34, #750710. http://www2.cslb.ca.gov C.S.I.A., (Chimney Safety Institute of America,) Certified Chimney Sweep, #2580. Held since 1990 re-certified in ‘93, ‘96, ‘99, ‘02, ‘05, '08,'11. http://www.csia.org F.I.R.E. (Fireplace Investigation, Research & Education Service,) Certified Inspector, #FP-006. Held since 2000, re-certified in ’03, ‘06. http://www.f-i-r-e-service.com Fireplace Investigation, Research & Education Service,) Advance Expert Consulting & Witness, certificate, ’05 N.F.I. (National Fireplace Institute,) Certified Gas & Wood-Burning Specialist, #133851. Held since 2002, re-certified in '05,‘08. http://nficertified.org

©2012 About.com, a part of The New York Times Company. All rights reserved.