Dear Sir,

Presently we are constructing a 02 storey building of size 44m X 10m. All around the building, a continuous RCC sloping sunshade has been planned. The RCC sunshade will be emerging from the bottom of the RCC roof beam ( 10mm dia Fe500 steel @ 150mm c/c)

While doing the ground floor roof concreting, we thought to do the sunshade later and we left the dowel bars in the roof beam .i.e 10mm dia Fe500 steel @ 150mm c/c. We have also plans to apply concrete bonding agents in the market for bonding old and new concrete while doing the sunshade later. However, the joint will be in junction of beam and sunshade throughout.

Whether what we have done are right ? we are now going to make the first floor slab also and plan to follow the same. Please advise us whether monolithic casting of roof beam and sunshade are essential ? whether we could go ahead with a concrete joint at beam/sunshade junction with the help of bonding chemicals in market?   

regards,

Geoffrey,
India.

Answer
Hi Babal,

Yes, what you have proposed is fine. Just ensure that before you cast the projecting sun-shade, you scabble the surface of the old concrete to expose the aggregate- after that you can apply the bonding agent and cast the new concrete.

An alternative and even better method is to bend the canopy bars at right angles, running along the outside cover of the 1st floor beam, and enclose these bars in polystyrene to a depth (thickness) of say 15-20mm (the bars and the polystyrene will be adjacent to the shuttering of the beam, outside the main beam rebar/links). The height of the polystyrene insert will be the same as the thickness of the canopy. Then, when you remove the side shutters of the beam, and after say 14 days, you can chisel out the polystyrene and straighten out the rebar and you will get a 20mm rebate within the beam, which will form an excellent shear key for the cantilevering canopy.

Civil Engineering

All Answers


Answers by Expert:


Ask Experts

Volunteer


Arshad Khan

Expertise

I can answer any questions to do with civil and structural engineering consultancy and construction industry in East Africa and the Middle East, and specifically with the analysis and design of reinforced concrete structures. My particular expertise is in the aseismic design and optimisation of tall buildings.

Experience

Employment history: 40 years in Construction and consultancy in the UK, Kenya, Tanzania, Uganda, Ethiopia, Eritrea, South Africa, Somalia, Zambia, Austria, Bahrain, Kuwait, Doha and the U.A.E.

Organizations
.Fellow of Institution of Structural Engineers (UK) .Fellow of Institution of Civil Engineers(UK) .Member of the Institution of Engineers, Kenya .Registered Engineer, ERB, Kenya .Member of the Architectural Association of Kenya (Engineers Chapter) .Chartered Engineer (UK)

Publications
•1984: International Conference on the Art and Practice of Structural Design, London •1994: 3rd Int. Kerensky Conference in Structural Engineering, Singapore •2008: International Conference on High-Rise Towers, Abu Dhabi •2013: IEK International Conference, Kisumu, Kenya

Education/Credentials
BSc, 1st Class Hons, in Building Engineering, University of Bath, UK MSc in Concrete Structures and Technology, University of London. Diploma of Imperial College, UK.

Awards and Honors
•Science Congress Special Award (for 2-seater Hovercraft - 1968) •Institution of Civil Engineers Award for outstanding performance at Bath University (1975) •Concrete Society Postgraduate study Bursary Award (1976) •Consular Representative for British High Commission, Nairobi. (1995 to 1998) •Examiner for Institution of Civil Engineers Professional Interviews, Nairobi. (1997 to 1998) •Branch Representative in Vienna for PI assessment for Inst. of Struct. Engrs. (1999 to 2010)

©2016 About.com. All rights reserved.