| Subject | Date Asked |
|
| motor maintenance | 11/26/2009 |
Q: does megger testing a 3 phase motor at 6 month intervals for planned maintenance damage the motor ... A: A megger is a non-destructive test, and can be used as often as needed. As for maintenance, This ...
|
| Motor won't start | 11/23/2009 |
Q: I have a Leeson 1hp 220v. motor, #110090 on an air compressor. I did not have 220 in my garage so ... A: First you need to check the actual voltage at the pressure switch. Next check to make sure the head ...
|
| drum switch and motor connections | 11/22/2009 |
Q: I am trying to wire a Bremas drum switch (see picture attached) to a Baldor 3/4 hp motor (model DL ... A: Unfortunately, I do not have details of how the Bremas switch makes up the contacts internally, or I ...
|
| Power cord replacement for AJAX motor | 11/20/2009 |
Q: I have an AJAX Model FZM 7184TCFR7058DL, 3 HP, 1750 RPM model. I need to replace the power cord and ... A: Ajax is a old and obsolete motor to the best of my knowledge. I have no actual wiring diagram, so I ...
|
| Power cord replacement for AJAX motor | 11/19/2009 |
Q: I have an AJAX Model FZM 7184TCFR7058DL, 3 HP, 1750 RPM model. I need to replace the power cord and ... A: From what I can gather, this is a single phase motor, that is connected for 230 volts. The numbers ...
|
| John S Barnes Corp. motor connections | 11/5/2009 |
Q: Motor details:-cat# 110578.000 model c6c17nz2d HP1/3 ... A: All pumps both liquid and hydraulic that I have worked on are set in one direction. If this motor ...
|
| wiring a 220 volt Doerr motor | 11/3/2009 |
Q: I was given a Doerr motor to replace the 3-phase motor on an old engine lathe (Sheldon) that I just ... A: I have been away this weekend, but I haven't forgot you. I will try to have a answer for you this ...
|
| the motor on my 10 inch Craftsman saw quit running | 10/28/2009 |
Q: I was ripping down 2x4's into strips using my 10 inch Craftsman table saw when while sawing, the ... A: Check for voltage at the motor. If the motor has a manual overload, see if it is tripped. Also check ...
|
| wiring a 220 volt Doerr motor | 10/28/2009 |
Q: I was given a Doerr motor to replace the 3-phase motor on an old engine lathe (Sheldon) that I just ... A: Les, all I can supply is this NEMA standard wiring diagram, ...
|
| Reverse an Electric motor | 10/23/2009 |
Q: I have a compressor motor that is rotating the wrong way for it to work properly.I need it to run ... A: Most, but not all compressor motors come from the factory with set rotation. This means that it ...
|
| Motor fuses | 10/22/2009 |
Q: I'm having a problem with a three phase motor that blows fuses at the disconnect switch. It's a 230 ... A: Have you checked the voltage and amperage while the motor is running? Is the motor subject to ...
|
| electric motor | 10/21/2009 |
Q: I have a doerr emerson 1/2 hp Lr22132 and it does not have a plate with diagram or marked wires, it ... A: Answer Using this diagram here, http://farm1.static.flickr.com/114/253735324_c7d4920bc5_o.jpg use ...
|
| Wiring Furnas Drum switch | 10/19/2009 |
Q: I have a SouthBend 9inch lathe, and I replaced the original motor with a US motors 1/3 hp motor ... A: Using this diagram here, http://farm1.static.flickr.com/114/253735324_c7d4920bc5_o.jpg use these ...
|
| Fix the wiring on a Sears 6 inch Bench Grinder | 9/30/2009 |
Q: I am hoping you can help me. My neighbor has a Sears 110V 6 inch Bench Grinder (Model 319.190620). ... A: First, to make it easy, label the white wires #1 and #4, makes no difference which one is which. Now ...
|
| 3 phase motor connections | 9/17/2009 |
Q: We have problems figuring out when we connect 9 lead and 12 lead motors if we should be using the ... A: Almost all nine lead motors are connected using the wye. Delta connected is the same for high ...
|
| single phase motor | 9/16/2009 |
Q: i have a single phase 240v 3 wire spa pump motor which has a single capacitor (i believe for start ... A: Have the capacitor checked, and if bad replace. If it is a run, (made from aluminum,) and after ...
|
| electric motor insulation testing | 8/18/2009 |
Q: I repair pool and spa motors and pumps and wonder if an insulation tester ( Megger) is of any real ... A: The megger is the first diagnostic tool that I use on every motor. If you can afford it, get it!. As ...
|
| Electric motor questions | 8/12/2009 |
Q: I am building a phase converter and I need a 10HP 3 phase motor. I found a motor of a large frame ... A: To answer your question, I will need a few details and measurements. First, what is the RPM of the ...
|
| missing capacitors | 8/11/2009 |
Q: I have a air compressor with a baldor 5hp motor. the capacitor box on top of box was missing. All I ... A: Here is the factory diagram, and the capacitor sizes from Baldor. ...
|
| Dayton Motor - no wiring codes | 8/4/2009 |
Q: Dayton model #4K641, 0.5 hp, CI, 1 ph, dual voltage, double shaft. Great old bench grinder motor, ... A: Bob, what you are describing leads me to believe you have a dead spot in the starting switch. Bleed ...
|
| dayton motor | 8/4/2009 |
Q: my dad gave me an air compressor with a dayton 115v/220v motor on it, he had it wired for 220 but i ... A: Remove the belt from the motor, recheck your connection and run the motor. You really need a amp ...
|
| Dayton Motor - no wiring codes | 8/2/2009 |
Q: Dayton model #4K641, 0.5 hp, CI, 1 ph, dual voltage, double shaft. Great old bench grinder motor, ... A: Bob, the trick here is determining the start and run windings. As you can see here in this diagram, ...
|
| Capacitor for GE type KC 1/4 HP motor | 7/30/2009 |
Q: Mr. Jones My ceiling mounted whole house fan has a General Electric 1/4 HP single phase 115Vac ... A: I have no way of knowing what size capacitor you will need. Each manufacture is different. As we ...
|
| test elec motors | 7/22/2009 |
Q: How do you ohm out a motor to see if it is bad? A: Using a ohm meter is not a adequate test for a motor. About all it is good for is to test continuity ...
|
| Motor is cyclying under load... | 7/19/2009 |
Q: I have a GE single phase motor, 1/2 hp 1725 rpm. It runs a long, custom made belt sander. When it ... A: It sounds like your motor start winding is not operating. Try replacing the capacitor. If that ...
|
| Converting 208v to 110v and the wirirng... | 7/9/2009 |
Q: I have seen the reply about the same subject, taking out a 3 phase breaker and replacing it with ... A: Mick, for 115 volts connect the white wire to the neutral bar in your breaker box. You should see a ...
|
| deep well pump not functioning | 7/4/2009 |
Q: I checked the voltage thru the pressure switch (240 volts), is OK, I measured the capacitor and ... A: Remove the wires from the control box, and test continuity from red to yellow, and yellow to black. ...
|
| D.C. Motors | 7/3/2009 |
Q: How do I test a DC motor to make sure its in good working order? My motor is rated for 24 volts at ... A: The motor will need to be disassembled to test. This is a complicated procedure. The field coils ...
|
| Craftsman 10" Table Saw Motor | 7/1/2009 |
Q: The motor on the 10" Craftsman table saw is a 1 HP 120/220 volt - dual capacitor motor. (No ... A: I would check the capacitors, and if bad replace them. If that doesn't fix the problem, then you ...
|
| REVERSING 1PH MOTOR WITH CONTACTOR | 6/24/2009 |
Q: Motor has 6 leads connected as follows: L1 to #1, L2 to #4 & 5, 2,3&8 are connected together. To ... A: I do not have a drawing handy for the high voltage connection using contactors, but have one for the ...
|
| 9 lead motor | 6/18/2009 |
Q: My friend has a 9 lead motor. He put it on a machine that has a 6 contact drum switch. It is a ... A: Try this diagram here. Connect as shown, except connect L2 to P1, and not to the drum switch. ...
|
| Doerr Electric Motor Wiring | 6/18/2009 |
Q: Working on a Boat Hoist with a Doerr Electroc Motor / Model #LR24684. Wired for 220VAC operation - ... A: All I can supply is a standard reversing switch diagram. This is for a Dayton, ...
|
| Rewire 240v to 120v DOERR LR22132 | 6/1/2009 |
Q: I have a Doerr aka Emerson Electric compressor motor LR22132. I is currently wired for 240v. I ... A: This motor is not capable of being connected for 115 volts in the field. It is a single voltage, set ...
|
| circuit breaker is tripped when I plug in my treadmill | 5/31/2009 |
Q: I have a dp fit for life powertrac treadmill with an emerson 1 hp-motor, model# s67kdf-7657, 115 ... A: If the breaker is tripping, then you have a dead short somewhere. It would be impossible to diagnose ...
|
| spa motor | 5/30/2009 |
Q: installed new 2 speed ao motor for spa,110volt when first turned on both speeds work,now only ... A: You possibly have a shorted winding, or a bad starting circuit. Because this is a spa motor, I ...
|
| 5hp 110 volt motor | 5/22/2009 |
Q: I was given this compressor after the man found out that the wiring could not handle the load. I ... A: I think that this motor is probably made in China. The wiring colors do not match the colors of the ...
|
| electric mower | 5/20/2009 |
Q: I replaced the switch, no change. Then I found a brush stuck in it's holder, unable to move ... A: This wiring is doing two things wrong. First, with the two red and blue wires as drawn, you are ...
|
| Century Motor Part #8-150257-02, single phase, 220VAC, 15 AMP, HP5.SPL, 60HZ, 3450 RPM | 5/10/2009 |
Q: I recently purchased a pressure switch (Furnas 69jf7ly2c)to replace my old switch (Furnas ... A: First, again push the reset button rally hard. You should hear a distinctive click. Did you check ...
|
| boat hoist motor/switch | 5/8/2009 |
Q: "I have an overhead boat hoist which utilizes a Century 3/4 hp motor. I broke the handle off the ... A: Your switch is wired incorrect. Here is a correct diagram, ...
|
| DD Blower motor 1/3 hp | 5/6/2009 |
Q: Mr.Jones replacing blower motor on my furnace!Coleman EB17B model.It had a GE motor!I got a ... A: I could not find a wiring diagram for the Dayton motor. But I believe the following will work. ...
|
| DD Blower motor 1/3 hp | 5/5/2009 |
Q: Mr.Jones replacing blower motor on my furnace!Coleman EB17B model.It had a GE motor!I got a ... A: There should be a wiring diagram on the new motor. Your new motor should have separate wires for the ...
|
| testing a motor under load | 4/22/2009 |
Q: what kind of reading should i get in testing a 3-phase 220/440 motor using a fluke multitester under ... A: You need to test with a amp meter. Uncouple the motor from the load, and test it with no load. The ...
|
| electric motor hp | 4/21/2009 |
Q: I am trying to make a auto transmission test bench and I am wondering about hp and motor rpm. I am ... A: The horsepower rating depends on just how much the motor will be loaded. With no load on the output ...
|
| Circular Saw 3 Phase Motor Star or Delta? | 4/8/2009 |
Q: I have been asked to install a D.O.L and E Stops to an old circular saw that has had a new motor ... A: What you have is for high voltage, and it is correct. Here is a diagram for other connections. The ...
|
| adding drum switch to electric motor | 4/7/2009 |
Q: I have a lathe with a Delco motor, model 8540, Type AD 1/2 hp running one phase on 110. The leads ... A: You will have to disassemble the motor, and find the number 8 lead. It needs to be brought out to ...
|
| GE AC Motor Wiring | 4/7/2009 |
Q: I just purchased a General Electric AC motor for use with a bandsaw and need to know how to wire it ... A: What is confusing to me is the number 7 lead. This is not a standard number. This may help you to ...
|
| GE AC Motor Wiring | 4/6/2009 |
Q: I just purchased a General Electric AC motor for use with a bandsaw and need to know how to wire it ... A: I am surprised this is a new motor that does not have a wiring diagram. I have no schematic, nor ...
|
| adding drum switch to electric motor | 4/4/2009 |
Q: I have a lathe with a Delco motor, model 8540, Type AD 1/2 hp running one phase on 110. The leads ... A: First of all, You will need six leads coming out from the motor. It being a Delco, it is a very old ...
|
| Wiring a 220V single phase motor | 4/3/2009 |
Q: Recently, I purchased two pieces of woodworking equipment for my home. Both are single phase 220V ... A: It depends on the full load amp rating of the machine. If the machine pulls 30 amps at full load, ...
|
| Electrical problem | 3/27/2009 |
Q: Charles I hope you can help. I have a machine with a 10HP 3phase mechanical brake motor at start the ... A: An arcing contactor could cause the problem you describe. If the new contactor does not cure your ...
|
| Emerson J56CZ 1 HP Ref#607710C Date code K3988 | 3/26/2009 |
Q: The line connection diagram plate has been removed & lost. It looks right to hook line to term. 1 & ... A: Your problem is wear in the bearing, housing, shaft or a combination of all three. When the motor is ...
|
| KW single phase motor, coupled to centrifugal pump | 3/19/2009 |
Q: We have a 1 KW single phase motor, coupled to centrifugal pump, capacitor start, 3 wires from the ... A: Your problem is in the starting circuit. It could be a bad capacitor, switch, governor or a open in ...
|
| 3 phase fan motor | 3/14/2009 |
Q: which has a junction box with eight wires for conbnection, i want to connect a five wire three phase ... A: Sorry, I'm not a mind reader. You have gave me no information to work with. First, I know of no ...
|
| Reversing dual voltage motor | 3/11/2009 |
Q: I have a Lincoln dual voltage motor that is wired 115. It will be connected to a drum switch for ... A: I do not have any info on how this motor is connected, whether it just brings out leads, or has a ...
|
| 220v motor wiring with reverse drum switch | 3/11/2009 |
Q: After looking through all the previous questions I still haven't answered mine. I have a 2 hp ... A: Shawn, I will try to have a drawing online for you shortly. You have a single voltage motor, while ...
|
| motor noise and vibration | 3/7/2009 |
Q: What would make a 1/2 hp AC 115v/60 hz motor have a rhythmic drone rather than a steady hum ? If ... A: Kinda hard to diagnose a noise over the internet. A loose rotor could cause a noise, as could ...
|
| Compressor motor wiring | 3/7/2009 |
Q: On a 7.5 HP 3 Phase 220VAC motor is it possible to not use a magnetic starter and still have the ... A: Though it can be done, I would not recommend it. You would wire two legs through the switch and the ...
|
| 3 phase motors | 3/4/2009 |
Q: I have a 50 HP 600V 3ph submersible pump on a soft starter. When I start the pump it pumps a low ... A: Not much I can tell you here. Soft starts are out of my expertise. Can you disconnect from the soft ...
|
| question regarding previous post/answer | 3/4/2009 |
Q: I am wiring a forward reverse off switch to a motor on my metal lathe. The motor is chicago electric ... A: There is a discrepancy in this drawing that I have not noticed until now. Connect you L1 to P1, and ...
|
| Electric motor issue | 3/1/2009 |
Q: I have a 1-1/2 HP Leeson 145 frame,dual capacitor single phase 115/230V electric motor. Question is: ... A: If the rotor and stator have heavy rust build up, a cleaning would be good maintenance, but that is ...
|
| themal overload reset on 3/4 hp AC motor | 2/28/2009 |
Q: The Magnatek pump motor at a property I purchased is non-functional. ID is Catalog B-625, Type CS, ... A: Your motor has a internal thermal overload. It resets automatically. Have you checked your voltage? ...
|
| wire a new drum switch for a boat lift | 2/27/2009 |
Q: I have a 1 hp GE motor, model #5KC49PN0216 on a farely new Boat Hoist USA lift. We want to install a ... A: This is all I can provide, which is NEMA standards. Use this diagram to identify the colors, ...
|
| Hooking up Magnetic Switch after Motor repairs | 2/24/2009 |
Q: I have a Delta table saw, 3hp, single ph , 240V, with Magnetic switch. Took the motor out to have ... A: L1 L3 L5 13 T2 T4 T6 13 To me, it makes no sense to have a jumper from L3 to T6, and ...
|
| 2 speed pump motor on spa | 2/21/2009 |
Q: i have 3, 2 speed pump motors for use on a spa, i have new control box on spa, none of the motors ... A: I will need more information to even consider a answer. My knowledge is limited to the motor itself, ...
|
| Wiring diagram | 2/19/2009 |
Q: I have a Dayton 11/2 HP motor 115/208-230 volts, 14.2/7,7-7.1 Amps, continuous duty, thermally ... A: This should help you to wire your switch. ...
|
| 3 phase motor | 2/12/2009 |
Q: I just bought a large used dough mixer. The machine was advertised as single phase, 3/4 hp, 3.28 ... A: My concern would be if the motor has single phased. This will cause a set of windings in the motor ...
|
| 220 v table saw wiring | 2/11/2009 |
Q: I have a fairly old (1950s) "Driver Line" electric motor made by Kearney and Trecker for their ... A: With a capacitor, I'm sure it is a capacitor start. To show you what is involved in connections, ...
|
| 230/460 single phase motors | 2/10/2009 |
Q: I have a 10HP, 230v, 1 phase, Cap start/induction run pool pump without a name plate. It's a ... A: I believe you may have the motor connected for 230 volts, but are running on 115 volts. And as for a ...
|
| electric motor wiring | 2/9/2009 |
Q: I have a single phase 230 volt motor capable also of running on 440 volts. Its a GEC cont rated unit ... A: I'm afraid what you have is a motor that lacks in starting torque needed for the application. The ...
|
| ? about alternator | 2/7/2009 |
Q: I built a small 3 phase ac alternator that uses pemanent magnets. my intention is to hook it up to ... A: You will have to nave the alternator under some type of load to get a measurement. I am assuming you ...
|
| Wiring GE type KC motor | 1/30/2009 |
Q: I have a GE type KC 110/220 1/2 hp motor (As best as I can read - 11E422DBY). There are 4 leads ... A: Sorry for the delay, I thought I had replied. If I knew what wires were the start, and which were ...
|
| Wiring GE type KC motor | 1/29/2009 |
Q: I have a GE type KC 110/220 1/2 hp motor (As best as I can read - 11E422DBY). There are 4 leads ... A: I'm thinking your motor is a import, because it does not conform to EASA standards. US motors do not ...
|
| single phase motor problem | 1/24/2009 |
Q: I have a double miter saw which has two 230V 1.5 single phase motors which come on at the same time. ... A: I can only take a educated guess here. Incorrect wiring. Not knowing how it is wired, and the type ...
|
| Leeson 1hp motor wiring | 1/17/2009 |
Q: Just purchased no. 110142 woodworking motor. It has T4 and T5 together, T2, T3 and T8 together and ... A: What you have now is the high voltage connection, 230 volts. If this is the voltage you want, ...
|
| Baldor Capacitors | 1/9/2009 |
Q: I have a 5hp Baldor Single phase motor,208-230 Volts,On the top of the motor is a cover with 3 ... A: If you can email the drawing, I will see if I can make it more simple to understand. Also, with the ...
|
| spa motor dead | 1/8/2009 |
Q: My spa motor is about 2-3 years old and has stopped working. Over the last few years I had to ... A: If you cannot see voltage between black/red to the common, or white, then one of two problems ...
|
| finding p1 p2 or all the lines | 1/7/2009 |
Q: 50 yr old machine repairman ford motor co. but more mechanically minded.recently purchased a 1950s ... A: I'm guessing you have no numbers on the leads. Here is a wiring diagram if you have numbers on the ...
|
| run/start | 1/6/2009 |
Q: here goes; 2 hp motor single ph 115v,has 2 capacitors in parallel wired to leg Z2 on motor,with no ... A: It appears you have a permanent split capacitor motor. These use capacitors to keep the start ...
|
| CENTURY ELETRIC MOTOR SWITCH REPLACEMENT | 1/4/2009 |
Q: I HAVE A CENTURY 5 HP SINGLE PHASE MOTOR: TYPE CP PART#8-164621-01 FRAME T56HZ 5.0HP ENCL DP 230 ... A: Your motor is factory set for CW rotation looking at the rear of the motor. It has no connections ...
|
| 2hp electric motor died | 1/3/2009 |
Q: the motor is on a air compressor. turned it on and it started momentarily then quit. it pooped the ... A: If the windings are bad, changing voltage will not help. It just could be a bad capacitor. Have it ...
|
| Dayton 6k325A | 1/3/2009 |
Q: I am installing a used coffee roaster into my new shop. As of right now, we have the shop wired ... A: Although your roaster may be connected for 115/220 volts, the motor will still use only 115 volts. ...
|
| start & run capacitors | 1/1/2009 |
Q: 1) How can one be certain of correctly identifying a cap as a "start" or "run"? Does the absence of ... A: Run capacitors are usually encased in aluminum, where start are in black plastic. If the motor has a ...
|
| wiring fan motor | 1/1/2009 |
Q: I'm trying to hang a coil with a squirrel cage motor behind it. The problem is that I think I need ... A: Yes, you will need a run capacitor. If you have a readable nameplate, check to make sure it is 110 ...
|
| WIRING A SWITCH | 12/30/2008 |
Q: CHARLES, I HAVE AN OLD CRAFTSMAN AIR COMPRESSOR AND MY PRESSURE SWITCH WENT OUT.I BOUGHT A NEW ONE ... A: L1 and L2 are the wires coming from your power, such as a breaker. T1 and T2 are the wires from the ...
|
| Power connection to 110/220 motor | 12/26/2008 |
Q: Charles- I inherited an old Craftsman 1 HP air compressor w/ a Howard motor, type RK5;, FR: K56; ... A: If 2 and 3 are on the same post, it is connected for 230 volts. As I have no diagrams for individual ...
|
| Wiring | 12/19/2008 |
Q: I want to wire in a 120vac receptacle off of a 220vac single phase recepticle. How do I do this? A: From a technical viewpoint,I do not advise that you use this method, as a failure in the 120 volt ...
|
| Baldor 3 phase motor | 12/19/2008 |
Q: I am replacing the old irrigation motor (Baldor JMM3312T) and I am wiring the way the old one was ... A: When checking the voltage, you should have 220 volts from phase to phase. Each leg will read 120 ...
|
| 3 phase | 12/9/2008 |
Q: Good Morning, I have a 3 phase in my warehouse i need to connect a machine that uses 220v 3 phase, ... A: You have 220 volts. Connect your black wires from the machine to any terminal. What you want to do ...
|
| rewind possibilities | 12/4/2008 |
Q: I need two 50HP 900RPM 575v shaft down C or D face TEFC motors, which are nonexistent on the ... A: Re-winding is not my expertise. I just do the machine work and mechanical work. To the best of my ...
|
| Centrifuge motor | 12/2/2008 |
Q: I am building a sculpture using some electronic parts. I have done simple wiring before, but I am ... A: I don't think the motor should smell after running. The only sure way to tell would be to check the ...
|
| 1phase electric motor keeps blowing house fuse | 12/1/2008 |
Q: both motors are 3hp but the single phase motor will run all day without the belt being conected but ... A: What voltage is the motor? And what voltage are you using ? My guess is that the motor is connected ...
|
| South Bend Lathe | 11/28/2008 |
Q: I have no eletrical wiring skills, so I hope you can tell me or show how to convert me 3 phase lathe ... A: These diagrams are for the most popular used drum switch. For 115 volts, ...
|
| 110-220 wires | 11/26/2008 |
Q: I'm converting my old Sears compressor from 110v to 220v. The Doerr motor has the diagram on it for ... A: Unless your motor has a resilient base, that is, one that has rubber bushings on the motor that ...
|
| ac 1 1/2 hp tefc wired for 120vac motor | 11/21/2008 |
Q: my 10 yr old tablesaw motor somtimes trips my 20amp breaker, it happens about 30-40% of the time. ... A: Sorry for the delay, it seems I overlooked this question. The capacitor needs to be checked with a ...
|
| two speed spa motor | 11/20/2008 |
Q: the motor/pump works fine on low speed and with low speed on the high speed works fine. starting ... A: Most, but not all 2 speed pump motors have a dual switch inside the motor.The motor has two separate ...
|
| 3 phase motor troubles. | 11/20/2008 |
Q: I have a fan motor on our roof that uses a 480 volt 3 phase motor. I had a dropped phase on the ... A: From your question, I guess you were reading each phase to ground. Did you check phase to phase to ...
|
| reversing a pump motors rotation | 11/17/2008 |
Q: I have a magnetek single phase 120volt pump motor that I would like to reverse the rotation on,it is ... A: Pump motors from the factory are in set rotation, and are not field reversible from the connection ...
|
| Weak motor is it Phase Rotation, Or ? | 11/17/2008 |
Q: Jones, I have read several of your articles and its obvious it will take more of your energy to ... A: Phase rotation is just the way a motor is connected to line. Such as L1 to T1, L2 to T2, L3 to T3. ...
|
| ac 1 1/2 hp tefc wired for 120vac motor | 11/16/2008 |
Q: my 10 yr old tablesaw motor somtimes trips my 20amp breaker, it happens about 30-40% of the time. ... A: If it has a run capacitor, (which are normally encased in aluminum) have it checked. The start ...
|
| single phase magnetic starter does not power tools | 11/15/2008 |
Q: I just completed wiring my shop with 240V. I have 118 volts on each leg from the breaker to the ... A: Before I could make any kind of answer, I would need to see how everything is wired. Here is a ...
|
| Starring Capacitor for Dayton Motor | 11/14/2008 |
Q: Charles - i have a dayton motor model 9K324H which needs a starting capacitor. The lettering on the ... A: I can only guess. The only way to truly know is to contact WW Grainger. There is no standard for ...
|
| Old Wagner 1/3HP four wires | 11/14/2008 |
Q: I am dealing with an old Wagner 1/3 hp motor. My Dad has it running his 1940's era Powerkraft table ... A: Not much to work with here, and the following may not work. Use a ohmmeter and find two leads that ...
|
| ringging out cut wires | 11/13/2008 |
Q: We Have Had Several Cut Cut And Now not sure where they all go they are still hooked up to motors , ... A: Unless the wires are color coded, you will have to check from the motor back to the cuts. You didn't ...
|
| How to convert a 120 VAC electric motor to 220 VAC | 11/11/2008 |
Q: I really like your web site here! And it looks like I stumbled upon just the place I need. You see, ... A: from central Alabama, USA. First of all, your motor is not able to be wired externally for 220 volt ...
|
| elect motor wiring | 11/8/2008 |
Q: I have a doerr single phase cap start 1.5 hp elect ac motor and we are trying to wire 230 v. the tag ... A: All I can offer is the standard wiring diagram from NEMA, which can be seen here. It only gives the ...
|
| motor capicitor | 11/7/2008 |
Q: I bought a small lathe with a 2hp 230v motor. the previous owner said that he had replaced it with ... A: There is no standard for sizing capacitors. This is done at the manufacturer. The only sure way is ...
|
| Dayton Drum switch wiring | 11/4/2008 |
Q: I couldnt find the right drawing for a dayton 2x440a in your answers. Here is the config. of the ... A: Paul, I'll try to get a drawing for you. As you didn't specify which voltage, I'll give both. It may ...
|
| motor switch contacts | 11/1/2008 |
Q: What is the purpose of the motor switch contacts 1 & 2? A: I'm guessing your speaking of the contacts on the stationary switch inside the motor. These control ...
|
| two speed motor | 10/15/2008 |
Q: I see you answered a question awhile back on this subject ..here is my problem the motor is on a hot ... A: The part on the armature is called a centrifugal switch. When the motor is at rest, the springs ...
|
| Single phase reversing motor connection assistance needed. | 10/13/2008 |
Q: I have a Dayton, Model 6K324BA, 1.5 HP. dual voltage, reversible motor and an Advanced Controls ... A: If you can, send the diagrams to me. I have never came across a reversing switch with this many ...
|
| motor wirong connections | 10/12/2008 |
Q: I have a 36-inch fan powered by a Dayton 2-speed 110vac motor. It has a chain-pull switch, 3 ... A: This motor is obsolete from ww grainger. As we do not stock dayton motors, I would have to make a ...
|
| 3 and 4 wire connections for 220 V. 1phase motors | 10/10/2008 |
Q: I am installing a 5 HP 220 volt motor to operate my hanger door. The motor leads are marked for ... A: This is the standard connection for a four wire plug: Top O ...
|
| Hooking up a motor at a different voltage | 10/10/2008 |
Q: I have a 5 hp 208/230 vac, single phase motor, 60HZ. Is there anyway that motor can be wired with ... A: At the most, you have four leads coming out of the motor. Numbers 1,4,5,8. Connection is L1, 1&5, ...
|
| gayton split phase motor/drum switch | 10/10/2008 |
Q: im reading similiar question/answer and i hope you can help, im trying to wire a drum switch to a ... A: I have your question, and will have a diagram for you tomorrow, as I have to draw it out and upload ...
|
| wiring diagram for ge single phasemotor | 10/10/2008 |
Q: I am looking for a diagram for a GE commercial ac motor model 5KC46LNO252AY 220 volt 60amp. single ... A: It seems you are missing one wire for your connection. T8. T8 and T5 are the start winding circuit, ...
|
| Hooking up a motor at a different voltage | 10/9/2008 |
Q: I have a 5 hp 208/230 vac, single phase motor, 60HZ. Is there anyway that motor can be wired with ... A: Capacitors are not used to determine voltage. Changing the voltage would require complete ...
|
| Motor pulling high amps | 10/7/2008 |
Q: I have a new Baldor 10Hp 230V 3ph motor on a liquid oxygen pump that is pulling 35-38 amps per ... A: I would first disconnect the motor from the pump, and run it with no load and re-test the amperage ...
|
| ge 240 volt motor | 10/6/2008 |
Q: charles i have a ge single phase motor with 4 terminals on it and i dont have a clue as to wiring it ... A: I have no wiring info for this motor. Use a ohm meter and find which leads read to each other. As a ...
|
| 3 phase to 1 phase | 10/2/2008 |
Q: I have located a natural gas motor that is set up with a 3 phase generator and I want to have single ... A: The voltage from the generator must be the same as your grid power. If they are the same, you would ...
|
| AMPS | 9/30/2008 |
Q: The company where I work recently bought a DAYTON motor.The motor is a 208-230 volts 3 phase ... A: Is the motor that was replaced the same RPM as the Dayton? The amperage draw is ok, by that I mean ...
|
| troubleshooting power saw motor problem | 9/24/2008 |
Q: Makita 16" Circular Saw Model 5402-a 110v 12amp Single phase motor The brushes are sparking ... A: If you can see the field coils are burnt, no more testing needed for those. I'm guessing this is a ...
|
| 220 hot tub wite | 9/23/2008 |
Q: When I replaced my hot tub I realize I have one white wire one green wire and two black wires. How ... A: The two black wires should be your 220 volt lines. White is neutral, and green is equipment ground. ...
|
| converting 208v to 110v? | 9/23/2008 |
Q: I have a 3phase 208v 30amp service that i would like to a break down to a 3 single phase 110v 20amp ... A: In place of a three pole breaker, just install a single pole. But at 208 volts, you may only get 104 ...
|
| Magnetek Single Phase | 9/21/2008 |
Q: Have a compressor with a Magnetek Single Phase, start and run capacitors. Will not run. Checked ... A: Is the motor trying to run, that is making a humming noise? If not check your voltage again. Also, ...
|
| Reversing motor | 9/18/2008 |
Q: I have an old Sears drill press that has a capacitor start A.C. motor. It says on the legend plate ... A: As you didn't specify what voltage your using, I will give both connections. These diagrams should ...
|
| Star/Delta Starter: Forward in Star and Reverse in Delta? | 9/18/2008 |
Q: I have a problem in Star/Delta starter problem which i still can't find the answer from internet. ... A: Your delta connection is U1-W2 ; V1-U2 ; W1-V2 Here is a copy for your records, ...
|
| old wagner motor | 9/17/2008 |
Q: I have a 1.5 hp Wagner motor on an air comp. it has 4 unlabeled wires,they are paired together and ... A: As I don't know the internal connections of the coils, I can only guess as to the connection. ...
|
| Single phase 2hp motor trips breaker | 9/12/2008 |
Q: I have a 2hp moter on a power washer, single phase 3450 rpm, that will start good and run for about ... A: Here is a start for checking your problem, Have the capacitor tested. Check for continuity between ...
|
| Star delta circuits | 9/10/2008 |
Q: Please find a digrame of pannel wiring of star delt starter for me. A: Sorry for the delay in answering, but I have had some internet provider problems. I can probably ...
|
| Spa motor start | 9/5/2008 |
Q: I'm having start problems on my spa pump motor. The motor just hums when starting. It hums for about ... A: This is from a previous answer: Next, check the capacitor. Bleed the capacitor first by using a ...
|
| motor not starting than tripping breaker | 9/1/2008 |
Q: I have a baldor 3HP, single phase motor on my table saw that has never had a problem. A month ago ... A: If you have a air hose, blow out the motor, it may be just dust between the contacts of the starting ...
|
| Power for a 3 Phase Motor | 8/31/2008 |
Q: I am not positive if this is in your score of question or not, so I apologize if it isn't. I have a ... A: My preference would be the rotary type. Parts, if you need them, can usually be had at your local ...
|
| Dayton Generator | 8/30/2008 |
Q: Dayton 5000 watt, model SU934 (older model), with 11 HP Briggs & Straton motor. Unit hasn't ... A: Sonny my knowledge of generators is limited. Flashing would have been my first answer. If it has ...
|
| GE AC Motor rewire from 115 to 230 volts | 8/29/2008 |
Q: I have a used AGET dust collector which has a GE AC Motor Model# 5KC45NG536, 1hp, RPM 3450 1 phase ... A: Darryl, unless those wires have numbers on them, I can't help. If the colors are standard, it would ...
|
| Need a wiring diagram for an old GE motor | 8/29/2008 |
Q: We have an old 2HP GE induction motor that we no longer have the wiring diagram for. Can you help? ... A: This is the only drawing that I have for a Ge motor, with reversing switch. ...
|
| reversing switch | 8/27/2008 |
Q: I HAVE AN OLD CUTLER HAMMER REVERSING SWITCH WHICH IS IN VERY GOOD CONDITION. I WOULD LIKE TO ... A: First, lets put numbers on those colors. White T2, Orange T3, Red T8, Blue T1, Black T5, Yellow T4 ...
|
| breaker | 8/25/2008 |
Q: 5kw pump can you tell me what size breaker I should install to protect it Thanks Kevin ( Spain ) A: As I am in the USA, I converted kw to hp. I came up with 3.3 hp. FLA will be approximately 12.8 ...
|
| DELCO Motor Wiring | 8/22/2008 |
Q: Restoring a DELCO Motor Model A2033; AC Motor; Series G-53; 1/3 HP; Code P; Type SP, 115 volt 60 hz. ... A: This is a really old motor. There should be four wires coming out of the stator windings, unless the ...
|
| wiring a 115 V 3/4 HP motor | 8/19/2008 |
Q: We have a single phase motor for our boat lift. It is a Marathon 115/230 Volt, 3/4 HP, 1750 RPM ... A: That is the motor. I needed the switch. Here is the wiring diagram for the reversing switch drawing ...
|
| Doerr motor wiring | 8/19/2008 |
Q: Mr. Jones: I have read many of your question/answer listings and am greatly impressed by the ... A: As this is a very old motor, and the color and numbering system is not standard, its tough for me to ...
|
| Generac 6500 Generator | 8/19/2008 |
Q: Have used it for several years to run a stick welder. Has had proper maintenance of fuel, oil, etc. ... A: My knowledge of the newer models of generators is limited. Most all now have circuit boards that ...
|
| Bathroom ven motor | 8/18/2008 |
Q: At my work, we have a bathroom vent (250mm) for each toilete cubicle & shower, 5 in total, all of ... A: These motors require air from the fan to keep them cool. We do not service these motors. just ...
|
| power phases in homes | 8/14/2008 |
Q: How do I easily determine if two outlets in my home are on the same phase leg of power? I have some ... A: I know of X-10 technology, but have never had any type of dealings with it. As for the circuits ...
|
| I need to reverse my dress press motor. Please Help. | 8/12/2008 |
Q: My name is Charles. I need some help reversing my drill press motor. I have a Delta drill press ... A: Tapping acrylic huh? Now I can agree with that. I could be wrong, and it would not be the first ...
|
| I need to reverse my dress press motor. Please Help. | 8/11/2008 |
Q: My name is Charles. I need some help reversing my drill press motor. I have a Delta drill press ... A: I am a machinist by trade, and I question your use of a drill press as a tapping machine, unless it ...
|
| wiring Sq D reversable drum switch 220v 1ph | 8/9/2008 |
Q: I have a boat hoist powered by a dual voltage Doehrr 1hp motor with a start winding and 2 run ... A: I did make a mistake in my wiring connection. P2 should be connected to where I show L2 in the ...
|
| Wiring asynchronous single phase motor | 8/8/2008 |
Q: I have a snap on compressor with a 90 lb/2 asynchronous single phase 240volt 3.o hp motor on it ... A: I do not have any info on imports. (I'm in the USA) I can only make a guess. Remove the rear ...
|
| 3 phase Electric Motor (measure load) | 8/7/2008 |
Q: I would like to monitor the load on 3 phase motor with permanent meter. Is it necessary to measure ... A: You might install current transformers, such as these, http://www.vias.org/feee/acmeter_02.html It ...
|
| 60 hp motor intermittent tripping of motor starter overloads | 8/3/2008 |
Q: 60 hp motor [rebuilt 8years in service] supports 60 ton chiller and has started to trip overloads on ... A: We all forget the words sometimes, but that doesn't help your motor. A humming motor makes me think ...
|
| SINGLE PHASE ELECTRIC M. PROBLEMS | 8/3/2008 |
Q: WHATS UP. I BOUGHT A 1/2 ROUTER FOR CABINET MAKING, HOWEVER IT LASTED ALL OF A FEW HRS. OF ... A: I'm guessing this is a used tool, or you would have already taken it back for a replacement. Are the ...
|
| doerr single stage electric motor. | 8/3/2008 |
Q: I have 1/3 HP Doerr motor used to pump beer through filters prior to packaging. When I turn it on ... A: Have the capacitor tested. Check for continuity between the two wires that connect to the capacitor. ...
|
| Radial arm saw motor | 8/3/2008 |
Q: I bought an older craftsman 12" radial saw from an estate and it had a 115 volt replacement plug on ... A: First, if it has a manual reset button, press it really hard, and listen for a audible click. You ...
|
| Lathe Motor Star/Delta | 8/2/2008 |
Q: I too am a sparkie. Last week I called on a local engineering company with a view to getting their ... A: Garry, can you supply the complete nameplate data? I question whether this is a part start, or a 2 ...
|
| furnace motor hum | 7/31/2008 |
Q: A couple of months ago I oiled my 20 yr. old direct drive squeaky furnace motor. I think its a Fasco ... A: 20 years! I would have that thing bronzed and put it on the mantle! It could very well be the ...
|
| three phase overspeed motor | 7/28/2008 |
Q: we have an arguement about electrical theory.If I have a three phase induction type motor and it is ... A: An induction motor cannot generate electricity. It can only consume. Now if you drive a generator ...
|
| wiring Sq D reversable drum switch 220v 1ph | 7/26/2008 |
Q: I have a boat hoist powered by a dual voltage Doehrr 1hp motor with a start winding and 2 run ... A: Try this diagram, and see if it matches up to your switch. The dotted lines are the internal ...
|
| ohm out a motor with meter set on ohms. | 7/12/2008 |
Q: WHEN I WANT TO OHM OUT A MOTOR TO SEE IF IT'S GOOD OR NOT. COULD YOU TELL ME HOW TO GO ABOUT IT AND ... A: An ohmmeter is not a very good test for a motor. It will show you continuity in the circuit. It can ...
|
| BUDGIT Hoist motor | 7/9/2008 |
Q: It's me again. I wish I could email you a drawing on the switch and the leads of this motor. The ... A: What you have is a DC (Direct Current) motor. I have never seen one of these on a hoist. They are ...
|
| Marathon B311 | 7/3/2008 |
Q: We have a Marathon B311 motor that we would like to utilize a Dayton 2X440 drum switch with to ... A: Due to safety reasons, the only way I wire a drum switch is to bring out all six leads to the drum ...
|
| How to verify the operation of a 3 phase motor | 7/3/2008 |
Q: I have a friend who would like me to check and make sure a 3-phase AC motor is still in good working ... A: It needs to be tested with a megohmmeter. This will give you a accurate reading of the insulation ...
|
| compressor motor problem | 6/30/2008 |
Q: I have a compressor with a 'Brooks Crompton' single phase 230v 3hp 2.2kw motor; it has two ... A: First check that the compressor turns free. Capacitors normally have the data written on them. Run ...
|
| AC electric motors | 6/30/2008 |
Q: Can a start capacitor be added to my single phase 3/4 hp. motor, to stop power drop at start up. It ... A: If the compressor is starting ok, then your problem is in the circuit it is connected too. It may be ...
|
| Reverse polarity | 6/29/2008 |
Q: The rear fan blade broke on my General Electric airconditioner,Model#AJCH12DCM1.To replace the ... A: Unless you have another set of wires brought out to reverse the motor, it is set rotation. Now I ...
|
| Electrical Phases | 6/25/2008 |
Q: I am confused about phasing in electricity. First is it possible to run single phase and three phase ... A: Yes you can get single phase from your three phase panel. You will use one or two lines. For ...
|
| electrical dryer | 6/24/2008 |
Q: I recently installed 10-2 wiring set up for an electrical dryer, along with a double 20amp breaker ... A: I do not service appliances, but you may have a bad heating element. You will need to check for 220 ...
|
| MOTOR STARTING | 6/23/2008 |
Q: I HAVE A BALDOR INDUSTRIAL SINGLE PHASE MOTOR RATED A 3HP, 3450 RPM, 60HZ, 28/14 AMPS. THE MOTOR IS ... A: It seems you still have a problem in the start winding. But first, do you hear the head release ...
|
| MOTOR STARTING | 6/20/2008 |
Q: I HAVE A BALDOR INDUSTRIAL SINGLE PHASE MOTOR RATED A 3HP, 3450 RPM, 60HZ, 28/14 AMPS. THE MOTOR IS ... A: The first two questions I ask is, Does the compressor turn free? Is the line voltage the same as the ...
|
| follow info: reversing boat winch motor | 6/18/2008 |
Q: Here is some additional info on the elec. motor I emailed about yesterday: Dayton Model:5K482K ... A: It will work just fine, you just need to bring out all the leads to the drum switch. (Leave 2&3 ...
|
| How do I wire a HVAC squirrel cage blower? | 6/17/2008 |
Q: I have a double squirrel cage blower without any markings on it. It has five wires ( blue , red , ... A: These units are not dual voltage. Black, red, blue, and yellow are the speeds. White is common. For ...
|
| d112m aei stayrite motor | 6/14/2008 |
Q: could you please tell me what size of capacitors are required for the above motor and also where ... A: Start capacitors are connected in series with the start winding. There is no rule for sizing ...
|
| testing an ac compressor motor | 6/12/2008 |
Q: Mr. Jones- I hope you can help me. I recently installed a 110v/220v compressor. I was told ... A: Continuity between three leads? There should be only two leads that have continuity, the ones that ...
|
| drum switch | 6/10/2008 |
Q: I have an early model (70's) jet lathe I bought as a basket case. I want to wire the drum switch for ... A: First, number A1 as #8, and A2 as #5. Then use this diagram to wire the drum switch: ...
|
| 3/4 HP 110/220VAC Cap Start Doerr Motor | 6/10/2008 |
Q: Motor appears to be wired permanently for 110VAC; Run windings are joined internally {with T1 to T3 ... A: The stationary switch you are referring to I believe is a instant reverse switch. It is made so that ...
|
| coil | 6/10/2008 |
Q: I would like to build an electric coil ( copper, solid wire AGW #8 ) and I don't know what kind of ... A: You cannot make a coil with bare wire. Any manufactured coil, whether for a contactor or ...
|
| electric motor | 5/28/2008 |
Q: I just bought a metal lathe and the guy i bought it off off cut the wires at the motor and they are ... A: Without numbers or colors, I'm as lost as you are. A service center could probably trace the wires ...
|
| dayton motor mod # 4k641 s/n 560201 frame 56 1/2 hp dble end shaft | 5/28/2008 |
Q: Want to use this good old dayton motor on my southbend 10" lathe. No wiring diagram that I can ... A: All I can supply is these diagrams. The motor will probably have to be disassembled for the ...
|
| 3/4 hp 3450 rpm motor replacement | 5/24/2008 |
Q: the sears repair said they no longer have most the parts for that motor. the instruction manual says ... A: Sears has had a bad habit of installing motors that are not standard frame sizes, just so you will ...
|
| winding resistance values for a 60 hp AC motor | 5/23/2008 |
Q: what resistance values should I expect through the windings of a 3ph, 60 hp, 575VAC motor ? An air ... A: I do not know the actual resistance values for any motor. We do not even test for these values. You ...
|
| 3 phase motor | 5/21/2008 |
Q: I am currently an apprentice and i am having difficulty with an assignment. I am working on an 3 ... A: Each phase should be tested and compared to each other. They should be uniform amperage draw. There ...
|
| oil filled motors | 5/18/2008 |
Q: Now my problem is that I've opened up a 220 single phase trash pump/submerged motor. All the oil ... A: They are the same. We use Chevron insulating oil, a 5W mineral oil. You can probably get yours at a ...
|
| Reversng motor | 5/16/2008 |
Q: For better clarification, the J wire comes off the overload reset switch which is located inside the ... A: The T5 cannot be on the same terminal as T4. As the left side of the diagram shows, T5,T4 are L1. ...
|
| Lesson single phase dual voltage motor | 5/16/2008 |
Q: Resently a co-worker installed about a 1/2 HP motor on a grinder pump,and all is well. Our ... A: T9 is probably connected to a capacitor, or possibly to the stationary switch. If you have a motor ...
|
| How to wire a reverse drum switch | 5/14/2008 |
Q: I see you have probably answered this question before but I cannot see a diagram if you sent one to ... A: This should fix you up just fine. http://www.flickr.com/photos/96245499@N00/1463777160/sizes/m/ ...
|
| 220V 1Ph motor - directional switching | 5/12/2008 |
Q: Just completing the re-wiring of a panel. Service is 3ph, all other motors are 3ph...but discovered ... A: I would be afraid to say yes or no to this wiring. If this motor is manufactured outside the USA, ...
|
| Wiring for Jet Pumps | 5/10/2008 |
Q: I've purchased a new jet pump and the instructions set out that depending on the Horsepower (1/2 HP ... A: 35 Years! I would have that one bronzed and put on the fire place mantel! Check with a voltmeter. If ...
|
| electric motor on a milling machine | 5/6/2008 |
Q: I purchased a 1978 Samson drilling/milling machine with a 1hp Yeong-Shing Machine Works electric ... A: Foreign motors (to the USA) do not adhere to the numbering or color coding system we have ...
|
| 5 HP 220V motor getting hot--breakers tripping | 5/6/2008 |
Q: Jones, I am woodshop owner and and am no stranger to hooking up large machinery-3 and single ... A: Gerry, first of all, thanks for your offer of a donation, but I do this to help someone in need. If ...
|
| wire colors on an electric motor | 5/3/2008 |
Q: I have a 1/4 hp Emerson motor, 115v,60hz single ph, 3 spd, with wire leads red,blue,black,white,and ... A: Red, blue and black are your speeds. Connect black from your power cord to motor black. Connect ...
|
| Color Code For AC Condenser Motor | 4/30/2008 |
Q: My old AC Condenser motor was an Emerson, part #HQ1086696EM, MFG #Go2 C, 1/3 HP, Amp. 1.9, Volt ... A: You will need both wires for the capacitor. You will need a separate capacitor for your new motor. ...
|
| how to wire 120v ac reversing cap start motor | 4/29/2008 |
Q: have a foreign 120v ac reversing cap start/run motor. No wiring diagram anywhere. I pulle the end ... A: Foreign motors do not use US or NEMA standards. Knowing that the green goes to the capacitor, that ...
|
| reversing a 220 single phase | 4/27/2008 |
Q: I adapted an EMERSON 220 single phase AquaFlo pool pump motor to a chop saw and need to run it ... A: This motor came from the factory in "set" rotation. The other end of the start winding is connected ...
|
| Wirring a switch to motor | 4/23/2008 |
Q: Yes I have a switch that has been wired for my motor. It has one wire marked l1 and one marked l2 ... A: All I can supply is this generic wiring diagram. You must be able to get all six leads from the ...
|
| Single phase compressor motor | 4/21/2008 |
Q: The motor just hums but will not start. I have read test procedures but they have been arbitrary. ... A: The start capacitors are usually black plastic. They are rated for the voltage of the motor. Dual ...
|
| Wiring a Square D Magnetic Starter for an Air Compressor | 4/14/2008 |
Q: I have a Square D 8911 magnetic starter - with overload protection. There really isn't a wiring ... A: First, I apologize for my late response, as I have satellite internet service, and sometimes it ...
|
| wiring-electric motor capacitors (dual voltage motor) | 4/5/2008 |
Q: Mr. Jones Here is my question. Is it possible to add a capacitor to a motor that all ready has one? ... A: Before I answer your question, I have one. Why would you want to add another capacitor? If your ...
|
| reversing direction in motor | 3/29/2008 |
Q: I carve as a hobby and would like to reverse the direction on my motor using a double pole ,double ... A: Try this Brian. Remove the red and black from the connection plate and wire them to the switch as ...
|
| wiring Dayton 9K324H fr.110v to 220v | 3/29/2008 |
Q: my motor currenty has #1 term with blk 110v,#2 term is blk motor wire,#3 is double term with white ... A: Is the wiring diagram missing? It should be with the main data plate. This motor is not listed on ...
|
| reversing direction in motor | 3/27/2008 |
Q: I carve as a hobby and would like to reverse the direction on my motor using a double pole ,double ... A: See if this will help. http://farm1.static.flickr.com/149/354425208_e69ef5b90b.jpg Most motors ...
|
| Dayton Boat Winch | 3/27/2008 |
Q: I have an old Dayton winch used to lift boats out of the water. The data plate has LR-22132 on the ... A: The T numbers are the leads from the motor. The L numbers are the 110 volt line from your plug. L1 ...
|
| wiring Doerr 1hp for 110 volts | 3/23/2008 |
Q: I want to wire a Doerr 1 hp motor (currently wired for 220) to run on 110 volts clockwise rotation ... A: Your connection is: L1= P1 L2= 2,4,5 3,8,P2 together and insulated. To reverse rotation, ...
|
| wiring color code | 3/23/2008 |
Q: Have new central pneumatic 230 volt Single Phase air compressor it has a black wire labeled "Hot" a ... A: The green is always a equipment ground! You do not have a neutral on a 220 volt circuit. Your hot ...
|
| cap. configuration | 3/16/2008 |
Q: removed the "caps" and didn't get the wiring corectly when reinstalled need to know how to rewire ... A: I will have a look at the shop tomorrow, and see what I can find. I don't have much hope at finding ...
|
| wiring hookup for blower motor | 3/12/2008 |
Q: I had lost my internet connection since I last submitted my question, so I will try again. My ... A: It will have to have a run capacitor. Usually the wiring diagram is with the nameplate data. I am ...
|
| vacuum pump motor | 3/8/2008 |
Q: i have a sinku kiko co. ulvac g-100d vacuum pump. the motor is a 4 pole. the motor has a capacitor ... A: Don, this may or may not work, but give it a try. Tie red to white, and connect to L1 from your ...
|
| 240V Switch | 3/7/2008 |
Q: I have a 240V logsplitter, but it wasn't wired with a switch on the motor/junction box on the ... A: All you need is a double pole switch like this one, ...
|
| Small motor repait | 3/2/2008 |
Q: I tried to repair a small fan motor from my dad's humidifier. The motor has 3 speeds and is wired ... A: You can omit the thermal, but I am against it. It's there for a purpose. The new thermal would not ...
|
| Powermate generator PC0545009 failed to excite | 3/1/2008 |
Q: I am not getting any power output from my generator. Following the manual instructions, I tried to ... A: From my experience with Powermate, most of the problems come down to the voltage regulator on the ...
|
| keeps blowing my house fuse | 2/29/2008 |
Q: When I turn it on, it runs for a minute or so than it blows my fuse. next to the on/off switch / ... A: I don't think the pressure switch is your problem, unless the bleeder valve is not releasing the ...
|
| three phase motor | 2/29/2008 |
Q: Just wondering what the best way to test the windings for a short to ground. I checked all the ... A: You need a megohm meter. This puts at least 500VDC to ground. A shorted coil or phase may not show a ...
|
| Well Pump Repair | 2/27/2008 |
Q: I have a Flint & Walling deep well jet pump that I suspect the bearings are going bad in the motor ... A: Evie, special tools are needed to replace the bearings. You will need a set of pullers to remove the ...
|
| ralph electric generator | 2/24/2008 |
Q: OK I have a older MH (1977) with a Ralph electric company generator and can not find any info on it, ... A: First of all, if you replaced the plug, check if the connecting bar between the upper and lower ...
|
| how to interpret this wiring diagram | 2/24/2008 |
Q: it looks likes wiring diagrams create problems for lots of people. I'd greatly appreciate if you ... A: The diagram is self explanatory. P1 will connect to the black wire from your plug. Black, white and ...
|
| reversing an electric motor. | 2/22/2008 |
Q: OK, this is a followup of a previous question from thread ... A: This motor is a set rotation. By that I mean it is wired from the factory to run in one direction ...
|
| GE type KC 1/4 HP motor | 2/15/2008 |
Q: I have read your answers for various old KC type GE electric motors and they were very good and ... A: Some how you're one wire short. To use a reversing switch, you must have six wires out. 1,2,3,4,5,8. ...
|
| 3 phase motor check | 2/15/2008 |
Q: Have a motor where no fuses are blown. Contactor won't pull in. If you push in the contactor it ... A: Check for a single phase condition above the contactor. If the coil in the contactor was bad, the ...
|
| Emerson Doerr 3 phase motor | 2/14/2008 |
Q: How to wire a Emerson Doerr 3 phase motor model number LR22132 with 1/3 horsepower, 1725 RPM, ... A: For 230 volts, 1&7 L1, 2&8, L2, 3&9 L3. 4,5,6, together and insulated. For 460 volt, 1 L1, 2 L2, 3 ...
|
| more drum switch | 2/12/2008 |
Q: I had to ask a new question as I had to many follow up questions. I have the drum switch and the ... A: Joe, got your diagram, and will try to get you a working diagram. Still having computer problems, so ...
|
| wiring a drum switch | 2/8/2008 |
Q: I have a Southbend lathe. The motor I have for it is a General Electric. Here are the numbers I have ... A: I looked at your pics, and I need to know how the contacts make up in the switch.Look inside the ...
|
| reversing motor | 2/6/2008 |
Q: I have a compressor motor that rotates counter clockwise looking at the shaft end-on. I would like ... A: The black wire is located on the back side of the connection plate. The motor will have to be ...
|
| Suitable motor... | 2/2/2008 |
Q: My question falls into the "everyday do-it yourself kinda person" category. I need advice regarding ... A: If you can use a 1800 rpm motor, it would save you some big money. Lower rpm motors for single phase ...
|
| motor forward&reverseing | 1/27/2008 |
Q: just remove a 3-phase motor off my lathe would like to wire up a 110v motor useing the 3-phase ... A: All I can supply is a generic wiring diagram. This is the most common type I see in the shop. It may ...
|
| how to tell if a 3 phase motor is bad? | 1/25/2008 |
Q: went for a job interview today..had several things to do.. then i came to electric motors...3 ... A: Not enough space here to go in great detail. but first check for a blown fuse. Then test for a ...
|
| capacitors for Doerr compressor motor | 1/20/2008 |
Q: just purchased a used Campbell Hausfeld 60 gal air compressor, which is about 14 yrs old. ... A: I was unable to find any info about that particular motor. Try using around a 600MFD/220Volt start ...
|
| capacitors for Doerr compressor motor | 1/20/2008 |
Q: just purchased a used Campbell Hausfeld 60 gal air compressor, which is about 14 yrs old. ... A: It is a cap. start, cap. run. and your capacitor is probably shorted. Some, but not all, ...
|
| Single phase pump motor runs but not for long | 1/19/2008 |
Q: I just took the back off the a Flint and Welling Pump and motor combination because it was humming ... A: It sounds like you still have a open circuit in the starting winding. The capacitor also needs to be ...
|
| Furnace Motor wireing 1Ph 115V | 1/17/2008 |
Q: My original motor has a different wire color code. Red,Blue,Yellow,black WHITE,one brown, w/ a three ... A: Kinda confused here. You said the red and blue were capped off, and then say the yellow was was ...
|
| Same spa problem | 1/9/2008 |
Q: I found your response to a GE spa motor question from last fall and I'm encountering a similar ... A: Not knowing how your motor is wired, it would be hard to give you a good answer. Have you tried ...
|
| Auto lift wiring | 1/7/2008 |
Q: I have a 2 post auot lift. On the motor plate it says: 3hp 220v 20 amps. There is also a saftey shut ... A: I would go with a 30 amp breaker, as a 20 is at the full load current of the motor, and may give you ...
|
| Wiring of magnetic switch for air compressor | 12/28/2007 |
Q: i recently bought a compressor from an auction the mag switch was removed i purchased a new switch ... A: Coil voltage must go into the line side of the pressure switch. The load side of the pressure switch ...
|
| connecting a 220 volt 1hp leeson motor | 12/23/2007 |
Q: Jones , this motor will be used to run a blower on a wood fired evaporator. There is no wiring ... A: You will only need the two wires coming from the breaker. Connect one to T1 and T5, and the other to ...
|
| current variation | 12/14/2007 |
Q: sir i have big confusion about the load current of the motor.my question is for example a 11KW motor ... A: I think you are confusing current with voltage. The voltage may be the same, but the ...
|
| 3 phase utility costs (via rotary phase converter) | 12/9/2007 |
Q: Charles, My wife and I purchased 5 used Sewing Machines, a Straight Knife Cutter, and a Cloth Drill ... A: I totally agree with what you said. Just remember, you don't pay for voltage, or amps. You pay for ...
|
| hi | 12/6/2007 |
Q: how do you test if a 1 phase motor is bad I know how to test a 3 phase motor with a megger can u ... A: First you will need a insulation tester, such as a megohm meter. Then you will need a meter that ...
|
| Motor Capacitor | 11/28/2007 |
Q: I have a capacitor for a 1/4 HP motor, marked as CBB60 SH, 20 mfd, 250 volt AC, -25/85Deg. C. The ... A: All you need is a 25mfd/250 or 370 volt run capacitor, usually available at any motor service ...
|
| Wiring a Leeson 3/4 HP Motor | 11/21/2007 |
Q: Charles, I have an old Leeson capacitor start motor I want to use to make a disk sander for my shop. ... A: If all wires are connected to terminals, your line voltage will connect to terminals #1 and #4. To ...
|
| Change motor wiring from 230VAC to 120VAC | 11/11/2007 |
Q: I bought a used Speedaire compressor with a 2HP Dayton motor. It's wired for 220VAC 1ph, but I need ... A: I could not locate any connection diagram for this motor. The only thing I can supply is the ...
|
| star delta starters | 11/5/2007 |
Q: Hallo Charles, Making sure that when replacing a bad motor with a good one that the motor does not ... A: As I only do in shop repairs on motors, I seldom see how the contactors are wired. As I am out sick ...
|
| 2 speed electric motor | 11/2/2007 |
Q: i have a 2 speed motor on a hot tub pump. the pump runs fine on the low speed. when switched to hi ... A: I believe you may have a loose wire on the stationary switch, or a shorted winding on the high ...
|
| wiring 1ph 220v electric motor - Doerr | 10/21/2007 |
Q: I have a 1HP Doerr electric motor. The nameplate indicates that it can run on 110v or 220v. It was ... A: Line 1 is T1. Line 2 is T4%T5. T2,T3,T8 are tied together and insulated. If you have what we call a ...
|
| motor tripping the breaker | 10/18/2007 |
Q: I have a 10 hp three phase motor running acooling tower fan it`s pulling 26-28.5 amps when i check ... A: I really need to know what voltage you are using. If you are using 230 volts, the motor is pulling ...
|
| Single phase motor | 9/29/2007 |
Q: We have a reversible capacitor start 230 VAC single phase motor. It is manually switched with a ... A: The switch is wired incorrect, leaving one side of the 220 volt line energized, letting the motor ...
|
| Reversing Electric Dual Voltage Motors | 9/26/2007 |
Q: Are all dual voltage motors reversible through a drum switch. I am assuming the motor I have, GE Mod ... A: Sorry Bob for the delay, I've got a touch of the flu, and not been up to par. Here is a diagram for ...
|
| Reversing Switch | 9/24/2007 |
Q: I would like to connect a Westinghouse 1/3hp, single phase 110v, 6.2A Motor that states on the lable ... A: Without actually seeing the connection plate, it would be hard to explain the connection. This might ...
|
| 3 phase motors | 9/17/2007 |
Q: I'm from the UK working in Africa and using equipment from both Europe and the US. I'm not an ... A: Most motors rated for 230 volts will operate ok on 208 volts. You will have a slightly higher ...
|
| condenser fan wiring | 9/5/2007 |
Q: I have a 15 y/o central air unit in which the condenser fan failed. A direct replacement was ... A: Yes. But you will still need to use the double capacitor to run the compressor. Put the black wire ...
|
| Mr. Slim | 8/31/2007 |
Q: I'm trying to put in a Mitsubishi Mr. Slim (24,000) btu heat pump. The outside unit calls for ... A: Use the black and white wire for your 230 volts. the bare wire will connect to the grounding bar in ...
|
| 3 phase power supply to single phase power supply | 8/30/2007 |
Q: i would to know the correct method to split a 3 phase power supply to single phase power supply ... A: Each Leg of the three phase service can be used for single phase, as long as each leg is equal in ...
|
| drum switch wiring | 8/20/2007 |
Q: Charles I have read so many different answers, I'm thoroughly confused as to how to wire this. ... A: handle a 1 b c 2 d e 3 f To test switch, disconnect ...
|
| Dimming lights | 8/2/2007 |
Q: I have some lights dimming in the house when I turn on other items and it is a concern. Everytime I ... A: Your dimming problem is caused by a drop in voltage, when something with a large current draw ...
|
| Bandsaw 3P 415V motor | 8/2/2007 |
Q: I am currently having a bit of a snag with the motor of a bandsaw. First of all the electromagnetic ... A: My best guess would be a single phase condition, or either a turn to turn short in the windings. ...
|
| a.o. smith motor wiring | 6/27/2007 |
Q: S# c56a04a19 Ser 2j01 type c. want to run 110 volts clockwise. no need to reverse. Has 8 wires ... A: Because this is a specialty motor, I have no info as to the correct wiring diagram. They are not ...
|
| Single Phase Motor | 6/24/2007 |
Q: I have two identical single phase capasitor starting motor with centrifugal switch in them.. The ... A: Your connection is correct. Motor B has a problem, either in the windings or the start switching ...
|
| calculation | 6/20/2007 |
Q: I have a motor of 1 hp single phase but there is no capacitor rating on motor so i want to know how ... A: I know of no way to size a motor capacitor, other than trial and error. Capacitors are sized at the ...
|
| AC Internal wiring | 6/8/2007 |
Q: I have a Magnetek (century),5hp,single phase,230VAC,2 capacitor motor that has all wires pulled off ... A: Have a look here, ...
|
| 6-pole drum switch | 6/7/2007 |
Q: Sorry, it's me again, I guess I neglected something when I sent my question to you. I see that your ... A: The connection you looked at has a internal overload (P1&P2) If you don't have those, just ...
|
| hospital grade wiring | 6/6/2007 |
Q: I received a treadmill that runs on 230VAC, 12 amps. The plug has three prongs (line, neutral and ... A: On a 230 volt single phase circuit, the "neutral" is the ground. If you remove the covers from your ...
|
| whole house fan | 6/3/2007 |
Q: I have a Dayton motor, three leads plus ground, T-1 line , T-2 high, and T-4 low...I need to wire ... A: O O T2 O O L1 (black from timer) O ...
|
| wiring diagram for an electrical switch on a 220V line | 6/1/2007 |
Q: How do I wire an on/off switch to turn a pump on/off on a 220V line? A diagram would be most ... A: Is this a three phase motor? If so, then you will need a 3 pole switch or disconnect,rated for the ...
|
| wiring diagram for an electrical switch on a 220V line | 5/31/2007 |
Q: How do I wire an on/off switch to turn a pump on/off on a 220V line? A diagram would be most ... A: You will need a double pole switch. Connect the lines from your breaker, white and black to the top ...
|
| Capacitor question | 5/31/2007 |
Q: I recently purchased a auto lift (used) that I'm having some trouble with. It doesn't lift to ... A: From what I can gather, you installed a start capacitor in place of the run. This is a no-no. The ...
|
| reversing switch | 5/30/2007 |
Q: I just purchased a Leeson Model # M6C17FB11H, 1/2 HP 115/208-230 V. to run my wood working lathe. ... A: What is the make and model of your drum switch? Maybe i can find a schematic of it. The dashed lines ...
|
| reversing switch | 5/30/2007 |
Q: I just purchased a Leeson Model # M6C17FB11H, 1/2 HP 115/208-230 V. to run my wood working lathe. ... A: Can you double check your drum switch connections? Every terminal should read to at least one more ...
|
| reversing switch | 5/25/2007 |
Q: I just purchased a Leeson Model # M6C17FB11H, 1/2 HP 115/208-230 V. to run my wood working lathe. ... A: In a single phase connection, the start winding determines the rotation of the motor. The start ...
|
| reversing switch | 5/25/2007 |
Q: I just purchased a Leeson Model # M6C17FB11H, 1/2 HP 115/208-230 V. to run my wood working lathe. ... A: You would need a reversing drum switch, like this one, ...
|
| reversing a motor thru a swich | 5/21/2007 |
Q: I would like the motor to reverse occasional and there is a jog forward switch can I change this ... A: What voltage are you going to use? Here is a diagram for a reversing drum switch, 230 volts, ...
|
| 115v to 22v motor | 5/21/2007 |
Q: I purchased a new spa pack (heater and controls)with 220v controls for a 2 speed motor. I looked at ... A: Not knowing how the heater and controls are connected, I would hesitate to try to answer your ...
|
| Motor housing dissassembly | 5/17/2007 |
Q: Charles, I recently "inherited" a small squirrel cage blower which I was hoping to use to make an ... A: Don, as you already know, it should have came apart after you removed the four thru bolts. I have ...
|
| Run and Start Capacitor | 5/12/2007 |
Q: Goodday.. What is meant by run and start capacitor? A: A run capacitor is used for reducing the amperage draw while the motor is under load. A start ...
|
| Lathe motor repair | 5/4/2007 |
Q: I have a lathe that I am attempting to repair. It runs a single phase 220v four pole motor. The ... A: Are you reading each wire to ground? No single wire should have 220 volts. If this is a single phase ...
|
| 3 phase motor connections | 4/30/2007 |
Q: Is there a way, using a multimeter, to read just the line connections, say at the contactor load ... A: I know of no way to tell using resistance readings, and if I did, your would need to know the ...
|
| START/RUN CAPACITOR TESTING | 4/29/2007 |
Q: MY OLD COMPRESSOR HAS A WESTINGHOUSE 11/2 HP TYPE FT 1725RPM sf1.15 ph1 v115/230 A14.4/7.2 ... A: The 540-600 is the start capacitor, and would be the most likely to cause your problem, but the run ...
|
| 3 phase motor connections | 4/27/2007 |
Q: Is there a way, using a multimeter, to read just the line connections, say at the contactor load ... A: Check the voltage at the contactor, and then look at how your motor is connected. For 230 volts, ...
|
| connecting 120vac motor to 220 vac single phase | 4/16/2007 |
Q: Mr. Jones, I have an air compressor with a 2 hp motor that is wired for 120 vac. I want to connect ... A: Connect black and white to the line side of the pressure switch. Connect a black and white wire from ...
|
| Motor wire connections to 6 pole switch | 4/15/2007 |
Q: I am wiring a boat lift motor to reversable 6 pole switch like what your scetch diagrams. I have ... A: I have received your question, and will work out a diagram for you. Paul, I'm sorry for being so ...
|
| reversing motor control problem | 4/10/2007 |
Q: I have a Marathon Electric 3/4 hp motor (model # 56c17f5326)that I'm trying to install. I'm using a ... A: I tried to find the switch using the number you provided, but no luck. As my company is a cutler ...
|
| 3/4 hp delco model A8525 | 3/20/2007 |
Q: This is an old 120/240 motor. The connecting studs are marked 1 thru 6. The wires out the motor ... A: It is very old! I have no info to find out which numbers are your start winding leads. This is one I ...
|
| Bremas Switch and a Dayton 6K346 | 3/11/2007 |
Q: I have a boatlift that had a MagneTek 3/4HP motor on each side for raising and lowering our boat. ... A: If you can remember which colored wires were connected to #8 and #5 on your leeson motor, disconnect ...
|
| Capacitor sizing problem | 3/8/2007 |
Q: I have a GE motor missing the capacitor. Is there a formula for calculating the proper size ... A: Sorry but no formula is available. Capacitors are sized at the the factory. Try a 200-250 ...
|
| 1-phase compressor motor | 1/17/2007 |
Q: I have an air compressor with a single phase electric motor on a 120v, 20 amp dedicated circuit. It ... A: I really don't like to test capacitors with a volt meter, it doesn't give a accurate reading. To ...
|
| DPDT reversing switch for Capacitor Start motor. | 1/13/2007 |
Q: I wired it as you had drawn, but either position of the switch trips the breaker. I removed the red ... A: You should have 6 wires coming out of the windings. Four of which should be labeled 1 thru 4. These ...
|
| DPDT reversing switch for Capacitor Start motor. | 1/7/2007 |
Q: I have an old 3/4 hp Delco motor Type CS which I assume means capacitor start. I would like to ... A: It seems your question was not delivered to my inbox, and the automated system sent me a email ...
|
| wiring a Single phase motor | 1/2/2007 |
Q: I am installing a roller shutter garage door. I have a "brooke crompton starter switch", and a 1/2 ... A: This is a generic wiring diagram for a drum switch. ...
|
| Four wires from an old single phase motor | 12/30/2006 |
Q: I found a Vaile-Kimes "Single Phase Repulsion Induction" Motor, (Plate states 110 Volts,60 ... A: First, sorry for the delay, due to holidays. Without numbers or something to go by, I have no idea. ...
|
| 220v single phase motor to switch wiring | 12/15/2006 |
Q: This looks like a great site and I apologize if I missed the answer I am looking for in my earlier ... A: Vic, inside your starter (switch) is a coil. This coil must be energized for the contacts to come ...
|
| PSC Motor Reverse Rotation | 12/15/2006 |
Q: Charles Thanks for your prompt answer to my question. When you say reassemble the motor backwards do ... A: The switch will be mounted on the endplate where the wires come out. It will have two wires ...
|
| PSC Motor Reverse Rotation | 12/13/2006 |
Q: I need to reverse the normal rotation of a Permanent Split Capacitor Motor. This motor has an arrow ... A: If this motor has a internal switch, it is non-reversible, as they will be marked on the nameplate ...
|
| tried reversing but wrong | 12/13/2006 |
Q: I have a question about a similar motor you've already answered. on my dual voltage 3HP motor has ... A: Your motor is not field reversible, if it doesn't say so on the nameplate. Compressor motors, like ...
|
| Reversing single phase motor with drum switch ? | 12/11/2006 |
Q: I have an old british pillar drill, originally 3phase, now fitted with a single phase motor. Using ... A: This diagram here, http://static.flickr.com/59/187576722_f686c5884a_o.jpg This diagram shows ...
|
| Another reversing switch question | 12/5/2006 |
Q: I did see these drawings from answers to other questions. My problem seems to be that the start ... A: Randy, first disconnect your rev. switch from the motor, and rewire it for a standard connection, ...
|
| Another reversing switch question | 12/3/2006 |
Q: Have a Dayton 3/4 hp 120 / 240 volt motor (4K859BA). Wired 120 volt. When connected to the reversing ... A: It looks like you have a problem in your start winding connection. Have a look at these wiring ...
|
| wiring 220v Baldor motor to reversing cam switch | 11/26/2006 |
Q: Charles, I'm trying to wire a Baldor #L3504 motor (220v) to a Bremas reversing cam switch. The ... A: Robert, to be honest, I have never had a opportunity to see one of these type switches. Looking at ...
|
| Extractor fan motor wiring | 11/26/2006 |
Q: I removed an extractor fan to have it cleaned. I and never noticed at the time that it has 3 wires ... A: It would be hard for me to advise you on this, because I don't which color is common out of the ...
|
| correct wiring to motor single phase | 11/20/2006 |
Q: 1 wire to earth 1marked u 1marked v on switch drawing is neutral wired to u and live to v. A: You will have to be more precise with your question. As I am in the USA, we do not use the letters U ...
|
| 2 speed motor stuck in hi speed | 11/19/2006 |
Q: I have a GE 2 speed motor (Mod #5KCR49WN2340X) that is on a hot tub. As soon as power is applied it ... A: This sounds like a switching problem to me. There should be a diagram on the motor itself, showing ...
|
| Reverse wiring motor for lathe | 11/17/2006 |
Q: The switch is a Dayton 2x440a. Do I remove the wires from the terminal block on the motor and take ... A: Yes, you will have to remove the wires (1, 4, 5, 8) from the terminals. You should be able to use my ...
|
| Electric motor application | 11/16/2006 |
Q: Would a single phase motor of like horsepower from a compressor be one that could be used on a ... A: Most compressor motors are 3450 rpm. Lathe motors are usually 1750 rpm. It will turn really, really ...
|
| reversing old motor | 11/5/2006 |
Q: I want to reverse a old electric motor. It's a Centry 1/2 h.p. The wires are labeled 1-5. 1,2,5 are ... A: You seem to be one wire short. You need to have a wire labeled #8. This motor must be really old, ...
|
| Motor wiring | 11/2/2006 |
Q: Charles- The info on the plate is Type RL FR 2B5G HP 1/6 V115 5 AMP RPM 1725 Ph 1 ... A: John, it seems that you may have a condensor motor, if you do not have a outside connection plate. ...
|
| Motor wiring | 11/1/2006 |
Q: Yes I was not sure about the horsepower being enough but was going to use it for something else ... A: John, it seems that you may have a condensor motor, if you do not have a outside connection plate. ...
|
| electric motor is connected for 110 or 220? | 10/28/2006 |
Q: I bought an old compressor with a 2hp single phase motor. There is no wiring diagram. The leads in ... A: Peter, your motor is connected for 220 volts. For a 110 volt connection, connect 1,3,S for line ...
|
| is a motor going bad | 10/25/2006 |
Q: I'm looking for some kind of predictive measure to help predict a failure before hit happen . I ... A: Motors running under a normal load will produce a certain amount of heat. Most motors have a cooling ...
|
| 500' circuit run | 10/25/2006 |
Q: I have decided to take your advice and run electrical service to the barn. In my county I am able to ... A: Whats ok here in my part of Alabama may not be ok in your state. For a 100 amp service here, a #8 ...
|
| electrical motor- changing rotation | 10/25/2006 |
Q: I just sent you a question about changing the motor rotation from ccw to cw and dicided to take ... A: Now we got something to work with. Connect it to your desired voltage, and to reverse rotation, swap ...
|
| is a motor going bad | 10/24/2006 |
Q: What a ways that a person can tell if a motor is going to fail in the near future (say within a ... A: Check the current draw of the motor(Amps) with the nameplate rating for a overload problem. Are the ...
|
| 230v single ph. motor for compressor | 10/22/2006 |
Q: Have a Ajax motor that the wires got pulled off when it was being loaded.It has 2 capacitors on ... A: First, are the wires pulled out of the windings itself? If so, then it would be far to complicated ...
|
| Wiring a reversing switch to a 110V motor | 10/21/2006 |
Q: my motor has P-1 to line 1; Blue connected to T1; Black, P2 and Orange connected: Red,white and ... A: Have a look at these diagrams and see if they can help you. ...
|
| 115V, 2Hp, 2 speed, GE Motor - no Hi speed | 10/20/2006 |
Q: I just got a hold of a 115v 2Hp 2 speed GE motor that I would like to use for a water pump project. ... A: I'm not sure what you are refering to, when you sau Ov to hi or lo. The white wire from your 115 ...
|
| 3 phase not working after power compay visit | 10/17/2006 |
Q: I have a small shop with 3 phase power to my lathe, band saw and milling machine. One leg of the ... A: It sure sounds like your single phasing. You have completed all the tests I would recommend. The ...
|
| 500' circuit run | 10/11/2006 |
Q: We plan to hook 2 110 volt 15 amp circuits onto my home electric. They will both be about 500 feet ... A: Man, that's a mighty long run. You might come out cheaper having your power co. set you up another ...
|
| contactors and motor starters | 10/11/2006 |
Q: what is the difference between a contactor and a motor starter? A: Ray, contactors and starters a basicaly the same as operation goes. They both utilize low voltage to ...
|
| reversing my elect motor | 10/10/2006 |
Q: Yes it is a drum switch.Thanks for the help, but there seams to be 6 connections in your drawing. I ... A: Every manufactor has differences in the way thier motor is connected, that is, the wiring for thier ...
|
| reversing my elect motor | 10/9/2006 |
Q: but there seams to be 6 connections in your drawing. I do not know what type of switch I have only ... A: The drawing I provided has the line voltage connected at the drum switch. (L1&L2) This assures that ...
|
| reversing my elect motor | 10/8/2006 |
Q: I have purchased a new single phase motor as a replacent. The replaced GE motor was reversed using 4 ... A: From your question, I assume you are refering to a reversing drum switch, as you said you know how ...
|
| My new 3 phase service and motors | 10/8/2006 |
Q: I am in the process of hooking up a 3 phase service to my shop. The saw I intend to get has a 230 ... A: I recomend you go with the 120/240 service. Most modern motors are rated for 230 volts. Using a 230 ...
|
| generator/air comp. | 10/7/2006 |
Q: I have a 5500/8500 gen. using the locking 240 4-prong plug connected to size 10 to a ... A: Robb, it seems that your wiring to the compressor is incorrect. I believe your compressor is trying ...
|
| Where to find local or mail order capacitor? | 10/7/2006 |
Q: yes this a run starter,can u please help?I have been looking for this part for a month now and I ... A: David, seems like you didn't get my previous answer. I apologize for that. And if you did, here's ...
|
| Type KC 1/3 motor for South Bend Lathe | 10/5/2006 |
Q: OK Charles, I do have a follow up.. I went back and looked at your NEMA wiring standard and then ... A: Yes, the ends of the start winding are probaly located behind the switch connection plate. They ...
|
| Type KC 1/3 motor for South Bend Lathe | 10/4/2006 |
Q: I acquired an older 9" South Bend lathe with a Type KC 5KC17AB899A motor..It says 120 / 220.. this ... A: I'm not sure what your asking. Can you be more precise in your question? I cannot, because of the ...
|
| Electric Motor Rotation | 10/3/2006 |
Q: We have a single phase, 220 volt grinder. It uses two 115 volt phases to get the 220. The two ... A: Reversing wires on a 220 volt, or 110 volt circuit will not cause a reversed rotation. Only ...
|
| motor reversing | 10/2/2006 |
Q: I HAVE A SIMILAR PROBLEM AS 7/11/06SINGLE PHASE LATHE. I HAVE A 1HP MOTOR RUNNING ON 220.IT IS GE ... A: I recieved your question, and will upload a diagram to show you how to wire your drum switch. I will ...
|
| DAYTON MOTOR | 10/1/2006 |
Q: I HAVE A DAYTON 1 HP REVERSABLE MOTOR MOD 5K432E IT IS WIRED FOR 115 VAC WOULD LIKE TO GO TO 220 VAC ... A: I have no info for this motor. It is a discontinued model from ww grangier, who made it. the only ...
|
| Troubleshooting 3 phase motor | 9/28/2006 |
Q: Could you suggest a line of investigation? The amperage is unbalanced on a motor load. 230 3 phase, ... A: I believe you are right in your thinking. Have you checked each leg to ground, for a individual line ...
|
| Capacitor for dayton motor | 9/27/2006 |
Q: I have a 2hp Dayton model 6K313H electric motor that i need a capacitor for,could you please give me ... A: Unfortunatley, there is no " look in the book answer." Put 5 motors side by side, from different ...
|
| replacing a capacitor | 9/26/2006 |
Q: Charles, Thanks for the quick and detailed response to my question. I seem to have something a ... A: The wire you are asking about has to connect to one side of the switch located inside the motor. to ...
|
| run a single phase w/ 3 phase power | 9/25/2006 |
Q: I have 208 3 phase power in my plant. My new machine coming in has a motor stating 220 VAC, ... A: Yes. From what little information you gave, it seems you will be using a 10HP single phase motor. I ...
|
| Electrical wiring | 9/25/2006 |
Q: I am in British Columbia. I am installing a hot tub having a 240vac 50A requirement about 150ft ... A: #4(copper 140amps, aluminium 110amps) will be more than enough to handle the amperage shown. I'm ...
|
| replacing a capacitor | 9/24/2006 |
Q: I recently bought an automotive vehicle lift from an auto repair shop. After assembling the huge ... A: I am going to assume that this is a single voltage motor, set rotation. If this is correct, lets ...
|
| How to read a voltmeter | 9/21/2006 |
Q: I am borrowing a Meterman DM7, but not sure how to read it. I am planning on making a haunted house ... A: You are reading 123.5 volts. You will have to use a amp meter to read your current draw, or amps. ...
|
| wiring Baldor PCL3519M electric motor | 9/18/2006 |
Q: Ok, I've followed the wires back to the breaker box. The red and black wires from the outlet are ... A: You can disregard the white wire. Tape up the end so it is insulated, and won't contact any ...
|
| wiring Baldor PCL3519M electric motor | 9/18/2006 |
Q: I have single phase power. Thanks.I have a 3 HP Baldor PCL3519M electric motor. I'm looking at the ... A: The reason I was asking if you had three phase is that you have to many wires. You will need to ...
|
| Dayton Motor Wiring Question- Reversing | 9/10/2006 |
Q: I have a Dayton capacitive start 1HP 115/230V 3450rpm motor (Model 9K4550). The wiring diagram on ... A: What you have is a "set" rotation motor. My guess is this was originally a pump or compressor motor. ...
|
| Wiring forward/reverse 3 phase switch | 9/6/2006 |
Q: Just bought a used lathe and it came with a forward/reversed/stop switch installed on the machine. ... A: Tim, looks like you are describing a pushbutton controller that operates a set of reversing ...
|
| 1 phase 220V Motor Reverse Wiring | 9/6/2006 |
Q: I have a John S Barnes 2HP 1 Phase 208-230V motor. It has a direction of rotation sticker on the ... A: What you have is a "set rotation" motor. It is connected this way so someone can't reverse the ...
|
| Variac | 9/2/2006 |
Q: While this question does not involve motors, your profile appears to be among the most qualified on ... A: Actually I do use a "Variac", which is really just a trade name, for a variable autotransformer ...
|
| 3 phase 230 motor | 8/31/2006 |
Q: how to wire in an on/off switch,do i use a triple pole single throw switch? A: That will depend on the HP of the motor. A motor starting across the line will have a very large ...
|
| Furnance blower motor problem | 8/30/2006 |
Q: I have a 120V furnace blower motor that hums, but won't run. The axle spins freely. I removed it and ... A: That cap. test is not totaly reliable. I would purchase a new one, as they are not expensive, and ...
|
| how to wire blower motor | 8/29/2006 |
Q: I have an old air handler with emergency heat strips in it that I would like to wire up to my ... A: I would wire them seperately. Having them both start at the same time will put a serious load on ...
|
| auto blower motor/switch | 8/25/2006 |
Q: I have a 2001 sebring limited convertible. The blower motor suddenly stopped working on speeds ... A: Although auto motors are out of my expertise, this is probaly a switch problem. If the motor runs ...
|
| wiring a 220 VAC electric motor | 8/24/2006 |
Q: Sorry, I should have included this information in my first question. The motor I am wanting to wire ... A: Connect the black wire from your power to P1, and the white wire to T5 and T4. If the motor is ...
|
| compressor hard to start on generator | 8/8/2006 |
Q: I have a 6500W generator and I am trying to run an air compressor. Sometimes it will start ok but ... A: Sorry for the delay in answering, but I didnt get it originally. Have you checked the actual output ...
|
| Testing 3 phase motors | 8/6/2006 |
Q: How do I test or more importantly what results should I expect on a good motor when testing a 3 ... A: Test each phase for continuity to the others. If any one phase fails to read, you have a open ...
|
| Using a 1phase in a 3 phase motors place | 8/1/2006 |
Q: If I have a 5hp 3 phase motor, what size 1phase motor would I have to repace it with ? A: 5 HP. Just be sure your circuit is large enough. A 5 Hp single phase motor will pull 56 amps on 115 ...
|
| Single phase trouble shooting | 7/24/2006 |
Q: I have a 1 hp single phase cap start and cap run motor to run my air compressor. It is approx. 5 yrs ... A: First of all, the reset button. If you tried to reset right after it quit, it may have still been to ...
|
| Carrier Condenser Fan Motor Not Turning | 7/20/2006 |
Q: Charles- I have a Carrier 38ED036300 (vintage 1986) Split system. Today, the compressor fan stopped ... A: First of all, the capicitor is a run capacitor. It is always in circit with the windings. The only ...
|
| motor wiring | 7/19/2006 |
Q: i bought a south bend lathe and the person i bought it from said that it was a 440 3ph 4.5hp motor. ... A: I have no idea what you have. Unless it is a special motor, I have never saw a 4.5 hp motor. Most 2 ...
|
| 3 Phase Motor Question | 7/16/2006 |
Q: I recently acquired a sander with an Italian 440 volt 60hz 3 phase motor, it is 2 speed, 1750 & 3450 ... A: If you only have six leads out of the motor, you will not be able to run on 208 volts. Depending on ...
|
| 3 phase motor connection | 7/14/2006 |
Q: I have a freind who said that you can connect a 3 phase motor to a single phase line. In this case ... A: You must have three lines of power to use a three phase motor.A phase converter, using either solid ...
|
| wiring a 220 switch | 7/12/2006 |
Q: I have a Arrow Hart Manual Controller Switch, it's basiclly an ON/OFF switch(looks like a regular ... A: It seems that you have a 3 pole switch. Wire it this way, on the right side, holding the toggle ...
|
| SINGLE PHASE LATHE | 7/11/2006 |
Q: WE HAVE A SOUTHBEND LATHE,IT HAS A GENERAL ELECTRIC 3/4 H.P 230 VOLT, SINGLE PHASE MOTOR ON IT. WHEN ... A: Bob, #1 and #4 by NEMA standards are where you connect your power. The standard connection for 230 ...
|
| SINGLE PHASE LATHE | 7/6/2006 |
Q: WE HAVE A SOUTHBEND LATHE,IT HAS A GENERAL ELECTRIC 3/4 H.P 230 VOLT, SINGLE PHASE MOTOR ON IT. WHEN ... A: Installing a reversing switch on this type of motor requires disassembly of the motor. It is also ...
|
| How to connect 3hp. peerless electric motor up ? | 7/2/2006 |
Q: The motor plate show 115/230 60gyc 36/18 amp C2243A is the serial number alternating current double ... A: I'm not familiar with the lead markings of this particular motor. This must be a very old motor, to ...
|
| 1 phase motor windings | 6/25/2006 |
Q: I have a question about testing single phase motor windings. What would be a typical ohm reading ... A: Jorge, unless you know the winding data of the particular motor you are testing, it is impossible to ...
|
| replacing bathroom light/fan vent | 6/24/2006 |
Q: I had a motor on a vent fan go bad.The unit is wired where one switch controls the light and the ... A: You have one of three possible problems. No voltage, bad switch, or bad motor. Just because its new ...
|
| wiring start & run capacitors to a 220v motor | 6/22/2006 |
Q: Can you show me how to wire two separate start & run capacitors to a 220v electric motor with ... A: I apologize for taking so long to get back to you, but I have been on vacation. To answer your ...
|
| a/c condenser fan not running | 6/11/2006 |
Q: Charles: I have 1/6 hp one phase 0.9 amp motor. I disconnected motor wires and checked continuity ... A: It seems my original answer may have not been sent. Not knowing the wiring data in the motor, it ...
|
| 220 single phase motor on a 208 3 phase circuit | 6/6/2006 |
Q: Is there any problem using a 220v single phase motor on a 208v 3 phase circuit? A: Yes it is possible, using only two legs of the three phase circuit. Be advised though, that the ...
|
| Motor Run Capacitor | 5/29/2006 |
Q: I have a 1/2 hp motor which appears to be permanent split phase (single cpacitor, no centrifigul ... A: Alan, I have not come across any set rules on capacitor sizing. all manufactures use different ways ...
|
| 50/60 cycles | 5/24/2006 |
Q: I am in Afghanistan and I would like to know what will happen if I run a 2oo V 50 cycle refrigerator ... A: Ted, before I get to your problem, I believe you must be a Military Person. First let me Thank You ...
|
| I just visited a site that... | 4/28/2006 |
Q: I just visited a site that talked about capacitors, but was dissappointed, cause they didn't go into ... A: Almost, but not all, single phase motors use capacitors. There are two different types. One is a ...
|
| ok give the generator | 4/22/2006 |
Q: ok give the trype of protection for generator and thank you for you effort A: This is my last request for information on what you are asking me. "Protection is to general" What ...
|
| Voltage spike and flickering | 4/19/2006 |
Q: I am not certain this question is in your area of expertise but I am hoping you will have some ... A: Marc I'm afraid that your circuits are maxed out. Even if it is a small apartment, two circuits are ...
|
| Single phase motors | 4/12/2006 |
Q: I work as a tech and I came across a single phase motor 2 caps (start and run external) its a simple ... A: It sounds like you have a open circuit in either the start or run windings. Inside the motor is also ...
|
| testing of 3 phase motors | 3/25/2006 |
Q: how do you do an insulation test using a megger on a motor A: To use a megger, connect to the line side of one of the motor leads with the red test lead. Connect ...
|
| 3phase to single phase motors | 3/8/2006 |
Q: can you help me to wire a motor to single phase. the motor in question is wired for 3 phase. i have ... A: I'm sorry Terry, but you can't use a 3 phase motor on single phase unless you use a phase converter. ...
|
| three phase electric motors | 3/1/2006 |
Q: I WANT TO PURCHASE A LARGE PRE-WAR AIR COMPRESSOR AND INSTALL IT AT MY WORK. THE MOTOR DRIVING THE ... A: Bill, my first question to you would be, where are you located? That you have 3 phase power in that ...
|
| 1 ph motor wont start but will run with a turn. | 2/11/2006 |
Q: i have an old motor used for grinding. it wont start by the switch, only when you spin the shaft. it ... A: First, I need to know what type capacitors you have. Some motors have both start and run caps. ...
|
| Hi-Pot | 1/13/2006 |
Q: I've worked in electrical maintenance and have heard the term "hi-pot" used when talking about motor ... A: "Hi-Pot" is a insulation test using DC voltage. We very seldom use this particular test anymore in ...
|
| 3 phase motor wiring (lathe) | 1/12/2006 |
Q: I have a lathe with a three phase 5hp motor. I am tring to wire it up. I have 3 cutler hammer ... A: Your best bet would to do away with all those contactors, and install a forward and reverse drum ...
|
| electric motors | 8/20/2005 |
Q: ..charles c jones what is normal temperature for motors A: Without knowing your specific application, I would be reluctant to describe what is normal. Most ...
|
| Motor won't start | 6/17/2005 |
Q: I have a ventilater which hasn't been run in about a year. It's a Loren Cook Belt drive. The motor ... A: If this motor is a capacitor start, you may have a bad capacitor. It is possible that trash may be ...
|
| ambient temperature | 5/11/2005 |
Q: I am working as an Electrical supervisor in India's leading tyrecord fabric manufacturing company ... A: Ambient Temperature is the is the atmosphere temperature surrounding the apparatus. This does not ...
|
| 3 phase motor- single phase | 3/20/2005 |
Q: I heard of people connecting a 3 phase motor to single phase supply with the use of capacitors. Have ... A: First let me apologize for the delay in answering. There is a way to do this, but at the moment I ...
|
| drawing power | 3/11/2005 |
Q: Can you give me an answer how a motor draws power from a transformer. I cannot see how the motor ... A: I'm not quite sure what your asking here. I will confess that i"m not a engineer, but maybe if you ...
|
| Switch Wiring for 220V Motor | 2/2/2005 |
Q: I am in the process of rebuilding some shop tools that are driven by 220 VAC motors. One of these ... A: Looking at the connections you gave, it looks like that maybe you have a motor with both start and ...
|
| 5 hp motor | 1/15/2005 |
Q: I have a 32 gallon compressor run by a 5hp electric motor. It runs off 120 volts ac but I was ... A: http://www.voltageconverters.com/customkititems.asp?kc=PBI3500-0AWG Have a look at this. Quite ...
|
| 4 general motor questions | 12/15/2004 |
Q: I've always assumed the motor used in these applications was a synchronous motor...it operates on AC ... A: As load increases in a induction motor, the current also increases. If the load continues past the ...
|
| 220volts to 208volts | 11/17/2004 |
Q: got a good deal on a convection oven that is rated at 208v 15amps single phase. can it be used on a ... A: Let er rip! no problem there, as most any electric products will take a variance in voltage. A ...
|
| Chuck,
I have a snow blower... | 10/23/2004 |
Q: Chuck, I have a snow blower that was given to me, alright fine I pulled it out of the garbage. I ... A: Whast you have there is a bridge rectifier. What it does is convert ac to dc. To test it, ...
|