AllExperts > Electrical Engineering 
Search      
Electrical Engineering
Volunteer
Answers to thousands of questions
 Home · More Electrical Engineering Questions · Answer Library  · Encyclopedia ·
More Electrical Engineering Answers
Question Library

Ask a question about Electrical Engineering
Volunteer
Experts of the Month
Expert Login

Awards

About Us
Tell friends
Link to Us
Disclaimer

 
 
 
 
About cleggsan
Expertise
All technical areas of Electronics Engineering.

Experience
BSEE, MBA, Design, R&D, University Research.
Senior Life Member of IEEE. Life Fellow of AES.

Organizations
IEEE, Consumer Electronics Society, Audio Engineering Society.
Broad teaching experience; work experience mostly in consumer electronics and conversion from analog to digital technologies. Pioneer in digital audio at all levels.
 
   

You are here:  Experts > Computing/Technology > Job Searching: Technical > Electrical Engineering > Meggering

Electrical Engineering - Meggering


Expert: cleggsan - 12/16/2006

Question
Dear all
Just now I meggered a compressor winding for 15 HP AC.Two compressores actually.For compressor 1, R-Y(0.2 ohm),Y-B(50 ohm),R-B(60 ohm) and for compressor 2 all phases are 0.82 ohm,which I concluded balance fpor each phase where as for compressor 1 not balance.Now I have a doubt since from theory the one with low ohm could be shorted but when I tested and replace the timer,top up the gas,this compressor can run(comp 2).Seems the 'shorted' compressor is OK.For compressor 1, we didnt test but it could be faulty since the phases ohms are not balance,or might be 1 phase is faulty.

1.Which one is consider faulty?

Answer
I am confused. Meggering is usually for testing insulation qualities from windings to case or winding one to winding two. In normal conditions the resistance is very high - in the megohms or millions of ohms.  That is why they call it meggering.  If there is an insulation short or leakage the resistance will drop down to something much less - or to a short which is near zero ohms.

The resistances you are reporting are more like the winding resistance.  And, you did not say if the unit was removed from external connections.  And, did you rotate the shaft to different positions and take more measurements?

So, I think you need to do more checking and make the test conditions more clear for better understanding of exactly what you were measuring.

Cleggsan