| Subject | Date Asked |
|
| extension box | 11/21/2009 |
Q: I would like to know if it exist in the market a extension box to permit extention (connecting 3 ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| wiring combination switch outlet | 11/20/2009 |
Q: I have an older wiring installation, hot and neutral only, no ground. Old combination single pole ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| wiring circuit | 11/19/2009 |
Q: I have power to outlet "B". There are outlets "C" and "D" to the right, and outlet "A" to the left. ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516-16765 * LIFE SAFETY ...
|
| potential shop power need | 11/18/2009 |
Q: I am anticipating building a relatively small shop to house: three 3-phase Oliver machines [mdl ... A: You need to contact the utility "new service department" or whatever they call it where you are. Try ...
|
| Electrical light problem | 11/17/2009 |
Q: I had a room wired and when I installed the light, it will not turn off. I have continuity to the ... A: something is missing here How is it you have 2 white and three black wires? [or 2 black, 2 white and ...
|
| amps volts | 11/9/2009 |
Q: Hi I have changed most of my appliances plus from australia to uk they only worked for a coupke of ... A: Sorry. I don't know ANYTHING about UK and Australia electricity, not even voltage levels. What I ...
|
| 3 way single pole and 3 way combo | 11/3/2009 |
Q: I replaced my light switches, a single pole 3 way and a single pole 3 way combo near the basement ... A: Though your description is unclear - [really] - I have derived the impression that there are THREE ...
|
| static phase converter | 11/1/2009 |
Q: I have a lathe with a 3 phase 7 1/2hp motor . I have run #10 wire 220v single phase to the ... A: Contact the manufacturer. By the way, did you know that most sources state something similar to the ...
|
| gfci tripping | 10/26/2009 |
Q: I have a gfci that began tripping with no obvious explanation; no new changes on the the circuit, no ... A: Hang any new pictures? Install any new molding? Basic troubleshooting is required. Something finally ...
|
| Electrical | 10/24/2009 |
Q: Robert, another person asked Don, about his planned 400' electric run out to his dock, Don gave him ... A: According to the NEC 250.4 and 250.32, as I understand it in this circumstance, it is required to ...
|
| high voltage | 10/22/2009 |
Q: i just bought a house an the voltage at sockets shows 144 to 148 on meter,what do you thinks the ... A: That's high. Call the utility before you burn something up, like your TV, due to overvoltage, which ...
|
| testing | 10/21/2009 |
Q: Just wondered if you could try and explain to me the difference between a continuity test and an R1 ... A: sorry-don't know what you mean by R1-R2 test also, what is a strapper? intermediate switch? [we have ...
|
| Erratic operation | 10/19/2009 |
Q: My dusk to dawn light fixture has worked good for years. The bulb gave out. I replaced it. Now It ... A: Often, when the bulb is allowed to failed completely and remain so for any period of time, the ...
|
| emt conduit | 10/16/2009 |
Q: I have a broken, pot metal emt coupler in the middle of my main conduit from the meter to the panel. ... A: I am not aware of an electrical manufacturer that makes such a gizmo, though they would occasionally ...
|
| Neutral wire | 10/14/2009 |
Q: I had previously asked Robert a question about a 2/0 aluminum wire being too large for my neutral ... A: Why are you suddenly installing a larger cable than existed in an obsolete panel, pray tell? ...
|
| ENT / Orange Smurf | 10/3/2009 |
Q: I'm running the orange version of smurf tube for some low-voltage wiring going from basement to ... A: Since the purpose is to reduce or prevent noise from induced current, it is best to keep as far as ...
|
| Electric stove - hotplate only gets warm | 10/2/2009 |
Q: One of the hotplates on my electric cooktop refuses to get hot! It will only become somewhat warm ... A: If it works at all, the wiring and socket should probably be ok. I would think it is probably the ...
|
| 240 in a 120 outlet | 10/1/2009 |
Q: Greetings from a fellow "Expert" (computers, not electrical stuff). I apologize for the length of ... A: Bummer... My bet is that the cable with the red and black has 240v between the red and black. Either ...
|
| 50 Amp Spa | 9/23/2009 |
Q: I plan to install a 50A 240V GFCI spa kit about 60 feet from the main panel. I think I need to use ... A: White? You need a neutral too? I take it you were planning on using copper THHN at 90 degrees? Most ...
|
| 240V electrical heater | 9/20/2009 |
Q: this heater has only black and red wire (of course, it also has a ground wire). I used #10 (black ... A: Why #10? Why 3-wire? There is no neutral in straight 240v applications. Cap the white. You don't ...
|
| Standby generator install | 9/19/2009 |
Q: Greetings, and thanks in advance for volunteering your skills to help someone out. I am looking to ... A: It doesn't matter where you put the transfer switch, you have to bring house power to it anyway. ...
|
| stalling baseboard heater and double pole thermstat | 9/18/2009 |
Q: 1 is 1500 watts 2nd 750 watts 240 volts baseboard heater and thermostat in my attic room can you ... A: 12 gauge, 2-pole 20 amp breaker WIRING DIAGRAM? You probably shouldn't be doing this yourself... * ...
|
| Electrical outlets not working | 9/16/2009 |
Q: I came home and tried to turn on the tv.. wouldn't turn on. then discovered that three outlets as ... A: You need a loop - transformer-hot-load-neutral-transformer It is a bad connection someplace. Could ...
|
| wiring affecting tv? | 9/12/2009 |
Q: We have an unusual situation. Several of our TV stations tend to get fuzzy while we are watching. ... A: Ghostbusters...... Sounds screwy to me. It may be that turning on the light in the next room seems ...
|
| electrical outlet problem | 9/10/2009 |
Q: I have two upstairs bathroom outlets that don't work when I plug in a hair dryer. The circuit ... A: yeah. weird Turn ther breaker off and on and see if that helps Also, trip and reset the GFI device. ...
|
| Power goes out on part of my house, but no breakers are kicked out... | 9/9/2009 |
Q: i am remodeling my kitchen. i installed a new dual oven range, and a new microwave vent above it. I ... A: It could be many things. Breakers that are dead wouldn't happen to be every other breaker pair, like ...
|
| telephone wiring | 9/8/2009 |
Q: Upon close examination of the exterior of our house, it appears the previous owners had installed 3 ... A: Maybe they had rented out rooms or had an office in the house, so you got more than one network ...
|
| help with wiring dimmer switch | 9/7/2009 |
Q: please explain the correct wiring for the ceiling light that connects to the dimmer switch in the ... A: Your photo didn't come through It can't be that hard anyway. It is just a switch and a light I will ...
|
| detached garage sub panel | 9/6/2009 |
Q: I was reading one of your responses on allexperts.com and I was curious about a situation I'm having ... A: According to the NEC [250.32] it is required that multiple buildings under common management [your ...
|
| Question | 9/3/2009 |
Q: Someone suggested I get a digital voltmeter to see what voltage is really coming into my house. What ... A: Can't speak for Ideal meters. The only tester I ever had of Ideal's was the yellow solenoid-type ...
|
| house wiring | 9/2/2009 |
Q: I have a (light) switch controlled receptacle, actually 1/2 half of the receptacle is controlled by ... A: Of course it is possible We have walked on the moon It will not necessarily be easy though Best ...
|
| Question | 8/31/2009 |
Q: I have an old Wadsworth service panel and it has "with ground fault interruptor" written on it. It ... A: Well, I thought I had seen about everything. Never ran across one of those. GFIs are great, even if ...
|
| recessed lighting | 8/23/2009 |
Q: i have a north/west facing living room thats pretty dark most of the time. we use it as a library ... A: You are opening up a real can of worms You need to decide whether you are creating real ...
|
| dryer troubleshooting | 8/22/2009 |
Q: Sir, I am a mechanic in the military so I know a bit about troubleshooting. However, I recently ... A: As in all things in life, timing is evberything. Disconnect the heater element and see if the ...
|
| 220volts from 110v, outlets | 8/21/2009 |
Q: I need to test a 220volt oven for about 10 minutes or less . I don't have a 220 volt outlet and I ... A: naaaahh..... ...won't work Don't do it. The product of your idea creates a hazard. What do you hope ...
|
| high electric bills | 8/20/2009 |
Q: What can cause high ($500+) electric bills? I have checked everything, disposed of old refridges ... A: Is the underground wiring which you suspect before or after the meter? You say you clamped all the ...
|
| High Power useage | 8/19/2009 |
Q: Help can wiring cause a high power usage ? I have change out all appliances , water heater , air ... A: Weird-someone else just asked the same question same answerWhat can cause high ($500+) electric ...
|
| Intermitent Power Failures | 8/16/2009 |
Q: Robert: My house lights flicker periodically, and I lose power in most of the house for 15 minutes ... A: You have a power problem It is either your service equipment or the utility company's equipment If ...
|
| old house wiring to new outside light | 8/14/2009 |
Q: we have an older house and the wiring behind the light switch has only one hot wire and the new ... A: WHADAYA MEAN ... there is only one hot wire...?!? Are you telling me there is only one single ...
|
| how do you connect a double receptecle to a single light switch | 8/12/2009 |
Q: I have a light switch that turns on the light in my garage. I want to connect a double receptacle to ... A: Sorry There doesn't seemm to be enough info here Do you mean to tell me that there is only one cable ...
|
| Internal electrical brown out | 8/11/2009 |
Q: During a power outage I turned off the main and used a generator, plugged into an external house ... A: I suggest you look at the fact that it is evident that you don't know what you are doing. It is ...
|
| ceiling fan connections | 8/7/2009 |
Q: I want to install a ceiling fan in the garage. The wire colors from the switch are red, white & ... A: For the fan, blue is usually the light kit wire, black the fan hot, white the neutral. As far as ...
|
| low voltage problem | 8/6/2009 |
Q: I live in Western Australia. A number of outlets in one part of the house are not powering ... A: Not familiar with Australian wiring practice [thought I had thought of relocating at one time] DO ...
|
| Fan works fan light does not. | 8/5/2009 |
Q: Had a power outage. When power came back on the fan worked at one speed, the remote did not and the ... A: Sounds like the remote relay module blew up. With remote, chain does nothing useful-module controls ...
|
| I know there is a splice, but I can't find it...Help please! | 8/4/2009 |
Q: Okay. We inherited a very old house (1913 two story could count as three with the size of the ... A: No apologies necessary This mess is likely fed off another hidden splice, very possibly into the ...
|
| Garage Door Opener Keeps Burning Out | 7/31/2009 |
Q: I have 2 side-by-side garage doors with openers. Ten years ago when I built the house, the builder ... A: Maybe...but lightning is millions of volts and jumps 30,000 feet. You don't really believe you can ...
|
| undercabinet lights | 7/28/2009 |
Q: I would like to ask for assistance regarding kitchen undercabinet lights. I have a utilitech xenon ... A: Interesting and thoughtful consideration I recommend you contact the manufacturer and find out what ...
|
| Outlets | 7/27/2009 |
Q: I have two outlets that are dead. One is outside lower level. One is outside main level (directly ... A: You may believe all GFIs were checked, but outside recps says GFI... Either you have missed a GFI ...
|
| power out in only 3 rooms | 7/24/2009 |
Q: My daughter plugged in a vacuum in the living room. For whatever reason, the power went out in that ... A: The high current from the vacuum possibly caused an already poor connection to fail. You are lucky, ...
|
| intermittent voltage drop in house | 7/22/2009 |
Q: I am having a problem in my 200 year old house in West NJ, the house was wired with early Romex and ... A: Have you noticed any lamps getting really bright at the same time? You may have an open neutral. Go ...
|
| Outdoor Wiring for Radon Pump | 7/16/2009 |
Q: It calls for GFCI on ALL outdoor RECEPTACLES, but I am simply mounting a wall switch outside to ... A: A pump? It is a fan. You are installing a hard wired switch for a fan. No receptacle, right? [a ...
|
| Ceiling Light Comes On By Itself | 7/13/2009 |
Q: I had one ceiling light capped off when they were bldg. townhouse. One fan stopped working, cap had ... A: Is this stuff all on one circuit? You need to map out the circuit and find the first item on the ...
|
| Low hanging aerial service lines | 7/12/2009 |
Q: I'm not sure this is the place to ask this, but I've been researching for days and I can't find ... A: Six feet is too low. Likely utility problem and not a homeowner issue but contact the utility and ...
|
| Electrical for Boat Lift Motors | 7/10/2009 |
Q: I'm installing two 1hp 120-240V 13.6amp/6.8amp motors with protected (GFCI built into the plugs) ... A: Voltage drop on 10s is too high. You will need to keep within 3% recommended internal voltage drop. ...
|
| change old fuse box too breaker panel | 7/9/2009 |
Q: having a problem in the old fuse box the main lights fuse wires were 2 fifty amp fuses.i need to ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Replacing an old combo switch | 7/7/2009 |
Q: I'm trying to replace a switch/receptacle combo that broke. The switch runs the garbage disposal in ... A: What you are stating is mechanically impossible. There had to be more terminals and more wires [if ...
|
| short in bathroom wiring to light fixture | 6/30/2009 |
Q: Our Old fixture was flickering and then the light stopped working. We bought a new fixture and ... A: I take it this is a ceiling-mounted fixture? Drop the fixture and look for the place where the hot ...
|
| Plastic cable sleeves | 6/28/2009 |
Q: I am upgrading my electrical service from 100a to 200a. I have purchased a 200A panel and am ... A: An electricial contractor who is willing to change the mast and meter for you won't care what exists ...
|
| Outdoor lights go out after couple minutes | 6/25/2009 |
Q: I have four outdoor porch lights that I put up a couple years ago to replace older ones. The ... A: There is a bad splice somewhere you can't see then [assuming the wire didn't just break or get cut ...
|
| 3 way switch hookup | 6/20/2009 |
Q: I am trying to wire up 3 way switches. I understand the concept but here's my problem: In one box I ... A: Yes, you can do it. Treat each "3-way" operation as a separate job. On one set you send the hot ...
|
| Bad Electrical Outlet | 6/19/2009 |
Q: BAD ELECTRICAL OUTLET I have an outlet that is not working. I tested it and it tested as ... A: I suppose it used to work ok? Wire it the way it was originally Plug in testers give false readings ...
|
| pool bonding | 6/18/2009 |
Q: The pool was bonded and inspected. The rebar was bonded but not inspected. The inspector shot the ... A: Nothing Whoever approved the pour without the inspection being completed was in error. If they do ...
|
| Grounding old house 2 prong outlets | 6/14/2009 |
Q: Our old house has mostly 2 prong outlets. An electrician installed 3 wall lights that had 3 prong ... A: What your "electrician" has done is against the NEC. The ground prong opening should be blocked or ...
|
| 3-Way -THREE pendant problem | 6/12/2009 |
Q: I had a previous entry - newer problems... My switches keep blowing. I will attach what I have ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Subpannel | 6/11/2009 |
Q: A licenced electrician installed two sub pannels in my home. One in the garage and one in the ... A: I could've sworn I had answered this one... Question A: if Neutral and ground are connected at the ...
|
| GFI | 6/11/2009 |
Q: I am rewiring my wet boathouse and want to be sure it's protected from faults. Are GFI's only for ... A: I am acting under the belief that this is a private, owner-only boathouse, not a marina or public ...
|
| Main breaker problem | 6/10/2009 |
Q: Robert, I own a small residential home that I converted into a daycare facility for my wife in the ... A: Get the utility to replace the damaged aerial cable. This may have contributed to the main tripping, ...
|
| Switch hook-up | 6/9/2009 |
Q: I have a line that comes from my house to my deck. At that point it hooks up to two outdoor outlets ... A: Is it your purpose to control the first two outlets? Well then, you put a switch in the circuit ...
|
| 240 wiring | 6/8/2009 |
Q: I am replacing a Jennair cooktop with a similar model with a similar energy rating. The newer ... A: A similar Jennair, or a similar non-Jennair unit? Never the less, the wiring configuration you ...
|
| Adding fan/lite from receptacle | 6/7/2009 |
Q: I want to add a dual switch to control a ceiling fan. I need to take the source from a receptacle ... A: If you REALLY knew how to do it at the end of the circuit, you would know how to do it in the middle ...
|
| Phone Jack...looks like a main line of some kind | 6/6/2009 |
Q: The phone jack in my kitchen was in an awkward place, in the corner under an island with seating. A ... A: That is an old outlet! You now only use 2 of the three wires - the ones which were connected to red ...
|
| 3 way switch | 6/5/2009 |
Q: I have a hallway light that is controlled by two switches. On switch one there are two groups of ... A: No need to be confused. No need to panic. Electricity is actually very simple. There are just a lot ...
|
| Attic Fan Wiring Therm-o-disc 775-1 | 5/29/2009 |
Q: I installed a new switched outlet in my attic and ran power to an attic fan that the previous ... A: If it only works when the temp is BELOW the attic temp, it makes it sound like a heating thermostat. ...
|
| Circuit breaker not working | 5/27/2009 |
Q: I have a an older electrical box with screw in fuses (4). I have a small picture diagram attached ... A: 1] You are installing a bad fuse as replacement 2] The fuse block is damaged 3] There is a bad ...
|
| Nema wiring and outlets | 5/23/2009 |
Q: I have an appliance that is rated 208-240v 13 amps 2700w. It came with a nema 6-20 power cord. I ... A: A real electrician shouldn't need a preamble or insteruction. Do you still want to plug in a dryer? ...
|
| 110 to 220 conversion | 5/22/2009 |
Q: I posted this to another expert and got the response below. Any information would be appreciated. ... A: No good You are out of luck. Period. The reason you can't find the "electrician" is because he ain't ...
|
| service grounding | 5/16/2009 |
Q: I have a 100 amp service with a 100 amp disconnect, I was wondering how to properly ground this ... A: Why do people do things they know nothing about? You have a meter, a disconnect and then a remote ...
|
| Wiring for well pump | 5/10/2009 |
Q: I am replacing a pump for a shallow well. The original was wired for 120 V. The new motor is ... A: The number seems to be an Agrisupply number, not an XKJ number 115/230 means you can use either. ...
|
| Changing out a 220 v 30 amp breaker | 5/9/2009 |
Q: While replacing a water heater in a 30 year old house my step-son purchased 10 months ago, the 30 ... A: unless the anticipated balance of your corporeal existence is worth less than a few dollars. If you ...
|
| Underground Wiring in Conduit Question | 4/29/2009 |
Q: I searched the Ohio Revised Electrical Code (doing a job in Cleveland Ohio) and cannot find any code ... A: The NEC does not determine the utility of materials. The NEC requires that all materials be ...
|
| wiring help | 4/24/2009 |
Q: Robert, I'm doing an installation similar to the picture but the plug is a GFCI plug/switch. I'm ... A: you only need a red if you are continuing on after the bath light at the recp/switch combo: white ...
|
| Outdoor electrical enclosure | 4/23/2009 |
Q: I have a water pond in my backyard that I'm "raising from the dead". There are 4 outdoor spotlights ... A: Nice Any NEMA 3 enclosure will do [maybe $60-$80] You can get a NEMA 12 with hinged cover and a back ...
|
| Wiring a GFCI | 4/18/2009 |
Q: Mr. Wilber - Can you suggest a solution? I am trying to replace a combination switch and 3 prong ... A: you connected both blacks and the red together and also the 2 whites to each other? and it doesn't ...
|
| Wiring a GFCI | 4/17/2009 |
Q: Mr. Wilber - Can you suggest a solution? I am trying to replace a combination switch and 3 prong ... A: Get rid of the recp at the switch and wire it for switch only. Drop a recp out of the switch in a ...
|
| Replacing (1) 3-way switch and (1) split outlet | 4/8/2009 |
Q: Robert. I hope you can help us; we cant find anything addressing our particular setup and have tried ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| occassional pops | 4/7/2009 |
Q: I moved an electrical outlet 1 foot over in prep of new kitchen. Used 3 wire Romex. Started ... A: What do you mean by "pops" - a noise or the circuit trips? It sounds, though, that you are referring ...
|
| service wire | 4/3/2009 |
Q: Robert I hope you can help me. I am running a service to my pole barn from 200 amp disconnect that ... A: shouldn't be a problem quadplex IS wet location rated [I mean-it is made to be in the rain and snow ...
|
| ceiling fan hook up | 3/31/2009 |
Q: Robert, I'd like to hook a ceiling fan for Mom, but I cant figure out how to open the fuse box ... A: The switch in a properly installed lighting configuration should shut the power off to the light. ...
|
| Re-routing Air Cond. power cable | 3/27/2009 |
Q: I recently discovered that my mother's A/C power cable (220 VAC, single phase, 10-2 plus GND ROMEX) ... A: Actually, wire nuts will do it just fine. They are rated for at least 300 volts and they make ...
|
| 3 way switch problem | 3/25/2009 |
Q: I have a switch problem that I need some help with. May I first say that I have a basic ... A: I sure really hope there are more than just one each of red black and white wires in each box. If ...
|
| where do the amps go? | 3/24/2009 |
Q: After the voltage and the amps reach the load/resistance and do work, they follow the neutral out, ... A: My answer to this must have gotten lost in the ether... There is no remainder Voltage is the measure ...
|
| drilling into a wall near electrical wiring box | 3/23/2009 |
Q: and hit something that prevented me from drilling...I realize the area was very close to the light ... A: It might have been a nail plate, if there was a wire there and the electriciaxcn did a proper job, ...
|
| Unfinished basement / Lighting near plumbing | 3/21/2009 |
Q: I have a question related to running some extra lighting boxes in my unfinished basement. I am ... A: Consideration of potential for future abnormal failure service emergencies is not an installation ...
|
| switches and plugs | 3/20/2009 |
Q: i have 6 wires at a light switch box.1 is power from source.2 is power to another room. 3 is to a ... A: Boy, are YOU ever screwed... Did you at least label what wire went to what? Which went to the switch ...
|
| Dead circuit | 3/17/2009 |
Q: My basement is fully finished and unfortunately drywalled, including the ceilings. One of the ... A: Sounds like you have a real problem. Have you tested from a known hot source [end of an extension ...
|
| disconnect box distance | 3/17/2009 |
Q: hey there bob. how far can my 100amp residential breaker panel be away from my meter socket b4 I ... A: It can be 1,000 feet away, as long as you don't enter the building. When you enter the building, the ...
|
| electrical reset button | 3/15/2009 |
Q: An outlet goes out about every other day and I have to go to another room and push a reset button ... A: First, I would get rid of any supplier who vaguely threatens that I am "a fire waiting to happen." ...
|
| electric range wiring | 3/14/2009 |
Q: I just removed a 35 year old electric range that was hard wired. Coming from the wall is a Black ... A: Assume nothing or you will receive my snide "response to arrogant know-it-alls" letter... Ranges ...
|
| new fixture has no ground wire | 3/12/2009 |
Q: I'm replacing a ceiling light fixture which was connected to the ground wire... with a new simple ... A: I suppose that this isn't a UL listed fixture then, som you won't be voiding the listing... Either ...
|
| Motion sensor control garage lights | 3/11/2009 |
Q: I had a motion control dual light installed outside in between my 2 car garage. It work okay on a ... A: Sure Get rid of the motion sensor I don't like them I won't install them I won't maintain them See ...
|
| Strange ground/neutral problems | 3/7/2009 |
Q: .. I have a problem in my 50 year old house's electrical system. There is no ground wire in the ... A: You are the most recently discovered victim of "Handy Jack" Handy Jack is my less than affectionate ...
|
| Outside lights won't work | 3/5/2009 |
Q: I have just recently bought a foreclosure and have done all the needed repairs by myself. However I ... A: Wherever you plug in an extension cord, if the outlet works, there is a working hot and a working ...
|
| Combination Switch/Receptacle | 2/28/2009 |
Q: Robert:I am replacing a regular light switch for the cellar because I also need to light the ... A: what you plan won't work what you have is actually called a "switch leg" and you have no neutral You ...
|
| Flickering and brown outs | 2/27/2009 |
Q: For 4-5 days, I've noticed lights flickering in the house, our detached garage, and our barn. All ... A: The electrician didn't call the utility? Sounds like a bad connection on their lines. Call the ...
|
| Undercabinet Lighting Problems | 2/26/2009 |
Q: Ok, we have puck lights under our cabinets in the kitchen. They were wired 2.5 years ago and as of ... A: I expect you can fix them yourself. After all, the electrician is just another guy, too. Right? ...
|
| knob and tube dilemma | 2/25/2009 |
Q: I am an experienced mechanical professional, but this situation is driving me crazy. One question! ... A: So, how would that work? [remember the neutral bar is grounded, unless you have a fused neutral with ...
|
| Arc Fault breaker circuit | 2/24/2009 |
Q: I tried to install an AFCI on a rather large circuit which included fluorescent lights and ... A: Depending on who wired the circuit, and when, an AFCI may never work on it. There may be an illegal ...
|
| Outlets in a Series Controlled by Two Three Way Switches | 2/23/2009 |
Q: We recently painted a room and decided to change out all the switches and outlets to white ones. ... A: Well, you have the right idea, but I guess you weren't all that methodical, or there was madness to ...
|
| problems with recessed lights and outlets frying polarized appliances | 2/22/2009 |
Q: I am having an issue with some remodel work. I added two recessed fixtures to their own circuit 15 ... A: Well, you thought wrong. Based on the spacing of existing breakers, I am absolutely certain you have ...
|
| problems with recessed lights and outlets frying polarized appliances | 2/20/2009 |
Q: I am having an issue with some remodel work. I added two recessed fixtures to their own circuit 15 ... A: Three phase? It could possibly be a delta system. Did you notice that every third breaker space was ...
|
| florescent lighs at my office | 2/18/2009 |
Q: I have seven 3 x 4' flourescents at my office. Three of them were wired to stay on all the time. I ... A: They were likely installed [at great expense] as night lights with emergency backup units. They were ...
|
| voltage on 220 | 2/13/2009 |
Q: I have a subpanel in my shop that is supplied from house panel by underground. There has been no ... A: You have an open neutral [or as near as ....] Check feed and load panel end terminations for ...
|
| probable damage to electrical wires | 2/11/2009 |
Q: We are building a new house in Indiana. The siding contractor shot nails through the breaker boxes. ... A: Bummer I know of no reliable test method that you could utilize The only sure answer would be to ...
|
| electric | 2/10/2009 |
Q: hi would want to know if its possible to put a 30 dbl to controll 4 heatears of 1500w A: 208 or 240 volt? It wouldn't matter if they are standard 240 volt heaters, because the wattage is ...
|
| Metal Buildings | 2/8/2009 |
Q: I have just recently installed a 200 amp meter can and main disconnect combo on a metal building ... A: The service ends at the main disconnect combo breaker. You need to run 4 conductors to the "panel" ...
|
| getting results in writing | 2/4/2009 |
Q: I might be barking up the wrong tree here,I moved into a old house 2 months ago and I received an ... A: Sue everyone in sight. File a complaint with the state Public Utility Commission. File a complaint ...
|
| light/fan dimmer | 2/2/2009 |
Q: "Hi. I am trying to connect a dimmer fan/light combo to my current fan with light. I have some ... A: you don't have enough wires to do what you want, you need at least one 3-wire up to the fan All ...
|
| bathroom circut | 1/31/2009 |
Q: I have 3 wires coming into where I want to put a gfci receptical. power coming in from panel, one ... A: It doesn't have 3 wires, it has 3 cables. Draw out the boxes, cables and wires [unterminated] and ...
|
| front door sconces -- wiring | 1/25/2009 |
Q: A friend of mine called me to take a look at this: she is having work done on her house (not ... A: Not enough info here to solve your problem. How many cables and wires at which boxes, and where do ...
|
| Sub Panel Wire Size | 1/24/2009 |
Q: I have a few questions regarding sub panels. Is the amp rating of a sub panel supposed to be higher ... A: There is no hope, only the rules. Conductor is protected by breaker. 50 amp breaker-50 amp ...
|
| dimmer switch on ceiling lights | 1/23/2009 |
Q: When I had my kitchen redone, the electrician installed lights in the ceiling and also wired a light ... A: For that to be true, the power not consumed at the light would have to be lost at the dimmer as ...
|
| Flickering light and burnt switch | 1/22/2009 |
Q: I have 2 lights on either side of my entry gate apporx 350 ft. from the house. I turned gate lights ... A: One bulb flickering means the problem is at the gate. Switch looking burnt could be caused due to ...
|
| Chandelier with 230 volts bulbs. | 1/21/2009 |
Q: I bought chandeliers from overseas. They have different European socket with light bulbs with 230 ... A: I just typed: 120v european lamps in the search window in google. These sites were ...
|
| lights dim when a/c energized | 1/20/2009 |
Q: when my condensing unit or dryer is energized, the lights on one or more circuits dim and flicker ... A: Don't worry about the aluminum cable or alloy bus. Just check terminations for mechanical failure ...
|
| Type of wire | 1/18/2009 |
Q: I am building a barn, it is 300 ft from the 320 power box on the house. I will have lights a couple ... A: CSA=KIL/Vd CSA=Conductor Area in circular mils K=Conductance factor I=Load Current in amps L=Round ...
|
| cold air coming out from high hat lighting | 1/17/2009 |
Q: My question to you is that we had installed high hat lighting in the summer time and now that it is ... A: There are 2 types of recessed light, those that are rated for direct contact with insulation and ...
|
| Too much on one circuit. | 1/9/2009 |
Q: Can you tell me if the 80% rule for circuit load is required or just recommended for unnecessary ... A: You have about 600 watts in lighting and an 1100 watt microwave. I would expect the circuit to trip ...
|
| Wall Recepticles | 1/6/2009 |
Q: I have 4 wall recepticles with two outlets in each. The top outlet on all the recepticles is only ... A: Just one red wire? Turn the power off. replace receptacle with a new duplex receptacle. do not break ...
|
| Service problem. | 1/3/2009 |
Q: I have a 200 amp underground service that runs 150 feet from the pole where the meter is directly to ... A: Bad news. Sure sounds like a bad conductor [if your tests are right] and, yes, it happens all the ...
|
| Service problem. | 1/2/2009 |
Q: I have a 200 amp underground service that runs 150 feet from the pole where the meter is directly to ... A: First of all, you did not lose a phase. You have single phase service from a center-tapped 240-volt ...
|
| Electrical interference With TV | 1/1/2009 |
Q: I have a TV,DVD on 1 outlet in a room with 3 outlets-on the other outlet I have a computer and paper ... A: Well, you have got me stumped. Know anyone with an oscilloscope? I had a commercial customer once ...
|
| interior lights on involuntary | 12/28/2008 |
Q: My home is 38 yrs old. The canned lights in my kitchen came on by themselves. I turned them off at ... A: The lots of rain statement makes me think it is probably related to your service entrance. Happen ...
|
| Twisting Wires | 12/26/2008 |
Q: I consider myself a reasonably skilled electrical DIYer and I understand most of the concepts of ... A: Linesman's pliers. Start with long unstripped conductor ends, twist them together leaving the ends ...
|
| Breakers crackling | 12/24/2008 |
Q: I have some crackling coming out of my breaker box and it is hard to tell what breaker the noise is ... A: Loose termination at breaker or lug Bad breaker REALLY bad breaker - loose connection to bus [risk ...
|
| Question about stripping wire | 12/23/2008 |
Q: I've read that you aren't supposed to nick the conductor when your stripping wire. I only read this ... A: well, there is nicked and there is marked... I think that if you use the number fourteen gauge ...
|
| Wiring a split a/c system | 12/18/2008 |
Q: Mr. Wilber, I am in the process of wiring up a 240 V ductless split a/c system. The outdoor unit ... A: On what basis are you allowing 14 gauge for the outdoor unit? ...and what fuse/breaker/protective ...
|
| trouble shooting electrical | 12/17/2008 |
Q: Last two weeks my garage electrical has worked one minute and the next it doesn't. I have a cb box ... A: Sounds like it could be a bad main, but it could also be the power company lost a line, or any one ...
|
| Cable size | 12/5/2008 |
Q: I am looking to put an outside light on my land I also would like to run wire to my out buildings ... A: calculate yourself Cross sectional area in circular mils= k factor [~12 for aluminum] * I [current ...
|
| Dining Room Chandelier Wiring | 11/29/2008 |
Q: My electrician has left 3 wires (black, white, red) and a copper wire for a dining room chandelier. ... A: I don't know what wiring practices are in Italy, so I guess you have to contact the manufacturer. [I ...
|
| Red and Black Wires taped Together | 11/27/2008 |
Q: Today I had a plumber install a new natural gas 50 gallon water heater. I converted from electric ... A: I feel I can say with reasonable confidence that your old water heater electric line has nothing to ...
|
| Circuit Breaker Trip | 11/26/2008 |
Q: I have a 7 year old house that we have been the only owners of. For the past two months, one ... A: Intermittent problems are the most annoying and the most difficult to address. Metal or plastic ...
|
| Service Entrance Wire - re-use, replace, or upgrade? | 11/25/2008 |
Q: In a big storm, my service entrance wire came unattached from the house. The electric company has ... A: It isn't 110, it is 100-amp. It isn't 220, it is 200-amp. You won't get 200-amp wire in a 100-amp ...
|
| Bathrrom Fixtures power is out but GFCI outlet works | 11/19/2008 |
Q: My 1/2 bathroom has a fan, ceiling light and vanity light. I flip the switch and they all do not ... A: Your GFI is probably on a different [20-amp appliance] circuit. [especially in a newer home] Sounds ...
|
| Changing my 200AMP panel | 11/6/2008 |
Q: I have an old Sylvania bolt-on 200amp service panel with 40 breaker slots. It's full and due to the ... A: Maybe you only have a 100-amp meter. And I can't see your job, so who am I to contradict someone who ...
|
| battery | 10/28/2008 |
Q: I guess i was wondering if that would work, and how long it would last, with a average size battery ... A: couldn't say How many volt-amp-hours will the battery deliver? and what is the heaters wattage? ...
|
| adding wiring to distant existing receptacle | 10/20/2008 |
Q: I have a question that it holding me back from completing this job. The situation is that the last ... A: Sounds like an old row house A newer building would have adequate receptacles on most if not all ...
|
| Change in VAc | 10/16/2008 |
Q: Robert, I currently have a 220 VAC stove that is being replaced with a gas unit that needs 110VAC to ... A: It isn't as simple as you make it sound, but properly configured, there is no reason you could not ...
|
| Automatic electrical shutoff switch | 10/14/2008 |
Q: I am adding a sunroom with a 2 ton HVAC. My house is fairly small with an HVAC already installed. ... A: It is difficult to say without knowing the precise configuration of your transfer setup. You could ...
|
| water heater element wiring burning out? | 10/13/2008 |
Q: I'm trying to find an answer to my problem, any advice you can share will be great. I have a ... A: Does the element burn out? ...or are we talking about the same element burning up the wire conected ...
|
| Generator Wiring | 10/10/2008 |
Q: I have a 5550 watt generator and want to run a two wire with ground 12 Ga 100' extension cord from ... A: You asked I answered That isn't sarcasm. I mean it. Install a transfer switch or do what you please. ...
|
| 220 volt switching | 10/5/2008 |
Q: Can I buy a 220 switch that will alow me to swich to 3 different locations from a single 220 source? ... A: I have never looked for one. I don't know what application they would make one for. You could always ...
|
| garage door opener wiring | 9/30/2008 |
Q: We want to pre wire for a garage door opener that we have not purchased or decided on yet. What ga. ... A: 18 ga. should be fine, but I would decide what door opener I want to install first and see what ...
|
| is my panel box up to code? | 9/29/2008 |
Q: i recently acquired an old shotgun house in ky. i wonder if my panelbox is up to code without hiring ... A: You would need a copy of the NEC in force when your house was wired and/or the service was upgraded. ...
|
| I screwed up a circuit in my house! | 9/28/2008 |
Q: To begin with, we have a switched outlet (the top of the outlet is switched, the bottom is always ... A: Switch leg.. one of the cables goes from the receptacle to the switch.. [there is only the one cable ...
|
| Adding ground wire to old 2 wire outlet | 9/22/2008 |
Q: I just had this done by an electrician I found in the Penny Savers. He supposed to have drilled ... A: Your conditions are unclear. I can't tell without seeing the installation or getting a better ...
|
| erratic table saw behavior | 9/18/2008 |
Q: ive got a 10" home table saw that suddenly has not behaved normally. while sawing one day, it just ... A: a clue here is the "it starts when I spin it by hand" note. circuit breaker? [thermal cutout unit?] ...
|
| Voltage drop | 9/17/2008 |
Q: In a 6 outlet GFCI circuit in a new Modular home kitchen 4 outlets measure 120v and function ... A: 1] GFIs are not designed to control voltage levels. 2] You shouldn't be able to read voltage to ...
|
| lighting, metal halides 208 versus 240 | 9/16/2008 |
Q: ..I have an opportunity to purchase numerous metal halide lights for greenhouse tomato production, ... A: have the equipment examined I think it likely you will find that the ballasts are multi-tap units ...
|
| Converting ceiling fixture to plug into wall plug | 9/9/2008 |
Q: First, thanks in advance for your help. I think this question has an easy answer, but here we go. ... A: search google with the phrase "male cord cap" this was on first page of results: ...
|
| GFCI Plug | 9/8/2008 |
Q: I'm trying to wire a GFCI Plug and am having a problem. There are a total of 9 wires in the old ... A: Your statement seems problematic. You say that the one black wire shows 120 volts when connected to ...
|
| Arc Fault Breaker tripping on new ceiling fan | 9/7/2008 |
Q: My house is 4 years old and has arc fault breakers for the bedrooms. I've installed a new ceiling ... A: since it happens when you try EITHER the fan OR lights, I don't see why it would be the fan.. does ...
|
| Electric current in my shower | 9/3/2008 |
Q: I can feel an electric current in my shower. I don't feel it unless I am in the shower, the shower ... A: You could always just be nuts, have a pinched nerve, etc., but your kid says he feels it too. ...of ...
|
| Low voltage in several outlets on the same circuit | 8/29/2008 |
Q: There are seven outlets in series all connected to a 20 amp GFCI breaker. The problem I'm having is ... A: if the gfi can interrupt the ciruit, there are contacts, right? my first guess would be a bad ...
|
| Square D Safety Switch | 8/28/2008 |
Q: This unit is early to mid-60's with screw in fuses and I believe is the overload trip for the ... A: OK then. I don't think this should be blowing the 15 amp fuse The only thing I can think is that you ...
|
| Square D Safety Switch | 8/27/2008 |
Q: This unit is early to mid-60's with screw in fuses and I believe is the overload trip for the ... A: The switch is rated for 30 amperes - current 15 amps on each leg would be 15 amps current. OK? ...
|
| Chandelier wiring | 8/26/2008 |
Q: I am trying to hang a new chandelier. The old one was wired to a yellow and a white wire from the ... A: 600 volts only refers to insulation rating, not actual voltage present. The neutral [really the ...
|
| Question about capping a wire to a wall heater | 8/25/2008 |
Q: I have just removed a baseboard heater, and do not want to install another, I just want to drywall ... A: YOU DO UNDERSTAND THE DIFFERENCE BETWEEN A HIGHLY SKILLED, EXPERIENCED PROFESSIONAL GIVING ...
|
| Question about capping a wire to a wall heater | 8/23/2008 |
Q: I have just removed a baseboard heater, and do not want to install another, I just want to drywall ... A: You obviously didnt read my profile. I don't teach basics to the ungrateful and lazy. Do your ...
|
| Garage Lights | 8/19/2008 |
Q: Have a problem with outside garage light pair, standard builders’ grade fixtures from Lowes: Both ... A: there are 2 possibilities that come to mind order of likelihood 1] loose connection at socket in ...
|
| Circuit for Cooktop | 8/17/2008 |
Q: I'm looking to replace a Jenn Air downdraft electric cooktop with an induction cooktop. The Jenn ... A: Sounds like it was undersupplied to begin with... 8 kw would be more than 30 amps, and there should ...
|
| Uneven Voltage | 8/11/2008 |
Q: Im having a big problem with electric in my duplex. Whenever anything electrical is run (lights, ... A: What makes you think it isn't the power coming into the building? Open neutral Main panel, meter ...
|
| 200 amp service on a 100 amp feed | 8/6/2008 |
Q: We are selling our home and ran into a problem when we had it inspected. We bought the property with ... A: you have a 100 amp service entrance on the pole? Does it go through a 100-amp breaker at the pole? ...
|
| Wall Oven | 7/31/2008 |
Q: Bob - I was reading an old posting about installing a wall oven. As I understood your answer, you ... A: The only reference I can find about anything like this was a cooktop rather than a wall oven, and ...
|
| requirements | 7/27/2008 |
Q: I'm selling my home. I recently replaced our old bubble tub with a new one. It's on it's own ... A: What inspector? A "Housing Inspector"? Like the guy who gets $300 to tell some buyer what is wrong ...
|
| Kitchen wiring | 7/26/2008 |
Q: A few questions questions ATM... I'm installing a sub-panel for the "new" half of the house in ... A: Why wouldn't GFIs be ok in a subpanel? Switches don't need to be GFI protected, but the receptacles ...
|
| electronics fail in one room only | 7/25/2008 |
Q: In one room of my house, all of my electonics routinely fail. I have been through several dvd ... A: ..sounds like you would just be preparing top discard a UPS if you do. Check your voltage levels for ...
|
| Lights blinking | 7/24/2008 |
Q: Just in the past week I have noticed that all of the lights in my house begin blinking once every 2 ... A: Define fire... It could be a bad breaker or an impending panel bus burnout due to loose breakers ...
|
| dead wires? | 7/23/2008 |
Q: I hope I haven't asked you before - I've tried so many people. OK, rain fried an outside receptacle ... A: Rain fried an outside receptacle (my fault, no GFI). **What do you mean by "fried"? COuld there be a ...
|
| 40 amp/30 amp circuit sharing | 7/4/2008 |
Q: I have two machines, one requires a 40 amp circuit, the other a 30 amp. I know that the two ... A: Don't quote me on this, but I think that you can use 10 gauge if terminated properly under the 25 or ...
|
| 50 amp breaker keeps triping | 7/2/2008 |
Q: i purchased a house approx 5 years ago w/ a separate workshop in the backyard that has been wired w/ ... A: Objectionable ground current is most copmmon unsatisfactory result Ground rods are lightning route, ...
|
| 50 amp breaker keeps triping | 6/30/2008 |
Q: i purchased a house approx 5 years ago w/ a separate workshop in the backyard that has been wired w/ ... A: Since the panel was fed with the wrong gauge conductors for the breaker size, Let us suppose that ...
|
| Electrical outlets | 6/18/2008 |
Q: In my house all the outlets have 2 holes instead of three. Most of the appliances out there have 3 ... A: The problem and expense aren't changing the outlets. Devices cost relatively nothing. The problem is ...
|
| Lawnmower disaster | 6/17/2008 |
Q: So I borrowed a lawnmower because mine was out of commission. The lawnmower I borrowed was an ... A: not THAT freaky really. it is allowed to have the lights on the bath receptacle circuit if the ...
|
| High electric bill, possible bad wiring? | 6/14/2008 |
Q: we bought our home a year and a half ago. It is a new construction with energy efficient everything ... A: So, shut EVERYTHING.. lights refrigerator water heater ice maker fans A/C Washer Dryer TVs ...off ...
|
| proper terminating techniques for solid wire | 6/9/2008 |
Q: Some of my co-workers and I are debating whether or not it is good practice to twist your solid ... A: I don't think you will find ANY manufacturer who says "ABSOLUTELY DON'T twist first!" They will say, ...
|
| replacement GFCI combo outlet/switch | 6/8/2008 |
Q: I have done most of the renovation in a bathroom in my NYC apartment, and wanted to change the light ... A: There are 2 blacks and 2 whites at the switch box There are one black and white at the light One ...
|
| color coding individual wires in SCH40 PVC conduit | 5/29/2008 |
Q: I have a question on color coding individual wires that are run in a SCH40 PVC conduit. I have a ... A: nope, that is the convention... of course you could always label both ends of the wires BEFORE you ...
|
| combo outlet | 5/27/2008 |
Q: I am having trouble installing a new combo outlet...the outlet is a combo switch/outlet..I have ... A: So, were you clever enough to make a drawing of where the wires went before you took them apart? ...
|
| Wiring a new receptacle from single-pole switch | 5/25/2008 |
Q: I am trying to add a receptacle near a new work box that currently has a single-pole switch in it ... A: One of the blacks on the switch is the hot, the other is controlled by the switch. So just find out ...
|
| short in electrical wiring for outlet | 5/24/2008 |
Q: I had a breaker for a bedroom that tripped and wouldn't reset. Ohmmeter readings at the wall outlets ... A: have you REMOVED all the devices from the circuit when taking your readings? ...you can at least ...
|
| 307 volts on 240 volt circuit | 5/8/2008 |
Q: I have a wall oven (electric) that I have replaced two control boards on. The first I replaced ... A: Well, unlikely anyway, but it would not be unusual to see 260 volts. Now 130 volts is not an ...
|
| 1-exhaust fan, 2-rooms, 2-switches | 5/2/2008 |
Q: I have (1) exhaust fan mounted in the attic with (2)-2" intake lines sucking air from one small ... A: why four-ways? there are only 2 control locations for one device... why double pole? isn't this a ...
|
| Capped neutral wire on a 240V circuit to well pump motor. | 4/29/2008 |
Q: From the main service panel on 2-30A breakers, a 3-wire 240V circuit runs outside to a subpanel at ... A: as long as all you have is a 240 volt load, there is no need for a neutral, only a ground, which ...
|
| Adding elec. stove to service | 4/28/2008 |
Q: I have a 200amp service box with (6 20amp110)(2 40amp220-one air conditioner, one dryer, on left ... A: If you go and look at a panel interior at one of the endless home supply centers, you may observe ...
|
| GFCI along side light switch | 4/26/2008 |
Q: I have a light switch next to a GFCI. I put all wires on Line side of GFCI and I have power but ... A: Your lighting and receptacle circuits shouldn't be tied together in the kitchen unless your house ...
|
| open neutral | 4/22/2008 |
Q: I have 5 receptacles on same circuit, 1 in the garage, 1 in the powder room, 2 in the bath room, and ... A: look for a loose connection or damage at the outside receptacle, as this sounds like the first ...
|
| Garage Overhead Lighting Wiring | 4/20/2008 |
Q: I tried to replace an overhead garage light and did not write down the wiring diagram. There are ... A: so, let me guess... you remade the splices in the lighting box, huh? didn't it occur to you that ...
|
| mysterious wiring issue, at least to me.... | 4/15/2008 |
Q: The problem I am having seems to be right up your alley. I just paid a giant bill to a guy who ... A: you need to draw out the circuit and figure where each wire goes to and comes from then you will ...
|
| Microwave keeps tripping breaker | 4/9/2008 |
Q: Help! We just had a new home constructed and recently moved in (30 days ago). I noticed the other ... A: I found a unit like the one described. GE Profile 36" Spacemaker Over The-Range Microwave Oven - ...
|
| generator | 3/21/2008 |
Q: We know that ground faults need a path to its source to operate the overcurrent device, the source ... A: I think they are saying not to bond the grounded conductor to the grounding conductor at the ...
|
| PhotoCell switched light | 3/20/2008 |
Q: I installed a photocell switch for the porch light to turn on at dusk and turn off in the morning. ... A: OMG I always get the weird ones... Next time the light fails to come on, you need to make sure ...
|
| plug ins | 3/18/2008 |
Q: I replaced all the plug ins and light switches in my cottage. Nothing works now, except the base ... A: The clue here seems to me to be the note about the lights dimming orange... sounds like you might ...
|
| plug ins | 3/17/2008 |
Q: I replaced all the plug ins and light switches in my cottage. Nothing works now, except the base ... A: OMG! How many openings are we talking about? of what types? What still works? Did you open any of ...
|
| 10-30R wiring help | 3/10/2008 |
Q: My mother just moved, and I need to hook up her dryer. There is a two wire cable connected to the ... A: Well, for one thing, you don't know much and haven't spent much time investigating or learning about ...
|
| HELP WIRES CROSSED" | 2/27/2008 |
Q: IM STUCK, I TOOK MY VANITY LIGHT DOWN AND PULLED THE WIRES APART,BUT I DONT KNOW WHERE THE WIRES ... A: Oops...time to slit your wrists..... actually, it is no biggie. But, that was dumb, why the hell did ...
|
| rewiring an old lamp | 2/26/2008 |
Q: I have an old Y shaped lamp with two bulb sockets and one switch. The switch is attached to the ... A: I guess so. Couldn't tell you. Who made the switch? You should be able to get a wiring diagram for ...
|
| Electrical Problem with Boiler Heater | 2/24/2008 |
Q: According to your profile you are up to challenges, Great! Here's good one. My Natural Gas Boiler ... A: Sounds like a classic open neutral [or substantially so] When your oven heats it provides a ...
|
| Suppling a Paint Booth | 2/20/2008 |
Q: Robert, I have been asked to wire the supply circuits for a new paint booth for a body shop that I ... A: 20 amps is too low for a 17 amp load [80% continuous loading rules] Check with the manufacturer. ...
|
| Wire gauge for 7.5hp Snap-on air compressor | 2/17/2008 |
Q: I recently bought a used 7.5hp 80 gallon Snap-on air compressor. It has a Baldor motor that ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| home wiring | 2/12/2008 |
Q: i have a problem with my lights. theres two lights in the middle if the hallway one light switch at ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Possible 220v wiring problem or bad electric clothe dryer. | 2/11/2008 |
Q: Today I started to do my laundry and when I tried to start the clothe dryer, nothing happened. I ... A: * LIFE SAFETY WARNING! [disclaimer] Electricity is dangerous! You can be injured or killed! Improper ...
|
| Crystal Chanedlier Wiring from Brataslavia | 2/5/2008 |
Q: I purchased 2 crystal chandeliers from Brataslavia and they have the 220 wiring in them. I wish to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Ridiculous ...
|
| 240v Electric Garage Heater | 2/4/2008 |
Q: I am in the process of installing a 240v heater for the garage. I have a 50amp sub panel (off a ... A: ...except you DON'T have a 50 amp subpanel - 8s aren't good for 50... you don't have a 30 amp ...
|
| Hot Water Heater Timer | 2/2/2008 |
Q: I'm replacing the timer that was 30 years old with a similar model. The old one just died. It's ... A: How should I know? Who made your old timer? Who made the new one? Same people? Did you change the ...
|
| strange voltage problem | 1/31/2008 |
Q: 1) If I turn off all the breakers in my panel, the incoming red hot to neutral is 110v, and incoming ... A: Depending where you are in the US, and what voltage you are served with, the incoming hot to hot ...
|
| hot water heater on/off switch | 1/28/2008 |
Q: I travel a lot and would like to install an ON/OFF switch to turn off my water heater. I have been ... A: What kind of switch and box? Water heaters are usually 5000 watt elements, so you will need a 240 ...
|
| wiring a light, 3-way switch and then outlet | 1/26/2008 |
Q: I have a kitchen light with a 2 wire power source that I need to add a 3-way switch to. After the ... A: the three wire is there because the hot travels through on the black. the red is switched you will ...
|
| Light fixture overheating | 1/16/2008 |
Q: I recently replaced an antiquated light fixture. It's rated for 75 watts and I put a 60 watt bulb ... A: I assume you are talking about the new fixture being rated for 75 watts [an unusual value...] Unless ...
|
| Please help me figure out a dryer cord.... | 12/11/2007 |
Q: Does ANYONE know what the 1/12 stands for? PETRA 90-2028 4-Wire Dryer Cords - 30A (Closed Eyelet) ... A: UL label is the key If an item has a UL label, you have to check what the listing is for. If the ...
|
| Outdoor receptiacle | 12/10/2007 |
Q: My outdoor receptale for Xmas light got a yellow light which I guess indicates that it's tripped. ... A: Hard to say. Some outlets have a light when on, some when off with power at line terminals. Could ...
|
| Please help me figure out a dryer cord.... | 12/9/2007 |
Q: Does ANYONE know what the 1/12 stands for? PETRA 90-2028 4-Wire Dryer Cords - 30A (Closed Eyelet) ... A: Here is the company site depicting your cord. http://www.petra.com/index.php?page=9 It says ten ...
|
| Dead short in wiring. | 12/6/2007 |
Q: I created a dead short in an split outlet. I do not know which circuit breaker because none of ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Sharing power | 12/3/2007 |
Q: I am installing 2 sets of recessed light in living room. Existing construction and on 1st floor i.e. ... A: Yes. It is ok to share power for lighting from a general convenience outlet, but not from kitchen, ...
|
| wirering?? | 11/29/2007 |
Q: Ok,I bought 3 ceiling lights that are the same,I had one light that was there before, replacing with ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| 220-volt | 11/28/2007 |
Q: Hey Robert, I am a remodeling contractor working on a masterbath, and it appears to have a heatlamp ... A: 220 heat lamp? ...not likely, though there may be a built in heater [common] that requires a whole ...
|
| ceiling fan wiring | 11/26/2007 |
Q: I am trying to install a ceiling fan. The junction box has 2 white wires capped, 1 purple, and 1 ... A: first and foremost, you must replace the existing box with a fan-rated box if it is not fan-rated My ...
|
| ac/furnace/ dryer on same circuit breaker | 11/18/2007 |
Q: I just bought a 10yr old condo-electrical box has 125 max. I have been replacing the ... A: Unfortunately, there is no easy way - you are using the way that works, unless you have a circuit ...
|
| Ceiling Fan Wiring | 11/16/2007 |
Q: I install two ceiling fans and have had no problem with the installations, but after I installed ... A: First, If you read the directions to seek information, you will read that it says I don't teach ...
|
| suggestion | 11/15/2007 |
Q: I just want to ask for your advice in bringing well pump, and septic pump wires from outside by ... A: 1] remove the well and septic from the existing source and extend them to a new subpanel fed by the ...
|
| Ceiling Fan Wiring | 11/13/2007 |
Q: I install two ceiling fans and have had no problem with the installations, but after I installed ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Changing shed wiring | 11/12/2007 |
Q: I have 10/2 UF running to my shed for 110v..I overwire everything. But now I'd like to change that ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Conduit for THHN Conductors? | 11/10/2007 |
Q: I've relocated to the Austin TX area and I'm purchasing a house built in 1992. During the ... A: yup need an accessible [not in an attic] disconnect and circuit overcurrent device where the service ...
|
| 2 prong to 3 prong outlet | 11/3/2007 |
Q: OK, I've done my research but can't seem to get a proper answer. I wish to upgrade the 2 prong ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * According ...
|
| Disconnect Switch | 11/2/2007 |
Q: I wanted to install a disconnect switch for my hot tub, so I bought a switch rated at 60 amps 240 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Service Panel Interlok | 10/29/2007 |
Q: I was considering installing a product "Interlokit" (Richmond, Va. company)and on their site they ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Too many wires in box | 10/28/2007 |
Q: I'm replacing a ceiling light in a bathroom. I put in a new ceiling octagon box to replace the old, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| neutral wire is hot | 10/24/2007 |
Q: at my church, i am having trouble with some wiring.the neutral wire is hot.the box which is embedded ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Ceiling fan wiring to wall recepticle, exposed romex, & outdated wiring | 10/23/2007 |
Q: Mr. Wilber - Thank you for taking the time to read my question. First, I'll mention that I worked ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Flickering Power and additional note | 10/22/2007 |
Q: Here's my situation. I have intermittent flickering power in my home. I'm not sure when it started, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Replacing existing ceiling fan/Adding remote receiver | 10/21/2007 |
Q: The home supplies three hots and three neutrals. When I tie in the ceiling fan to the receiver, I am ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| grounding an ungrounded run | 10/20/2007 |
Q: I have a 1960 built home in Tyler texas. There are two bathrooms with ceiling light/heater/exhaust ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| home electric, breaker no power | 10/18/2007 |
Q: ok.. here's a good one.. noticed one outlet not working.. so I started to look into it.. found out ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| code | 10/17/2007 |
Q: I am a carpenter not a electrician. Recently I had two electricians doing some work for me in a ... A: AIN'T IT A SHAME WHEN KIDS CAN'T PLAY TOGETHER? ..anyway ... Delaware County where? Largely, most ...
|
| 400watt commercial outside light | 10/16/2007 |
Q: Robert, what wire and amp breaker do i have to use to make this work? I hooked it up to a 2o amp ... A: Check that the voltage supplied matches the voltage required. [400 watts is 3.5 amps at 120 volts, ...
|
| Electrical Short | 10/8/2007 |
Q: I was installing drywall over a light switch when it hit another switch and sparked, killing the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Hot on ...
|
| douplex outlet on switch | 10/7/2007 |
Q: I just build a new house and requested for 1 outlet per room be on a switch. The electrician wired ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It depends ...
|
| partial power outages | 10/5/2007 |
Q: I appreciate your time on this as it is perplexing me greatly! For the past few days, I have been ... A: I would bet on a loose wire in the receptacle behind your bed ... You may find a bad speed-wire ...
|
| surge protecters, line conditioners | 10/1/2007 |
Q: I have 2 questions. First of all, I bought a APC ups for my computer and music equipment. My issue ... A: 1] off click is bigger because the current is attempting to continue flowing... I had a customer ...
|
| 3 wire plug 4 wire outlet | 9/29/2007 |
Q: I read your answer to the question about hooking up a 220V welder or air compressor to a 4 wire ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| ceiling fan wiring | 9/27/2007 |
Q: i am replacing a ceiling fan with seperate wall switchs... from the ceiling there are 2 white, 2 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Well, ...
|
| RV Wiring | 9/22/2007 |
Q: I am in NZ and have an american Motor home. We Have 240 volt supply into a step down transformer, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * ...
|
| Outlet(s) Failures | 9/20/2007 |
Q: In the middle of some home improvement projects, I've taken down a wall and moved one outlet around. ... A: Further investigation show 110V across the hot and neutral, but next to nothing is registering ...
|
| Severed Extension Cord | 9/17/2007 |
Q: .. Recently, my wife was using our electric hedge trimmer at our new house (built in 1995). She ... A: sounds like a GFI trip to me keep looking could be in the basement at the panel or a sump pump ...
|
| still voltage when light turned off | 9/16/2007 |
Q: I am a non-pro home handyman I would say, I have wired basements, and replaced many receptacles, ... A: hmm..... sounds like some standards in Canada are sifferent than here.. In the US the center post in ...
|
| compact flourescent bulbs | 9/15/2007 |
Q: I wonder if you can explain what is happening. I just returned from a friend that built a new house ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Probably ...
|
| Sub panel feed | 9/14/2007 |
Q: i have a 100 amp main for the house, and have added 1 floor to the house. to feed the sub panel ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * If you ...
|
| tankless water heater electricity spike | 9/13/2007 |
Q: I'm interested in getting an electric tankless water heater which pulls 100 amps of electricity. I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I have ...
|
| Utilizing 14-30 receptacle for Steam Generator | 9/10/2007 |
Q: My laundry and master bath is in one room. My dryer is gas. I have just purchased a modular steam ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I suppose ...
|
| re wiring a new light | 9/9/2007 |
Q: I currently have a standard bayonet cup light that is controlled from 2 switches. I have just bought ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You have a ...
|
| Fed Pacific Circuit Breakers/Fuse box | 9/7/2007 |
Q: IS there any credence behind the fire hazard/faulty breaker rumor regarding Fed. Pacific fuse box? ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * National ...
|
| 220 plug single phase | 9/6/2007 |
Q: I believe it's a 220 plug single phase, but please correct me if I'm wrong. How would I be able to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sounds ...
|
| Old style combined parallel/tandem outlet | 9/3/2007 |
Q: o. ? - the house, not the dad) I found an outlet I've never seen before. It looks like this: ... A: Looks like a standard obsolete 110v outlet. 48 volts sounds like a dead circuit with a digital ...
|
| determining wire rating in degrees celcius | 8/30/2007 |
Q: I want to install an overhead light (already purchased). A warning on the box states it requires ... A: well, I guess it is like so much else in life .. you can follow the rules, or have what you want, ...
|
| Pool pump was tripping gri until I... | 8/27/2007 |
Q: Put wd 40 on the rusted part that spins when the motor is on. This is a small rod type piece that ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I cannot ...
|
| 220v to 110v | 8/26/2007 |
Q: I have existing 220v where a stove was and I want to use the source to power a 110v exhaust fan and ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * What about ...
|
| outdoor pool/pond | 8/24/2007 |
Q: I have dug out an old inground pond. I poured a new floor and piping. I have built a pump house 6 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sorry. I ...
|
| Ceiling fan switch | 8/17/2007 |
Q: We also have a ceiling fan w/light, and the light turns on itself. Also, the fan will change speed ... A: More likely that the fan and light are controlled by a unit in the fan canopy, with a remote ...
|
| GFI Failure/ | 8/15/2007 |
Q: Ihave a circuit in my home that includes 3 outlets in a kitchen, and 2 outlets in an adjacent room. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Load centers | 8/13/2007 |
Q: Help! can you tell me what is the lingo with breaker box What is 20/30 20/20 20/24 poles. I have ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I believe ...
|
| outlet working off a switch | 8/12/2007 |
Q: I have an outlet in my home office where the top part of the outlet is live all the time and the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Leave it ...
|
| Switching Problem | 8/11/2007 |
Q: I'm installing some pot lights and wall skonses in my basement and I'm running into a problem ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| outlet wiring | 8/9/2007 |
Q: in general, how many 15amp outlets do you link to one fuse?? 1 fuse per room (4-5 outlets), more or ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I will ...
|
| Adding subpanel to detached carriage house | 8/8/2007 |
Q: Recently moved into a house built in 1901 in Central Ohio. Main elec panel and almost all wiring has ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Air Compressor hook up | 8/7/2007 |
Q: I just got a Coleman Powermate 60 Gal Air Compressor that runs on 220. It came with no plug so I am ... A: well, that's great. Glad to hear it. I guess if I had a chance to have come by and look at what you ...
|
| Electric leaking | 8/6/2007 |
Q: I have a problem with my kettle where I can feel electric shock when touching it. Its not only ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There are ...
|
| faulty switches? | 8/4/2007 |
Q: I have two rooms that I assume are on the same circuit because neither light is coming on. I know ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * How do you ...
|
| Circut Breaker | 8/3/2007 |
Q: We were watching tv and both went out on main floor everthing else was still working. We reset the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * both WHAT ...
|
| Home wiring/ 4 gang box with a traveler | 8/2/2007 |
Q: I have a big problem with my wiring. I'm remodeling my kitchen. In the process i knocked a wall down ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| wiring to detached garage | 8/1/2007 |
Q: I am going to replace the wiring to my garage. From 200A panel in house, a 30A breaker is dedicated ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Multi-gang wallbox 1? | 7/31/2007 |
Q: I am about to install a 4-gang wallbox to house the following Lutron NovaT switches: 1) A general ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You had me ...
|
| electric outlet | 7/28/2007 |
Q: The electrical outlet in a wall that is the GFI (the one with the test buttons) is not working has ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| 12/3 SJTOW wire | 7/27/2007 |
Q: I need to run a 12/3 wire to my shop that is 50ft away from the house. There will be a 20amp break ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| overhead ceiling fan light | 7/26/2007 |
Q: Our Casablanca ceiling fan light is operated by a wall switch. It has started to come on by itself. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * If the ...
|
| Light switch trips breaker when turned off | 7/24/2007 |
Q: I have a light switch that trips the breaker when it is in the off position. The breaker will trip ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The ...
|
| burnt up electrical outlet | 7/23/2007 |
Q: I have a outlet that my aboveground pool is plugged up to by extension cord. It has worked fine for ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 1] Loose ...
|
| Installing a GFCI in a 14/3 Box to 2 Appliances | 7/21/2007 |
Q: I have an existing outlet box on my house's exterior patio wall. The box was used by the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Did the ...
|
| hot tub wiring | 7/20/2007 |
Q: I have an older house with an ungrounded electrical panel with an available 40 amp 220 ungrounded ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I don't ...
|
| new service | 7/17/2007 |
Q: Robert I'm installing new service to my garage,200 amp single phase,I have the breaker box mounted ... A: Service ends at disconnect below meter. Ground rod connected to neutral at disconnect below meter. ...
|
| new service | 7/16/2007 |
Q: Robert I'm installing new service to my garage,200 amp single phase,I have the breaker box mounted ... A: Will there be a disconnect [breaker] at the meter location for the feeder to the new panel? [Service ...
|
| GFCI outlet keeps tripping | 7/14/2007 |
Q: I have a GFCI outlet in my garage(back side of the kitchen and bathroom), I ASSUME it is this way ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I don't ...
|
| Ceiling Fan and Dimmer Switch | 7/13/2007 |
Q: I am having trouble with a ceiling fan /dimmer combo and I would appreciate your help. Note that ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Tripping GFI Breaker | 7/11/2007 |
Q: I wired a bedroom with 12/2wg on three sockets and 14/2wg on two lights. I used a 20amp GFI breaker ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| three way | 7/10/2007 |
Q: Hey robert I have a problem with a 3way. I have power coming into first box 2wire, switch leg goes ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| appliances don't work AFTER INSTALL | 7/8/2007 |
Q: Hey......I just rewired the main service wires upto the breaker in my house. Instead of BUYING the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| 220 wiring for electric baseboard heat | 7/4/2007 |
Q: I want to install some electric baseboard heaters in several apartments I am rehabing, but have not ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| wiring multiple lights | 7/3/2007 |
Q: I want to connect five reccessed lights. The feed comes through first switch to each light then ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| pool pump | 6/30/2007 |
Q: My new pool pump comes wired for 230v...it is easily changed to 115v. How can I find out what my ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| old dryer wiring receptacle | 6/28/2007 |
Q: I have some friends in a kennel in Long Pond PA that I recently purchased an oldie but goodie Maytag ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| GFI Reset | 6/26/2007 |
Q: both other day both my outside outlets went dead. I checked the breaker box and they are listed as ... A: - Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There is a ...
|
| spotlights | 6/25/2007 |
Q: i hope you can help me. I have a living room that leads into the dining room. The living room has 8 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I would ...
|
| Outlet sparked all electric stopped working | 6/23/2007 |
Q: There was a outlet that sparked in my living room and then all the outlets stopped working along ... A: If you were not doing something at the outlet that sparked, I would suggest that is where the ...
|
| Changing the cord on my dryer | 6/22/2007 |
Q: I have a dryer that has three prongs, but the house I move into has a plug for a four prong dryer. ... A: I think if you follow the green wire in the machine, it will come to a splice point, from which it ...
|
| salt water dock wiring | 6/19/2007 |
Q: I am having my dock wired by an electrician who needs to go 550 ft from my house to end of dock for ... A: Well, common logic would suggest this to be true. But, I am not knowledgeable in this matter, so I ...
|
| Replaced Fixture - Light won't turn off - 1963 house - 2 switches | 6/18/2007 |
Q: switches, and now the light won't turn off. Can you tell me how to fix this? also, have wiring ... A: let me guess, you didn't just take down the old light .. open up the splices in the box as well? ...
|
| Intermittent Electrical problem. | 6/12/2007 |
Q: I live in an older small home (built in the mid 1960s) and lately I'm having this strange problem ... A: You have created a problem. If there is no ground, you should not use grounded receptacles. Remove ...
|
| Voltage Dropout switch | 6/6/2007 |
Q: We have a neighborhood pool with two pumps and motors. When the power goes out both pumps try to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Do both ...
|
| hot floor spot | 6/5/2007 |
Q: In the master bathroom, between the shower and the cabinet with twin sinks, there is a warm spot on ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Well, it ...
|
| Power, correct wiring... no light | 6/4/2007 |
Q: I am rather stumped and not sure what is happening. I have wired plenty lighting features before, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Replacing Electric Baseboard Thermostat | 6/2/2007 |
Q: I'm in the process of remodeling our kitchen and want to replace the 30+ year old electric baseboard ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| open ground | 5/29/2007 |
Q: My name is Kristin. I have a question, I know NOTHING about electricity and I have just moved into ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * All the ...
|
| Adding Breakers/outlets | 5/27/2007 |
Q: I need to add two new outlets each on their own 20 amp breaker to accomodate a kiln designed to run ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| electric | 5/25/2007 |
Q: I have a single pole switch with two wires in the box .One is the feed and the other is 14-2 to the ... A: at switch- black to black and switch red to other switch terminal white to ...
|
| New Home electrical issues | 5/24/2007 |
Q: I just purchased a new custom home. During the inspection it was noted that some connections were ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Recessed ...
|
| philadelphia licence | 5/23/2007 |
Q: I finished an electrical course with CHI Institute in Southampton, PA. How can i obtain a license ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You don't ...
|
| multi gang switches | 5/21/2007 |
Q: I would like to know can I put 3 diffrent phases inside a 3 gang lighting switch?is there any ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You have ...
|
| Tripping a breaker | 5/15/2007 |
Q: I've got a real stumper. One of my tenants kept complaining every time she turned on her oven/stove, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| motion sensor | 5/13/2007 |
Q: Ok, this is probably going to be an easy answer, but I'm a retard when it comes to messing with ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Wiring 3 switches | 5/9/2007 |
Q: I am installing a wall light and a fan light combo in my basement bathroom. I want all 3 switches to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| pulling wires | 5/8/2007 |
Q: I will be pulling 4 - 2/0 copper wires in a 2" pvc conduit which will be onehead in two buildings ... A: NOPE what I said was that the first pull should probably be from the first LB [the one over the ...
|
| j box sizing | 5/7/2007 |
Q: yes have 1 4in, conduit entering a box and on other side have 1 2 in., 1 1/14,1 1in..I think ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Problem with three-way switch controls two outlets | 5/6/2007 |
Q: if one is mis-wired, the whole circuit doesn't work. In this circuit, we have two duplex outlets ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| whole house fans-do I need a dedicated line? | 5/5/2007 |
Q: I am installing a whole house fan which has a 4 amp motor, and a uses 480 watts. I currently have ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| pulling wires | 5/4/2007 |
Q: I will be pulling 4 - 2/0 copper wires in a 2" pvc conduit which will be onehead in two buildings ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Light Switch problem | 5/3/2007 |
Q: I had a renter who replaced a light switch to match paint (almond to White). They replaced it with ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The hot ...
|
| Neutral and ground blocks in panel | 5/2/2007 |
Q: I noticed that both the neutral (white) and ground (bare) wires are connected to the same block in ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It is ...
|
| V230/208 conversion to 115v | 4/30/2007 |
Q: I have 2 wall unit air conditioners (V230/208, Amps 8.2/8.4) in a duplex that I own. I am wanting ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Cut Wire | 4/29/2007 |
Q: My husband and I have a house in Sea Isle City. This weekend, we were getting ready to have new ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| add a second light fixture | 4/27/2007 |
Q: I am remodeling a bathroom with one light over the vanity. I want to use 2 lights instead, one on ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| AFCI | 4/25/2007 |
Q: Ok, Here's my problem. All is good with the arc fault except when my inspector came to do a final he ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The ...
|
| exhaust fan | 4/24/2007 |
Q: I just replaced a century type cp motor on a pool room exhaust fan and it runs backwards. Appears ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I suggest ...
|
| short circuit? | 4/23/2007 |
Q: I have two breakers that are somehow interfeering with each other - both will remain on if the other ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You could ...
|
| Wiring electric baseboard | 4/20/2007 |
Q: I am converting my detached garage to an office. It is 12 x 16 feet and well insulated. My main box ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Since you ...
|
| Upgrade Service from 100 to 150 or 200? | 4/18/2007 |
Q: I'm interested in upgrading my electrical service from 100 amps to 200 amps and am in the process of ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Unless you ...
|
| Light bulbs burning out b4 their time | 4/17/2007 |
Q: I manage a 16 unit apartment building and one of the tenants has recently complained that light ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * An open ...
|
| Installing ceiling fan with light kit and remote | 4/15/2007 |
Q: I am installing a ceiling fan with a light kit and a remote control on two switches. The first ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Did you ...
|
| half of a curcuit is out | 4/14/2007 |
Q: My roommate who lives in my guest bedroom came home from work last night to find that the ceiling ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Moved dryer from US to South America | 4/13/2007 |
Q: .. You say you like stuff that stumps other people.. well here's one that's got my electrician ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 110 volts ...
|
| Control light/fan from 2 locations | 4/12/2007 |
Q: I had a light in my house that was being controlled by two 3-way switches. I replaced the light with ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I hope you ...
|
| main breaker | 4/11/2007 |
Q: I want to install an arc fault circuit breaker. I tried to turn off the main circuit breaker but it ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The main ...
|
| electrical problem | 4/8/2007 |
Q: I'm stumped! Four days ago, I connected a Rug Doctor cord to my bathroom outlet. Ten seconds later, ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Don't know ...
|
| Ceiling Lights & Electrical Outlets Suddenly Not Working | 4/6/2007 |
Q: A few days ago I noticed the lights weren't working on the living room ceiling light. The fan is ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sounds ...
|
| Home wiring using something like flex pc board | 4/4/2007 |
Q: I do not have a plug in the middle of basement carpeted room. I want something that carries 115v for ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Flat ...
|
| house wire | 4/3/2007 |
Q: I have 2 old wires each connected to a 30amp breaker each was hooked up to an double oven or a stove ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| junction box | 4/2/2007 |
Q: I need to buy a toner to locate my junction box; someone told me they cost $l50, yet I see them ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The unit I ...
|
| 220 SINGLE PHASE FROM THREE PHASE POWER | 3/30/2007 |
Q: I HAVE A STEREO FROM GERMANY THAT DOESNT HAVE THE SWITCH ON THE BACK FOR 110 IN US AND 220 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Fan switch problems | 3/28/2007 |
Q: Ok, hope its not too long, but its complicated (to me anyway). I can't operate my middle room ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * My guess ...
|
| How to run wire from an outlet to new fixture | 3/27/2007 |
Q: What's the best way to add a new light fixture to the existing switch by out attic access (I only ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| wiring problem | 3/25/2007 |
Q: I have a dead outlet in my house. It went dead suddenly. There are also a coulpe of lights on this ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Smoke Detectors | 3/22/2007 |
Q: Mr. Wilber, I just moved into an 18 year old home and need to replace the smoke detectors. When I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Installing multiple baseboards off one thermostat | 3/19/2007 |
Q: Help needed!!! Thanks in advance. Background - 3 baseboard heaters (2) 6.1amp 1500 Watt (1) 4.1amp ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| Push button switch | 3/15/2007 |
Q: What is the difference between normally open or normally closed? I need to push the button to make ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Normally ...
|
| New house pops gfci's | 3/14/2007 |
Q: By "other leg" are your referring to the other 110 circuit in the 220 CB Box? By looking at the ... A: I was speaking of the other 110 side of the panel. There may be something wrong with the way it is ...
|
| subpanel | 3/13/2007 |
Q: I currently have a 200 amp Murray panel in my home. I need to add a subpanel due to most of the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Panel type ...
|
| New house pops gfci's | 3/12/2007 |
Q: My new house has four GFCI's located in 3 separate rooms and wired into the same circuit. The ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I take it ...
|
| light bulbs fall apart in recessed fixtures | 3/10/2007 |
Q: my basement has 5 recessed light fixtures in the ceiling, which operate off one wall switch. Almost ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You are ...
|
| ceiling light | 3/9/2007 |
Q: I took down a lighted fan to replace with typical ceiling light. After hooking up wires(two black ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| old baseboard heater wiring... | 3/8/2007 |
Q: I'm replacing my baseboard heaters and wiring in one bedroom. I have done plenty of new work on ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * ...
|
| Bathroom Fan | 3/6/2007 |
Q: Hey, I'm remodeling my bathroom and i have added a new bathroom fan, there was no fan before. i just ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Wiring a replacement oven broiler element | 3/4/2007 |
Q: I am attempting to replace the broiler element in my built in oven. In removing the old element I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Ya got me ...
|
| Treadmill Power Requirements | 3/3/2007 |
Q: I would like to keep a commercial treadmill in my home, and am concerned about the power ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * When I was ...
|
| Two 3 way switches and an outlet | 3/2/2007 |
Q: Ok I want to have the power run into the 1st 3-way (dimmer) switch on a 14/2 and then up to the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Honeywell Thermostat | 2/27/2007 |
Q: I have installed three new Honeywell digital thermostats. I think that I wired them correctly as ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It is ...
|
| Wiring | 2/26/2007 |
Q: I recently installed a bathroom light/fan all in one. There was previously a light already in the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You have a ...
|
| Main Braker Problem | 2/24/2007 |
Q: I run a (70 year old) church campground, we have a 200 amp main breaker box.. Last year we changed ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The reason ...
|
| lots of wires | 2/23/2007 |
Q: I recently bought a house. when i moved in i noticed in the kitchen there was a panel of 4 light ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sounds ...
|
| outlet placement with regard to hot water baseboard heating | 2/22/2007 |
Q: What is the appropriate distance to place electric outlets with regard to hot water baseboard ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There is ...
|
| commercial wiring | 2/21/2007 |
Q: Think I have the answer, but anyway. I want to put a 120V SP switch in the same 2 gang box with a ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * According ...
|
| losing half of circuits-no breakers tripped | 2/20/2007 |
Q: Yes. we called the power company early on because I noticed an arc burn behind one of the incoming ... A: As I indicated initially, your original symptoms suggest a partially or completely open neutral. ...
|
| losing half of circuits-no breakers tripped | 2/19/2007 |
Q: After several rounds of power surges where some lights dimmed and others went bright, which also ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Neutral? ...
|
| no power | 2/17/2007 |
Q: we have a sun room off the back of the house and everything was fine until power went out to the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There is ...
|
| Wiring | 2/15/2007 |
Q: I currently have a 4 wire cooktop and I purchased a 3 wire cooktop. The new cooktop is a plug in ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The NEC ...
|
| New Home | 2/14/2007 |
Q: We are getting a new mobile home and need a new pole and loop for service. We have gotten some ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| outlet box | 2/13/2007 |
Q: I would like to take out my old exhaust hood over my range and replace it with a microwave oven. I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Condensation in Main Panel | 2/12/2007 |
Q: I will tryto describe to you the situation. House is a 2,500s.f. ranch, with full basement, 1.5 yr ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| ARC Fault Breaker Trips | 2/6/2007 |
Q: I've lived in my home for 4 years no issues - came home today and although earlier in the evening we ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Aluminum Wiring | 2/5/2007 |
Q: I have a home that was constructed in 1955 that has Aluminum wiring. I wanted to install a bathroom ... A: I have no experience of either the AMP method nor the AlumiConn product. I can have no opinion. As, ...
|
| Aluminum Wiring | 2/4/2007 |
Q: I have a home that was constructed in 1955 that has Aluminum wiring. I wanted to install a bathroom ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Dry wall cut out too big for switch plate cover | 2/2/2007 |
Q: we had a shady electrician who has dropped off the planet install a light switch in our home. We ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I suggest ...
|
| Home Additions | 2/1/2007 |
Q: What is the min. size conductor needed for 200 amp service and what size conduit should I use? Does ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Electrical hgouse wiring problem | 1/31/2007 |
Q: Some of my electrical lines don't work. The only one that works is the one near the circuit breaker. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You have ...
|
| difference between 110 volt 120 volt | 1/30/2007 |
Q: what is the difference between 110 volt plug and 120 volt appliances. I am interested in a 120 volt ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * For ...
|
| 3 wire ballasts | 1/28/2007 |
Q: i am changing a ballast in a single bulb 8 foot fixture the ballast only has 3 wires black white red ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Wire size. | 1/27/2007 |
Q: Is it possible to install or use to large a gauge wire for a load? I know too small is not good. Is ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| 3 phase power requirements | 1/26/2007 |
Q: I am running some circuitry for two three phase 240 volt motors, both 3 phase. I have 3/4" conduit ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Wall heater | 1/25/2007 |
Q: I have a 2000 watt 240 volt wall heater that I will be puting on a 20 amp 2 pole circuit breaker. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You won't ...
|
| under caninet lights | 1/23/2007 |
Q: I am installing some under cabinet lights in a built in bookshelf. here is the materials I am ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * First, you ...
|
| 2 switch, 3 lights? | 1/20/2007 |
Q: Good evening Robert, I just came across your website & have a cedar homes business in central PA. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| 4way wiring in family room | 1/19/2007 |
Q: You are correct. In re-checking and switching around wires today, I found that the middle 4way ... A: Good for you! If you had more experience you would have realized to look for it yourself. [All I did ...
|
| 4way wiring in family room | 1/18/2007 |
Q: Sir: I am 4 way wiring the switches in a new family room ( so you can operate lights from all entry ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| generator | 1/15/2007 |
Q: During a power outage, if I shut off the main breaker, can I plug a generator into any outlet to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Baseboard Heater Thermostat | 1/13/2007 |
Q: I have two baseboard heaters running on one Honeywell thermostat (programmable) (RLV430A) . I have ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 1] I can't ...
|
| European Voltage | 1/11/2007 |
Q: Wilber : I recently purchased a front porch light fixture made in Italy. After installation, my ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Yes. Your ...
|
| outlet noise | 1/10/2007 |
Q: Sorry, I should have told you it was an inside wall with no outlet on the opposite wall. What action ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Have you ...
|
| Wiring a switch/outlet combo | 1/7/2007 |
Q: I live in an older house (built 1959) and the bathroom has no electrical outlets. There is a light ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You are ...
|
| Hot/Ground Reversed | 1/6/2007 |
Q: Last night, several receptacles went out in my home cutting off power to several appliances. I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I can't ...
|
| 100 amp to 200 amp service | 1/3/2007 |
Q: Robert, Im looking to upgrade my current 100 amp service to 200 amp service. what are my hardware ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * so, if you ...
|
| Ampacity of Disconnect v. Main Panel CB | 1/1/2007 |
Q: MyThe evaporator (fan coil) unit for my heat pump system includes a "supplemental" 8KW electric ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Fusible ...
|
| Doorbell Problem | 12/31/2006 |
Q: The solenoid in the doorbell chime continually stays energized (making a humming noise). I thought ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The only ...
|
| wiring | 12/29/2006 |
Q: We are building a new house and our electrican came in and did all the new wiring... he drilled ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Absotively ...
|
| Transition between interior and exterior | 12/27/2006 |
Q: I'm in the process of pulling power from a subpanel in the garage to the side of the house where we ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Candle Lights with timers | 12/26/2006 |
Q: There is no intentional interruption of the circuit. I have checked the circuit panel for any ... A: Fascinating. I can't imagine what could cause such behavior. Contact the manufacturer. Electronic or ...
|
| flickering lights | 12/26/2006 |
Q: I recently purchase a house, when I did the initial inspection I did not notice this problem. When ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Just found ...
|
| Candle Lights with timers | 12/25/2006 |
Q: We have about A dozen of the candles with timers that we put up for the Christmas Holiday. Ten are ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Without ...
|
| blown light bulbs | 12/24/2006 |
Q: My Light bulbs dont last. I can install new bulbs and have blown bulbs in a couple of days. What ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Why do ...
|
| Safety in the home. | 12/23/2006 |
Q: How can I let the nation know of a possible very dangerous situation? When asked to check two faulty ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The danger ...
|
| GFCI Wiring | 12/20/2006 |
Q: I am installing an outdoor GFCI outlet at the base of the lamp post. Is there a GFCI outlet on the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Never seen ...
|
| Wire repair | 12/19/2006 |
Q: I just had a new cable and phone line put into my home. The installer nicked a romex wire in the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Well, I'm ...
|
| 3 way wiring with multiple fixtures | 12/18/2006 |
Q: I am just curious and want to be sure. I understand to use 4 wire for wiring this type of setup. Is ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * What you ...
|
| water heater | 12/17/2006 |
Q: good morning robert yesterday i went to home depot and purchased a 40 gal.3500 watt 240 volt ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Well, the ...
|
| 220 shop wiring | 12/15/2006 |
Q: I have a 220V dust collector puls a table saw and band saw that can be switched to 220. I have ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Open hot side in outdoor outlet | 12/12/2006 |
Q: I am stuck on this I have an outdoor outlet that has the hot side open,the house is 5 years old and ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 610-299-0452 ...
|
| outdoor 120 lights and gfi issue | 12/11/2006 |
Q: sorry for the long description about to come - i want to give as much detail as possible so you may ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 610-299-0452 ...
|
| 220vac circuit | 12/8/2006 |
Q: When calculating the current through each leg of a 220VAC circuit that is wired to a devise (say a ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Run this ...
|
| Installing a outside outlet | 12/7/2006 |
Q: I am wanting to install a outside outlet to plug my Christmas lights in. I have a plug in my sunroom ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| single pole switch wiring to light | 12/5/2006 |
Q: Florescent fixture when hooked to power lights up but when switch is flipped to on circuit blows. ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| grounding short | 12/4/2006 |
Q: I get shocked everytime I use my dryer if I am touching the wash machine and have wet clothes in my ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Wiring a Bath Fan Switch | 12/1/2006 |
Q: I installed a bath exhaust fan (no light/no heater) in my bathroom and now I need to wire it up. I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * If there ...
|
| Multiple single pole switches in one gang box controlling multiple lights and an outdoor outlet | 11/30/2006 |
Q: Master Bob, I need to wire three single pole switches in one boc with one incomming electrical feed ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| 220V Infrared Heaters burned out instantly | 11/29/2006 |
Q: What a wonderful thing you are doing. Must eat up a lot of your free time though. Just thought I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Are these ...
|
| 220V Infrared Heaters burned out instantly | 11/28/2006 |
Q: I have a couple of infrared heaters from Sweden rated 1000W at 230V 50Hz. I installed a 220V ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The ...
|
| Outdoor Lamp Posts | 11/27/2006 |
Q: I have three outdoor lamp posts. Two on either side of my horseshoe driveway and one by my steps to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Your drive ...
|
| ceiling fan | 11/26/2006 |
Q: I have a light I took down from my ceoling unfortunatley I missed what all the wires where conneted. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Please ...
|
| Wiring a Chandelier | 11/23/2006 |
Q: "Hello, In our dining room we have two recessed cans. I was told by a buddy he has seen on multiple ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I didn't ...
|
| T8 Florecent Light problem | 11/22/2006 |
Q: Robert. I got a new 96" T8 fixture that takes 4 48" T8 lights and 4 new lights. I Installed the ... A: Weird Are the sockets in the right places? Proper voltage input? I would contact the fixture ...
|
| 220V Wiring | 11/20/2006 |
Q: I have 220V 30Amp prewired in the wall behind the clothes dryer (consisting of 1 ground, 1 white & 1 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sounds ...
|
| Electrical | 11/18/2006 |
Q: "The lights on one circuit in my house occasionally flickers and goes out. It only effects the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The only ...
|
| gfi won't reset. | 11/17/2006 |
Q: Robert, I've recently renovated my home. I had wired the upstairs bathroom in with one of the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There is ...
|
| some lights out | 11/15/2006 |
Q: I was changing a lightbulb and a piece of metal fell in the socket. I tried to get it out and little ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You most ...
|
| BREAKER NEVER TRIPPED | 11/14/2006 |
Q: MY QUESTION INVOLVES HOUSEHOLD WIRING. THE OUTLETS IN OUR LIVING ROOM STOPPED WORKING WHEN OUR ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The only ...
|
| Lights dim or flicker | 11/12/2006 |
Q: We recently had a power outage, and ever since then my lights dim or flicker, an sometimes get ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Bad ...
|
| Garage wiring | 11/9/2006 |
Q: I am adding electric to a detached garage. When I began my work, I was told that unless I was adding ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Oops! That ...
|
| breaker panel and outlet box wiring | 11/7/2006 |
Q: When homeruns or wires with sheathing are entered into a panel or outlet box, how much of the ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Length of ...
|
| fan wiring | 11/6/2006 |
Q: I wired electric for a fan with a light. 2 seperate switches 12-2 wire in black wire with 2 ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Phantom ...
|
| I think I nailed into a wire | 11/4/2006 |
Q: Yesterday I replace some base board of the floor in my dining room. Last night when we got home I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Baseboard ...
|
| dryer, short out | 11/2/2006 |
Q: I got a used dryer, after plugging it in, i turned it on then it sounded like something shorted out. ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I got a ...
|
| wiring a plug | 11/1/2006 |
Q: I purchased a new wall oven I was told it had to be wired on a plug not hard wired How do i wire it ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE ...
|
| GFCI question for beginner | 10/31/2006 |
Q: I am a little confused here and was hoping you can provide some insight. Ive been researching all ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * read more ...
|
| single vs double pole circuit | 10/29/2006 |
Q: I have a Singer electric 240 volt fan-forced heater on a 20 amp double pole breaker. I want to ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You got it ...
|
| Home Lighting | 10/28/2006 |
Q: Mr. Wilbur, I have an overhead incandescent light fixture with two bulb sockets. I install both ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Quality ...
|
| Adding a basement sub-panel | 10/25/2006 |
Q: Good morning, My wife and I are finishing our basement. We have a 200 amp main panel in our ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE ...
|
| Voltage variation | 10/23/2006 |
Q: 5 yr old wall outlet tests 120v. When I plug in a (test) Fan the voltage drops to Zero. When I ... A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Getting ...
|
| recessed lights | 10/22/2006 |
Q: how many ic remodel can lights can i put on one switch 120v 75 watt max bulb ic rated A: - * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * How many ...
|
| 400 amp service | 10/21/2006 |
Q: I was looking in a NEC book the other day about Parallel main Entrance cable. It said That a 400 Amp ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * What you are ...
|
| cieling fan wiring | 10/18/2006 |
Q: I am confused on the wiring for a cieling fan. In the cieling I have a red, white,black and bare ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Read the ...
|
| 220 line for a welder | 10/16/2006 |
Q: i have an old screw in type fuse panel....i want to run a subpanel off of that just for my welder. ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It is not ...
|
| Electrical Drain | 10/14/2006 |
Q: Robert; I have just wired my basement with Romex 14/2 with approximately 14 outlets and a couple of ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * First things ...
|
| Electrical Sub-Panel | 10/12/2006 |
Q: I have a old Federal Pacific 100 amp panel. I have a double 100 amp breaker. The total amp readings ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Sub-panel? ...
|
| switched outlet voltage | 10/11/2006 |
Q: Home Inspector here. Getting into homes with switched outlets mainly in newer construction. Bottom ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * On a ...
|
| Wiring a motion sensing 3-way wall switch | 10/9/2006 |
Q: I have a Cooper (#6107) Motion Sensing 3-way Wall switch. The switch has one green, one brown, one ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Where do the ...
|
| wires | 10/8/2006 |
Q: I currently have a 100 amp service in my home. I have just built a 30x30x10 garage out back and will ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * New 200 amp ...
|
| Lights don't work | 10/7/2006 |
Q: I have three recessed light fixtures on one circuit. One stopped working, then a few weeks ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Three lights ...
|
| knob and tube wiring | 10/5/2006 |
Q: Robert I have an oler home in central Pa. Most of the wiring has been upgraded and a new 200 amp ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Knob and ...
|
| Low Voltage house home system | 10/4/2006 |
Q: I have a large house (over 50 yeras old) with low voltage system based on "touchplate" dimmers and ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Gee, Ed ...
|
| Faulty Wiring Causing no "trip" in breakers | 10/3/2006 |
Q: I am having a problem where many different lights and outlets will flicker and sometimes go out then ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 1] Do you ...
|
| GFCI wiring in a 2-wire house | 9/30/2006 |
Q: 1. I have a 2-wire house (1937) in Minnesota. 2. I have an outlet in the liv. room on an outside ... A: More information please Are the 2 rubber/cloth conductors in a common cable covering? Is the ...
|
| circuit breaker | 9/29/2006 |
Q: I am the original owner of a 29 yr old house which came with a GE panel wired with central air.I ... A: Let me guess The 50 amp breaker on the 10 wire goes to the AC unit Try a 40 amp breaker and tell the ...
|
| 220 water heater | 9/28/2006 |
Q: I bought a 220 water heater with a red and a black wire. My house is an older house (40 yrs) and the ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Water heater ...
|
| Light switch not working.... | 9/22/2006 |
Q: First off, thank you for any assistance you can provide. In my living room there are two electrical ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I changed my ...
|
| 220v heater swap out | 9/21/2006 |
Q: Probably a stupid question, but... I'm in the process of swapping out some seriously old ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| GFCI and/or hot/neutral reversal | 9/20/2006 |
Q: Here's my situation: I built a workshop in my backyard- it has a subpanel that is fed from a 50 amp ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You just ...
|
| Recess lighting and 220V wiring | 9/19/2006 |
Q: A few questions about my wiring project for my finished basement. Your answers will be appreciated. ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| affixing receptacle boxes in brick walls | 9/17/2006 |
Q: We are trying to install light and receptacle in our brick wall and are stumped at how to affix the ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It is common ...
|
| Wiring GFI w/ 3-line elec cable | 9/16/2006 |
Q: I have an outlet in the laundry room that I would like to instl a GFI. The present outlet is 15 amp ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * To replace a ...
|
| Installing a new GFCI Outlet in exisying bathroom and kitchen | 9/14/2006 |
Q: I would like to install GFCI outlets in existing bathrooms and kitchen. Can I replace an existing ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * GFCI ...
|
| hot water heater and mild shocks | 9/13/2006 |
Q: Recently, we had a bad thunderstorm and lightening struck very close to our house. After that, one ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Why did you ...
|
| a long run of outdoor wire | 9/12/2006 |
Q: We're building a house and living in a little trailer (9x17). The house is way behind schedule so ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 1500 watts ...
|
| Changing a ballast | 9/11/2006 |
Q: I bought a ballast to convert a light fixture from 220 to 110. It says it's for 4 lamps F25t12. The ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You want to ...
|
| electric baseboard | 9/8/2006 |
Q: I am installing electric baseboard heat in an upstairs apartment and I am running the wires through ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Second ...
|
| Fan switch wiring | 9/6/2006 |
Q: oops i forgot to mention.. (i dunno if it matters or not) but the existing switch for the original ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There is no ...
|
| Fan switch wiring | 9/5/2006 |
Q: ok.. ill try to keep this short and simple.. I have existing light im taking down and installing 2 ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| electrical | 9/4/2006 |
Q: underground wiring how deep does it have to be? A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * How deep ...
|
| new ceiling fan installation | 9/2/2006 |
Q: Just installed a hunter ceiling fan. At first it didn't work at all. I re-did the entire wiring ... A: * Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Voltage ...
|
| Light switches should be down when off | 9/1/2006 |
Q: My foyer light has two switches to turn it on or off. One is just inside the front door is one is ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You want ...
|
| Shunt breaker | 8/31/2006 |
Q: Good morning, I am interested in knowing what a "shunt breaker" is and how it is wired in. I'm told ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| light switch wiring | 8/30/2006 |
Q: I've installed a light switch, but the breaker trips when I turn on the switch - any ideas? Thanks ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Insufficient ...
|
| 220volt Dryer wont run | 8/27/2006 |
Q: Good Afternoon, And thank you first off - Brand new dryer - 3wire 4prong in the wall and for the ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You haven't ...
|
| THE LIGHT SWITCH IS HOT BUT NO LIGHTS | 8/26/2006 |
Q: I replaced a light switch because the old one was not staying on, you had to fiddle with it. (The ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You replaced a ...
|
| Diming lights when A/C comes on | 8/25/2006 |
Q: My home is less than 1 year old, we have had a problem with diming lights when the Lennon ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * There was no ...
|
| outdoor low voltage lighting; indoor timer? | 8/23/2006 |
Q: We moved into this house in 2002 and replaced all the exterior walkway lighting had some help from ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * As you ...
|
| light fixture / switch problem | 8/22/2006 |
Q: My house was built in 1962. I have a ceiling light in my hall that I want to replace. My problem is ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * You have a ...
|
| lighted wall switches | 8/20/2006 |
Q: replacing a standard wass light switch with an illuminated switch . the new switch has two screw ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| ADDING PENDANT LIGHTS BY CONNECTING TO EXCISTING CEILING LIGHT FIXTURE | 8/19/2006 |
Q: IS IT POSSIBLE OR EVEN LEGAL TO CONNECT SURFACE WIRING FROM EXCISTING CEILING LIGHT, OVER TO PENDANT ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Man has walked ...
|
| lights not working | 8/18/2006 |
Q: several lights have stopped working in my house yet the fuse hasn't blown and the light bulbs are ... A: You said several lights have stopped working in your house, yet the fuse hasn't blown and the light ...
|
| electric out to part of one circuit | 8/16/2006 |
Q: about a week ago when i turned on a television in the upstairs of my house the power to the upstairs ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| Fuse box | 8/14/2006 |
Q: I recently inherited and old farm house from my dad wired with a fuse box. The box says 60 amps on ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| service cord voltage rating | 8/13/2006 |
Q: I do not understand the voltage rating on service cords. They are rated at 300v and 600v. Is this ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| replacing an outlet | 8/12/2006 |
Q: Ok I just got a dryer which needs a 3 wire outlet, but the outlet in my wall is a 4 wire outlet. Is ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| follow-up ceiling fan wiring | 8/9/2006 |
Q: to clarify my previous question- the switch is in a 3 gang box, the switch that runs to the ceiling ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| Generator to Compressor | 8/6/2006 |
Q: Bob, I'm trying to put together a cord to run my compressor off of my generator. From my searching, ... A: 20 amp 240 volt needs no neutral, only two hots and a ground. Therefor, there is no need to bring ...
|
| electrical wiring | 8/5/2006 |
Q: I am planning on installing a wall mount air conditioner in my florida room and the voltage required ... A: 208 isn't the same thing, but you have the idea. Water heater was 30 amp breaker probably, 10 gauge ...
|
| house wiring | 8/4/2006 |
Q: I have 4 outlets in home office & 2 in master bedroom that are out. I have checked the breakers ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| temporary electric pole | 8/3/2006 |
Q: I need to install a temporary pole to power a well until the house is built. Have bought all (I ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| Generator Home Wiring | 8/2/2006 |
Q: First off, you must understand that so far I have run into many snags with hooking up a few circuits ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * (LIFE SAFETY ...
|
| Above Ground Pool Grounding | 8/1/2006 |
Q: Robert: I recently helped my sone install some wiring for his above ground pool. All is working OK. ... A: Contact the local "authority having jurisdiction" Pool bonding and equipment grounding is a critical ...
|
| Panel redo | 7/31/2006 |
Q: I have a panel upgrade from fuses to circuit breakers when I redid this I could not find a panel ... A: Splices in the panel with wirenuts are acceptable provided there is enough wire to make a reasonable ...
|
| Trying to make a conversion cable. | 7/28/2006 |
Q: I recently purchased a Bosch Axxis+ washing machine for a great deal. My problem is that I have a ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The "L" shaped ...
|
| hot tubs | 7/25/2006 |
Q: Ok well I chose your profile because I'm originally from Penn. Trying to get a handle on the code ... A: NMWU is a Canadian approved material not applied in the US. It is apparently rated for direct burial ...
|
| electrical outlets | 7/21/2006 |
Q: I own a 30+ home and I want to replace my vent-a-hood with a overhead microwave when taking the hood ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Older kitchen ...
|
| running a 220 line | 7/17/2006 |
Q: Robert, sorry you've dealt with ungrateful people. I too volunteer my time and patience (working ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Kathleen Do ...
|
| Licensing | 7/13/2006 |
Q: I have a friend he's a great electrician, the only problem is he went to school in Mexico, and i ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * If your friend ...
|
| Lighting fixture wiring problem | 7/12/2006 |
Q: I really hope you can help me and I truly appreciate your advise! I wil try to give as much detail ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Didn't trip ...
|
| single phase 240 Volt | 7/11/2006 |
Q: Robert my question is. A single family home that is 240Volts, one leg is 120v and the other leg is ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Center-tap ...
|
| Aluminum wire | 7/6/2006 |
Q: My home was built in 1969 and recently the lights have been flickering quite a bit and with larger ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| double pole switch wiring | 7/5/2006 |
Q: I need to replace a single pole switch that controls a fan and light with a double pole switch that ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| loss of power | 7/4/2006 |
Q: I live in a double wide modular home built in 2003. Lost all power in a cicuit that services my ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Replace Double Lugging with twin breakers | 6/30/2006 |
Q: Can you help me out? We need to replace 2 breakers in the breaker box with twin breakers because ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| 30A breaker instead of 15A breaker | 6/29/2006 |
Q: I wanna install a extra stove in my home, and when i was trying to install this i saw their is no ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| loss of power | 6/28/2006 |
Q: I hope you can help because I have done everything I can think of and have called all of the ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| wrong wiring between lights | 6/27/2006 |
Q: I try to explain the best I can the problem.In the basement of my house we have instaled panel ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Aluminum wiring - outlet works intermitenly | 6/26/2006 |
Q: Robert, I live in the townhome built in the 70's and it has aluminum wiring. Recently, electrical ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Floor Lamp | 6/21/2006 |
Q: I have an old floor lamp that my wife likes. Around where the switch is, just below the bulb, it ... A: There are two possibilities: This is normal, and you never noticed it before, or this is not ...
|
| plug wires hot side burning out | 6/20/2006 |
Q: recently i had a washer cord where the black hot side melted...scorced prong and melted the plug on ... A: Mechanical connections fail. Heat gets created across loose connection. The higher the load, the ...
|
| Power loss in outlets of old home | 6/14/2006 |
Q: BACKGROUND: My house is 110 yrs old; I can't date the wiring at all, because it seems to have been ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| pool bonding | 6/13/2006 |
Q: I am instaling a inground 18x36 vinyl lined polymer walled pool. Have most of electrical wired but ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Swimming pool ...
|
| romex wiring | 6/12/2006 |
Q: I live in Monroe County Pennsylvania My house is wired with romex. My neighbor says taht I should ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Non-metallic ...
|
| End-of-run switch controlling two fixtures | 6/10/2006 |
Q: I found out how to properly wire a single fixture that is controlled by an end-of-run light switch, ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Phone jacks | 6/8/2006 |
Q: I just moved in to a new apartment and my land lord is a bum. I have wires running in my house to ... A: One phone pair is most commonly run on the green and red pair, second pair is usually yellow and ...
|
| Flickering Lights | 6/8/2006 |
Q: My house lights flicker. I also have a problem with getting a shock when i touch the shower handle. ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Flickering ...
|
| Bathroom Fan Wiring | 6/6/2006 |
Q: I've been getting a bit of conflicting advice on this one, so I'm seeking another opinion. I'm ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Odd Voltage Reading | 6/3/2006 |
Q: Mr. Wilber, Nothing worked when plugged into a receptacle in our bedroom. I disconnected the ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * A receptacle ...
|
| remote control ceiling fan | 6/1/2006 |
Q: Here is a real stumper, hope you can help. I recently changed my bedroom ceiling fan to a remote ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Remote control ...
|
| Electrical Wiring | 5/31/2006 |
Q: I will look into the access panels. Another question. When the house was built I had a 220V 20 ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * A splice is ...
|
| Room Inside of a Room | 5/30/2006 |
Q: I have a finished room into which I am building a high-end audio listening room. The dimensions ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Dealing with ...
|
| Low voltage on one receptacle | 5/29/2006 |
Q: I have been using this same receptacle since we built our house 19 years ago, however yesterday one ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| GFCI Protection | 5/28/2006 |
Q: Mr. Wilbur, I've done a good bit of wiring over the years but this one has me stumped. A friend is ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Read more ...
|
| Electrical damage to transformer | 5/27/2006 |
Q: Subject Electrical damage to invisible fence installation Question What are the electricians using ... A: Sorry, this is outside my area, but a quick search turned up the following link for a "standard" ...
|
| Problem on part of a cicuit & some voltage on neutral | 5/26/2006 |
Q: Robert, (My first time to this website.) A have a fair amount of electrical experience but am ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Electrical ...
|
| new wall oven | 5/25/2006 |
Q: I'm remodeling my kitchen and just received my new wall oven. looking at the wiring I saw that it ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Wiring to accommodate tankless water heaters | 5/23/2006 |
Q: New home with two (2) 28K tankless water heaters(Seisco). Each has 4 elements and 7000w. Our house ... A: Sorry, you are out of luck a 28 kw load is over 100 amps you are talking over 200 amp demand from ...
|
| reversed wiring problem | 5/22/2006 |
Q: Boy, I feel dumb. I was just trying to replace the 3-prong plug on my Champion Juicer and as careful ... A: Sorry, I don't have a clue what the battery size thingie is, capacitor, coil, gremlin motel ... ...
|
| single pole light switch | 5/19/2006 |
Q: I replaced a single pole light switch. When the switch is off the tester still has a faint glow at ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Curious ...
|
| Intermittent light failure of new halogen ceiling fixture | 5/18/2006 |
Q: We just replaced an old incandescent ceiling fixture in the kitchen of our 1970s-vintage house ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I am not ...
|
| Transient Voltage Surge Suppressor | 5/17/2006 |
Q: Can I install a three phase Transient Voltage Surge Suppressor in single phase home by using two of ... A: Yes and no ... A three phase suppressor is simply multiple suppressors connected internally, so yes ...
|
| Wiring Ceiling Fan | 5/15/2006 |
Q: I'm installing a ceiling fan and need some help with the wiring. The fan has a light kit and remote ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Installing a ...
|
| Gate opener-120 vs 240 | 5/14/2006 |
Q: I plan to install a gate opener at my house. The prior owner ran aproximately 400' of 10ga stranded ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * At the ...
|
| Faulty light switch? | 5/13/2006 |
Q: Robert, I installed a new 4-light vanity wall fixture in my bathroom recently. It is fed by a ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * I agree with ...
|
| UF cable | 5/12/2006 |
Q: Is there an easy way of stripping Direct Burial (UF) cable? A: Unfortunately not. Always comes down to a sharp knife and caution. Fortunately, it isn't necessary ...
|
| electrical wires | 5/11/2006 |
Q: I have purchase a new ceiling light but when I removed the old one I realised that the wires had ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The wires are ...
|
| Switched outlet | 5/10/2006 |
Q: We are installing a new switch and outlet in the kitchen. The garbage disposal was plugged into an ... A: The reason for the receptacle is to facilitate replacement of the disposal when it fails. The switch ...
|
| 110v motorhome GFI outlet | 5/9/2006 |
Q: I have a 110v 20 amp gfi outlet on my motorhome that I use to supply power to a towed trailer while ... A: I have a 110v 20 amp gfi outlet on my motorhome that I use to supply power to a towed trailer while ...
|
| circuit testor | 5/8/2006 |
Q: My Home Wiring Simplified book says regarding those little testors with the neon light that if you ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Good fuse? Why ...
|
| recessed lighting | 5/7/2006 |
Q: i have just had installed 6 reccesed lights in my kitchen along with a dimmer switch and 2 lights ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * The key here ...
|
| Circuit breaker clamp | 5/6/2006 |
Q: Nearly all of the single pole breakers in my panel box are tandem units as installed in my new house ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * It is called a ...
|
| Subpanel Wiring | 5/5/2006 |
Q: Im putting in a 60 amp subpanel and for wire im running 3-#8, copper, THHN/THWN insulation and a #10 ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * 8s are too ...
|
| Ground Wiring | 5/4/2006 |
Q: On a ceiling light fixture, what is the purpose of the ground wire? Is it to protect somebody from ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * What is the ...
|
| Multiple tripping breakers | 5/3/2006 |
Q: I just installed a new 60 amp hot tub. A few weeks after the install the owner started having ... A: Is it a new 60 amp breaker? What is the location of the breakers that trip? Is it always the same ...
|
| GFCI trips and cannot be reset | 5/3/2006 |
Q: I have a gfci outlet in my kitchen. A garbage disposal is on the same circuit. Worked well for 10 ... A: Something is doing something. Sounds like a ground fault to me. Turn off power, pull out all devices ...
|
| Sparking when plugging in 220 dryer | 5/2/2006 |
Q: Yes, the blue is actually green. I don't quite understand the rest. What is the dryer block & wher ... A: The frame is the shell of the dryer, the whole box where you changed the cord ends is the terminal ...
|
| wiring a ceiling light | 5/2/2006 |
Q: I am replacing a flourescent ceiling light fixture with a two-bulb, incandescent fixture. It should ... A: I take it the switch worked ok and controlled the fluorescent light properly. Make sure you get a ...
|
| Sparking when plugging in 220 dryer | 5/1/2006 |
Q: I moved into an older home & had to convert my dryer from 3 prong to 4 prong. I connected the 4 ... A: Sure the "blue" wasn't green? Standard connection would be green to frame. Make sure to eliminate ...
|
| Extending outside outlet | 5/1/2006 |
Q: I have an outside recepticle, flush in the outside wall, with a GFI recepticle ahead of it and a arc ... A: If you plug a regular extension cord into the GFI outlet and run it out to the tree, does it still ...
|
| extension cords | 4/26/2006 |
Q: Please also answer my first question. About my second question, I don't understand what you wrote. ... A: Wire size or gauge is related to current 14 gauge is good for 15 amps 16 gauge, I think for 12 amp ...
|
| gfci breaker | 4/25/2006 |
Q: I replaced a regular breker with a gfci breaker for my pool equipment. It worked fine until I turned ... A: Your pool and garage wiring share the neutral GFI reads the energized garage breaker load on the ...
|
| electrical | 4/24/2006 |
Q: Light bulbs burn out after only 2 or 3 days. What could be the problem? Thanks A: 1] High utility voltage envelope [125-135 volt] with low rated lamp [115 volt] 2] overvoltage - ...
|
| Electrical Wiring | 4/23/2006 |
Q: We have wired a new chandelier in the dining room. When we turn the circuitbreaker on to send power ... A: Was there previously a light controlled by the dimmer at THAT location? ...did you take down a light ...
|
| pump stumped | 4/23/2006 |
Q: Ok, my father and I are baffled here. We have a perfectly good water pump that was attached to our ... A: My guess would be that all the "3 wire outlets" everywhere in the 60 year old house don't have a ...
|
| WAC low voltage transformer wiring | 4/22/2006 |
Q: Robert, I am wiring two low voltage xenon puck lights with a WAC model en-1260-r-ar 60 watt ... A: Vic Should be a diagram of the transformer connections with your equipment. None the less, the reds ...
|
| Dedecated 20 amp circuit to microwave/hood location | 4/20/2006 |
Q: I recently purchased a 4 year old home from a reputable home builder in Gilbert AZ. After moving in, ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * Skip the ...
|
| Floodlights not working | 4/20/2006 |
Q: How do recommend eliminating the photocell?I recently purchased a home which was a former builder's ... A: LIFE SAFETY WARNING! [disclaimer] Electricity is dangerous! You can be injured or killed! Improper ...
|
| residential subpanel feeder sizing | 4/19/2006 |
Q: Why wouldn't you use the 75 degree C column in 310.16? The insulation on SER is XHHW. This would ... A: Doesn't matter what the insulation rating is The TERMINATIONS at the breaker are only 60 degree ...
|
| replace old switchs | 4/19/2006 |
Q: I live in CA in a home built in 1953. I recently found that on some of my plugs the connections are ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| residential subpanel feeder sizing | 4/19/2006 |
Q: I am planning on running #2 SER Al to feed a subpanel 25' from the main panel. I am not sure who ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Floodlights not working | 4/16/2006 |
Q: I recently purchased a home which was a former builder's model. To showcase the house at night, ... A: Eliminate the photocell from the circuit Anything is possible [as far as how they wired the lights] ...
|
| Range Oven Wiring (and other Kitchen appliance wiring) | 4/12/2006 |
Q: I live in Chester County, PA and am in the midst of remodelling my kitchen. The house is 23 years ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 NO! This is ...
|
| fixture replacement | 4/10/2006 |
Q: Do you mean, though, that it is safe to use and that the "warning" is meaningless?I live in an old ... A: Technically, it would be a violation of the NEC to install the light fixture, as the code requires ...
|
| Junctiion boxes | 4/10/2006 |
Q: What are the rules pertaining to the number and size of wires permitted to be joined in a junction ... A: There is no set minimum. You can bury the box, if the conductors, enclosure and splice method is ...
|
| fixture replacement | 4/10/2006 |
Q: I live in an old (1919) NYC apartment buildng. Wiring is original. I have replaced many of the old ... A: Give them the light back. All building wiring is 60 degree wire. Even the 90 degree wire cannot be ...
|
| Home electical problem | 4/10/2006 |
Q: I have a problem with the wiring in my basement and I am totally stumped as to what could be causing ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| Junctiion boxes | 4/9/2006 |
Q: What are the rules pertaining to the number and size of wires permitted to be joined in a junction ... A: You have 11 conductors: two in each 2 wire cable plus 3 in each 3 wire cable, plus 1 for all the ...
|
| REPLACING LIGHT WITH 2 PENDANTS | 4/7/2006 |
Q: I would like to replace the one kitchen ceiling light with 2 pendant lights over the island. The ... A: Robert Wilber Licensed Philadelphia Electrician Philadelphia License # 3516 - 16765 * LIFE SAFETY ...
|
| 220v wiring | 4/6/2006 |
Q: Should I run #6 stranded inside the house and if so, does it need to be in conduit or should I run ... A: Does your locality allow non-metallic cable? If so, get 6/3 with ground nm and run that. If not, get ...
|
| REPLACING LIGHT WITH 2 PENDANTS | 4/6/2006 |
Q: I would like to replace the one kitchen ceiling light with 2 pendant lights over the island. The ... A: That is perfectly ok. Only limitation is that you have to keep the existing outlet location, unless ...
|
| what size service coming to my house | 4/5/2006 |
Q: I have aluminum wire coming from the meter to my service panel. each hot leg goes to a 50 amp ... A: What you are describing is a 50 amp service. Never seen one. Are you sure the cable doesn't go to a ...
|
| Circuit Breaker Question | 3/31/2006 |
Q: Here's my crazy story. I hope you can help. A repair man recently damaged some wiring in our stove ... A: Sorry, he pinched the wire, but you trying to turn it on more than once contributed to the problem ...
|
| Outdoor recepticles | 3/30/2006 |
Q: I am installing two recepticles under my deck, I am extending a line from a ground fault recepticle. ... A: Attach wires run to new outside outlets to the load side of the existing GFI. The new outlets will ...
|