| furnace/blower dead | 10/12/2008 | Craig HVAC Expert |
Q: I own a York Diamond 80. my cellar flooded water level half way control panel covering the ... A: It is likly more then just the run cap. I would bet the control board or even the motor could be ...
|
| HEATER NOT WORKING | 10/11/2008 | Howard Livingston |
Q: I HAVE AN EVCON HEATER/AC THAT DOES NOT PUT OUT HEAT NOW. BLOWER WORKS, BUT NO HEAT. SOMETIMES IT ... A: Not enough info, Bill but I can make a guess. Main thing to know if this is a circuit board ...
|
| trane gaspack furnace | 10/11/2008 | Howard Livingston |
Q: unit has been cleaned and inspected but yet in am when it is not too cold out the heat seems to fire ... A: Wonder if you have low gas pressure ?? The flame sensor may not be sensing flames that are too weak. ...
|
| gas furnace cycling time | 10/11/2008 | Jim Barnhart |
Q: I recently bought a house with an American Standard two stage gas furnace (maybe mid 90's vintage). ... A: Lance, When you set your thermostat to a temperature such as 66 the furnace can't start and go off ...
|
| return vents | 10/11/2008 | Bill Brainard |
Q: We have a 200 year old cape in NH that has been used as a summer house until recently. We have a 7 ... A: Covering returns will cause furnace problems. It will not help at all. Close 1/2 of the hot air ...
|
| a/c compressor | 10/11/2008 | Jim Barnhart |
Q: My compressor unit (outside) was replaced 6 yrs ago. It stopped working a month ago and I have 3 ... A: Maria, I don't know exactly what your units are but the outside unit is your main air conditioner ...
|
| Air conditioning | 10/11/2008 | Jim Barnhart |
Q: My home has two AC units that are almost two years old which cool opposite ends of my home. On one ... A: Kristy, I think you hit the nail on the head. "AC units" are insulated on the inside of the units ...
|
| drainage | 10/11/2008 | Craig HVAC Expert |
Q: I have a carrier model 38ycc. The pvc pipe that drains when using the air is making a loud suction ... A: The reason for the noise....no water in the trap or no trap. If the unit is not cooling, that could ...
|
| Airflow into center of finished basement. | 10/11/2008 | Howard Livingston |
Q: I don't think I have enough air getting into the room which houses 2 H/W/H, and a 100k btu furnace. ... A: A stopped up flue pipe can cause this, Nick. Don't run it with yellow flames. That creates soot, ...
|
| fuse keeps blowing out | 10/11/2008 | Eric Campion |
Q: Why does the 3 amp fuse keep blowing out A: Unfortunately our expertise is with Major Home Appliances only. This would include washers, dryers, ...
|
| ductwork | 10/10/2008 | Jim Barnhart |
Q: We discovered a leak in ceiling and found it was a lot of condensation in the insulation. Also ... A: Rosemary, What are "the galvanized steel ducts" for? heating, cooling, both. What else is in the ...
|
| HVAC quote from 2 companies | 10/10/2008 | Jim Barnhart |
Q: I received two quotes for two different companies that are a couple of thousand dollars apart for ... A: Howard, You would need to ask the companies that gave you the quote's. There are no set standards on ...
|
| exhaust fan | 10/10/2008 | Eric Campion |
Q: Can I use a speed control switch on an exhaust fan to regulate the cfm? The fan I have didn't come ... A: I am not sure.....It depends on the type of motor you have now. Is it a two speed? If so, it has 2 ...
|
| Air Conditioning | 10/10/2008 | Howard Livingston |
Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ... A: You do it with a garden hose & an oil can using about 5 drops of oil at the start of every Summer. ...
|
| Changing an a/c transformer | 10/10/2008 | Bill Brainard |
Q: Our dog chewed thru the a/c wires. We have re-attached the wires, checked the fuses and think it ... A: Don't jump to that conclusion. Does the unit (furnace) work at all? How did you check the fuses? ...
|
| Evaporator freezes over blocking airflow | 10/10/2008 | Eric Campion |
Q: We have a Frigidaire side-by-side (Model #FRS26ZRF) that is probably about 11-12 years old ... A: That could be a problem. The defrost timer has a little cog that can be turned with a flat bladed ...
|
| Tempstar DC90 - Thermal Limits switch trips | 10/10/2008 | Howard Livingston |
Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ... A: If dirt or soot has accumulated to plug up the heat exchanger or the flue pipe, the flame, or too ...
|
| installing a low voltage programmable thermostat | 10/9/2008 | Craig HVAC Expert |
Q: I'm looking at installing a programmable thermostat to replace a "builders" manial model. There are ... A: You need to do two things...get a thermostat that works with batteries, because you do not have a ...
|
| Blower Control | 10/9/2008 | Craig HVAC Expert |
Q: I have an older GE Weathertron air pump with an ICG electric auxillary heat source/air handler with ... A: As long as the board will handle the amps, and you can connect the wiring to it to make it work...go ...
|
| Central Air units | 10/9/2008 | Jim Barnhart |
Q: Can you tell me anything about the Intertherm brand and how it compares in quality to other brands. A: Robin, INTERTHERM Became Nordyne company in 1987. Brand-mate Miller. In 1998, Nordyne started ...
|
| horizontal FAU in attic | 10/9/2008 | Jim Barnhart |
Q: The heat exchanger is cracked (small hair line crack about 3 inches long at the base of the return ... A: Olins, What's an FAU? How high efficiency, dose it freeze in your attic? I like Goodman furnaces, I ...
|
| fridge leaking | 10/9/2008 | Eric Campion |
Q: my 5 year old fridge from sears canada is leaking water INSIDE the fridge and leaving puddles on the ... A: The problem you are experiencing is normally a blocked evaporator drain line. Whether you have a ...
|
| Punctured evaportor coil | 10/9/2008 | Jim Barnhart |
Q: Jim, while defrosting the freezer of my refrigerator I accidentally functured the coil. The ref is ... A: Donde, I don't do kitchen appliances but if you "punctured the coil you lost all the refringent, the ...
|
| Decode Help | 10/9/2008 | Eric Campion |
Q: I need to break-down the model number of a Tempstar gas furnace to identify the blower tonnage. ... A: Unfortunately our expertise is with Major Home Appliances only. This would include washers, dryers, ...
|
| Tempstar DC90 - Thermal Limits switch trips | 10/9/2008 | Howard Livingston |
Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ... A: Is there any flames rolling from the burners ?? Is this switch one of those little red manual reset ...
|
| HVAC / Evap Cooler Lockout Circuit | 10/9/2008 | Howard Livingston |
Q: Does anyone make a "lock-out" circuit for an HVAC unit, such that it will not come on if an evap ... A: Boy, Don, that's a good one ! Swamp cooler & a/c going at the same time !! Don't know of anything on ...
|
| Floating Neutral Power Surge v. HVAC | 10/9/2008 | Jim Barnhart |
Q: I have a 2 year old Central Heat and A/C Unit all Electric. The power company did a big No-NO and ... A: Tricia, When something is working as it should work I think it's all but impossible to find any ...
|
| electric start tappan furnce | 10/9/2008 | Craig HVAC Expert |
Q: I have had my furnace running for about 2 weeks now to take the chill off some. Last night i noticed ... A: The problem can be any number of elect. problems in the unit. You need to have a meter and ...
|
| Furnace | 10/8/2008 | Howard Livingston |
Q: I currently have a Thermopride 1995 oil furnace and am thinking of switching to natural gas. I have ... A: Variable speed motors are quiet, but blow the same amount of air as a common motor. They do ramp up ...
|
| 2 HVAC units home humidification | 10/8/2008 | Craig HVAC Expert |
Q: Craig We have a 3 story home with 2 heating/cooling units (one upstairs, one downstairs). The one ... A: A whole house humidifier does not mean much unfortantly. You really need to know the capacity of ...
|
| Armstrong Ultra 80 won't ignite | 10/8/2008 | Joe |
Q: I’ve got an Armstrong furnace that won’t go past the pilot ignition stage. What it does when I call ... A: Joe, Look at wiring diagram on unit possible a roll out switch is open (if equipt.),would be a ...
|
| Armstrong Ultra 80 won't ignite | 10/8/2008 | J Cook |
Q: I’ve got an Armstrong furnace that won’t go past the pilot ignition stage. What it does when I call ... A: I would try jumping the pressure switch, but on most units, if the pressure switch does not make, ...
|
| DUAL ZONE | 10/8/2008 | Craig HVAC Expert |
Q: We have a 5 yr old custom built house. Our HVAC is dual zone so that we would be guaranteed warmth ... A: I need to add a bit to my answer...Air source heatpumps may not work well in PA during the extreme ...
|
| Cracked Heat Exchanger | 10/8/2008 | Jim Barnhart |
Q: We have a Bryant Deluxe furnace (split system w/ac thing outside). The furnace is on the ground ... A: Susan: Contract, What kind of a contract? what's it for? I know you said you seen a "hairline crack ...
|
| Air Conditioning | 10/8/2008 | Howard Livingston |
Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ... A: Not yet. R22 is phasing out in 2010, R410 replacing it. BUT, recycled R22 will be around awhile yet ...
|
| Tempstar 9000 furnace | 10/8/2008 | Bill Brainard |
Q: I have about a ten year old Tempstar 9000 furnace in my home in Milwaukee WI. I recently had to move ... A: Take some steel wool & wipe the sensor rod clean. Do not scrub. Check ground connections at the ...
|
| Charging a refrigerator | 10/8/2008 | Eric Campion |
Q: I am a maintenance man at a large apartment comunity.We,of course, take care of all the appliances.I ... A: Good Morning Gregg....trying not to open a can of worms..but most time when refrigerant needs ...
|
| leaking ice maker | 10/8/2008 | Eric Campion |
Q: ice maker is leaking water inside the freezer and out the ice dispenser. it leaks a steady stream of ... A: Go to the rear of the refrigerator and unplug the wiring harness going to the water inlet valve. ...
|
| Humidifier Connection | 10/7/2008 | Jim Barnhart |
Q: Greetings, I have a Trane XV 95 two stage furnace and a Aprilaire 500 series humidifier. I have ... A: Darrell, I don't have the literature on your "Trane XV 95" or your "Aprilaire 500 series ...
|
| DUAL ZONE | 10/7/2008 | Craig HVAC Expert |
Q: We have a 5 yr old custom built house. Our HVAC is dual zone so that we would be guaranteed warmth ... A: You did not tell me where you live, so the heatpump may not work very well. Most air source ...
|