What size chimney liner is required in a masonry chimney to vent a125,000 gas btu fan induced furnace and a 40 gallon gas hot water heater

Hi Rick, The liner size should match the exhaust pipe on your furnace. Most hi- efficiency furnaces are 3". You will have to find your local code about connecting the hot water heater into the same liner. I would vent the hot water heater separately. If the cap or liner would become blocked the furnace would vent out at the hot water tank.

Hope this helps.