Water in A/C Ducts2/8/2012
  Q: I have a central A/C system with a York Air Handler Model F2RP042(it is about 6 years old) with ...
  A: Jeff, OK, Then what happened is that your indoor A/C coil froze up and when it thawed it thawed on ...
HVAC Choice2/4/2012
  Q: I am looking at replacing of furnace and air conditioner. I am looking at Goodwin vs, Lennox. Any ...
  A: Bob, The most important factor with any equipment that heats or cools is the installation. From ...
Water in A/C Ducts2/2/2012
  Q: I have a central A/C system with a York Air Handler Model F2RP042(it is about 6 years old) with ...
  A: Jeff, So, the (supply) ducts in the attic are the ones with the water in them? Where is the Air ...
RUDD AC-HEAT PUMP CONTACTOR2/1/2012
  Q: JOHN, New part (honeywell Contactor) installed and works great..the other was pitted and totally ...
  A: Gail, Thank you. Yes when I joined this site I had no idea I would be helping almost a thousand ...
rudd ac-HEAT PUMP contactor install1/31/2012
  Q: WE HAVE AN OLDER rudd A/C HEAT PUMP COMBO. wE WANT TO CHANGE THE OLD CONTACTOR BECAUSE ITS PITTED ...
  A: Gail, Have the thermostat off and then turn on all breakers in any order. Then turn on the ...
rudd ac-HEAT PUMP contactor install1/31/2012
  Q: WE HAVE AN OLDER rudd A/C HEAT PUMP COMBO. wE WANT TO CHANGE THE OLD CONTACTOR BECAUSE ITS PITTED ...
  A: Gail, You will need to use the wire connectors that are on the inlet side of the contactor as they ...
rudd ac-HEAT PUMP contactor install1/31/2012
  Q: WE HAVE AN OLDER rudd A/C HEAT PUMP COMBO. wE WANT TO CHANGE THE OLD CONTACTOR BECAUSE ITS PITTED ...
  A: Gail, I want to caution you on doing this job as there is 240 volts at the outdoor unit and yes ...
CAC1/30/2012
  Q: I have a odd but simple question for you. What is the lowest outside temp you can or should run a ...
  A: John, It does only move the air inside the home. But if the furnace is in a cold garage or ...
CAC1/30/2012
  Q: I have a odd but simple question for you. What is the lowest outside temp you can or should run a ...
  A: John, Actually a very good question that most want to know, but, no one asks. If it is a newer ...
Ruud 90 Plus Model# UGRA-09EZAJS1/28/2012
  Q: I have a Ruud Plus 90 Furnace Model# UGRA-09EZAJS. I just noticed that it was not blowing warm air ...
  A: Nick, There is no pilot on that furnace, it has a Hot Surface Ignitor. The draft inducer motor ...
Lennox Dimension won't come on1/26/2012
  Q: I have a Lennox Innovation Series Dimension furnace, model # G32Q3-75-2. I have a problem with my ...
  A: Paul, Not knowing the age of it or what the ledger says for that flashing code I can only guess. ...
SANYO Concealed duct Heat pump1/20/2012
  Q: Is a Sanyo 36UHW72R suitable for mounting in an attic to heat and cool the upstairs level in a four ...
  A: Aidan, I am not sure what you mean by 4 square? I live in Portland Oregon and work for Colunbia ...
Synder General Comfortmaker1/19/2012
  Q: I have a Synder General Comfortmaker furnace in my home. The ignitor is not working and I was quoted ...
  A: Allison, It is something you can do yourself. Breaker should be off and DO NOT TOUCH the carbide ...
Heat pump keeps cycling on and off1/19/2012
  Q: I have a new R-410A split system heat pump (a few months old). It seemed fine during the summer ...
  A: Mike, At 53 degrees outside and 73 inside with R410a refrigerant (which is what you have) and the ...
Intertherm Combined Unit- Little Heat- Won't Turn off1/18/2012
  Q: I have an intertherm combined unit heatpump and I have been out of town for a few months. When I ...
  A: AC, You should try the same thing with the filter removed (just for testing) and see what it does. ...
Intertherm Combined Unit- Little Heat- Won't Turn off1/18/2012
  Q: I have an intertherm combined unit heatpump and I have been out of town for a few months. When I ...
  A: AC, Not knowing the type of t-stat, I would say if it did not come on switched to emergency heat ...
Intertherm Combined Unit- Little Heat- Won't Turn off1/17/2012
  Q: I have an intertherm combined unit heatpump and I have been out of town for a few months. When I ...
  A: AC, It sounds to me like the outdoor unit is not coming on. If so, the thermostat does not know ...
electric heater1/15/2012
  Q: When the blower motor goes off there is still heat coming from the vent. I have turned the heater ...
  A: Rich, It sounds like a sequencer is stuck in the closed position. That is the timed relay that ...
Problem with my Weatherking/Ruud/Rheem1/14/2012
  Q: I am having a recurring problem with my furnace.I have (at least have in the past) had good results ...
  A: Joanne, The first thing you need to do is call the owner of that company and tell him what you ...
PTC heater assembly1/11/2012
  Q: John, As we can see that many air conditioners are using PTC heater for auxilary heating.Why it is ...
  A: Daniel, The refrigerant in a heat pump actually boils at 20 plus degrees below zero, so there is ...
Heat pump keeps cycling on and off1/9/2012
  Q: I have a new R-410A split system heat pump (a few months old). It seemed fine during the summer ...
  A: Mike, Those are much better numbers than what you had, but still not correct. Did you actually ...
bryant furnace plus 80 / 11yrs old1/5/2012
  Q: my furnace starts up and shuts off within seconds, I have replaced the heat sensor and placed a new ...
  A: Geno, Your "Carrier" furnace has two compartments. The lower one (usually) has the gas valve and ...
Lennox furnace sequencer1/3/2012
  Q: My all-electric Lennox furnace is less than 10 years old, and has 3 heating elements, with ...
  A: Dan, The "stack" sequencers you have in your furnace are the same as every other Electric furnace ...
Humidifier Installation1/2/2012
  Q: I have a Lennox G51 MP gas furnace and an Aprilaire 600 humidifier. I am getting no humidity in to ...
  A: Peter, Only seeing the picture you sent I cannot address everything. What I can say is that the ...
Furnace Trouble1/1/2012
  Q: I have an Armstrong furnace (not sure of the model, I can probably get it later though) with a ...
  A: Kenneth, You can also pull the flame sensor and polish it with a green scratch pad or emery paper ...
Furnace Trouble12/30/2011
  Q: I have an Armstrong furnace (not sure of the model, I can probably get it later though) with a ...
  A: Kenneth, It really depends on the age of the furnace as to what I could help you with.Model age, ...
Heat pump keeps cycling on and off12/30/2011
  Q: I have a new R-410A split system heat pump (a few months old). It seemed fine during the summer ...
  A: Mike, You need to get the install company back out ASAP!!! That unit is either way overcharged or ...
KEEP-RITE DC 90 ULTRA HIGH EFFICIENCY FURNACE12/14/2011
  Q: FAN SOME TIMES CONTINUOUSLY RUNS WITHOUTH PILOT LIGHTING, FAN RUNS SOMETIMES AND PILOT WILL LIGHT ...
  A: Roddy, Sorry I have been swamped with work. It is sounding like the control board or module which ...
Air return in an OK place?12/13/2011
  Q: Although I am in Perth, Western Australia you obviously know your stuff and I’m sure airconditioning ...
  A: Melissa, I find it odd that even the manufacturer of the product would use the terminology that ...
KEEP-RITE DC 90 ULTRA HIGH EFFICIENCY FURNACE12/12/2011
  Q: FAN SOME TIMES CONTINUOUSLY RUNS WITHOUTH PILOT LIGHTING, FAN RUNS SOMETIMES AND PILOT WILL LIGHT ...
  A: Roddy, I need to know if you are describing the inducer motor or the "blower" motor that moves the ...
Heating12/9/2011
  Q: I want to replace my old line thermostat with a new honeywell RTH221B. Last year I had my boiler ...
  A: Larry, First of all a LINE thermostat is for high voltage, ie, 110 or 220 volts. If you have a ...
High electric bills are killing us12/8/2011
  Q: My home is 800 square feet. Hubby and I work at home. Last year got $360 electric bill per month ...
  A: Adry, First, I assume you also have an electric ? Is this a manufacture home? If what you say is ...
janitrol gas furnace pilot issue12/8/2011
  Q: at first, pilot would go out at some point after winter. then this season re-lit pilot and ran one ...
  A: William, When you cleaned the pilot assembly, did you pull the pilot tube off the flame hood ...
Lennox G4OUH-36A-070-11 - No Heat12/7/2011
  Q: I have 2 Lennox G4OUH-36A-070-11 units - the downstairs unit functions fine, the upstairs unit works ...
  A: Ken, It sounds like the furnace is not getting 24 volts to the "w" connection for heat. ...
where to put filter - old Custom Aire furnace11/12/2011
  Q: Such a basic question I'm embarrassed -- PG&E came out recently and turned off pilot light due to ...
  A: Susan, If your filter was that bad, just think what your duct system must look like. You might ...
where to put filter - old Custom Aire furnace11/12/2011
  Q: Such a basic question I'm embarrassed -- PG&E came out recently and turned off pilot light due to ...
  A: Susan, Call the company [ tech ] that you had out. That is the best answer. I believe custom air ...
HVAC American Standard Freedom 90 furnace11/8/2011
  Q: When I turn on the furnace at the power switch, the draft blower immediately kicks on and a few ...
  A: Bill, I honestly have never seen that on a ledger before. So, the first thing that needs to be ...
American Standard Freedom 8011/7/2011
  Q: On mu panel l get three flashes. It says pressure switch. Can you tell me how much a new one will ...
  A: Clyde, All that flashing code tells you is that 24 volts circuit is not being completed. It ...
Sanyo Ductless problem11/3/2011
  Q: Last year I bought the SANYO CMH 2472 Multi-System Heat Pump Ductless Split Outdoor Unit with DC ...
  A: Zel, OK. The service manual on the pdf file I sent you has a list of the error codes and they will ...
Register size needed10/30/2011
  Q: I have a 40 year old home that was originally installed with 48" baseboard registers under windows. ...
  A: Frank, I mean the equipment size and duct size as far as the cfm's needed and if the duct system ...
Bryant 383KAV upflow gas furnace – status code 31 - Part 210/29/2011
  Q: Sorry, but I meant to add a picture of my furnace to my follow-up question. Then I could not see an ...
  A: Walter, The pressure switch is the circle next to the electrical box that says installation. The ...
Dorve by Heatilator10/29/2011
  Q: I am looking to buy a used Freestanding Gas Fireplace. It is a Dovre by Heatilator model #GA259371. ...
  A: Kathy, I work on a lot of fireplace and stoves, but have not seen the model "dovre" I do, however ...
Bryant 383KAV upflow gas furnace – status code 3110/28/2011
  Q: I have a duel zone system. The unit for the upstairs zone is a Bryant 383KAV036070 upflow gas ...
  A: Walter, You have an UPFLOW for the upstairs? That is kinda odd, must be in a closet or a long ...
HVAC American Standard Freedom 90 furnace10/27/2011
  Q: When I turn on the furnace at the power switch, the draft blower immediately kicks on and a few ...
  A: Bill, I do not remember those numbers. Are you sure they are not on either side of the door, or ...
Bryant plus 90 furnace10/27/2011
  Q: the inducer motor runs, the pilot ignites, but main burner will not come on. This happened the first ...
  A: Tony, Cool, except I believe there was no red but a white wire, lol. Keep your air filter clean. ...
Ruud Silhouette II Gas Furnace10/26/2011
  Q: John, I have a Ruud Silhouette II Gas Furnace and during the lighting cycle, only three of the six ...
  A: Al, You need to pull the burners themselves. Along the ends, there are "spreader" plates that the ...
Bryant plus 90 furnace10/21/2011
  Q: the inducer motor runs, the pilot ignites, but main burner will not come on. This happened the first ...
  A: Tony, That's a pretty old furnace, you should be thinking about replacement. Meantime, your issue ...
HVAC American Standard Freedom 90 furnace10/19/2011
  Q: When I turn on the furnace at the power switch, the draft blower immediately kicks on and a few ...
  A: Bill, It does not sound like the module is bad, rather the ignitor or the inducer is not making ...
Fan Operation9/17/2011
  Q: I just recently cleaned out my old furnace and can't get the fan to come on. It is a Lear Siegler ...
  A: Rory, All you can do is remove it and take a look. You either damaged the wires, they got pulled ...
Bryant furnace fault code9/13/2011
  Q: I have a Bryant model 320AAZ036060 the blower starts up but shuts off after about 20 or 30 seconds ...
  A: Wayne, Do you mean the "blower"? That is the motor that moves air through the duct system and ...
Trane XE 809/4/2011
  Q: I am trying to find out what the proper size filter is for the Trane XE 80 Upflow/Horizontal Gas ...
  A: Marcy, Every furnace is different, if it is the factory opening at least it should be a common ...
Coleman EB15B A/C9/1/2011
  Q: I have a coleman EB15B with a-coil and outside a/c unit. Unit operates and blows cold air, but it ...
  A: James, You have given me the Air Handler model number, which is a basic model that only has set of ...
AC use in bedroom8/31/2011
  Q: Just had a geeneral question that my wife and I have been talking about lately.....She says she ...
  A: Brent, The more air that is allowed to leave the room and return to the return air the more air is ...
concept 1000 central a/c problem8/25/2011
  Q: My a/c works, however even when the unit is not cooling the house the fan will not stop running. The ...
  A: Brandi, I assume you are talking about the FAN that blows the air through the duct system in your ...
a/c smell8/23/2011
  Q: My a/c unit suddenly smells like burnt rubber. It has been running constantly since the 100C days ...
  A: Debbie, Usually a burning smell is first the blower motor going out and next a board or switching ...
AC Motor wiring8/20/2011
  Q: I've installed a new AC motor in my Rheem Home AC system but dont know how to wire it. The motor is ...
  A: John, I assume you are talking about the condenser fan motor. ( the one at the outdoor unit that ...
2-8 degree indoor temp. split8/19/2011
  Q: Intermittent cooling, high suction pressure on 5 ton Carrier split AC with Millennium Scroll, ...
  A: Darren, Am a little confused on a few things you wrote, please clarify. I get Ra return temp and ...
HVAC 2-stage Control Wiring7/22/2011
  Q: Is it possible to temporarily wire up a furnace such that the furnace blower will run on low while ...
  A: Steve, Sorry to hear about your issues. You have a blower motor that is variable speed, not just ...
how to know if unit struck by lightning7/21/2011
  Q: I recently had a 12 year old compressor replaced. The company installed a 4 year old unit 3 weeks ...
  A: Chuck, "The company installed a 4 year old unit" is that a correct statement? I do not think ...
hi pressure switch7/20/2011
  Q: My unit is a 2002 Amana (bought out by???). The pressure switch was changed recently but it took the ...
  A: Joe, If that amount also covered the call diagnostic AND it is on a roof top you got a deal. You ...
Compressor vs. New unit7/20/2011
  Q: We have a 9 year old goodman heat pump in which the compressor has bellied up. We got our first ...
  A: Lynn, I am not familiar with the technical term "bellied up". LOL I think you either need to ...
Moisture from Evaporator7/19/2011
  Q: We are designing a air cooled downflow Air Conditioner of 7.5 Tons for computer room application ...
  A: Shrikant, Why are you using so much air? Is that the requirement for the computer room? Water is ...
Goodman Model CLJ36-1C7/17/2011
  Q: I have Goodman Model: CLJ36-1C, it is not working, i.e. no cooling. The Service Tech said - the ...
  A: Tom, First of all you are covered as far as warranty, they can go by the serial number, it has the ...
Trane XE800 Weathertron and exorbitant electricity bill7/15/2011
  Q: We are renting an 800 sq ft duplex and we have an old 80s model Trane Weathertron XE800 in the home. ...
  A: Brian, Does the unit still cool your home? The property company should be told and the company ...
hi pressure switch7/14/2011
  Q: My unit is a 2002 Amana (bought out by???). The pressure switch was changed recently but it took the ...
  A: Joe, Are you talking about the high or low pressure switch for the refrigerant? In the outdoor ...
pancake air handler7/13/2011
  Q: what is the easiest way to change the blower motor, double shaft, with blower cages still on.
  A: Tommy, I have never heard of a "pancake air handler"??? As far as a double shaft blower, the ...
Pro-Stat thermostat7/12/2011
  Q: I am looking for a Harper-Wyman thermostat Pro-Stat T5000 or T5020. Do you know where I could get ...
  A: Rick, I was on call this weekend and worked about 20 hours. Did not get a chance to go to storage, ...
Pro-Stat thermostat7/11/2011
  Q: I am looking for a Harper-Wyman thermostat Pro-Stat T5000 or T5020. Do you know where I could get ...
  A: Rick, So, what is it that makes you want one of these? If it is for what it does or how it works ...
Trane XE 900 Weatertron Heatpump7/10/2011
  Q: The unit seems to come on more often than in the past. I think the unit may need a little freon and ...
  A: Keith, If it was low it would stay on longer on each cycle, not shorter cycles more often usually, ...
capacitor part number for my bryant 693dnd42c unit7/10/2011
  Q: I just had the capacitor replaced on my unit in Dec, and it has already quit. I took out the ...
  A: Debbie, If a new cap is no good within 6 months, there is something else wrong with the system and ...
tempstar air handler coil7/8/2011
  Q: i have a 3 year old tempstar 2.5 ton HP. noticed for the first time yesterday that when i changed my ...
  A: Scott, What temperature was it outdoors when those where taken? And what was the sub-cooling? I ...
tempstar air handler coil7/7/2011
  Q: i have a 3 year old tempstar 2.5 ton HP. noticed for the first time yesterday that when i changed my ...
  A: Scott, You need to get the service company back out while it is still close enough to the service ...
VFD module on 1999 vintage Carrier System7/7/2011
  Q: John, First thank you for the service you provide. I am on the road and don't have the exact ...
  A: Jeff, I didn't think where you are that you would even have back up strips. So, it would be more ...
air conditioning7/7/2011
  Q: I have a Goodman GPH1348H21AB 4 ton 13 seer unit has only 2 seasons on it, it is not kicking on the ...
  A: Will, First check your air filter, if it is clogged your unit will freeze the coil inside and no ...
VFD module on 1999 vintage Carrier System7/6/2011
  Q: John, First thank you for the service you provide. I am on the road and don't have the exact ...
  A: Jeff, I am a Carrier dealer and have never heard of a VFD? Are you talking about the ECM? That ...
Coleman furnace question.7/4/2011
  Q: I am working on a coleman evcon furnace what the problem is that it the Fan turns on by its self and ...
  A: Troy, I give priority to those who want to learn and a desire to do things the right way, so feel ...
ac7/4/2011
  Q: I was wondering how often a central a.c. unit should be cleaned? Thanks!
  A: Lauren, It depends on what you are actually asking. The outdoor unit should have a clean, ...
dead air conditioner7/3/2011
  Q: My air conditioner just stopped working, no movement or sound. I replaced the fuses but it still no ...
  A: Kerri, You are past warranty by one year. It could be a few things. One it could be is if you ...
Outdoor AC air intake7/2/2011
  Q: I recently noticed a buildup of fibers on the mesh intake grills on all sides of my Goodman AC. This ...
  A: Fran, That is a common problem. Most of the time it IS lint as the outdoor units are sometimes ...
Coleman furnace question.7/1/2011
  Q: I am working on a coleman evcon furnace what the problem is that it the Fan turns on by its self and ...
  A: Troy, It has to be in the furnace. I believe the newer colemans have a board that controls the ...
Low Voltage wiring diagram for Rheem RPLA-036JAZ6/27/2011
  Q: Do you have or know where I can find the low voltage wiring diagram for a Rheem A/C unit model #: ...
  A: Espy, I don't understand? Your first question you said "If I manually push on the contactor ...
Unico/Bryant system & odor6/26/2011
  Q: I have 3 Unico 2 year old HVAC systems w/ exterior Bryant AC units that use Puron 410A. I have a ...
  A: Dan, First if you have a leak the A/C would stop cooling as R410a is very charge critical. The ...
Low Voltage wiring diagram for Rheem RPLA-036JAZ6/26/2011
  Q: Do you have or know where I can find the low voltage wiring diagram for a Rheem A/C unit model #: ...
  A: Espy, Are you sure it is not RPKA instead of RPLA? I think it is and if so it is heat pump. And ...
Blower turns itself on and off & thermostat is off6/24/2011
  Q: Coleman DGATO56BDE - furnace blower motor comes on and runs for several minutes and then turns ...
  A: Try this for the manual ...
Trouble restarting without flipping breaker6/24/2011
  Q: This started when the unit would go off and trip the breaker, technician came out said it was ...
  A: Tracey, Call the owner of the company and tell him your story and insist on your money back for ...
1985 ArcoAire condenser6/23/2011
  Q: I have a 1750 sq ft home that was built in 1985. I believe that the A/C system is the original one. ...
  A: Roy, A Month??? Call a local HVAC company. The tech will have it fixed by the following day at ...
Ac problem6/22/2011
  Q: I have a carrier puron ac/ heat unit. Called tech and he cant find the problem. Ac is always set on ...
  A: Tiffany, You need to get a tech out that understands the Carrier Infinity system. It will tell ...
Blower turns itself on and off & thermostat is off6/19/2011
  Q: Coleman DGATO56BDE - furnace blower motor comes on and runs for several minutes and then turns ...
  A: Larry, The blower on that furnace is energized through a small single pole single throw relay and ...
Current and Potential Relays6/18/2011
  Q: Last night I googled potential and current relays. What I remember today is: They both connect ...
  A: John, I can tell you that 25 years ago I still stocked my service van with a full range of start ...
an expansion valve problem?6/17/2011
  Q: Borgman, I live in southern Texas and have a 20 year old Lennox split A/C furnace. Recently, the ...
  A: Mike, If the suction line ( that is the big one with black rubber insulation) at the outdoor unit, ...
Your recommendation in Answer to Chris: If bad capacitor, change "current relay"6/16/2011
  Q: On the Recent Questions and Answers page (yours), reagarding a 6-year old Carrier system, part of ...
  A: John, In days past almost all compressors had a starting circuit, now days only a few do. It ...
Is my A/C system overcharged?6/16/2011
  Q: I'm no A/C tech, just a DIYer with Fieldpiece diagnostic tools and a desire to learn. I have an ...
  A: Jim, You are correct that your superheat is 17, 17.5 actually and yes it is too high. You didn't ...
Home AC question6/14/2011
  Q: I have an old 2 ½ ton Payne unit model # 30PAC1S6A6 that is going out. This unit covers 686 square ...
  A: Mike, With the limited info all I could do is guess. Although it sounds like the current unit is ...
Proper Method For Setting Heat Anticipator6/14/2011
  Q: Please tell me the proper way to set a Heat Anticipator when installing a new mechanical thermostat, ...
  A: John, You put a mili-amp meter on the anticipator which is in series as you suspect and adjust it ...
Electrical Specs For Electric Furnace6/14/2011
  Q: My other question was about information contained in Nordyne's Technical Specs manual (Electric ...
  A: Yes the lower rated breaker will have the blower and usually the control voltage ( transformer, ect. ...
AC leak, replace or repare?/ & Start capacitor needed?6/9/2011
  Q: I have a six year old carrier unit that started blowing cold two weeks ago here in Houston after ...
  A: Chris, I was gone for the weekend. As far a the leak, yes oil is an indicator, but not a sure ...
Can I add a Fan-On (only) switch?6/9/2011
  Q: On a mobile home furnace (not split system, but single-packaged unit A/C (only) (if that's the ...
  A: First, unless his house was below 55 degrees inside it should not freeze up unless something is ...
Capacitors6/9/2011
  Q: In some of the self-contained, outdoor air-conditioning units I see, there are often two capacitors ...
  A: No, just for a compressor and only if the original cap is weak, not shorted . Hard start caps have ...
Capacitors6/9/2011
  Q: In some of the self-contained, outdoor air-conditioning units I see, there are often two capacitors ...
  A: Correct, Although they are classed RUN caps, they also add energy during the start period and have ...
New A/C needs circuit breaker reset to function6/9/2011
  Q: A brand new Comfortmaker SX2300 connect to a brand new Comfortmaker 2-stage furnace. Had a white ...
  A: Howard, My bad, I thought that was a heat pump, we have very few of that companies equipment here. ...
Capacitors6/8/2011
  Q: In some of the self-contained, outdoor air-conditioning units I see, there are often two capacitors ...
  A: Your not going to get hurt in any way from the caps that you will come across and since they are ...
A/C Freezing Up6/7/2011
  Q: We have a new (less than a year old) Goodman central unit at our new house (2200 sq ft LA). Our ...
  A: Jeff, Although I do not understand trying to use the A/C when it is the 60's outside, it is your ...
New A/C needs circuit breaker reset to function6/7/2011
  Q: A brand new Comfortmaker SX2300 connect to a brand new Comfortmaker 2-stage furnace. Had a white ...
  A: Howard, You need to call the owner and get a senior tech out there. That one does not know what ...
too much humidity in my house6/6/2011
  Q: Two years ago I had a new heating and air conditioning system installed in my house. The old air ...
  A: Glen, The A/C is not oversized for that size home, so short cycling is not the problem. I assume ...
tempstar heat pump problem6/5/2011
  Q: I have a 5 ton slant top tempstar heat pump 13 seer unit that was installed in July of 2006. It has ...
  A: Tommy, I will assume that all air vents are open and clean filter?? After the unit runs for 10 to ...
Appropriate A/C Guages for my work.6/4/2011
  Q: I do part-time AC repair in a mobile home park. I'm not HVAC certified, but most of the problems I ...
  A: The amp draw of the compressors and the fans are all listed on the equipment as either RLA or FLA. ...
Appropriate A/C Guages for my work.6/4/2011
  Q: I do part-time AC repair in a mobile home park. I'm not HVAC certified, but most of the problems I ...
  A: A cheap set is all you need. But, just putting on gauges and looking at a chart will only get you ...
A/C control6/3/2011
  Q: John, I live in Houston, TX so my air conditioners have been running for several months already this ...
  A: Kenny, It depends where you are loosing the 24 volts. There is a transformer in the furnace that ...
A/C stopped running5/30/2011
  Q: I have a Nordyne js5bd 024kb compressor outside and a Rheem RCBA 3765GG17 air handler in the house ...
  A: Bill, There are breakers in the Air Handler on that furnace, check them. If they are not tripped ...
wrong size air handler5/30/2011
  Q: i had a 2/12 ton compressor installed by one company,then a year later a 3 ton air handler installed ...
  A: Len, All you could have lost is humidity control. That is assuming that the condo is matched for a ...
Home ac unit5/29/2011
  Q: I guess I should give a little background first. Last summer I had my a/c unit disconnected and ...
  A: Rich, The "wet" line means the refrigerant charge is at least close. So, if it worked well before ...
Home ac unit5/29/2011
  Q: I guess I should give a little background first. Last summer I had my a/c unit disconnected and ...
  A: Rich, I can tell you that the re-install was not done right. It sounds like your indoor coil is ...
Wires not marked5/24/2011
  Q: I am installing a honeywell rth221b and my wires are not marked by corresponding letters. I have two ...
  A: Kendall, There is no way I can know where the wires are coming from. Obviously they are not ...
A continious leak5/23/2011
  Q: I bought a foreclosed home May of 2010. I had a brand new A/C unit installed (and coil inside) as ...
  A: Winona, It is out of freon AGAIN. You need to call and talk to the owner of the company ( he may ...
condensate5/22/2011
  Q: I will keep short what I could make a very long story. About 12 years ago, my wife and I had a ...
  A: Patrick, That is not a condensing gas furnace! It does not make water, so if it is causing water ...
Clare Natural Gas Furnace5/21/2011
  Q: 12 years ago when gas became available in our area, we had a Clare Natural Gas Furnace installed: ...
  A: Laurie, In short the answer to your question is yes. I am not familiar with that make of furnace ...
5 ton Goodman HVAC split unit5/17/2011
  Q: I have a goodman 5 ton split unit heat pump 16 seer rating. It's a two stage compressor and blower. ...
  A: Tom, Correct about running a separate R/A from the R/A plenum. A plenum is the name of the sheet ...
wiring a/c to thermostat5/17/2011
  Q: i just added a/c to my furnace, my furnace is a goodman that was one of the first 80% furnaces. but, ...
  A: Zeke, First off if you have wires hanging from a limit and it is not in the system, you could ...
Propane Trane Unit Heater5/15/2011
  Q: The model number is MGPND020ADF10000. It was set up for natural gas, I bought the kit to switch it ...
  A: Summer, Tell me about the kit you used. What all did you change? You should have had a new ...
5 ton Goodman HVAC split unit5/12/2011
  Q: I have a goodman 5 ton split unit heat pump 16 seer rating. It's a two stage compressor and blower. ...
  A: Tom, Your floor plan didn't come through good enough to help. But, it would help, for sure, to ...
HVAC question5/7/2011
  Q: I have a 9 year old system that I am being told has a "restriction inside the coil, need to clear ...
  A: Mike, That helped a little. I assume you ment 61 degree's outdoor ambient? I really need the ...
HVAC question5/7/2011
  Q: I have a 9 year old system that I am being told has a "restriction inside the coil, need to clear ...
  A: Mike, I would need more tech info to give you a proper answer. Generally a restriction is in the ...
Request help for gas usage calculation5/6/2011
  Q: I have 3 bedrooms/2.5 baths house in IL. Above Ground Living Area (Square Feet): 2048 Basement ...
  A: Amy, Google clock a gas meter. You turn off every other appliance and pilot light. Then run the ...
flexible ductless a/c lines5/4/2011
  Q: Where can I get flexible hose refrigerant lines that are R-22 compatable that are or can be made for ...
  A: Michael, That is because they do not exist. It is all soft drawn copper that is work hardening. ...
A/C stops working & temp increases5/3/2011
  Q: I live in a condo & usually keep my a/c on 72 to 74, depending on outside temp (I live in ...
  A: Ashley, I will have to guess you have a heat pump, but I don't know what kind, ie, split system, ...
A/C Outside Unit5/1/2011
  Q: My outside A/C unit has quit working. I think the motor is no good. It's a bit old, so I'm ...
  A: John, If you are talking about replacing the entire outdoor unit, then you have to replace the ...
Heat Pump - Ice in inside unit4/28/2011
  Q: I am a residential homeowner who knows very little about heatpumps. I recently used the cooling ...
  A: Ken, I am happy to help someone who wants to know about there HVAC equipment . Here is an over ...
Request help for gas usage calculation4/27/2011
  Q: I have 3 bedrooms/2.5 baths house in IL. Above Ground Living Area (Square Feet): 2048 Basement ...
  A: Amy, I think you need to get your utility involved if this is really bothering you. I really do ...
Request help for gas usage calculation4/26/2011
  Q: I have 3 bedrooms/2.5 baths house in IL. Above Ground Living Area (Square Feet): 2048 Basement ...
  A: Amy, I assume that you either have your meter read on a monthly basis or it is estimated and then ...
tempstar a/c unit4/26/2011
  Q: I have an older tempstar mobile home unit that is a all in one unit, it doesnt have a unit outsude ...
  A: Crystal, I assume you mean that you have no indoor unit? That is called a package unit. What I ...
Heat Pump fan stops4/24/2011
  Q: I just recently paid a service company 100 for house call 95 for him to replace a Capacitor. The ...
  A: James, I can only guess you are talking about a Rheem or Ruud unit and that you are talking about ...
Air Noise4/23/2011
  Q: 4 year old Bryant 340AAV 4 way condensing gas furnace - hot air system. Periodically when heat is ...
  A: Bruce, Just curious why if I helped you that good and promptly, you only gave me 9's? Just curious
HVAC 4 ton train unit4/22/2011
  Q: I replaced my condensing unit 2 yr's ago. Have no problems until now. I turned on the unit set temp ...
  A: Ron, It sounds like your "freon level" is not full. If it has worked the way you described in the ...
Air Noise4/21/2011
  Q: 4 year old Bryant 340AAV 4 way condensing gas furnace - hot air system. Periodically when heat is ...
  A: Bruce, That is a pretty tough one to do over the internet. One thing I have seen that fits that ...
bad coils in rheem ac4/21/2011
  Q: I live in a mobile home park with about 40 new units installed in the last 4 years.1400 sqare feet ...
  A: Andy, As I said, yes Rheem had some issues with a more than normal failure rate or metering ...
bad coils in rheem ac4/15/2011
  Q: I live in a mobile home park with about 40 new units installed in the last 4 years.1400 sqare feet ...
  A: Andy, Got this question from the question pool. The coils themselves have not gone bad, only the ...
A/C UNIT4/10/2011
  Q: I have a Tempstar high efficiency 5000 slit system outside unit. It stopped cooling and froze up and ...
  A: A.T. I am answering this question from our question pool. It does sound odd that it would stop ...
air-heater coil4/9/2011
  Q: I had my AC serviced last week and the technician reported that the 'unit is low on R-410A ...
  A: Robert, Because it is warranty it SHOULD be replaced. But, the labor is way high. The refrigerant ...
furnance3/30/2011
  Q: I just purchased a xv95 trane furnace. I know this is a 2 stage furnace. Do I need to have a 2 ...
  A: Diane, A 2 stage thermostat is what you want. If you let the board on the furnace run both stages ...
heat pump3/29/2011
  Q: I have a 1000 series armstrong heat and air unit. My problem, the air conditioner works but the heat ...
  A: You said the tech put it in a new board....in the outdoor unit? What you describe makes no sense ...
gas burner not igniting American Standard 903/29/2011
  Q: I have an American standard Freedom 90 unit that will not ignite the gas burner. I’ve tested all the ...
  A: ooops missed that.Is one of 2 things. The ignitor or the board. The ignitor does not spark it ...
gas burner not igniting American Standard 903/29/2011
  Q: I have an American standard Freedom 90 unit that will not ignite the gas burner. I’ve tested all the ...
  A: What error is flashing? How many flashes and what does the ledger say for that number of flashes.? ...
gas burner not igniting American Standard 903/28/2011
  Q: I have an American standard Freedom 90 unit that will not ignite the gas burner. I’ve tested all the ...
  A: David, I do not need a manual, what I need is more info from you. Where in the start up sequence ...
Heil Furnace3/26/2011
  Q: Good Afernoon : I have a LP Forced Hot Air Heil Furnace, Model H9MPD125L20A3. It is 8 years Old and ...
  A: That's why I hate the valve being called a "SMART" valve, because it is not. You need a tech to ...
Heil Furnace3/26/2011
  Q: Good Afernoon : I have a LP Forced Hot Air Heil Furnace, Model H9MPD125L20A3. It is 8 years Old and ...
  A: I think that unit has a honeywell Smart valve on it. If so the ignitor plugs right into the gas ...
heat pump3/22/2011
  Q: I have a 1000 series armstrong heat and air unit. My problem, the air conditioner works but the heat ...
  A: Danny, I hope this is new unit under warranty and if not, that you have not been charged for any ...
temperature at register3/19/2011
  Q: for a central air-conditioning system, what temperature should the air be at the point where it is ...
  A: Grace, The temperature coming out of the "supply" vents should be about 20 degrees colder than the ...
martin gas log stove thermocouple3/18/2011
  Q: I have a martin gas log stove that came with the house when we bought it 10 years ago. The pilot ...
  A: Cathy, We do not have that brand in this part of the country, but any local HVAC company can get ...
York furnace blower will not shut off3/7/2011
  Q: I have a York roof mount hvac M#D3GH036N06006A Sometimes after the house is warm the blower fan ...
  A: Paul, The proper way to find your problem is to jump R and W at the RU at the circuit board. If ...
Carrie HVAC Package Unit3/6/2011
  Q: The heat will not go off. The only way we can get it to turn off is if we turn it to AC and then ...
  A: Kelly Lee, Either the thermostat, thermostat wires shorted together or the control board would be ...
Air Filtration Options3/3/2011
  Q: My Trane 4 ton XL 19i air handler uses an electronic filter system with a 1" pre-filter (metal ...
  A: In that case you should purchase from Trane if they have one available. I have not bought one ...
Goodman heatpump3/3/2011
  Q: I have a Goodman 18 seer 4 ton heat pump. I noticed that the system is running on aux heat and not ...
  A: George, Need more info. How old, what setting is thermostat, is thermostat set to lock out heat ...
Air Filtration Options3/2/2011
  Q: My Trane 4 ton XL 19i air handler uses an electronic filter system with a 1" pre-filter (metal ...
  A: Steve, For allergies you can't beat the E.A.C cells, with the pre screens. But you can add what ...
Thermostat problems3/1/2011
  Q: I've been living in my house for about a year and a half. When I moved in, a carrier debonair 450 ...
  A: Katie, Usually when a thermostat is blank it means there is no 24 volts going to it. I don't know ...
Furnance stops intermitantly2/27/2011
  Q: I have a York Diamond series furnace (14 years old). My furance will start, ignite and as soon as ...
  A: Dan, I need more info than it" did not do anything." As far as the first things you stated, it ...
replacement of air conditioner2/25/2011
  Q: I have an 10yr old goodmand unit split system with gas furnace. My dog has urinated on the unit ...
  A: James, I think you mean 13 SEER...lol Anyway, No you do not have to replace the indoor coil. The ...
RUUD, Model# UAMB-030JAZ won't run2/22/2011
  Q: I have a RUUD, Model# UAMB-030JAZ. Stat has been on heat for about a month. Flipped back to AC, ...
  A: Glenn, The model number that you supplied appears to be an Air Conditioner. RUUD UAMB-030J* Air ...
HVAC2/20/2011
  Q: I live in a double trailer and when I went looking for a unit to put in my trailer I was told I ...
  A: John, The most common reason for lack of humidity control is either an over sized A/C unit or the ...
HVAC Cooling Problems2/16/2011
  Q: We have emerson PAC in our Data center with DX unit and it is operational. Recently, in an incident ...
  A: Manish, The first thing to check is the air filter at the indoor unit, if it is clogged, the coil ...
tempstar furnace2/11/2011
  Q: I noted a lack of warming in the house, although present. checked the duct work for warmth; found ...
  A: Bob, Look on the door to the furnace, front or inside, or somewhere including the control itself ...
luxair 95+2/9/2011
  Q: I have a 2005 luxair 95+ furnace. This unit operates fine when the temperature is set at a ...
  A: Vaughn' The water made by the furnace is backing up into the furnace and causing the pressure ...
outside electrical issue2/8/2011
  Q: ruud UPNE- 036JBZ 2 years old (outside unit) Ruud Acheiver air handler 1 year old inside unit... ...
  A: Mitch, First check your air filter(s), they might be clogged. If you let them get real dirty, the ...
central ac duct for new home2/6/2011
  Q: home will be approx 2340 living aera,would like to know what would be the best duct to use,flex with ...
  A: Galeon, You will best served to find a company that really knows what they are doing for this job. ...
Bryant Plus 90 code 312/5/2011
  Q: I recently replaced the pressure switch on my Bryant Plus 90. After this last week's huge midwest ...
  A: Tina, About the easiest way to keep that from happening again is once a year at the start of the ...
Bryant Plus 90 code 312/5/2011
  Q: I recently replaced the pressure switch on my Bryant Plus 90. After this last week's huge midwest ...
  A: Tina, The P-trap inside the furnace is probably clogged and water backs up into the collector box ...
Heat Pump--What's Happening?2/3/2011
  Q: My heat pump was running in the normal heat mode while I was standing next to the outside unit and ...
  A: Dan, Everything you describe sounds like the defrost cycle, except for the fan blade stopping like ...
DIY Humidifier Install2/2/2011
  Q: Afternoon John: I am trying to hook up an atomizing humidifier and have some questions. First, ...
  A: Paul, I recommend you have a tech out to wire that up. First most furnace transformers are not ...
Trane xl12002/2/2011
  Q: I have a 22 year old Trand XL1200 heat pump. It is beginning to give trouble, and my tech says it ...
  A: Sam, If the air handler is built in really good it would be cheaper to rebuild it if needed it ...
York Heat Pump2/1/2011
  Q: I have a heat pump that is blowing luke warm air. I checked the thermostat and it shows that ...
  A: Mark, Sounds like one of 2 problems. First check you air filter and make sure ALL the air vents ...
Hole in line to expansion valve bulb1/30/2011
  Q: While searching for a leak in my 2003 Trane heat pump (leaking schrader valve), the service tech ...
  A: Dee, Did he show you the hole? It should have looked like it happened from the very start of its ...
Furnace is cycle but no heat1/29/2011
  Q: I have a FG6RA 072C-12A - Nordyne. It is currently cycling like it wants to kick into heat, but ...
  A: Joanne, I need more info than cycles. The whole furnace, the start up, the burners, the hsi???? ...
hvac no electric1/27/2011
  Q: We just had power out for a day here after a snow storm (annapolis) and the power comes back on but ...
  A: Matt, That model number does not come up with anything when I try and look it up. But I assume it ...
Locating elusive electric heat relay1/25/2011
  Q: I have electric heat in my house, each room on it's own breaker in the garage. One room now bakes at ...
  A: Carol, Sorry I don't know what your electrician is thinking, unless you have the Cadet in the wall ...
changing swithover temperature on Honeywell thermostat1/25/2011
  Q: I have a Honeywell TH8000 thermostat which is great. It controls my heat pump and also my secondary ...
  A: Bradly, On the installation booklet, it shows which "tabs" to push on the bottom row to get into ...
Rheem RGPJ 05EAUER furnace will not stay lit longer than 5 sec1/24/2011
  Q: I changed out the filters (which I try to do on a regular basis) the other night. Didn't notice ...
  A: Joe, Not sure what wire you are describing, but any burn mark is not good. Generally what you ...
Residential gas furnace replaced parts1/23/2011
  Q: I live in Texas. Have a Goodman Model HCA100ND4R Serial 911108496 residential natural gas furnace ...
  A: Jim, As long as you did not alter the pipe size at the inlet, have the valve with the arrow going ...
universal remote for air conditioner1/22/2011
  Q: we have a chigo split air conditioner. the remote got stolen and friends bought us a chunghop ...
  A: Neil, We have nothing like that in America, but if you want to send me the full name, model and ...
York Gas Pack Unit1/21/2011
  Q: We have a 3ton York Unit electric air/propane heat. The problem is that; you can hear the fan come ...
  A: Linda, How old is that unit? If it has a flame sensor in it, it does not have a pilot that needs ...
AS Gas Furnace diagnosis1/20/2011
  Q: I have a 10 year old AS Freedom 80 two stage gas furnace installed in my attic, which has stopped ...
  A: Steve, Not knowing what model, I assume you are talking about a little green interface board? If ...
Central heating unit1/19/2011
  Q: I have owned my home for 12 years and it was new when I bought it. For the past five years we have ...
  A: Denise, I can help you, but I will need more info. First what model Carrier do you have. If the ...
York Stellar P3CUD furnace.1/18/2011
  Q: Customer complained about no heat. Arrived at residence and immediately found bad spiral type HSI ...
  A: Rich, One more thought. If you used a honeywell s86u series or ever do, you have to use all and ...
Air Flo central air (heating) making a whistling noise1/17/2011
  Q: I have a 5 yr old Air-Flo central air system installed by the builder. I'm not sure if it's ...
  A: Amie, What you describe could be a lot of things, but for sure, it should be looked at. An amp ...
2-stage furnace works in first stage only1/15/2011
  Q: My furnace runs fine in the first stage, but when it calls for the second stage, it gives an ...
  A: Kip, There is only one way to proceed to the next step. That is to put a manometer on the vacuum ...
Gas Furnace Malfunction1/15/2011
  Q: I have a unit that had normal blinking light until ther was a call for heat then it givave 3 flash ...
  A: Steve, It sounds like the drain for the water might be clogged and the water backs up into the ...
AS Gas Furnace diagnosis1/14/2011
  Q: I have a 10 year old AS Freedom 80 two stage gas furnace installed in my attic, which has stopped ...
  A: Steve, As far as swapping the board, you don't need to worry about dip switches as it is just a ...
AS Gas Furnace diagnosis1/13/2011
  Q: I have a 10 year old AS Freedom 80 two stage gas furnace installed in my attic, which has stopped ...
  A: Steve, All the blinks count for the error code, so 7 is the code. With what you describe, first ...
Emergency heat on heat pump1/13/2011
  Q: Re Simple Comfort thermostat Model 2200. Every once in a while I think the heat strip goes on, and ...
  A: Rich, Yes that will eliminate the thermostat from calling for the strips to come on. However they ...
Monitor Heater 2400 Kero (flashing E-14 in display)1/6/2011
  Q: We understand that your problem is: I have a MPI Monitor Heater - model 2400 Heater ( kerosene) and ...
  A: Peggy, I am not familiar with that make and model, but there should be a ledger on the door of ...
Air Conditioning Order1/5/2011
  Q: I had new duct work installed last summer. A/C ran fine all year long. In December, we needed to run ...
  A: Shawn, I would venture that something to do with the new duct work has caused water to invade the ...
Question1/5/2011
  Q: I was working in my yard - The out side unit suddenly got very loud . The fan stopped too . It is a ...
  A: Steven, I got this question from our Question pool. Yes, it sounds like it was just going through ...
Fan stopped and a burning smell1/3/2011
  Q: Coleman Evcon H&A.Was running only the fan for ventilation,no ac or heat.The fan stopped and a ...
  A: Eddie, The wires from that fan motor go into that box, mounted on the front of the blower ...
Older In-floor Single Grill Gas Furnace Stopped Working1/2/2011
  Q: John, 2011 greeted us by killing our heat which is perfect timing in Portland right now (it's ...
  A: Damian, Portland here also. The company I work for can fix that for you, but , the first opening ...
Carrier Control Panel12/30/2010
  Q: I have a gas furnace. I select "heat". The house is warm. The fan is "off." Do I need to turn ...
  A: Josh, You don't need the fan "on" for heating or cooling. That switch is just for if you want air ...
return for heat-hump12/29/2010
  Q: I currently have a heat pump on the lower floor in my home that have two cut-out for returns that ...
  A: Rob, Sorry, your description does not make sense to me. First if they are returns, they cannot ...
Heil furnace, Model NTGM100EHA312/28/2010
  Q: furnace would not heat yesterday. Fan blew constant(even though on 'auto'). Turned it off, then back ...
  A: Jerry, You stated " roll out " and " limit " which are 2 different things. But, either one is a ...
Gibson Heater/furnace - fan always ON12/28/2010
  Q: We have a Gibson heater/furnace. Used to work very well for the past 8 years without a problem. ...
  A: Ramu, The limit circuit is for when the indoor furnace has overheated. Generally limit switches ...
Gas Furnace12/27/2010
  Q: I am considering purchasing a Goodman GKS90904CX Gas Furnace 92,000 BTU Furnace, 92.1% Efficiency, ...
  A: Barelohim, Goodman is what is called a "contractors model". It is lower end equipment. I can see ...
defrost problem12/27/2010
  Q: I have an Intertherm T3BC/T3QC system. I live just outside Charlotte NC. I have noticed since it has ...
  A: Jack, I do not know what Board that outdoor unit has in it, but pretty much every board will ...
Central Heat12/26/2010
  Q: I have a Rheem Thermostat and when the heat is initially set to auto heat at 72 the unit works and ...
  A: Joseph, Your outdoor unit is shutting down and when the room temperature drops 3 or more degrees ...
humidifier in attic12/25/2010
  Q: I have 2 air handlers in the attic for the second floor and 1 in the basement for the first floor ...
  A: Jeff, Having the supply pipe heat tape wrapped will work fine. The only issue will be just how ...
hvac12/24/2010
  Q: I recently installed a Nat. gas self-contained air-quest unit it ran about 5 min and stopped the ...
  A: Dale, Not familiar with that name. Is this a regular duct system gas furnace or a stand alone ...
Rheem outside of split unit fan problem12/19/2010
  Q: The Rheem condenser unit outside had several inches of ice on it. After melting all the ice on this ...
  A: Drew, I need more info. Did you manually melt the ice or are you talking about the end of the ...
Rheem heat pump gone wacky12/18/2010
  Q: I had the same question as here --> ...
  A: Toney, Need a little more info. Model and serial number of the heat pump? What color led(s) ...
Heat Pump problems / Furnace Non Operational12/17/2010
  Q: Scott, Thanks for offering this service. I am having the following issues : Pepco had come down ...
  A: Jitesh, First things first. Lets address the "heat pump mode". When the thermostat calls for heat ...
Odd noise from furnace12/16/2010
  Q: I had a Bryant Evolution System Plus 95s gas furnace with Evolution Control installed over the ...
  A: Kirk, What you are describing is normal expect for the duration. If you watch, the ECM will ...
Coleman Presidential II pilot light problems12/12/2010
  Q: John: My son, Bob, wrote you the following letter: Expert: john t. borgman - 12/5/2010 Question I ...
  A: What you are saying is happening is totally different than what Bob said was happening. If you are ...
please help with my heater12/10/2010
  Q: I have electric heat and air in a mobile home, the heater is only blowing cold air,can you please ...
  A: Jim, The first thing to check is the breakers and make sure they are not off or in the tripped ...
Mini-Split Heat Pump Blower Cycling12/10/2010
  Q: I have a new mini split system installed early this summer. A one ton unit for a 200 sq ft room in a ...
  A: Casey, Like I said all those mini splits have configurations like that and each one , each company ...
Mini-Split Heat Pump Blower Cycling12/10/2010
  Q: I have a new mini split system installed early this summer. A one ton unit for a 200 sq ft room in a ...
  A: Casey, You should be OK then when you get the manual. Are you sure that installing it yourself ...
Mini-Split Heat Pump Blower Cycling12/9/2010
  Q: I have a new mini split system installed early this summer. A one ton unit for a 200 sq ft room in a ...
  A: Casey, I personally have never saw a Air-con mini split, but work on others. That unit is under ...
re: Circuit board replacement for Wesco12/9/2010
  Q: John, I currently have a HVAC repair service looking for the replacement or repair of a damaged ...
  A: Dave, I need to add to my answer to you. There is a possibility it is one of Jay Kays really ...
Central air and heater12/9/2010
  Q: I have a 30 year old rheem central air and heater(gas). the air works fine the heater does not come ...
  A: Alan, It depends on what you mean about what is not getting any electricity. If the furnace ...
furnace burners12/8/2010
  Q: i have a 22 year old tempstar 90% lp furnace i just had it cleaned and my gas pressure set. it ...
  A: Brian, Are you saying he cleaned the "inside" of the heat exchanger? If so and all he used was a ...
furnace burners12/8/2010
  Q: i have a 22 year old tempstar 90% lp furnace i just had it cleaned and my gas pressure set. it ...
  A: Brian, You have one of 2 things wrong. An obstruction or improper gas pressure. Since you just ...
central heat problem12/8/2010
  Q: I have a NG furnace that is giving this problem: The unit seems to work just fine except for one ...
  A: Landon, An HH board, huh? Must be about 20 plus years old? That replacement number is not ...
Thermostat Illiterate12/7/2010
  Q: We have just moved into a new home where the owners did not leave behind any manuals. We have a ...
  A: Kari, Find the breaker in the panel marked furnace. Turn it off, wait a few seconds and then back ...
Resistive Heat/Frigidare B3VM Air Handler12/7/2010
  Q: I would like to disable the "emergency heat" on the air handler. I am retired but, I have an ...
  A: John, The answer is yes if it works correctly now. The outdoor unit has low voltage wiring ...
Re: AIR PURIFYER-LIVING AIR XL15:12/7/2010
  Q: John Borgman: It stopped working at all; no sound, no movement. I found the fuse was shot, so I put ...
  A: Makoto, That is not a product that is generally repaired in the field. I looked it up and it does ...
central heat problem12/7/2010
  Q: I have a NG furnace that is giving this problem: The unit seems to work just fine except for one ...
  A: Landon, There is a board available for that furnace still. It no longer has the big clear plastic ...
no voltage to thermostat12/6/2010
  Q: Panye econoair, model 24/60 YAC-108T, yr 6-30-72. Not getting 24 volts to thermostat
  A: Ron, Got this question from our question pool. The 24 volts comes from the furnace. I am not ...
new unit12/5/2010
  Q: I'm a home owner and general contractor in the L A area. I have had very little contact with hvac ...
  A: Tom, Not a real fan of any of their products. And yes you are limited, although you should have ...
Gas Furnace Problem12/5/2010
  Q: I live in a mobile home, and my furnace is a coleman 7656 b 856 presidential two. The problem is ...
  A: Bob, The thermocouple is the small copper rod that screws into the gas valve and the other end ...
Heil Heater12/4/2010
  Q: I have a heil heater, and can not get the pilot light to ignite. This unit is old as I can not read ...
  A: Renee, First off it is the LAW that the landlord supply you with heat, he cannot refuse. You can ...
Pro-stat thermostat by Harper-wyman12/3/2010
  Q: this unit has controlled our therma floor (240v, converts to DC to heat brass mesh wire in floor, ...
  A: Clee, I for one was sorry to to see the Pro Stat go away, I loved that thermostat. All that 24 ...
Bard HVAC Heating Problem12/3/2010
  Q: I have a 3ton wallmount Bard on the side of my house, my wife turned on the heat and the unit shut ...
  A: Seth, I have never seen a Bard on a private residence. And if you are a tech let me know, I give ...
Trane xl 1200 circuit board code12/3/2010
  Q: When i turn on heating it runs for about 20 minutes then the red light starts blinking twice on the ...
  A: Michael, Hi, John Borgman here, I got this from our question pool. Yes and if you look close the ...
Intertherm unit frosting up12/3/2010
  Q: I had to go outside about 3AM last night and noticed almost the entire sides of the unit were ...
  A: Sure Jack. But as I said there must be a plastic (housing) jumper missing. Did you look in the ...
Intertherm unit frosting up12/2/2010
  Q: I had to go outside about 3AM last night and noticed almost the entire sides of the unit were ...
  A: Jack, It is perfectly normal to frost, as a matter of fact it can be a few inches thick as long as ...
Manual J and Furnace Sizing12/2/2010
  Q: The contractor we are working with has agreed to match the AC to what is recommended by the manual J ...
  A: Steve, You know HVAC sales guys get a percentage, you are getting enough knowledge to make ...
Manual J and Furnace Sizing12/2/2010
  Q: The contractor we are working with has agreed to match the AC to what is recommended by the manual J ...
  A: Steve, Very interesting points for sure. I will admit that if the duct work can handle a larger ...
Heat not turning on11/30/2010
  Q: I have a Lennox Merit Series 10hpb30-12p. 5yrs old.My air works fine, when I turn on my heat no heat ...
  A: Jason, You can run emergency heat forever. The difference is that when your heat pump is running ...
Boiler age11/29/2010
  Q: I have a boiler (gas, hot water heat manufactured by HB Smith or AO Smith?) that was installed when ...
  A: Dave, John Borgman here, I picked this question from our "question Pool". The first thing you ...
Ductwork11/28/2010
  Q: We just had the furnace and AC replaced and a mistake was made when sizing it so it ended up ...
  A: Steve, The suggestion from the Rheem Rep. falls in the same category as before...CYA. Yes you are ...
furnace trouble11/28/2010
  Q: My Bryant Furnace will start and run for about 4 min and the burner shuts off like normal,then it ...
  A: James, The board for that isn't cheap. you should have a service tech out and look further. It ...
Resistive Heat/Frigidare B3VM Air Handler11/28/2010
  Q: I would like to disable the "emergency heat" on the air handler. I am retired but, I have an ...
  A: John, Got this question out of our question pool. In the air handler, the thermostat wires hook ...
lopi besrkshire gas stove11/27/2010
  Q: My stove gets a lot of black soot when burning and the glass gets black. Is this normal? Sometimes ...
  A: Dan, I don't know if this is heat or cook unit, but, the flame should be as blue as possible and ...
Westinghouse FG5RA 060C-12A Furnance11/27/2010
  Q: the furnance was installed in a new house in 2006 and was used about 3 years. i bought the house ...
  A: Jim, I got this question from our question pool. John Borgman here. There should be a ledger on ...
Oversized Equipment11/27/2010
  Q: We just had the furnace and AC replaced and a mistake was made when sizing it so it ended up ...
  A: As far as the Rheem Rep, that Is a CYA answer for sure. And not a good cover at that, for he is ...
Oversized Equipment11/27/2010
  Q: We just had the furnace and AC replaced and a mistake was made when sizing it so it ended up ...
  A: Steve, I assumed you picked me because of my engineering background in this field? I cannot offer ...
furnace trouble11/27/2010
  Q: My Bryant Furnace will start and run for about 4 min and the burner shuts off like normal,then it ...
  A: James, Ok, that unit was made 1993 ( first 3 serial numbers). That is right about the year that ...
age of Trane gas pack11/27/2010
  Q: How can I tell the age of Trane gas pack. We were told that is was bought the year before we moved ...
  A: Trudy, Got this question from our question pool. Trane is really good on their Gas Packs putting ...
furnace trouble11/26/2010
  Q: My Bryant Furnace will start and run for about 4 min and the burner shuts off like normal,then it ...
  A: James, how old is that carrier product? Is is old enough to have a thermocouple, Or new enough ...
armstrong gravity furnace, natural gas.11/25/2010
  Q: Im currently working on an Armstrong Gravity Furnace ( 101a-g2-85, input btu 85.000, bonnet cap ...
  A: James, With a name like Coleman you should be the expert...lol You have a direct ground Jason. ...
troubleshoot furnace11/25/2010
  Q: when theres a call for heat the blower moter goes on right away with the draft moter and the furnace ...
  A: Dan, I got this from our question pool, I am another expert on this site. That means that a limit ...
Heat and AC at the same time11/24/2010
  Q: I am working on a unit that has both the A/C and Heater coming on at thte same time. I have checked ...
  A: Bill, Got this question from the question pool. It is not the transformer. The 24 volt line that ...
Condensation forming on HVAC Lines11/22/2010
  Q: I have a Goodman 3 Ton Heat Pump 2nd story and 5 Ton AC (with gas furnace) main and a 2 ton (with ...
  A: John, Either the insulation on the large line is missing in some place and it is dripping water, ...
blower fan11/17/2010
  Q: my rheem central air cond. unit has a vibration in it... works fine just vibrates like dust build up ...
  A: Mark, John Borgman here another site expert.At the "air handler" in the attic is where the blower ...
Heat pump and 2.5 ton carrier air handler11/15/2010
  Q: I have a 12 yr old heat pump in which the compressor has gone out twice within 12 month each time. ...
  A: Canida, I got this question from our question pool. First if you lost a compressor withing 12 ...
hearter blower wont come on11/12/2010
  Q: blower motor wont come on after heat cycle. can turn blower on in fan and then start heater and get ...
  A: Kirk, Got this question out of the question pool, Hi name is John Borgman another expert on this ...
not getting power to control i think?11/7/2010
  Q: I have a synder general comfortmaker model no. gua080a012-12, serial no. 0000246425-p29-0280, mfg. ...
  A: Shirelle, Do you have 24 volts when you measure from Red to Common on the board? If not is there ...
Bryant Plus 9011/7/2010
  Q: I have had numerous problems with my Bryant Plus 90 furnace which was purchased new and installed in ...
  A: Rick, I got this from our question pool. I have been on vacation due to a back operation, but it ...
Furnace replacement11/4/2010
  Q: I have a 19 year old amana gas furnace to replace in a 1961 california ranch single level home of ...
  A: Steve, You should really look at the Carrier Infinity system with matching thermostat. It would ...
Fan making noise11/2/2010
  Q: I have an American Standard 80 Furnace. Just this morning when the fan kicks on or off it sometimes ...
  A: George, Good morning. That is called a draft inducer motor. It pulls the air that is mixed with ...
coleman furnace pilot light goes off11/1/2010
  Q: The coleman furnace in my manufactured home is the original 1993 Evcon Presidential. This fall, ...
  A: Ok, lets sort this out. If you are talking about surface rust only on the inside of the furnace and ...
coleman furnace pilot light goes off11/1/2010
  Q: The coleman furnace in my manufactured home is the original 1993 Evcon Presidential. This fall, ...
  A: Eileen, You led me to believe that other than the pilot going out the furnace was in great shape. ...
coleman furnace pilot light goes off10/31/2010
  Q: The coleman furnace in my manufactured home is the original 1993 Evcon Presidential. This fall, ...
  A: Eileen. Although your furnace is 17 years old and a little inefficient, unless the heat exchanger ...
New RUUD system -very noisy heat mode10/31/2010
  Q: Have a new RUUD 3 ton heat pump (UPRL-036JEC - Model Number & RHPL-HM3621 Air Handler). This summer ...
  A: Frances, Have you given the company that installed it a chance to look at it? It should be under ...
air conditioner10/30/2010
  Q: i recently replaced my thermostat and my air conditioner wont stop running unless i turn it off at ...
  A: Jeremy, You either have it wired wrong or the wrong thermostat. Your tstat should be a ...
?10/30/2010
  Q: i have a home. i was laid off earlier in the year and its been difficult to get back to work. with ...
  A: west, There is no magic number. It depends on house size, insulation, windows and on and on. If ...
furnace10/18/2010
  Q: My furnace blows cool air during heat cycle. clogged coiled?
  A: Rob, Going to need a lot more info. Does it heat at all? Does the blower stay on all the time? ...
Black Soot10/18/2010
  Q: I am hoping you can give me some ideas here. We seem to have a black soot problem. It is on the ...
  A: Terri, Here is what you can try to find if the heating system is causing the problem. Get some ...
Heat pump thermo expansion valve repplacement10/17/2010
  Q: I have a Rudd heat pump that is 10 years old. Had a service check done on it the other day and the ...
  A: Matt, A little confused? The ok pressure I assume is for an R22 system and is the high side ...
Tempstar T4H10/17/2010
  Q: I have a Tempstar T4H unit heat pump, electric unit. It defrosts frequently even when it is not real ...
  A: Susan, There is a place on the control board for the outdoor unit that adjusts the time. There ...
Payne Forced Air Heater10/17/2010
  Q: My Payne forced air heater 115,000 BTU, is not working today, worked yesterday. Was installed in ...
  A: Larry, Are you saying that you checked the white and black leads to the inducer motor and there is ...
Furnace burners not all lighting10/16/2010
  Q: I am working on this for my Dad, who doesn't really use a computer much. He has a Carrier Gas ...
  A: Cindy, First he is not blowing raw gas into the duct work, if he was, then when the furnace was ...
American Standard Heat Pump sparking at T-Stat10/16/2010
  Q: I am diagnosing an American Standard heat pump that is from 1993. She said it worked great during ...
  A: Gabriel, Are you a tech? If so I will walk you through the process for this situation that you ...
A/C Coil Replacement10/15/2010
  Q: I have a home warranty and the a/c person came out to fix a problem. They said the coil needed ...
  A: Shelly, You are getting scammed. Don't let them back to your home and ask for your money back ...
singer air handeler: mod #bch 322010/12/2010
  Q: Sir, I have a singer air handler mod# BCH 322, serial # 8172395-C11-0053. Currently the system is ...
  A: Bryan, If Singer does not have a current strip heat package available for that Air Handler there ...
RUUD Heat Pump10/12/2010
  Q: I have a 3 year-old RUUD Heat Pump, Model # UHSA-HM3617JA. The Condensor is Model #PNE-036JAZ. One ...
  A: Paul, there is a ledger on the inside of the door (panel) you remove to get to that board. It has ...
leaking oil from york a/c10/11/2010
  Q: i was wondering if you could help me out my a/c unit York about 2-3 ton has been leaking freon and i ...
  A: Norman, That is not something that a home owner can fix, it will take a tech with the proper ...
Sq.Ft. vs. Tonnage10/10/2010
  Q: What is the rule of thumb of the home vs. the a/c tonnage needed? Thanks for your time, Ed.
  A: Ed, There is no rule of thumb other than a blind guess. Tonnage is figured out by figuring the ...
replacement filter10/10/2010
  Q: I've bought a house and I've found that the air handler unit of my heating/air system should have a ...
  A: Jennifer, All company's supply some kind of a filter, usually washable with a new Air Handler. ...
heat pump10/8/2010
  Q: I have an outside heat pump. It is a heat and air combo. When the air is running and the compressor ...
  A: Paula, Ok, first are you sure that the fan switch on the thermostat is in the auto position, not ...
question about my furnace10/7/2010
  Q: I have an American Standard freedom 80 single stage upright furnace. Yesterday the furnace just ...
  A: Matt, Unfold a paper clip and "rod" out the hole. DO NOT DROP THE CLIP INSIDE. If you do, you ...
replacement10/7/2010
  Q: I live in Kansas, AC season lasts about 6 months, have a ranch house of 1780 SQFT, average pitch ...
  A: Anne, Goodman is what is known in the business as a contractors model. They are very cheaply made ...
question about my furnace10/6/2010
  Q: I have an American Standard freedom 80 single stage upright furnace. Yesterday the furnace just ...
  A: Matt, Do the burners actually light? Is that what you are saying? If you have a pressure switch ...
Hot Water Heater REPLACEMENT10/5/2010
  Q: I have a nine year old gas HW heater... I assume it is near it's end of life (?) Does it make ...
  A: Leonard, Gas tankless is way more efficient than a standing tank of water, they do not make ...
heat pump10/4/2010
  Q: I have an outside heat pump. It is a heat and air combo. When the air is running and the compressor ...
  A: Paula, I need a better mental picture. The indoor "AIR HANDLER" has a "BLOWER" motor in it that ...
Colman Furnace Model # DGAH077BBSA10/4/2010
  Q: About a month or so ago I started my furnace just to make sure there were no issues before it ...
  A: Jim, First the bright orange/red glow is the Hot Surface Ignitor and I don't think you actually ...
base board heat units10/4/2010
  Q: Is it safe we have baseboard heat in each room. I notice that the unit was hot one evening but i did ...
  A: Shirley, You need to get someone out right away. It might just be a bad thermostat, but since ...
dehumidifying indoor pool area10/4/2010
  Q: I'm adding a sunroom (19'x23') to my home that will contain an Endless Pool (7'x14'). The pool ...
  A: Nancy, That equipment is not designed to be a de-humidifier. It will handle humidity better than a ...
a/c smells like gasoline10/4/2010
  Q: We are in a rental home and every time the a/c compressor kicks on I smell a very strong smell of ...
  A: Jean, There is nothing in an Air Conditioner Air Handler ( the indoor unit ) that smells like gas ...
Residential heat and air not starting10/4/2010
  Q: I have an Armstrong Unit. Model # AHSA20A-1A. Ser-# 5597E95404. The unit stopped coming on at all. ...
  A: Ty, There is no DC voltage or device that you are looking for. There is line voltage and control ...
comparing a/c models10/3/2010
  Q: 888 sq. ft. rental- Can you compare a 2 ton 12 SEER Frigidare condenser E54BD-224KA and air handler ...
  A: Kathy, Generally you can go by what was there before, unless your A/C died an early death due to ...
camparing a/c models10/2/2010
  Q: 888 sq. ft. rental- Can you compare a 2 ton 12 SEER Frigidare condenser E54BD-224KA and air handler ...
  A: Kathy, Not sure what you are really asking. First of all, you cannot just put any tonnage on any ...
Genaire air conditioner9/29/2010
  Q: Can you please advise where I can contact the company that makes Genaire air conditioners? There is ...
  A: Larry, I believe Genaire is just a company name not the type. What does the name plate say? ...
Heating and Air Cond.9/28/2010
  Q: My gas heater and electric air cond are both in my attic. I noticed they are sitting on 3 boards ...
  A: Erie, Sorry this somehow went to spam file. All codes involving that are on a local basis, ...
Drain pan full of water9/26/2010
  Q: We live in Florida and have a 2001 TraneAC/heat pump. The air handler is in the hot attic and sits ...
  A: Amy, First, why the water? The only way for it to get in the second pan is a backed up drain or ...
Lennox Pulse furnace air valve9/24/2010
  Q: What is the required clearance on the air flapper valve on a G14Q3-60 Lennox Pulse furnace?
  A: Phil, There is a washer that fits inbetween the plates with the holes that is the clearance, if ...
HVAC Residential9/23/2010
  Q: I have an older model Arcoaire furnace(1998) and AC unit. I notice water on the floor next to the ...
  A: Yes it is possible to just replace the pan on most coils. There are a few that have it welded to ...
coil pin hole leaks9/22/2010
  Q: American standard unit around five years.this the third air handler coil going to be ...
  A: No, everything they are telling you is jiberish. If you are in fact loosing freon, find an HVAC ...
coil pin hole leaks9/21/2010
  Q: American standard unit around five years.this the third air handler coil going to be ...
  A: Bobby, If you are saying 3 coils in 5 years yes I have an answer. If you have a leak it is not in ...
Double Wide Heating/Vent Question9/21/2010
  Q: I own a double wide trailer. The vents lining both sides of the trailer blow out heat. However the 4 ...
  A: Sara, That is a supply duct just like the ones on the side, which is just a sheetmetal box that is ...
hvac9/20/2010
  Q: I have a 20 year old york heat pump system and the air conditioning stopped working. The outside ...
  A: Tom, You need to cal a service tech out and look at it. You have 2 fault codes that indicate ...
Furnace Fan Won't Shut Off9/20/2010
  Q: I have Trane XR90 furnace and A/C units (2 of each for 1st & 2nd floor) in my 30-month old house. I ...
  A: Brent, Thanks for ragging on me. And I hope for your sake that a limit is not tripped or a short ...
central A/C9/20/2010
  Q: I have a central air unit that was just barely cooling. Everything sounded the same inside and out. ...
  A: Gail, Yes you need to get a tech out. That insulated copper pipe being warm and dry indicates ...
AC company Can't find leak-want to reset lines9/20/2010
  Q: I just read your answer to Melissa from 8/2010 regarding the use of dye to find a leak. Today the ...
  A: Nancy, Bummer at 15 plus words per minute that took a WHILE. OK, First we will reverse the ...
410a system 3 ton goodman9/20/2010
  Q: what would cause the low side line to be very hot to touch?The compressor was slow to start,then the ...
  A: Matthew, What do you mean the low side was pegged? The low side gauge on R410a is more than 200 ...
410a system 3 ton goodman9/20/2010
  Q: what would cause the low side line to be very hot to touch?The compressor was slow to start,then the ...
  A: Matthew, Shut it off right away!!! It is either low on refrigerant or has a metering or flow ...
Coleman Forced Air Heater9/19/2010
  Q: I have a mobile home with a Coleman central heat system. The heater is Model #7956-856 and works on ...
  A: Ed, No it is not supposed to get blown out. The pilot flame baths the end of the thermocouple in ...
Blower won't shut off, mobile home furnace9/18/2010
  Q: From the previous question/answer session: The only thing remaining, for me, is the overall ...
  A: I thought you were describing a switch on the top panel of the furnace that is in the blower ...
Coleman Forced Air Heater9/18/2010
  Q: I have a mobile home with a Coleman central heat system. The heater is Model #7956-856 and works on ...
  A: Its about time to pull the pilot assembly out and clean the oriface, replace the thermocouple and ...
AC company Can't find leak-want to reset lines9/17/2010
  Q: I just read your answer to Melissa from 8/2010 regarding the use of dye to find a leak. Today the ...
  A: Nancy, The sub-cooling number is on the name plate for the outdoor unit. usually about 1/4 way ...
Blower won't shut off, mobile home furnace9/15/2010
  Q: I'm working on an older Miller (20-30 years or more), down-flow, mobile home furnace. Standing ...
  A: That is called an aux. blower limit switch and it is usually there with a manual reset button in the ...
Blower won't shut off, mobile home furnace9/15/2010
  Q: I'm working on an older Miller (20-30 years or more), down-flow, mobile home furnace. Standing ...
  A: The fan switch activates at 115 degrees and opens no later than 30 degrees below that. The Limit ...
Residential AC Unit9/14/2010
  Q: This is a long one...my father who is 93 needed a new AC, he originally had a heat pump but when ...
  A: Claire, Yes your dad got taken. They should have replaced what he had with another heat pump. ...
Blower won't shut off, mobile home furnace9/14/2010
  Q: I'm working on an older Miller (20-30 years or more), down-flow, mobile home furnace. Standing ...
  A: ducky...lol Ok where to start. First whenever you have a snap disc it is either a limit or fan ...
Compressor capacitors9/13/2010
  Q: My a/c compressor dims the lights in the house when it starts. I have been told it is because the ...
  A: Jim, Really high odds that it is not the capacitor's, And if it is, the odds are even higher that ...
Trane XB 80 Furnace Unit condensating tremendously9/11/2010
  Q: I have a two story house with dual AC system. Upstairs AC system is zoned to allow for extra cooling ...
  A: Jim, Water only goes into the pan under the duct work when there is a problem. Either you have a ...
drain pipe confusion9/10/2010
  Q: Water constantly drips out of visible drain pipe to outside of house. Drain pan under and separate ...
  A: Jeff, The drain can go into your sewer, yes, but is in the norm to have it exit right at the ...
drain pipe confusion9/10/2010
  Q: Water constantly drips out of visible drain pipe to outside of house. Drain pan under and separate ...
  A: Jeff, The "XTRA' drain pan that is not part of the equipment is for the situation that the drain ...
Air unit shut off and wont start9/8/2010
  Q: Where is the reset button on a 2003 heat pump model number PH5536AKA, the unit just stopped. Willit ...
  A: Tara, Since you didn't tell me what kind of equipment ( Brand ) I cannot tell you for sure what ...
heat pump won't start, intermittant9/7/2010
  Q: Goodman heat pump with oil backup, about 8 years old. I noticed the indoor fan running but no ...
  A: Alan, The vision Pro does have 3 aaa batteries, but they last forever. They are for keeping your ...
heat pump won't start, intermittant9/6/2010
  Q: Goodman heat pump with oil backup, about 8 years old. I noticed the indoor fan running but no ...
  A: Alan, The first thing I would do is call that company, talk to the owner and get my money back as, ...
Natural gas furnace9/5/2010
  Q: I have a 20 years old natural gas forsed air furnace with a Honeywell S86E pilot gas heating system. ...
  A: Cosmo, That is a very reliable control module, one of the best ever made. Two things could cause ...
Heat Pump A/C leaking water out of bottom9/5/2010
  Q: I have a 24 year old Carrier unit that I maintain annually. I just noticed water seeping out of the ...
  A: Susan, there are 2 things that cause the indoor coil to freeze. One is air flow, the other is ...
heat pump9/3/2010
  Q: this has to do with a Armstrong heat pump, model# PGE10B30D075A-2A,SERIAL 8400F10183, Its natural ...
  A: Shirley, The "mother board" as he called it? Is this the board in the furnace or the heat pump ...
2 speed Lennox condenser, fan partial fail9/2/2010
  Q: M#HS14-653V-6Y, S#5188K19865 I should have owner shoot it but he doesn't want to, 22 y/o unit. Fan ...
  A: Nick, What is it you are asking? What is the measured amp draw compared to the rated amp draw for ...
New air compaired to old9/1/2010
  Q: I recently had a colman DGAA070BDTB furnace and a weather king (13 seer) outdoor central air in ...
  A: OK, I need to know this. Before 2 years ago and problems started did the old equipment cool your ...
New air compaired to old9/1/2010
  Q: I recently had a colman DGAA070BDTB furnace and a weather king (13 seer) outdoor central air in ...
  A: Melissa, Right off the bat I question the ability of the people doing the work just from your ...
Undersized system, poor duct work or both?8/13/2010
  Q: I have an issue with my HVAC system in my 11 year old home in Kansas City. It is a 2 story with a ...
  A: Michael, My suggestion was if you can increase the size of the duct work where you can get to it ...
air-conditioner throwing breaker8/12/2010
  Q: Outside temps have been 95-100 for several days. The breaker for our air-conditioner started ...
  A: Jerry, If all the high voltage electrical connections have been checked, including the common and ...
Undersized system, poor duct work or both?8/12/2010
  Q: I have an issue with my HVAC system in my 11 year old home in Kansas City. It is a 2 story with a ...
  A: Michael, I run across this all the time. It is unfortunate that when nice homes, such as yours ...
Payne AC Unit8/11/2010
  Q: The fan in my AC Unit is not working if I start it manually it works it seems to me that the ...
  A: stephanice, turn off the breaker to the outdoor unit!!! You have a bad dual run capacitor and you ...
A/C not Cooling8/10/2010
  Q: I had a 2.5 ton a/c unit installed last July and it worked fine until this summer. Now the tempeture ...
  A: John Borgman here. got this question from our question pool. IF the system is in fact running ...
HVAC8/10/2010
  Q: I just had my hvac replaced. With my old unit, the condensation line was taken outside. When they ...
  A: Linda, Thank you for the positive feedback, it is my only reward for the hundreds of hours I give ...
smaller capacitor installed8/9/2010
  Q: I recently had a service tech come out on a Sat morning to get a unit back online in 105 degree ...
  A: Wendy, He screwed up with the fan cap also. And the fact that it went to ground means the wiring ...
smaller capacitor installed8/9/2010
  Q: I recently had a service tech come out on a Sat morning to get a unit back online in 105 degree ...
  A: Wendy, First...the dual capacitor that went bad was a dual and you said he replaced it with 2 ...
Trane Fan/Compressor Not Working8/8/2010
  Q: I have a gas Trane central A/C unit, 4 units/zones in my house, and one unit/zone isn't working (the ...
  A: Rich, Pour some BLEACH in the pump well. How much depends on hot grimey it is. Then follow that ...
Trane Fan/Compressor Not Working8/8/2010
  Q: I have a gas Trane central A/C unit, 4 units/zones in my house, and one unit/zone isn't working (the ...
  A: Rich, Ok now we are on the same page. With your background I assume you have a simple volt meter? ...
Draft inducer motor pressure problem8/8/2010
  Q: I have a GSW direct vent water tank that has been operating flawlessly since installed new 2 yrs ...
  A: Tony, How much water was backed up into the inducer housing when you took it apart? If the drain ...
Trane Fan/Compressor Not Working8/8/2010
  Q: I have a gas Trane central A/C unit, 4 units/zones in my house, and one unit/zone isn't working (the ...
  A: Rich, I am confused...You talk about Zones as if you are zoning the duct system air flow to 4 ...
HVAC8/6/2010
  Q: I just had my hvac replaced. With my old unit, the condensation line was taken outside. When they ...
  A: Linda, Sounds like the installers were just too lazy to match up the existing pvc drain with the ...
Payne heat pump8/5/2010
  Q: My heat pump was operating fine, then my wife got home the other evening and the unit had shut ...
  A: Charles, Because it stopped working so quickly, you can rule out the freon as the first suspects. ...
HVAC not cooling8/5/2010
  Q: I have a two story Florida home built in 2001 with the original Bryant, split unit, gas furnace, 4.0 ...
  A: 275-400? do you mean it goes that high? No R22 unit should ever go that high. With 70 suction ( ...
Indoor unit just clicks8/5/2010
  Q: I have a Lennox model G24M3/4-100A-2. When the a/c tries to turn on, one of the relays on the mother ...
  A: Matt, Using your meter....call for cooling from the thermostat with the fan in the auto mode. ...
Carrier home a/c question8/4/2010
  Q: Live in southern Texas, home is roughly 2300 sqft, home A/C system is from Carrier installed when ...
  A: Glenn, You need a better tech. The expansion valve is behind the panel he never removed and the ...
Vent Cover Direction8/4/2010
  Q: I am having a new air conditioning unit placed in my home. I had two people give me quotes. During ...
  A: Larecia, I don't know what old and new style refers to, but, a supply " register " has what is ...
fluctuating suction8/3/2010
  Q: Have a 3 ton outdoor unit (Goodman) 9 years old that suddenly started putting out air that was not ...
  A: Lee, First the ambient air has nothing to do with suction pressure, that is a function of the ...
can I use table fan with out electricity?8/3/2010
  Q: If suppose I don't have an electricity, can I use table fan with car battery or any other potable ...
  A: AD, Not sure about all the power sources in England, but here in the states, house fans are AC ( ...
convert swamp coolers to hvac system8/3/2010
  Q: We have a 2944 sq. ft. house that is currently cooled by swamp coolers. We have 2 large coolers ...
  A: Cathy, If your gas furnace uses your duct system to heat your home then you can add AC onto it. ...
Leak Test on central air8/2/2010
  Q: Simple question here (at least I hope it's simple!)...I tried searching online but can't seem to ...
  A: Melissa, I hope this answer gets to you before they put in the dye. DO NOT LET THEM PUT DYE IN. ...
Mitsubishi Slit Zone8/2/2010
  Q: I have a 2 split zone system, 12000 BTU in the living room and 9000 BTU in the bedroom. We only use ...
  A: Ronald, The first thing you need to do is contact Mitsubishi and find a qualified service company ...
Split system not cooling all the time8/1/2010
  Q: Mr. Borgman, I have a 14 year old 5 ton carrier unit model #38CKB060300. Three months ago the ...
  A: Darren, Nothing but red flags on your story. First if the compressor is shutting down from ...
Janitrol Air Conditioner7/22/2010
  Q: Our ac unit stopped working, so we replaced the motor, capacitor and fuses. The unit will start and ...
  A: If the new fan motor is what is getting hot and shutting down, it sounds like you have the wrong ...
Air conditioning not working7/21/2010
  Q: I have two air condition units one for first floor and other for second floor. When i switch on the ...
  A: I am another expert here and got this question from our question pool. First check the air filter ...
Trane Heat Pump7/21/2010
  Q: I hope you can help me. I am a 70 yr old woman and know nothing about heat pumps or anything else ...
  A: Gwen, They are yanking your chain. Blower motors do not slow down. They either work or they ...
HVAC not cooling7/20/2010
  Q: I have a two story Florida home built in 2001 with the original Bryant, split unit, gas furnace, 4.0 ...
  A: I got this question from our question pool, I am another expert here. What you are describing is ...
TXV Problem - Trane7/20/2010
  Q: I had a service guy just come in to service my systems. He changed filters, did "tune up" and took ...
  A: Larry, You actually need more info than he gave you to make an decision on R410a systems, at least ...
Return Air Ducts7/20/2010
  Q: I'm building a new home and the AC contractor located the return air duct about 2 feet away from the ...
  A: Tom, The return air should be in the hall as close to the thermostat as possible and away from ...
residential a c7/18/2010
  Q: I have a 2 ton package unit.It was working fine.but now I cant get the liquid line to get hot.I have ...
  A: Archie, I got this from our question pool. If that is an r22 unit with a fixed metering device, ...
central air7/18/2010
  Q: My mom just had a 3 ton air and heating unit installed with a 3 ton blower.My question is how much ...
  A: http://www.engineeringtoolbox.com/air-duct-calculator-d_813.html Here is a great link to calculate ...
AC fan stops & starts often7/17/2010
  Q: I live in central Indiana in a house with a Goodman furnace. We noticed a problem today. The AC ...
  A: Kevin, The way to trouble shoot that is as follows. Remove the wires from the thermostat ...
central air unit question7/16/2010
  Q: I have a question about lightening possibly striking a central air conditioning unit. The unit was ...
  A: Monica, You are correct. A lighting strike, consisting of a half a million volts will leave a ...
drain lines7/16/2010
  Q: Some air handlers drains are being siphoned by the fan and leaking in ceiling preventing condensate ...
  A: Mark, First off if you find that kind of thing happening, it has to be due to being starved for ...
hvac not cooling enough7/16/2010
  Q: my unit is at least 10 years old and has started to show it's age by not cooling as well as it did. ...
  A: Maro, If you have filters in the return air grills that is what I ment. Hopefully they removed ...
Central air conditioner not turning on.7/16/2010
  Q: I have a 2001 Lincoln central air conditioner connected to Lennox electric air handler. The ...
  A: Jan, I just happen to be on line. Remove the thermostat from the wall, it should just "pop" off ...
hvac not cooling enough7/15/2010
  Q: my unit is at least 10 years old and has started to show it's age by not cooling as well as it did. ...
  A: Maro, The first thing to check is your furnace filter. If it is clogged, you will get no cooling ...
uneven air flow7/15/2010
  Q: I had a A/C-Heat unit installed two years ago. I have Five bedrooms. Two of the rooms were additions ...
  A: Maria, I agree with you. It sounds like either the duct system is poorly designed/installed or it ...
AC not cooling sufficient7/7/2010
  Q: My upstairs AC system is not cooling well. Condenser fan and duct fan are working, filters are ...
  A: Thomas, The sight glass is on the LIQUID line and should be feeding nothing but liquid to the ...
2nd floor ac unit7/7/2010
  Q: I have a two story house with a full basement. Two Trane units installed. The larger unit ...
  A: Joe, Yes 2 suggestions. First verifying that the freon charge, fan speed, ect is correct. You ...
How to determine ductwork runs7/6/2010
  Q: we live in an older home that has an existing Forced Air Heating and Cooling System. We are trying ...
  A: Andy, It is sad, but even most of the people in this field think the same way and air does not ...
trying to get info7/6/2010
  Q: im a maintenance tech in kansas city, mo., and i had a job where the tech before me swapped out a 2 ...
  A: Deric, Hi, first want you to know that I give extra attention to tech's like you that want to ...
RUUD Acheiver 10 not running7/5/2010
  Q: My home has a Ruud achiever 10 outdoor unit and an electric furnace inside, no manufacturer name on ...
  A: Matt, The red and black wire from the A/C unit outside are for the contactor which turns on the ...
filter drier noise7/5/2010
  Q: I have an 18 month old Rheem/Ruud Achiever with the RCFL cooling coils. Whenever the AC starts, ...
  A: Darren, Very good description. It is not the filter drier as the material inside the drier is ...
high indoor humidity with central ac question 27/5/2010
  Q: I live near tampa florida my ac was recently serviced. while now it seems to be cooling set at 74 ...
  A: Donna, I am sorry but I am just not understanding you. Your question says high humidity after the ...
Blower fan in attic unit7/5/2010
  Q: Have “identical” zoned units in attic and downstairs. When temp in attic goes >90F unit blower fan ...
  A: Steve, Outdoor unit has NOTHING to do with the indoor fan operation. You say zoned, so I will ...
high indoor humidity with central ac7/5/2010
  Q: I live near tampa florida my ac was recently serviced. while now it seems to be cooling set at 74 ...
  A: Donna, Was the A/C working before the service call? Was the humidity lower before the service ...
air filter7/4/2010
  Q: my home has a kenmore power miser 80 gas furaces can you plaes tell me were on eath is the air ...
  A: Michael, All furnace have a factory slot for a filter, some installs use that filter and others ...
Trane xe 9007/3/2010
  Q: Have Hunter t-stat on xe 900. Have checked wiring, breaker, and put new batteries in t-stat. Will ...
  A: Wayne, If you have checked wiring and it is correct and you have 24 volts coming to the thermostat ...
Heat pump not working when it's very hot6/29/2010
  Q: My 3 year old Lennox heat pump HXP15 needs service every summer when the weather is very hot. Now I ...
  A: Mai, If you mean they have to add freon every year, they never leak checked it when they installed ...
capacitor location in A/C compressor6/29/2010
  Q: Mr. Borgman, Maybe you can help me understand my options here: ... HVAC = Bryant 376CAV036055 ...
  A: Paul, The overheating of the fan has nothing to do with the freon. The outdoor fan motor doesn't ...
a-coil6/26/2010
  Q: was told by HVAC company that the a-coil in my mobile home's AC unit is leaking and needs replaced. ...
  A: Mike, That is way too high! Should be around 800 bucks, unless your outdoor unit does not have ...
A/C Condensor Fan hums when off6/26/2010
  Q: My a/c is cold and works fine until it is shut off. When it turns off the fan motor hums outside. I ...
  A: Tim, If you are absolutely sure it is the motor, then no it is not the motor as that motor should ...
Ac not cooling very well6/25/2010
  Q: we recently moved to our new house and turn on the AC when the summer starts. Though the AC runs ...
  A: Tadios, How long ago was the tech there? Did you pay for a service call? If so and he said that ...
Heat pump thermastat6/25/2010
  Q: What thermostat would I use that would monitor the outdoor temperature and switch off the heat pump ...
  A: Don, I gave you the answer and solution to what you would like your heat pump to do. As they do ...
AC HELP ASAP6/25/2010
  Q: I moved into a 1985 mobile home 1800 sq. ft late last summer. I had the ac unit serviced and it ...
  A: Quentin, First you should check your air filter, it needs to be clean for the A/C to work. What ...
AC Selection6/23/2010
  Q: I was left completely confused after getting a couple of quotes from reputable installers. When ...
  A: Stan, I can tell you right now that neither company should be installing a " zoned " system, for ...
A/C6/23/2010
  Q: My home A/C was working yesterday but I noticed it was getting warmer, and today it turned hot and ...
  A: First thing you need to do is pull your air filter out, it is clogged solid. When you do, if it ...
air cnditioning not coming on6/23/2010
  Q: Could it be a thermostat problem if when we turn the air on the compressor will come on but the ...
  A: Sharon, Yes it could be, or other things. What kind of equipment do you have? Gas/oil/electric ...
Condensation on central air unit.6/23/2010
  Q: I have energy efficient home, ridge vent roof, foil on rafters, insulation every wall, and roof. ...
  A: Tim, "I did all this to have lower utility bills but i am having larger ones with more efficient ...
Blocking basement AC Vents?6/23/2010
  Q: I have a three story townhouse with central air. When it is running the basement is very cold, the ...
  A: Kevin, No it wouldn't. Think about it like this. You have a very large straw in your mouth ...
air on gas pack6/23/2010
  Q: okay , lets see if you can help . I have a Goodman Gas pack model # GPG12360901A 12 seer 3 ton unit ...
  A: Donna, Just a coincidence that we had a company here in Portland called 4 seasons that did poor ...
air on gas pack6/23/2010
  Q: okay , lets see if you can help . I have a Goodman Gas pack model # GPG12360901A 12 seer 3 ton unit ...
  A: Donna, Yes you would have trouble in heating also for the same reason. The pictures would help, ...
Blocking basement AC Vents?6/23/2010
  Q: I have a three story townhouse with central air. When it is running the basement is very cold, the ...
  A: Kevin, The problem you have is common and not an easy fix. You cannot shut down the basement ...
Changing Heat Pump Thermostat from a Janitrol HPT18-60 to a LUX TX9100E6/22/2010
  Q: I have a heat pump with emergency heat, Goodman PHK024-1. Replacing Janitrol thermostat with LUX ...
  A: Paul, The heat pump gets its signal to turn on both for heating and cooling through the yellow ...
air on gas pack6/22/2010
  Q: okay , lets see if you can help . I have a Goodman Gas pack model # GPG12360901A 12 seer 3 ton unit ...
  A: Donna, Yes, I can tell you the problem. It is air flow. Just because they added a return they ...
hvac6/22/2010
  Q: Refrierant cannot be recovered without isolating a parallel compresor system because of what?
  A: Greg, Hi, I don't answer private questions. I try and help as many as I can, so I do everything ...
McQuay Water Source Heat Pump fan blower shuts off6/7/2010
  Q: I read one of your previous responses and your vast exerience and thought maybe you could help me. I ...
  A: Marc, I see you have a volt/ohm meter, you will also need an amp meter or amp probe that hooks to ...
HEPA filter6/7/2010
  Q: I am doing an addition/remodel to my house, including installing a new HVAC system (furnace and ...
  A: Linda, First did you not read what category you are asking questions in? I am an expert in HVAC, ...
air handler leaking6/7/2010
  Q: I checked drain %26 coils, no frost on coil or blockage/tilt in drain pan. Coil condensing/cooling ...
  A: Thomas, I am not following your description of where the water is actually leaking. If you are ...
heat pump6/7/2010
  Q: We live in Clarksville, Tn, 60 miles north of Nashville. Summer temperatures are usually in the ...
  A: Amy, Howdy. Well, this is a little more involved than I usually take, as I volunteer all of my ...
Rheem split hp 13 seer bad contactor....6/6/2010
  Q: Reply... I had system worked on because condenser would not shut off. That was the first time. They ...
  A: Michael, Either the tech just made those numbers up or his test equipment is off. By those ...
central air conditioning outside condenser6/6/2010
  Q: I do not know much about ac/heating, so I will be as detailed as possible. I do not know if the ...
  A: Shirley, Here is what you can do on your own. Turn the breaker to the outdoor unit off at the ...
HEPA filter6/6/2010
  Q: I am doing an addition/remodel to my house, including installing a new HVAC system (furnace and ...
  A: Linda, The function of a HEPA type filter is to remove air born particulates to a very low micron ...
Attic Drip Pan - How to clean ?6/5/2010
  Q: It appears that the condensation drain pipe attached to the attic unit maybe clogged. Fortunately, ...
  A: Brian, Most likely either it is partly cloged on the main drain, or those 2 outlets have one ...
air handler leaking6/5/2010
  Q: Need to look at my brother's customer air handler, front filter radco about 10 yrs old, 2 ton. I am ...
  A: Tom, If the drain (pvc) is clogged or the coil pan is pitched the wrong way it will leak. If the ...
Attic Drip Pan - How to clean ?6/5/2010
  Q: It appears that the condensation drain pipe attached to the attic unit maybe clogged. Fortunately, ...
  A: Brian, I am an advocate for running the secondary drain line out over the front door of the home, ...
Attic Drip Pan - How to clean ?6/5/2010
  Q: It appears that the condensation drain pipe attached to the attic unit maybe clogged. Fortunately, ...
  A: Brian, drill a hole in the elbow at the top of the trap, right at the easiest place to get to. ...
a/c Blower Speed6/4/2010
  Q: Good day sir, I have a ducane split air system Outside Model-ac12b36 and inside model-MPGA075B4A. ...
  A: Ian, It was good to have a tech out, unfortunately the tech was not very good. An indoor drop of ...
central air conditioning outside condenser6/4/2010
  Q: I do not know much about ac/heating, so I will be as detailed as possible. I do not know if the ...
  A: Shirley, Lets hope you did not destroy the outdoor unit. No matter what happens, outdoor units ...
Heat pumps6/4/2010
  Q: I Have the following bids from contractors to replace heat pump and furnace. I live near ...
  A: Stephen, If all you find are bad reviews, that answer is easy. Do not use them, keep looking. ...
Goodman Heatpump - A/C Problem after a Power Outage6/3/2010
  Q: We have a Goodman heatpump that is 18 months old and recently our power flickered (off for 3 to 5 ...
  A: Shell, So, you checked the fuses at the disconnect box next to the outdoor unit ? And you got 220 ...
Maintenance6/3/2010
  Q: I have a 5 year old Carrier Puron central air system with two zones: one 2 ton and one 2.5 ton. I ...
  A: Dave, You should have had them looked at at 3,6 and 9 for the first decade, that is all they need ...
American Standard Freedom 80 Furnace6/3/2010
  Q: My furnace is an American Standard freedom 80. I had problems twice with the igniter over two months ...
  A: On the inside of the furnace door where the blower motor is and you see the LED flashing, you will ...
outside fan6/3/2010
  Q: why does my fan on my york stellar aircondition stays on after t-stat shuts down inside? ANSWER: ...
  A: T%hank you, will be sure to never try and give you FREE help again. It's too bad your command of ...
Rheem condenser bad contactor?!6/2/2010
  Q: Service guy replaced it last year system worked for 5 months and just went out again. Replaced ...
  A: Michael, I would still be interested in the data I requested, if you would like to know if it is ...
Humidity and air returns6/2/2010
  Q: I hate to reveal how stupid we are but...to make it short, an hvac guy told us once that our returns ...
  A: Denise, If the hole from downstairs makes it upstairs with nothing obstructing it, and the ...
HVAC6/2/2010
  Q: I have a leak from my Bryant system. My HVAC unit is in the attic, there is a secondary/auxiliary ...
  A: Joe, Auxillary means you have a problem and this second line of defense before you ruin the ...
Bryant air cond. compressor6/1/2010
  Q: When I turn my residential air Bryant air cond. on the fan on the compressor kicks on then the ...
  A: Dan, You have either an under or over charged refrigant system, a restriction in the refrigerant ...
a/c Blower Speed6/1/2010
  Q: Good day sir, I have a ducane split air system Outside Model-ac12b36 and inside model-MPGA075B4A. ...
  A: Ian, We don't have Ducane out here, but they are basically a York unit. If that blower assembly ...
amana hvac reverse relay5/31/2010
  Q: on our roof top ac unit it blows hot in winter and then the repair guy comes out in summer and ...
  A: Don, Without knowing more than that, it sounds like, you don't have enough "good condition" ...
AC filter-Clarified5/31/2010
  Q: I previously may have asked you a question about our A/C filter. This is a clarification of my ...
  A: David, All modern furnaces have a factory filter rack inside the blower assembly of the furnace. ...
Load calculations and install on HVAC units5/30/2010
  Q: I'm shocked and disappointed by the reviews I've read of ALL brands of HVACs. So I guess I better ...
  A: Christina, A manual J load calculation can be done by you with the purchase of a $240 manual and ...
American Standard Freedom 80 Furnace5/30/2010
  Q: My furnace is an American Standard freedom 80. I had problems twice with the igniter over two months ...
  A: Santhosh, The reason for the blower running continuously is a lockout due to several failed ...
Trane xl1400 troubleshooting5/16/2010
  Q: I have a Trane XL1400 gas pack with 2 stage gas. The unit LED calls for heat (and it does try to ...
  A: Doug, Not knowing the whole story sounds like some low voltage wires are touching. With he power ...
short-cycle5/16/2010
  Q: 2yr. old 2 and half ton, 13 sear heil unit. Just replaced expansion valve on indoor unit one week ...
  A: Rick, Are you working on it or the owner? If you are in the cooling mode and the unit is short ...
blank thermostat5/16/2010
  Q: My thermostat went blank from a power surge. The storm was yesterday. My thermostat worked ...
  A: Mike, That means you have lost power to the thermostat. First thing to check is the breaker in ...
replacement of builder's quality ac and/or furnace5/15/2010
  Q: My home is 1700 sq ft. I live in Houston, Texas. My home was built in 2002. I recently discovered ...
  A: Trish, I didn't say that only Trane is good, it is in my opinion the best equipment on the market, ...
Replace HVAC or wait? Probable cost? Equipment recommendation5/13/2010
  Q: My current Day-Night HVAC system is a split unit -- 5 ton AC (installed outdoors in 1992) and ...
  A: Andy If you are a position to afford replaement, yes, I would do it now while all the incentives ...
Trane XL1400 Weathertron Heat Pump5/13/2010
  Q: Our heat pump in the backyard recently started making a strange noise. We had a repair man come out ...
  A: Warren, First I would get another company and ask for N.A.T.E certified tech's. Second I would ...
crankcase heater5/13/2010
  Q: is there a way to ohm it out and what should it read and a good explanation of operation thank you
  A: Rob, The crankcase heater will read infinity on an ohm meter. If it reads any number other than ...
Carrier 50YQ capacitor size...5/12/2010
  Q: 1983 Carrier Packaged Heat Pump Mdl 50YQ030300... What is the correct size of the Dual Run ...
  A: Jeff, You do not want to run a permanent split capacitor motor with a run cap that is the wrong ...
best home air conditioning system Florida5/11/2010
  Q: We have to replace our Rudd system and have been getting extimates. A few have recommended ...
  A: D, Truthfully Lennox is a little over priced compared to Trane equipment, but as a rule is some of ...
best home air conditioning system Florida5/11/2010
  Q: We have to replace our Rudd system and have been getting extimates. A few have recommended ...
  A: I cannot go through your bids with you and I also do not do private help. I volunteer my time to ...
replacing motor start capacitor with different type5/11/2010
  Q: i replaced the condenser fan motor with a universal replacement that came with a two terminal ...
  A: Alvin, You need to buy a replacement " duel " run cap that has the same mfd rating for the ...
Fan blowing, nothing else works5/11/2010
  Q: I have a central heating/ac unit, Trane. When I set it to heat, nothing. When I set it to cool, ...
  A: Shanna, Yes it is. You never said what kind of equipment you have? How long are you going to ...
Fan blowing, nothing else works5/10/2010
  Q: I have a central heating/ac unit, Trane. When I set it to heat, nothing. When I set it to cool, ...
  A: Shanna, Is this a heat pump? Gas heat and electric A/C? Actually either way it has to be the ...
best home air conditioning system Florida5/10/2010
  Q: We have to replace our Rudd system and have been getting extimates. A few have recommended ...
  A: D, If you want the best for the money it would be a Trane. That is what I put in even my parents ...
Rheem Air Handler Problem5/6/2010
  Q: I've got a Rheem RHSA-HM1817JA 240vac Air Handler in my house that isn't working. This unit is only ...
  A: David, Unless you have a volt/ohm meter, this is what we can do. Get a couple of those fuses. ...
backwards LL filter drier3/27/2010
  Q: hi I was soldering in a new 13 seer 3ton R-22 AC last week and after i had already pulled vaccum and ...
  A: Phillip, Yes you will have to change it and unfortunately you will also loose most of those ...
Lennox blower3/27/2010
  Q: I have a Lennox furnace with a Honeywell Auto/Manual control box...problem is the fan won't go to ...
  A: Janice, Are you describing a control with a white shaft that protrudes out the front of a ...
set up a new thermostat Honeywell TH8110U10033/24/2010
  Q: Replacing a Climate technology Model 43054 with a Honeywell TH8110U1003. I have a blue, green, white ...
  A: Max, Not knowing the type of system this is on I can only go by the colors you gave and hope that ...
Lennox Pulse Limit Switch3/5/2010
  Q: Please Help : ) I have a Lennox Pulse Furnace that is pretty old. I don't know if this helps, but ...
  A: Jennifer, I don't know what b/c means? The flapper is under a 1/2" thick piece or steel in a ...
high pitched hum in attic3/4/2010
  Q: We (live in NJ) have 2 Trane heat pump units outside (AC & Heat), one zone upstairs and one zone ...
  A: Elaine, Are you talking about the air handler for the heat pump? Is the noise coming through the ...
Oven temperature3/4/2010
  Q: We have opened New aluminium Air grilles business. We are facing problem with the OVEN. The ...
  A: Mohammed, Gonna need more info to help you. What is the oven supposed to run at? Minimum and ...
NEw AC broken3/3/2010
  Q: Last week a company changed my old 10 seer residential AC to a new 16 seer trane but a day later we ...
  A: Mary, Where exactly was it leaking the oil and gas? Are you saying the used the old line set from ...
Lennox Pulse Limit Switch3/2/2010
  Q: Please Help : ) I have a Lennox Pulse Furnace that is pretty old. I don't know if this helps, but ...
  A: Jennifer, If you have not had it serviced in a long time, you need to. There is a "flapper ...
txv3/1/2010
  Q: what will happen whent the sensing valve of your txv got disconnectedand hung loose?
  A: Mike, It will not sense the temperature at the end of the evaporator coil. Without being able to ...
Heat pump defrost time?2/28/2010
  Q: I live in an Indianapolis suburb... My heat pump's defrost cycle is set at 30 minutes. My other ...
  A: Brett, The longer time is for mild weather where it rarely goes into defrost. In colder climate, ...
not hot heat.2/28/2010
  Q: model: n2ahd14a06a york heater problem:electric backup on a heat pump,electric only on,blows cold ...
  A: Lad, I am un clear with your description, but if you are saying that on emergency heat you get ...
Compressor problems2/27/2010
  Q: The compressor is not running but is hot to the touch. I tested motor windings. C to S and C to R ...
  A: Robert, The first thing you have to do is cool the compressor down with the power off to the unit. ...
Vents2/27/2010
  Q: we just moved into our single / split level house about 6 months ago.. We are re-doing our bedrooms ...
  A: Mike, I am not sure what you are saying, either a typo or ??? What is %26 mean? What do you mean ...
Gas furnace. cool heat2/27/2010
  Q: I have a Trane XR90 furnace that, since the day it was installed, blows nothing but cool air. I ...
  A: Rick, In that case, how about this. Find the certified techs as stated and tell him/her when they ...
ignitor/ sensor2/25/2010
  Q: The instruction book for my Rheem gas furnace says that the hot surface ignitor also serves as the ...
  A: Donald, Rheem/Ruud uses the white common wire as a resistance reading back to the board for that. ...
RUUD 90 runs continuously2/24/2010
  Q: I have a RUUD 90 gas furnace installed around 1990. The ignitor was replaced two years ago. I ...
  A: Ron, Either one of the limits is open ( that is why fan runs, too cool it down or that some ...
Air Conditioning in Attic2/23/2010
  Q: When we purchased our single family home four years ago we only had one AC unit in the house. About ...
  A: Mike, Yes an attic fan should have been the first thing you tried. At 95 degrees it can reach ...
Bryant Heat pump ( Evolution controls)2/22/2010
  Q: First a few technical items, Heat pump Bryant 288ANA036 Fan coil FV4BNF005, T stat SYSTXBUID01 ...
  A: Herbert, As far as problem 1 I have never seen that, but it should not cause a problem with the ...
Water coming from furnace2/22/2010
  Q: I have a Quatro True Blue 90 furnace in my garage, it works fine except when its running, water ...
  A: Richard, Those high efficiency units make water and it runs out through a pvc drain. So either ...
Heat pump2/21/2010
  Q: We’re in Florida and have had this heat pump for the last 10 years and it has worked great, but last ...
  A: Nancy, With the high side bleeding to the low there is no physical way to charge the unit ...
Heat pump2/21/2010
  Q: We’re in Florida and have had this heat pump for the last 10 years and it has worked great, but last ...
  A: Nancy, I can only go by what you have written and that the measurements of the techs that were ...
nordyne gas furnace/air condition model GR4GA-024K072C2/18/2010
  Q: Flame will not come on. Inducer motor starts,new ignitor glows fine,gas valve clicks but flame ...
  A: John, You are correct about where you are looking. Everything else in the furnace has to work ...
furnace lighting problem2/17/2010
  Q: I have a Trane XE90 and all of a sudden it doesn't alway light it will only blow cold air. If I ...
  A: Marty, With no more info than that all I can tell you is that one of the safeties is failing. If ...
heil furnace wont fire2/17/2010
  Q: i have a heil natural gas furnace that wont fire when its set low at night i have to reset the ...
  A: Daniel, So, you are a tech? Do, you mean when you turn it back up in the morning it will not ...
Furnace Ruining Controller Boards2/17/2010
  Q: About two weeks ago my furnace stopped working (Goodman GMP075, circa 1993). I opened it up and saw ...
  A: Forrest, Yes, it could be the inducer motor itself. An amp draw should be taken and compared to ...
duct work2/16/2010
  Q: I just installed a new 4 ton rheem hvac system in my home. Heat is electric. Air handler is rated ...
  A: Angela, Never close down dampers to " adjust " air flow. It is a common mistake made by many, ...
emergency heat2/16/2010
  Q: Ihave a heat pump.I was told that because my heat pump has been off this winter I need to first run ...
  A: Brian, What are you calling off. First a heat pump has a crankcase heater, around the compressor ...
Whirlpool electric heat/old unit no heat pump2/16/2010
  Q: INSTALLED NEW THERMOSTATS / FAN RELAY/ WORKED FINE FOR ABOUT TWO WEEKS. NO HEAT. THE ELEMENT IS NOT ...
  A: Roy, To check the elements ( they are called strips ) you need an ohm meter. As you look at each ...
My fridge2/16/2010
  Q: John, first off what company do you work for? Are you in the Portland area? I am a residential ...
  A: Marshall, I live in Milwaukie and currently work for Smiths heating out of Oregon City. I have no ...
Bryant thermostat2/15/2010
  Q: I have a 12 year old TRANE air conditioner model XL 1200, TTX018-060C. The thermostat is a BRYANT ...
  A: Ron, Some thermostats have a 2 to 3 degree adjustment, but none that I know of have that kind of ...
Heil gas furnace erratic functioning2/15/2010
  Q: My HEIL gas furnace would not respond to call for heat. Tech came out and took sandpaper to ...
  A: David, Wow, I am in shock. Tell me what the first service ticket says and what were you charged ...
Hi-efficiency PVC flue condensation shuts down furnace2/14/2010
  Q: I have a hi-efficiency Goodman furnace/AC unit installed two years ago. Last week, the furnace ...
  A: Craig, It is a condensing gas furnace and is called that because it does condense water in the ...
Maintenance2/14/2010
  Q: I have an apartment complex with 64 split units in Florida. It seems that these units are going bad ...
  A: Bob, 5 to 10 years old should not be having that many problems. What brand are they and what ...
Lennox G26 Furnace (Heat Pump with propane backup)2/13/2010
  Q: I have a Lennox G26 Furnace which uses propane as the secondary heat source when heating with the ...
  A: Lenny, There are only two things that could most likely cause that under the circumstances you ...
noisy in heat mode Amana ASZ1603612/13/2010
  Q: Bought an Amana heat pump system 16-seer model ASZ160361 in May 2009. Ran fine in summer (in ...
  A: Donna, All that changing the setting on the outdoor thermostat did was change the temperature that ...
furnace problem2/13/2010
  Q: Nordyne model G6RC 100C-16B Possiblly 3-4 years old.Last year I had to replace the heat ...
  A: Mike, First why a heat exchanger on a 4 year old unit? There is no possible way it could have ...
noisy in heat mode Amana ASZ1603612/12/2010
  Q: Bought an Amana heat pump system 16-seer model ASZ160361 in May 2009. Ran fine in summer (in ...
  A: Donna, I would venture to say it is nothing more than the solonoid on the reversing valve. Call ...
AC/heating fan turning itself on and off2/12/2010
  Q: I've recently bought a brands new home,and I've been using the AC/heating system quite often. ...
  A: I will need a lot more info than that to try and help you. What kind and model of equipment do ...
Freedom 90 American Standard Furnace2/12/2010
  Q: Sir, I have a model #AUX100C948B4, SN M394J505G furnace that has what appears to be a pressure ...
  A: Paul, It is possible the switch is bad, but it is rare. The only way to check that switch is with ...
HELP PLEASE2/12/2010
  Q: Our gas furnace has stopped working suddenly. The blower went out a few weeks ago and we had the ...
  A: Sarah, You had the starter replaced? Do you mean the run capacitor? If you turn the fan switch ...
furnace #ff792/11/2010
  Q: I have gone all thought my house tring to find a electric cutoff switch for the furnac with no ...
  A: Shaun, The furnace itself does not have one, but is common for a light switch to be installed on ...
HVAC not clicking on...2/11/2010
  Q: this has happened for both settings - on cool and on heat... The system detects the need to turn ...
  A: Denise, Do you have a heat pump or gas with A/C? Does the blower turn on and blow air through the ...
Evaporator Coil Replacement2/10/2010
  Q: I am in the process of buying a 2,200 sq ft home and I just had a separate HVAC inspection since the ...
  A: Lynn, In that case, I would suspect a dirty coil is the only problem and because it was cobbled ...
Faulty Heat Pump2/10/2010
  Q: We had a new Carrier HVAC system(model:FB4ANF030) installed in 2002 and have had numerous problems. ...
  A: Floyd, I see all kind of red flags with this company. First they say you need a new coil, now ...
Evaporator Coil Replacement2/10/2010
  Q: I am in the process of buying a 2,200 sq ft home and I just had a separate HVAC inspection since the ...
  A: Lynn, What you have sent me a picture of is the auxiliary drain pan with the auxiliary float switch. ...
defrost cycle2/10/2010
  Q: I have a heat pump. The indoor unit is Bryant 517EN030 with electric aux heat. I have noticed that ...
  A: Giles, First the tech was either pulling your leg or too lazy to do the job, because that strip ...
Heil furnace2/10/2010
  Q: This is pertaining to the Heil furnace that wouldn't stay lit. Do i need to replace the flame ...
  A: Alex, The flame sensor is located on either the right or left end burner. It has a single wire ...
Amana furnace flame inside burner2/10/2010
  Q: Amana GUX045B30A S/N 9202206878 MFR P1119801F 2 questions #1) (easy) - this is a 90% furnace. Should ...
  A: By the way, the burners are called inshot and the burner blower as you call it is an inducer motor ...
Amana furnace flame inside burner2/9/2010
  Q: Amana GUX045B30A S/N 9202206878 MFR P1119801F 2 questions #1) (easy) - this is a 90% furnace. Should ...
  A: Steve, Flames backing up into the burners? That is where it is supposed to be. If this is the ...
Evaporator Coil Replacement2/9/2010
  Q: I am in the process of buying a 2,200 sq ft home and I just had a separate HVAC inspection since the ...
  A: That sounds a little high, but it depends. It is high if there are steps, a wooden floor, light and ...
TempStar Heating/AC2/9/2010
  Q: Thermostat won't turn on system Heating or AC. Have power to Air Handler and Compressor. 220VAC. ...
  A: Ted, If you have a meter and that is how you are checking voltage. Turn off the power, pull the 2 ...
Heil Furnace2/9/2010
  Q: I have an older Heil furnace, a 1993 i believe. The spark ignites a flame, but only for a second, ...
  A: Alex, There is a flame sensor rod that sends a signal back to the controls that keeps the flame ...
Upflow Heat Furnace2/9/2010
  Q: I have a York Upflow Heat Furnace (model GY9S080C16UP11). It is working fine except that the ...
  A: Dennis, That is called a condensing gas furnace as it condenses water in the flue pipe as a result ...
Heat pump smelly air on heat2/9/2010
  Q: I have a Trane air handler in the attic that is four years old. When the heating coils come on I am ...
  A: Perry, Yes it is debris that gas accumulated on the coils. They are not unlike the coils in an ...
leak2/9/2010
  Q: I have a Goodman furnace 80.0 efficient rating. It was installed in May of 2009 before i bought the ...
  A: Nick, Asbestos? That was outlawed years ago. Are you seeing galvanized pipe that has some type ...
Freedom 90 American Standard Furnace2/8/2010
  Q: Sir, I have a model #AUX100C948B4, SN M394J505G furnace that has what appears to be a pressure ...
  A: Paul, The pvc water trap where the water runs through a rubber hose to it off the heat exchanger ...
"Leaking" from Furnace Vent (type B) at joint in cold attic2/7/2010
  Q: Everything works well except I was in my attic and noticed a white residue on the vent pipe that ...
  A: Cary, Correct, you do not want to be taping those joints and that would not change anything as it ...
Lennox Furnace2/7/2010
  Q: Lennox furnace model G20 damper door doesn't open all the way , i have to give it a slight push down ...
  A: Robert, First let me caution you that if you " force " that door you can damage that motor and they ...
Furnace cycles on and off when it calls for heat2/7/2010
  Q: I am a residential customer, my furnace is an American Standard Freedom 80 (Model # AUD080R9V3H4) ...
  A: James, No that is not normal, it should complete the whole cycle until the desired temperature is ...
Faulty Heat Pump2/7/2010
  Q: We had a new Carrier HVAC system(model:FB4ANF030) installed in 2002 and have had numerous problems. ...
  A: So, you have never been given a bill or paid anything? until now? I still do not know what you are ...
breaker tripping2/7/2010
  Q: I have a five ton trane unit and when I turned it on to heat the house the lights inside began to ...
  A: Jim, The breaker that is tripping is for the heat pump. That means that something in the outdoor ...
Faulty Heat Pump2/6/2010
  Q: We had a new Carrier HVAC system(model:FB4ANF030) installed in 2002 and have had numerous problems. ...
  A: Floyd, I need some clarification on some of what you said to better answer this question. What ...
philco furnace won't ignite2/6/2010
  Q: we are getting an 4- error code on our furnace...it will not ignite. in snow storm and snow has ...
  A: Brian, If by " good glow on ignite" you mean that the Hot Surface Ignitor goes through the cycle ...
Replacement A/C unit2/6/2010
  Q: I read a recent answer you gave to a customer about replacing the copper lines "MUST" be changed. ...
  A: Jose, No the tubing can be run up the exterior wall and then covered with a sheet metal or some ...
R10 change from r22 fro a/c's2/5/2010
  Q: Our warranty company has asked us to pay an additional premium for coverage of any problems with ...
  A: Patty, The Montreal protocol was put into effect a decade ago and the clean air act right behind ...
HVAC locking down2/5/2010
  Q: My 10 year old Amana HVAC stops working in the middle of the night during extreme winter conditions ...
  A: Bhuwan, There are a lot of factors including, location and mounting of equipment, quality and type ...
ruud silhouette ii2/5/2010
  Q: My blower won't stop blowing. I have to unplug the unit or remove the cover to cut it off. What's ...
  A: Greg, OK, what did you find to get it to work that far? The main limit? Are you saying that the ...
Carrier furnace intermittently locks out2/5/2010
  Q: Problems with a 19 year old Carrier 58SXA060 high efficiency furnace. Two years ago it began locking ...
  A: Denny, Again I am with you as far as confidence. He said " bouncing" ? What the heck is ...
ruud silhouette ii2/5/2010
  Q: My blower won't stop blowing. I have to unplug the unit or remove the cover to cut it off. What's ...
  A: Greg, You have an open limit switch, probably the main limit which is just above the burners on ...
Draft inducer2/4/2010
  Q: We have a Goodman Model#GMNT060-3B from 1999. It is making a rattling noise whenever it goes on. I ...
  A: Jeanette, The draft inducer is the first motor to start up on a call for heat. It is right above ...
Carrier furnace intermittently locks out2/4/2010
  Q: Problems with a 19 year old Carrier 58SXA060 high efficiency furnace. Two years ago it began locking ...
  A: Denny, It is not the gas valve they do not fail very often. When you say the pilot assembly do you ...
Heat Pump Emergency Heat2/4/2010
  Q: John, I am trying to understand the logic of the Emergency heat circuit. If I get a 240V reading ...
  A: Joe, No. If you put your probes on the 2 lines coming to the breaker you will read 240 even with ...
Heat Pump Emergency Heat not working2/4/2010
  Q: Emergency Heat not working. Thermostat calling for heat, emergency heat switch on, red light on. Air ...
  A: Joe, It tells you, that there is 120 volts to each side of the strip connection, but does not tell ...
Heat Pump Emergency Heat not working2/4/2010
  Q: Emergency Heat not working. Thermostat calling for heat, emergency heat switch on, red light on. Air ...
  A: Joe, First you should be getting at least 75 not 72 on the pump, so, dirty filter low charge, ...
central heat / thermostat2/4/2010
  Q: My heater got stuck on recently. I switched the digital thermostat to off -- didn't work. I tried ...
  A: Scott, John borgman here, got this from our question pool. Pulling the tstat from the wall and it ...
Best H/AC Unit2/4/2010
  Q: I currently have an electric Coleman Heat Pump (AC & Heat) that was installed in 2003. The ac has ...
  A: Crystal, Coleman used to be the THE name when it came to heat pumps, but as you found out, not so ...
Heat Pump Emergency Heat not working2/4/2010
  Q: Emergency Heat not working. Thermostat calling for heat, emergency heat switch on, red light on. Air ...
  A: Joe, A little confused of your explanation, so we will just address the way it should work. First ...
ruud silhouette ii2/4/2010
  Q: My blower won't stop blowing. I have to unplug the unit or remove the cover to cut it off. What's ...
  A: Greg, The most obvious is to make sure that the fan switch on the thermostat is in the auto not ...
Armstrong Air Ultra 5 Enhanced 95 V2/3/2010
  Q: I have an Armstrong Air Ultra 5 Enhanced 95 V that I think was installed in 2001. Since I moved in ...
  A: Lacey, The only thing in common between heating and cooling both not working, is the blower motor, ...
98 Weathermaker 9200 Carrier gas funace burner2/3/2010
  Q: I just had my burner assemble replaced on my gas furnace hoping it would solve the problem of my ...
  A: Carol, There are 2 ways to check a heat exchanger. One is with a meter while it is running in the ...
Cost Efficiency of a Heat Pump2/3/2010
  Q: I have a Janitrol heat pump with the complete unit outdoors (no air handler). The unit was new in ...
  A: Craig, I don't know the mean average temperature there in the winter, but the heat pump should be ...
Im not sure if you can help, but i thought i could ask :(2/2/2010
  Q: My Goldstar GR-141CGP fridge has a chemical smell coming out of it. It still gets cold and I cleaned ...
  A: Not only does freon have no odor, but your unit only holds a few ounces. Any leak would result in ...
payne heat pumps2/2/2010
  Q: ive been troubleshooting this payne heat pump for a couple days it has been icing up like an iceberg ...
  A: Jen, No, that is the last place for a restriction. Either the defrost sensor or the defrost board ...
Fuse Blows in Air Handler2/2/2010
  Q: John, this is a followup to yesterdays question. The fuse blows on heat. I removed the white wire ...
  A: This is at the board.And the board is hot or it would not blow the fuse, so, breaker off in between ...
Fuse Blows in Air Handler2/1/2010
  Q: John, this is a followup to yesterdays question. The fuse blows on heat. I removed the white wire ...
  A: Don, When you said furnace and A/C didn't know it was a heat pump. If you have a volt meter ( or ...
Air source heat pumps2/1/2010
  Q: I have been hearing about "Air source heat pumps". can you please simplify to me how these operate; ...
  A: Jon, Air source heat pumps are an air conditioner that can change directs of which way it moves ...
Fuse Blows in Air Handler2/1/2010
  Q: I am trying to help my son. Recently he awoke to a cold house and no power to the thermostat. ...
  A: Don, The first thing to do is to open the air handler ( where the fuse is ) and with the power ...
heater issue1/31/2010
  Q: i have a goodman model no: GMP100-3 REV B home furnace, my problem is the blower and everything ...
  A: Steven, It is probably the flame roll out switch on the sheet metal plate directly over the ...
burning smell and greatly reduced air flow leading to little cooling effect.1/31/2010
  Q: Serving a one bedroom apartment in a 4 unit building in South Beach: The compressor outside is a ...
  A: Yes it is the heart of the air handler. Depending on upflow or downflow it is on the opposite side ...
burning smell and greatly reduced air flow leading to little cooling effect.1/31/2010
  Q: Serving a one bedroom apartment in a 4 unit building in South Beach: The compressor outside is a ...
  A: Michael, The thing to do is to look at the blower motor. If it is old enough for a belt then, ...
Heat Pump outdoor unit icing1/30/2010
  Q: I have a Carrier Heat Pump. The outdoor unit has ice on the coils, fans running inside and out, unit ...
  A: Joe, There is a setting on the defrost board for 30,60 and 90 minutes. That is the amount of time ...
Heat Pump outdoor unit icing1/30/2010
  Q: I have a Carrier Heat Pump. The outdoor unit has ice on the coils, fans running inside and out, unit ...
  A: Joe, The first thing is the type of ice. If it is a pourous fluffy snow cone kinda ice it is ...
heat pumps1/30/2010
  Q: can i run my heat pump on the cool cycle in winter to aid in defrosting the outside coil
  A: Larry, No, if the system charge is correct and the board is set at 30 minutes, instead of 60 or ...
2-story house thermostat settings1/30/2010
  Q: We have a 2 story house that has 3 a/c units: upstairs, downstairs, master suite. We would like to ...
  A: Leslie, If the upstairs can be physically closed to the air from downstairs, you can run it down ...
carrier infinity freezes up drain clogging?1/30/2010
  Q: ANSWER: Mike, What you need to do when it gets that cold is to put a large bucket next to the ...
  A: Mike, On that furnace there is a small rectangle white water trap that the hoses drain into. It ...
carrier infinity freezes up drain clogging?1/29/2010
  Q:
  A: Mike, What you need to do when it gets that cold is to put a large bucket next to the furnace and ...
hvac1/28/2010
  Q: Ihave a carrier attic hvac about 20 yrs new just recently only works when it wants to, new ...
  A: Chris, It sounds like at the very least you need the run capacitor for that motor replaced, but be ...
heating1/27/2010
  Q: i followed the wiring instructions and still blowing cold air like when i had the old thermostat. ...
  A: Rpberto, Ok, you have a spark model, not the HSI glow coil. So, what you need to do is ...
3-tube furnace, only 2 tubes fire1/27/2010
  Q: I have a Frigidaire furnace (manual is here, even though it calls itself a Westinghouse? ...
  A: Nicolette, You will find that the left "clam shell" heat exchanger that the burner sticks into is ...
Heat pump seems to be working but no warm air?1/27/2010
  Q: My 2 ton air/air heat pump w/ elec. 2nd stage seems to be functioning, running endlessly. I only use ...
  A: Mark, If you are getting one degree temp rise across the air handler and in fact the large copper ...
heating1/26/2010
  Q: i followed the wiring instructions and still blowing cold air like when i had the old thermostat. ...
  A: Roberto, If the furnace blows cold air no matter what you try, then you probably have a main limit ...
Heat pump problems1/25/2010
  Q: I have a 2 ton, split system heat pump (Goodman) unit that is about 3 years old. My home is new ...
  A: Tammy, Wow, sounds like a big hassle for sure. The first thing I question is the size of the ...
Heat Pump Defrost Problem1/19/2010
  Q: We emailed Honeywell the manufacturer of our thermostat asking them if they thought their thermostat ...
  A: John, The thermostat has nothing to do with the defrost at all. There is a defrost board in the ...
Noisy Unit1/18/2010
  Q: Heating AC Unit is outside condo - all of which is on the same concrete. Has always been a noisy ...
  A: Karina, I am going to assume from your description that you have what is called a package unit? ...
goodman 45,000 btu furnace model 050-31/18/2010
  Q: turn the furnace off the blower still comes on
  A: David, More info is needed. Are you saying that when you turn the thermostat off the blower ...
5-year old Trane TXV Valve1/18/2010
  Q: Trane Unit was purchased on Nov 6, 2004 with a five year warranty. Purchase also included a service ...
  A: Susan, No that sounds fishy, especially with all the up sell he was trying to do. Did he write ...
A/C evaporator coils (fins)1/17/2010
  Q: I live in an apartment (older - 80's ?)in Florida - two strikes against me! BUT, I have lived in ...
  A: Frances, You live in a high humidity area and will always have moisture problems. If you contact ...
2 non-working heat pumps1/17/2010
  Q: Had too many follow ups to my earlier questions so I'm starting again. You may be on to something ...
  A: Roberta, The indoor coil, depends on if it is what is called a cased coil or not. What that means ...
Sorry So many questions1/16/2010
  Q: So i looked fo rthe high pressure switch and could not find it..there is a hi/lo marking on the ...
  A: garrett, Those are the access fittings for service gauges to hook up to and record what pressures ...
Air Handler1/16/2010
  Q: I have a Tempstar EBX-36 Air Handler..in the last few weeks when the unit shut off i would notice ...
  A: It is art of the outdoor unit, if you have one you will either be able to see it on the base, ...
Air Handler1/16/2010
  Q: I have a Tempstar EBX-36 Air Handler..in the last few weeks when the unit shut off i would notice ...
  A: Garrett, I have to assume you have a heat pump, as you did not say. Could be that the outdoor ...
retrofit Bryant 3ton R22 to R410a1/15/2010
  Q: I have a Bryant 3 ton R-22 electric central air unit and I wanted to know if I could retrofit this ...
  A: Bobby, you can replace the indoor coil and replace the entire outdoor unit. That is the only way to ...
heat pumps not heating1/15/2010
  Q: John, I have a similar problem as other posters: real cold temps in Fla, heat pumps not working. ...
  A: Roberta, This tells us that the first unit had just gone through a defrost and cleared the coil of ...
heatpump1/14/2010
  Q: Had no heat last Wed. and had to call a local HVAC. The guy came out and replaced the transformer. ...
  A: Jim, Yes, if you want to start guessing, that is one of the answers, along with incorrect ...
heat pumps not heating1/14/2010
  Q: John, I have a similar problem as other posters: real cold temps in Fla, heat pumps not working. ...
  A: Roberta, 20 degrees from the vent that blows warm air and the great big white grill in the hall ...
Goodman Furnance1/14/2010
  Q: My Goodman furnance (model GMT 070 53A) won't ignite. I've checked the power source with a voltage ...
  A: Does the blower come on when you call for it from the thermostat? If not you need to open the ...
heat pumps not heating1/14/2010
  Q: John, I have a similar problem as other posters: real cold temps in Fla, heat pumps not working. ...
  A: Roberta, Are you sure you have 2 heat pumps? If so, then that is the wrong thermostat for it. If ...
heatpump1/14/2010
  Q: Had no heat last Wed. and had to call a local HVAC. The guy came out and replaced the transformer. ...
  A: The test pins are on the defrost board. They are shorted with a screw driver. If you touch the ...
intertherm heat pump1/14/2010
  Q: I have an Intertherm heat pump probally about 15 years old. Lately it will be working fine but ...
  A: Yes you should go somewhere else. I have helped 1,300 people in 6 just the last 6 months. That is ...
heatpump1/14/2010
  Q: Had no heat last Wed. and had to call a local HVAC. The guy came out and replaced the transformer. ...
  A: Jim, Anybody checking the defrost sensor when they are plugging and unplugging them from the ...
gas furnace1/13/2010
  Q: I have an armstrong ulta 80 gas furnace.the blower keeps on running untill i turn the power off and ...
  A: bill, Sounds like you need to change your air filter and do a better job in the future, Bill. ...
HVAC1/13/2010
  Q: Have an Amana heat pump. Used to have a OPES / 4 star hot water system for AUX heat in place of the ...
  A: Greg, I assume that you installed the " electric heating coil ? " in the air stream before the ...
HVAC1/13/2010
  Q: I just replaced the mercury flame ignitor of an old rudd HVAC. I heard the solenoid click and the ...
  A: Jeff, Is this mercury device one that plugs onto 3 brass posts that stick up? If so, there is a ...
Gas Valve1/12/2010
  Q: Good evening. My name is Paul Keithley and I work for Ferguson Enterprises in Salisbury, MD. I have ...
  A: Paul, I am sorry, I have never seen that brand before. But any gas valve can be substituted for. ...
Heat Pump - Filter Replacement1/12/2010
  Q: NO ONE EVER told me to switch to E-heat when the temp outside drops below 25. I can now feel warm ...
  A: Lee, Your welcome for the knowledge. The electric heat is 4 times as expensive, but when the heat ...
HVAC Randomly Trips Circuit Breaker1/12/2010
  Q: Good Morning, I have an Armstrong HVAC unit with 2 circuit breakers. Whenever the unit is running ...
  A: Daniel, The fan as you call it is the blower. That is the one that is in your closet. The fan is ...
HVAC Randomly Trips Circuit Breaker1/12/2010
  Q: Good Morning, I have an Armstrong HVAC unit with 2 circuit breakers. Whenever the unit is running ...
  A: Daniel, Which breaker is tripping? Do you have a heat pump and the outdoor unit is tripping the ...
Trane TXV valve1/12/2010
  Q: My husband and I bought a home 2 years ago that had just had a brand new Trane heat pump installed ...
  A: JESSICA, First get the installation papers and see if that is correct on the warranty. It goes ...
A/C1/12/2010
  Q: Receiving proposals from different companies to replace my A/C. Only one said I need a condensate ...
  A: Shirley, Primary drain and condensate pump both remove the water created in the indoor coil when ...
AC Handler1/11/2010
  Q: I have a Tempstar EBX-36 Air Handler..in the last few weeks when the unit shut off i would notice ...
  A: Garrett, You need to remove the blower cover with the power shut off and reach in and spin the ...
Central Heat1/11/2010
  Q: My central heat quit working, then mysterious began working again. It was set to auto at ...
  A: Jenn, I'm good but no body is that good lol I have to at least know if it is a furnace / heat ...
Attic furnace, humidifier and attic condensation1/11/2010
  Q: John, I am a remodeling contractor in Colorado. As such, it is my job to know as much about every ...
  A: Carl, First let me applaud you for your endeavor into making the whole home work as a system. I ...
Ruud heat pump reset button1/11/2010
  Q: The red reset button on the outside unit is damaged, the rubber is torn off and there seems to be ...
  A: Liz, That is a high pressure shut off, that pops a black plastic button out that is supposed to be ...
Thermostat wiring1/10/2010
  Q: I need the thermostat wiring for the Pro-Stat Model 5010 Electronic Commercial Thermostat. The ...
  A: Glenn, sorry I thought I had that cleared up with my last answer. The extra wire you found and ...
Thermostat wiring1/10/2010
  Q: I need the thermostat wiring for the Pro-Stat Model 5010 Electronic Commercial Thermostat. The ...
  A: Glenn, So you did hook up the common? It needs that for power ( 24 volts ) to the thermostat, ...
Freedom 80 problem1/10/2010
  Q: A couple of days ago I noticed that my American Standard Freedom 80 was not working properly. The ...
  A: Garry, First FYI...when the system is failing to ignite properly those led pulses will change to ...
Thermostat wiring1/10/2010
  Q: I need the thermostat wiring for the Pro-Stat Model 5010 Electronic Commercial Thermostat. The ...
  A: Glenn, You asked the right person, I know that prostat inside and out. Rc & Rh must be jumpered ...
heil dc90 furnace1/10/2010
  Q: We ran out of propane, I hooked up a smaller tank to the residential line. The furnace came on and ...
  A: Brad, The reason I followed up is that I am just a normal regular guy like yourself that happens ...
Inducer blower runs, doesn't shut off1/10/2010
  Q: We have a Heil SP80 (about 12 years old), and sometimes the inducer motor starts up, but nothing ...
  A: Jeff, So, you have a honeywell "smart valve". The way to tell is if the Hot Surface Ignitor gets ...
Condensate line1/10/2010
  Q: I have two Lenox G21Q%26V series Gas Furnaces installed in a twostory house attic, in the mountains ...
  A: Olga, That is a common problem when the install company does not take into account that this can ...
heat pump heating failure1/10/2010
  Q: I have a Ruud heat pump unit originally purchased in 1998, in June 2006 I had the outdoor unit ...
  A: Tony, Right off the get go I see a BIG problem. The 2 numbers you gave me at the start of your ...
Furnace problem?1/10/2010
  Q: We have a very perplexing and frustrating problem that we think involves our furnace. We sure hope ...
  A: Cheryl, If you are correct in either odors from the area or your attic area that are actually ...
Insulation in furnace filter1/10/2010
  Q: I live in a brand new condo. I have a Lennox forced air gas furnace. The last two times I've ...
  A: Larry, The best way to handle this is crawl up to the duct work and see if there are tears or ...
Under heating1/9/2010
  Q: I live in Michigan and have just purchased a new house with 3500 sq feet. It is a colonial with two ...
  A: Lowe, Glad you wrote me. Do not even consider zoning, not just for the headaches of all the " ...
Heat Pump or Electric Furnace in Seattle?1/9/2010
  Q: We are renovating an old split level home in Seattle area(2100 sq feet upstairs and 1200 sq feet ...
  A: Heidi, On that type of question, it is prudent to have a few contractors come and give you bids ...
Black stains/dust1/8/2010
  Q: I have a small apartment with hot water heat (no vents). Every winter black stains (soot or dust ...
  A: Fred, That is called heat stratification. The hot air raises directly up the wall and deposits ...
pressure switch1/8/2010
  Q: I have a Rheem criterion II model RGPH-10EAMER serial #FD5D302F260101279. I need to replace the ...
  A: Tyler, As with all pressure switches, the have a "h2o rating and that is the difference , unless ...
heil dc90 furnace1/8/2010
  Q: We ran out of propane, I hooked up a smaller tank to the residential line. The furnace came on and ...
  A: Brad, I am just curious why when I answered your question and was correct the first time " since ...
heat pump operation1/8/2010
  Q: I have had an Lennox XP16-048 heat pump and CBX32MV-048-23 air handler installed about 18 months ...
  A: The compressor is cutting out like that to keep from blowing up. SHUT that outdoor unit off, ...
Carrier Furnace1/8/2010
  Q: I have a Carrier furnace Model # 58GSo75-88 Series 150 serial # 2588A1240 I believe its a 1986 My ...
  A: Paul, The blower is running because the furnace has failed ti light correctly 3 times in a row. ...
Nutone A/C-Heatpump - cold nights1/7/2010
  Q: I have a 1 yr old Nutone model B5BM-X49K 4 ton R410 13seer system. For the first time since I have ...
  A: Stephen, If he did not record the data for you, call him and have him give you the following data ...
Wiring related faults1/7/2010
  Q: I have a York Affinity 18 SEER heat pump 15kw heater w/two pc air handler w/variable speed blower ...
  A: Tom, We can rule out the thermostat........You state every winter it quits and goes to aux. So ...
heat pump operation1/7/2010
  Q: I have had an Lennox XP16-048 heat pump and CBX32MV-048-23 air handler installed about 18 months ...
  A: Wayne, WOW.....you have a major problem. First I am gonna guess that they installed the indoor ...
Airflow1/7/2010
  Q: Our house has HVAC system. It's a two-story townhouse, so on the first floor there is one return ...
  A: Timur, First things first. You have a heat I assume from your last statement. It is air flow ...
Heil Gas Furnace won't heat with filter in1/6/2010
  Q: I have a 2002 Gas furnace, I changed the filter in Sept. and the system ran fine. At Christmas we ...
  A: Jenni, In that case then the furnace is running, just showing signs of a future shut down with the ...
intertherm heat pump1/6/2010
  Q: I have an Intertherm heat pump probally about 15 years old. Lately it will be working fine but ...
  A: You are now on my never help again list. This is a frees service and the questions that were in ...
Poor Heating1/6/2010
  Q: I moved into our current home in 2005. Ever since then we have had poor heat. By that I mean that it ...
  A: fuck you asshole your rating will be deleted and you will be blocked
intertherm heat pump1/6/2010
  Q: I have an Intertherm heat pump probally about 15 years old. Lately it will be working fine but ...
  A: Dan, First always make sure you have a clean filter. Next is the outdoor unit iced up? After it ...
Heil Gas Furnace won't heat with filter in1/6/2010
  Q: I have a 2002 Gas furnace, I changed the filter in Sept. and the system ran fine. At Christmas we ...
  A: Jenni, The clicking noise is the spark for the pilot to light. If it is clicking that much then ...
Problem With Tempstar Heat pump1/6/2010
  Q: I have a 13 year old Temp star heatpump.I live in Ky.We are having 20 and below temps right now.My ...
  A: Kathy, I am happy to help someone who wants to know about there HVAC equipment . Here is an over ...
Problem With Tempstar Heat pump1/6/2010
  Q: I have a 13 year old Temp star heatpump.I live in Ky.We are having 20 and below temps right now.My ...
  A: Kathy, I need a small amount of facts from you. When the thermostat calls for heat, What happens? ...
american standard furnace fan1/6/2010
  Q: My American Standard Freedom 80 single stage furnace fan runs constantly. The furnace maintains ...
  A: Steve, The answer to your problem starts from letting your air filters work over time remain and get ...
Trane XR12 (heat pump)1/5/2010
  Q: Grayson I hope you can help! I have a Trane XR12 w/heat pump(I'm pretty sure HP) new build 2002. I ...
  A: Bobby, You can probably save the one you have by these methods. You have to understand how ...
TRANE XL80 won't stay lit1/5/2010
  Q: We have a Trane XL80 furnace (Model:TUD100R948A1) with a mercury Trane thermostat ...
  A: Matthew, The material the sensor is made of, degrades due to heat obviously, but looses its ...
Watchguard lights1/5/2010
  Q: I have an older Honeywell VR8200. It is not running properly. Here is what is happening: 1. ...
  A: Laura, Then you probably cannot see the heat exchanger or blower motor, which with that info I ...
Poor Heating1/5/2010
  Q: I moved into our current home in 2005. Ever since then we have had poor heat. By that I mean that it ...
  A: That honeywell number does not google to a product? But from the letters on the stat it is a heat ...
Intertherm heat pump costs to operate1/5/2010
  Q: We have a new Intertherm single package system installed outside a 14x76 mobile home. We are in ...
  A: Dallas, Although you appear to be having a cold winter for your climate, the strips should not be ...
1985-1986 clare brothers gas furnace1/5/2010
  Q: I have an older gas furnace that just isn't' cutting it anymore. I was wondering if it would be ...
  A: Walter, That furnace is going to be in the 70 to 75% range. If you look it might have input btu's ...
Watchguard lights1/5/2010
  Q: I have an older Honeywell VR8200. It is not running properly. Here is what is happening: 1. ...
  A: Laura, It is not your thermostat. The control board for your furnace is failing, most likely a ...
Trane XR12 (heat pump)1/5/2010
  Q: Grayson I hope you can help! I have a Trane XR12 w/heat pump(I'm pretty sure HP) new build 2002. I ...
  A: Bobby, This is another expert, John here. Trane is the only manufacture company to build its own ...
Furnace blower stopping, residential1/4/2010
  Q: This is my first allexperts question, so forgive me if I don't understand the protocol. The blower ...
  A: Paul, Had you called a tech the first failure the motor might be ok, but with all the things you ...
furnace1/3/2010
  Q: my fan comes on but the unit won,t light could it be ignitor?
  A: If your talking about the inducer motor and you have a hot surface ignitor , yes. Then after a few ...
Lennox Heat Pump HP26-018-7P1/2/2010
  Q: We own a duplex with each unit using the above heat pump. Our renter called this morning and their ...
  A: Stacie, Are you sure there were no fuses in the handle he removed? or behind a shield? If he ...
Lennox Heat Pump HP26-018-7P1/2/2010
  Q: We own a duplex with each unit using the above heat pump. Our renter called this morning and their ...
  A: Stacie, The first thing to check is the electrical box on the outside next to the pump, there ...
R 22 boiling at -40?? per John t Borgman yes!??1/2/2010
  Q: john t borgman wrote at 2009-12-08 14:13:53 this "expert" is mistaken as the refrigerant used in ...
  A: I was not going to respond to bashing , but for the sake of any techs I help that might read this. ...
Heil Heat Pump1/2/2010
  Q: John, the temp. where I am is going to be in the teens at night and only in the 20's for highs for ...
  A: Ron, You are better off going to emergency heat, as at that temperature it will never reach your ...
transfer heat from wood stove to baseboard hot water heat system1/2/2010
  Q: I have an interesting project on deck that needs expert advice. My house is heated with a baseboard ...
  A: Michelle, Since you are one of the few that actually read my bio....lol Anyway, in theory yes it ...
Heil heat pump1/2/2010
  Q: I recently moved into a condo in Pennsylvania that has a heat pump -- my first h.p. experience. ...
  A: Sandy, The contactor is probably a good idea, if your equipment is over 5 years old and never ...
error code1/1/2010
  Q: I have a Am/Std GUA080DIN furnace since 1994. (first problem) It short cycles like the flame sensor ...
  A: Earl, When you look at the burners, you will see the pipe from the gas valve curving down to the ...
HVAC Smells1/1/2010
  Q: My wife has noticed that our house has started "smelling" like urine or sewer when the furnace is ...
  A: G.W, Because you have a very old furnace, you need a tech out with a co2 meter, co2 can kill you ...
Carrier Central Unit problem1/1/2010
  Q: I have a 1988 Carrier central unit with a 100,000 BTU gas furnace. Model: 58GP100 – CA ...
  A: Do you realize that 1/4 of the heat that old furnace is putting out goes right out the flue to the ...
Gas furnace on short cycle1/1/2010
  Q: We moved into our Townhouse in June, and until December everything was good. But, with the cold ...
  A: Joe, I agree with you. But it will take some trouble shooting with a volt/ohm meter to find such ...
HVAC - heater problem.1/1/2010
  Q: I have Carrier model 48GS-024060301. A few days ago, the heater stopped working. A contractor came ...
  A: Huy, Sounds like the flame sensor. The burners light, usually on the right and spread to the ...
Heil heat pump12/31/2009
  Q: I recently moved into a condo in Pennsylvania that has a heat pump -- my first h.p. experience. ...
  A: Sandy, If you are in the 30's or less your outdoor unit will frost and should frost as long as it ...
Tappan Furnace Noise12/31/2009
  Q: I have an old Tappan furnace (not sure model no.). One of the four brackets that hold the blower ...
  A: Randy, If that is a " belly band " mount, they sell universal kits that you can use to replace the ...
Bryant Heating unit not functioning12/31/2009
  Q: I have a Bryant 355MAV gas furnace that is not working properly. For some reason whenever I turn the ...
  A: Virginia, You have a high efficiency model which means sealed combustion. There is a small round ...
Trane Heat Pump12/31/2009
  Q: My question deals with the outside unit. I have a Trane heat pump that is about 8 years old. I ...
  A: Gabe, An amp draw must be taken, should have been taken by the pro, it was part of his job. On ...
Induced draft motor will not fully start12/30/2009
  Q: I have two Goodman GMP series furnaces (about 1995 models)installed at the same time in 1996 and ...
  A: Robert, You have line voltage coming to the furnace in a small metal box. Inside the furnace ...
heat pump12/30/2009
  Q: i have a Ducane heat pump and a honeywell T-stat. thermostat is new and the heat pump is only one ...
  A: Dustin, The best thing to do it put the thermostat on emergency heat and run your back up furnace ...
rheem imperial 80 burner not lighting12/29/2009
  Q: above unit calls for heat, pilot comes on igniter clicks several times,but no gas supply other than ...
  A: Wally, After the pilot lights there is a metal rod that sits in the flame " flame sensor " that ...
Tappan Heater12/29/2009
  Q: I have a Tappan heater in my house that is not working properly. When i turn the heat on it only ...
  A: Jason, Does the fan stay on even if you do not call for heat? If so it could be your main limit ...
gmph075-4 furnace that turns on and then turns off...12/29/2009
  Q: I have a goodman gmph075-4 furnace that i am having trouble with. It turns on and after a few ...
  A: Shakar, There is a rubber hose that connects that to the inducer motor. Remove the hose from the ...
Nordyne Furnace12/29/2009
  Q: I have a Nordyne gas furnace Mo# G2RL-075A14. I have had 2 different repairmen here and still no ...
  A: Harold, I would check your water drain, sounds like it is backing up at the end of a run cycle, ...
HEAT PUMP NOISE12/28/2009
  Q: .. My heat pump ... a TRANE unit installed in 1992 ... has started making a noise that sounds like ...
  A: Mary, When he returns ask him to do his job and take those readings, it only takes a few minutes ...
HEAT PUMP NOISE12/28/2009
  Q: .. My heat pump ... a TRANE unit installed in 1992 ... has started making a noise that sounds like ...
  A: Mary, He should not charge you for a return visit. There is nothing in there to be oiled or ...
Ducane heat pump12/27/2009
  Q: Last year I purchased a ducane heating & air conditioning unit installed in my attic..due to no ...
  A: Pamela, Not sure what the attic info is for, but as far as your heat pump, it will frost up doing ...
Gas furnace on short cycle12/27/2009
  Q: We moved into our Townhouse in June, and until December everything was good. But, with the cold ...
  A: Joe, It is purely a function of the thermostat, as long as the home is staying comfortable. It ...
heat wont turn off12/26/2009
  Q: I have a central air system in my house. The system was replaced a few years ago so its fairly new. ...
  A: Stephanie, Turn the switch off to the furnace and pull off the doors. You will see where the ...
Pilot Won't Stay Lit12/26/2009
  Q: We have a gas furnace for a mobile home. The pilot will not stay lit. I've had the thermocouple ...
  A: Sean, It sounds like the pilot flame is not strong enough. It should cover the end of the ...
Vexar by York Int12/26/2009
  Q: I have manaufacted house and the heating unit is a Vexar by York Int. When I turn on the thermostat ...
  A: Jonathan, When you start the furnace there is a small motor just above the burners that starts to ...
Excess condensation / Gas furnace12/26/2009
  Q: I have a 15 year old Ruud 90 gas furnace and have noticed considerable amounts of condensation ...
  A: Tom, I am in Portland are you? If so you can give me your number and I will call, much easier. ...
Gas furnace on short cycle12/26/2009
  Q: We moved into our Townhouse in June, and until December everything was good. But, with the cold ...
  A: Joe, So is the furnace keeping the house warm? Or would you like a bigger temperature swing, ie, ...
new furnace12/26/2009
  Q: az--5200' elevation with some cold weather and snow and several winter nights between 10 and 20 ...
  A: George, I would jump all over that deal, after rebates and tax credits you will do all right. The ...
rollout switch tripping12/26/2009
  Q: I've got a 6-year-old Bryan 2-stage 90%(?) furnace (sorry I don't have the exact model # handy). ...
  A: Steve, First if it was a flue blockage your system would be shutting down on the pressure switch, ...
Residential HVAC: heating unit intermittently sticks, overheating home12/25/2009
  Q: Borgman- If my question is not appropriate in any way please disregard. - My Aquatherm air ...
  A: The diagram shows the pump relay gives power to the pump and the fan for heating. So a check to see ...
electric igniter12/24/2009
  Q: My self igniting gas furnace will not ignite. It clicks when the thermostat is activated.The ...
  A: Tom, So, what you hear is the spark ignitor that is supposed to light the pilot, does the pilot ...
A/C noise12/24/2009
  Q: I live on the third floor(top floor) of condo building. When A/C is running(all electric, condensor ...
  A: Kent, Probably was a poor installation. Generally every 10 feet there is supposed to be an oil ...
heatpump outside unit12/24/2009
  Q: what would cause an outside unit to freeze up in the winter. I changed the furnace filter but that ...
  A: Cheryl, It is normal for a heat pump to frost up in the winter, but it should be a fluffy frost, ...
Bryant Code 2412/24/2009
  Q: I have a Bryant 373LAV Gas Furnace. Every few days I get an LED Code 24, 24V problem. The fuse ...
  A: Steve, Not knowing the age and history I can offer only this.....First check the voltage to the ...
furnance troubleshooting12/23/2009
  Q: The heat in my furnace went completely out so I called my uncle to fix it. He "fixed" it in five ...
  A: Lynnsie, Without knowing more I cannot help you. What did they plug in? Is this gas, electric, ...
Residential HVAC: heating unit intermittently sticks, overheating home12/23/2009
  Q: Borgman- If my question is not appropriate in any way please disregard. - My Aquatherm air ...
  A: Brian, We don't have many of those in this area, but, it would seem that it in fact it is not the ...
Induced draft motor will not fully start12/23/2009
  Q: I have two Goodman GMP series furnaces (about 1995 models)installed at the same time in 1996 and ...
  A: Robert, That does sound strange. The first thing I would check is supply voltage to the board. ...
Furnace...Lennox Ultra X Gas... Sputtering Start12/22/2009
  Q: we have a 10 year old furnace that has worked great in every respect except now it does this ...
  A: Seidean, I am glad that it is working for you now. I question the need for a new board. A ...
Miller ac with heater kit keeps trippin the breaker12/22/2009
  Q: Everytime I turn on the heater it keeps tripping the breaker. Here is the setup: Miller 3.5 ton ...
  A: Chris, OK, then you are going to need a tech to come out and take a look. If you have not had a ...
Miller ac with heater kit keeps trippin the breaker12/22/2009
  Q: Everytime I turn on the heater it keeps tripping the breaker. Here is the setup: Miller 3.5 ton ...
  A: Chris, Which breaker is tripping? How old? If the numbers you supplied are correct then when all ...
Ultra V only does the 7 sec ignition trial12/21/2009
  Q: I have an Ultra v Teck 80 furnace. I've watched it run and the 15 second purge works correctly but ...
  A: John, That is a honeywell smart valve and before you change it out you need to be sure, they are ...
Heat pump w/Aux heat no fan outside running12/21/2009
  Q: I have a Rudd unit outside and it's over 10yrs old. Just had a circuit board replaced in it. I ...
  A: Thomas, Something is not wired correctly. The Y or yellow wire should turn on the outdoor unit on ...
Musty odor12/21/2009
  Q: My nutone heat pump split system is blowing a very musty odor from the vents when it first kicks on ...
  A: Berdine, Generally something that new cannot have anything internal to get "musty" in that amount ...
Furnace...Lennox Ultra X Gas... Sputtering Start12/21/2009
  Q: we have a 10 year old furnace that has worked great in every respect except now it does this ...
  A: Seidean, Yes it could be, but thermostats are usually not the problem ( rare, but a possibility ) ...
Furnace Not Getting Heating12/20/2009
  Q: Older electric furnace that runs, blows strong, is quiet, but does not heat up. Older dual ...
  A: Gwen, It could be one of 3 things and unfortunately you need a multi meter to find out. It could ...
Ceiling mounted Carrier Air handler12/20/2009
  Q: I have a leak in my ceiling-mounted ducted air handler (Carrier model 40DQ, mid '80s) in our ...
  A: Sam, Because of the installation problems, it would be better to fix what you have. If it is a ...
Heat intermittent12/7/2009
  Q: Ruud Achiever 90plus furnace, Honeywell RTH6300B Thermostat. Moved to new house 2 months ago and ...
  A: Parker, Turning the power off then on resets the board. Next time it fails look at the led's on ...
Lennon G23 Series Furnace12/6/2009
  Q: Our furnace (Lennox G23 Series Gas Furnace) won't stay on today. It says low flame on the back. It ...
  A: Denise, It is one of 2 things, either the flame is low, due to clogged burners, or the flame ...
White dust like Joan(10/23/09)12/6/2009
  Q: We are experiencing the same problem with our new(Jan 09)HEIL AC w/ gas furnace system as Joan ...
  A: Dale, Unless you have an E.A.C cleaner, that is probably the case, or it is pulling in somewhere ...
Furnance12/4/2009
  Q: I have a Arcoaire RJII furnace. The exhaust fan runs contiuously and the furnance will not kick on ...
  A: Dan, there is a hose going from the exhaust fan housing to a pressure switch. remove the hose ...
Rheem indoor furnace12/4/2009
  Q: John I have an Rheum furnace less than ten years old. The furnace has a IFC board and all the green ...
  A: Sorry I thought you said board, my bad. The way you find out is a manometer on the outlet to the ...
Rheem indoor furnace12/4/2009
  Q: John I have an Rheum furnace less than ten years old. The furnace has a IFC board and all the green ...
  A: Donald, On the left side there is a sheet metal cover with 2 screws that covers the board that you ...
Found solution, but wondering if there is a bigger problem.12/3/2009
  Q: I had an Armstrong Air V (heat/air) with led blinking 3 times. One of the other answers said "would ...
  A: George, Yes, that is a condensing gas furnace, which means it condenses water in the flue pipe ...
replacing h/a package unit12/3/2009
  Q: i have to replace a 10 year old ruud outside package unit. the heat exchanger has rusted. i have ...
  A: Jackie, American standard is Trane and the best of the choices, for that matter some of the best ...
gas heater not working12/2/2009
  Q: I bought my first house a couple months ago and am now having trouble with the heater. It is an ...
  A: Drew, If the gas valve is getting 24 volts when the ignitor is at it's hottest, then it is the ...
AC condensation12/1/2009
  Q: I have gas central ac which is separate from my forced hot water heat. I live in the northeast (MA). ...
  A: Wayne, I would venture to say that the metal "boot" that the duct attaches to is uninsulated and ...
size of furnace11/30/2009
  Q: recently had a energy efficient furnace installed (carrier infinity 58mvc 100-24) My home is a 2 ...
  A: Deryl, Far as I know you will have to pay full price for manual J. If the new unit is the same ...
Armstrong Ultra III furnace11/30/2009
  Q: I have an Armstrong Ultra III furnace. The unit turns on an lights the burns but then shuts off the ...
  A: Ray, Gonna need more info."turns on a light?" is this on the board? And do you mean the burner ...
Ultra V tech 91 gas furnace11/29/2009
  Q: I have an Ultra V Tech 91 gas furnace. The clear hose that appears to go into the front of the ...
  A: Steve, You have a high efficiency condensing gas furnace. This means that water condenses in the ...
Temperature Differential11/28/2009
  Q: A technician tells me that my AC is not cooling properly at 25.7 degrees "temperature differential." ...
  A: John, It depends on a lot of factors, but if you have duct work that is correct in static ...
Propane xe90 won't ignite11/27/2009
  Q: My propane furnace won't light. The vent blower works, the igniter heats up, the gas starts to enter ...
  A: Shawn, Just happened to be on line and saw your question come in. I am assuming you are referring ...
Vented or Ventless Fireplace Logs11/26/2009
  Q: We have a electric furnace to heat our home. We also have a fireplace with a metal tube chimney. ...
  A: Sandy, Stay away from any vent less gas products. Not safe. Read the instructions carefully and ...
Rheem Heater11/26/2009
  Q: I have a Rheem model RGDD-06NC-ER furnace. About a year ago I replaced the ignition module (S8910U) ...
  A: Brent, A couple things there Brent. The first thing you do is turn the blower on at the ...
hvac11/26/2009
  Q: I recently purchased a older story and a half home with basement. The HVAC equipment is in the ...
  A: Landon, It is impossible to see without being there! Call a couple local contractors ( hvac ) and ...
Feasability of heat pump11/25/2009
  Q: I have a two story house 30W x 40L with a full basement. Attached to the house I have a second ...
  A: Robert, Over the years I have " dreamed " about even putting the coil IN the duct work. But ...
Forced Air Furnace11/25/2009
  Q: Subject: Forced Air furnaceHi, I was told my forced air furnace needed a new electric starter. ...
  A: Susan, I dont know what you mean by a starter, never heard of one on a furnace. You could have a ...
American Standard Freedom 8011/24/2009
  Q: Just had my gas service turned on, but my furnace refuses to start. I have a White-Rogers ...
  A: Ray, Are you talking about the blower or the inducer fan motor? On the white rodgers control ...
ruud gas heater cuts out11/24/2009
  Q: I have a Ruud Silhouette II model UGPH-15EARJR , about 7 yrs old...running on propane , ...
  A: dave, It could be those things or others. Does the blower come on? does it stay on? It is most ...
HVAC duct noise11/24/2009
  Q: My home is just 5 years old this past July. It is a builder spec home we bought new in the summer ...
  A: Bob, First let me help by saying that the same duct work is used for heating, cooling and ...
Heater doesn't run with fan on auto11/23/2009
  Q: Quick question - We replaced the digital thermostat in the house already in an attempt to fix this ...
  A: Laura, If it is an older furnace it is the fan limit switch that is bad, if it is a newer furnace ...
Aluminum Tape for pipe11/23/2009
  Q: A piece of what looks like aluminum tape came off of a pipe and someone gave me some aluminum tape ...
  A: Kc,, I do not do private answers, I volunteer my time for all residential help. That tape not ...
american standard freedom 90 propane furnace11/22/2009
  Q: our furnace is 9 years old. It is american standard freedom 70 propane with one zone. Recently, ...
  A: Sherry, Yes had you said that during the first e-mail we could have had this fixed....lol The ...
changing the heat strip11/22/2009
  Q: I have a Payne furnace that i purchased to heat an area of about 1500 square feet. My electric bill ...
  A: Ronald, Ok, I really cannot advise you any further. If you cannot fill in the blanks from my ...
Placement of registers11/22/2009
  Q: My furnace is in the attic (small house - about 1000 sq feet). The heat supply registers are close ...
  A: Ann, A central return is the " norm ", however for this to work efficiently, the rooms that have ...
changing the heat strip11/22/2009
  Q: I have a Payne furnace that i purchased to heat an area of about 1500 square feet. My electric bill ...
  A: Ronald, The sequencer is the relay that energizes the strips. If you have 24 volts at the ...
Heating11/22/2009
  Q: I have a York split system unit. It was installed originally with the house in 1992. It has an ...
  A: When you have an intermittent problem like that, the best thing to do is leave it the failed state, ...
Placement of registers11/21/2009
  Q: My furnace is in the attic (small house - about 1000 sq feet). The heat supply registers are close ...
  A: Ann, flex duct is fine to use. It comes already insulated, and is easy to handle. Return(s) are ...
Rheem 1x200011/21/2009
  Q: John, I would like to clean the filter on my furnace but can't find it. I looked in the manual but ...
  A: John, Depending on up-flow or down-flow and where the furnace is located is where you look. If ...
Heating11/21/2009
  Q: I have a York split system unit. It was installed originally with the house in 1992. It has an ...
  A: Brantley, Your description does not make sense. For "YEARS" you have not had heat, but the ...
Heating/AC unit11/21/2009
  Q: I have a roof top, residential heating unit, that is dual, both heating and AC. The problem I have ...
  A: Stephanie, It will not cost anything for an Heating/cooling company to come out and give you a bid ...
Gas furnace Blower noise11/20/2009
  Q: The blower started to make a whining noise. The blower motor appears to be turning normally. I saw ...
  A: Rich, It sounds to me like you are describing the draft inducer motor not the blower. What is the ...
heat pump, little heat,11/19/2009
  Q: I'm new to this, and I have a little schooling on this, so here is the problem. I have a heat pump ...
  A: Gary, Well now.......could be they wired the lock out for the strips backwards and they won't work ...
Wishing the death of 18 yr old heat pump11/19/2009
  Q: I just bought a home with a 18 yr old Carrier 2.5 ton heat pump. The furnace was replaced last year. ...
  A: Angela, Wow, thank god your poor husband got out from that marriage. And FYI your rating will be ...
Gas central heat unit11/19/2009
  Q: I am replacing the thermocouple that keeps the pilot light lit and I notice that there is a lot of ...
  A: Bill, The air that is mixed with the gas has impurity in it. Depending on the area and the area ...
Little air flow from duct work11/18/2009
  Q: My husband and I are building our own home. We purchased a outdoor wood hot air furnace WADENA. Our ...
  A: Amy, Going to need more info to answer your question.An 8" duct cannot move even half that amount ...
heat pump, little heat,11/18/2009
  Q: I'm new to this, and I have a little schooling on this, so here is the problem. I have a heat pump ...
  A: Gary, The thermostat should have first and second stage heat, second stage is usually wired ...
amana 9011/18/2009
  Q: I have a amana 90 furnace that will light sometime and sometimes it won't light i think it might be ...
  A: Aki, I need a bit more info....Is the lighting device a Hot Surface Ignitor, spark with a pilot, ...
Thermostat11/18/2009
  Q: John, I have recently purchased a new house. It's over 1 1/2 years old..no ones has lived in it. We ...
  A: Bill, Here is the owners manual for that thermostat. ...
heat pump11/17/2009
  Q: I hve a carrier unit modle # fb4anf030. also have a programable thermostat. went to adjust heat ...
  A: Todd, I am not sure what you are asking. Where do you hear a hum? And you are sure it is a ...
Intertherm heatstrip air handler(mod home)11/17/2009
  Q: My neighbor has a intertherm air handler that is heating, but will not turn the fan on in auto on ...
  A: John, Ih the cooling mode the blower is turned on by a small black relay that is in the upper left ...
Heat Pump Pressures11/15/2009
  Q: How do you determine if the compressor valves are bad or the reversing valve is not shifting 100% ...
  A: Bill,\ Sorry I mistook your knowledge level. It will depend on the degree of leakage. In other ...
Wishing the death of 18 yr old heat pump11/15/2009
  Q: I just bought a home with a 18 yr old Carrier 2.5 ton heat pump. The furnace was replaced last year. ...
  A: Angela, I do not answer private questions that ask to break the law!!!!!!!!!!!!!!!!!! But I will ...
Heat Pump Pressures11/15/2009
  Q: How do you determine if the compressor valves are bad or the reversing valve is not shifting 100% ...
  A: Bill, Simple answer bill. You check the amp draw of the compressor while it is running. If the ...
american standard freedom 70 propane furnace11/14/2009
  Q: our furnace is 9 years old. It is american standard freedom 70 propane with one zone. Recently, ...
  A: Sherry, It is not the control board. There are several reasons for that "fault" code, but most ...
freezers11/14/2009
  Q: Can a freezer be transported on it's side and then be set upright and work without problems, or are ...
  A: Ron, Although it is highly recommended not to do that, if you do then you must have it upright and ...
Vibration from Heat pump11/13/2009
  Q: We have an outside AC unit/heat pump. The unit kicked on all last winter and all summer providing ...
  A: Micah, The first thing would be to look at the fan blade on the top while it is running and see if ...
PROGRAMMABLE TSTAT11/12/2009
  Q: I recently installed a rite-temp model 6036 7 day programmable tstat to update my heat pump. i ...
  A: Kurt, That thermostat will work fine on your heat pump, it just has to get wired correctly. So, ...
payne furnace11/11/2009
  Q: igniter lights, furnace fires and stays lit, blower comes on, spark ignition continues to spark when ...
  A: Barry, You want to be careful not to break the ceramic, but the rod needs to be in a position to ...
Rheem Criterion II Noise11/11/2009
  Q: This furnace is 8 years old & installed in a 2000 sq ft 4 bdrm house in SoCal. It makes a whining ...
  A: Don, In that case it might be, I got the impression from the way you wrote the question this has ...
Rheem Criterion II Noise11/10/2009
  Q: This furnace is 8 years old & installed in a 2000 sq ft 4 bdrm house in SoCal. It makes a whining ...
  A: Don, The sound is coming from the louvers on your return air grill. Take some needle nose pliers ...
AC Unit.... what to do???11/10/2009
  Q: I'm very confused about a problem with my outside AC Unit and would be really grateful to hear your ...
  A: Juliet, You should replace it now. 2 reasons....if it dies then the compressor will run EXTREMELY ...
payne furnace11/10/2009
  Q: igniter lights, furnace fires and stays lit, blower comes on, spark ignition continues to spark when ...
  A: Barry, sorry I wasn't even close,I guess I am getting old,.lol, yes that is the one. Built in that ...
payne furnace11/10/2009
  Q: igniter lights, furnace fires and stays lit, blower comes on, spark ignition continues to spark when ...
  A: Barry, No, you have a three wire pilot part # Lh360 that needs to be replaced. If you look the ...
Squeal blower motor11/9/2009
  Q: my AC air handler (no heat) is horizontally installed in a hot and tight fitting attic -- a UPG 4 ...
  A: Patrick, You say direct drive , but it sounds like you have a belt drive is that correct? If so ...
Rewiring a Coleman Elec. Furnance11/9/2009
  Q: I have a Coleman Electric Furnace model 3500a, it has the controls on the furnace. I want to ...
  A: Doyle, you must have some kind of thermostat, besides the manual fan switch if you have heating ...
Electric Furnace with strange cycle11/9/2009
  Q: I have a airforce central heat/air conditioning. The Furnace is a YORK model N4AHD14A06A (located ...
  A: Thong, It sounds like you probably have a mechanical fan/limit switch that is in need of ...
humidity in house11/9/2009
  Q: I recently purchased a house and am noticing a problem with very humid air in the house. The windows ...
  A: Nick, No, windows , being a better grade I assume will just make it worse. What form of heat do ...
Compressor matching air handler11/8/2009
  Q: John, You're so helpful I need to ask you another question. I have a 3 Ton Luxaire Compressor and ...
  A: Hey Scott, What that means is that you have an air handler capable of 1,600 cfm or air across the ...
Central heating11/7/2009
  Q: my central heating system is 3 months old and 2 months ago i have changed the thermostat to a ...
  A: Niles, When you open the door you stop power to the circuit board and it clears any faults, or ...
air conditioner11/6/2009
  Q: I currently have a 4 ton 14 seer Rheem bought in 1998. Then handler and the condensing unit are ...
  A: Lisa, Sounds like you have an air flow problem or the unit is not charged correctly. That TXV ...
Air Handler11/4/2009
  Q: I have a UPG Model MA Modular non-variable speed air handler. It is hooked up with ac and forced ...
  A: Scott, You did not tell me that it was that way for a year!!! The fan runs when there is power to ...
Trane XB1000 Problem11/3/2009
  Q: This pas Saturday my AC kicked on and the Trane XB1000 that sits outside my house start making this ...
  A: Eric, First go out and spin the fan blade with nothing on, if it does not spin freely and go for a ...
Trane XL 90 not igniting11/3/2009
  Q: My Trane XL 90 is not igniting. The AC/fan works fine. When I turn the heat up on the thermostat, ...
  A: Joe, If the blower motor is bad ( check by switching tstat fan switch to on) then the furnace ...
Air Handler11/3/2009
  Q: I have a UPG Model MA Modular non-variable speed air handler. It is hooked up with ac and forced ...
  A: Scott, The fan gets it's power through the G wire and the tstat has a fan ON/Auto position. If ...
Little Giant Pump Company VCMA-20 Series11/3/2009
  Q: I saw you gave some great advice, so I had a question for you. I have a Little Giant Pump Company ...
  A: Jeff, I have actually had that happen. The micro switch reverses it's operation. You need a new ...
Wall Heater11/2/2009
  Q: I have a wall heater from williams company, its a old heater as the cold weather starts i turn on ...
  A: Sam, You need to change the thermocouple, the rod the pilot light hits and gets hot. It has a ...
Heat Pump10/31/2009
  Q: I have a Ducane 4 ton heat pump HP12B48 S/N 4468700322, Compressor ZR47K3FPV135 (scroll). The ...
  A: David, You have either a refrigerant or an air flow restriction. It would not be the indoor txv ...
American Standard vs. Carrier10/31/2009
  Q: I am going to be replacing our twenty year old gas furnace with a new 95%unit, so that we can ...
  A: Bob, American standard is Trane. And from a tech's point of view, Trane is far superior to the ...
Replacing Air handler10/30/2009
  Q: My air handler is rusty and the system leaked...and was repaired a month ago. The system is 10 ...
  A: Walt, What "system" was repaired? I can tell you this. For you to loose a compressor in 8 years ...
Day & night 373lav10/29/2009
  Q: I have a day & night 373lav Horizontal that will not open the gas valve. They provide a pretty handy ...
  A: Don, There are tons of boards out there, Don, but I believe that one gets the gas valve voltage ...
programmable thermostat10/29/2009
  Q: I'm trying to install a Honeywell Programmable thermostat to replace a Comfortmaker. I've got the ...
  A: David, I have not seen one with a #4. But the R & Rc are 24 hot, the W is heat, The G is for the ...
goodmen ninty-two furnace10/28/2009
  Q: when i turn it on and go down and watch it . blower comes on glows up clicks then trys again it ...
  A: Mike, The path for the 24 volts to the gas valve goes through the pressure switch and then up into ...
Water damage?10/28/2009
  Q: I just resently had a tolet flood, and when it flooded a lot of water got into the heating vent next ...
  A: William, It has to be either metal or flex. If it is metal and there is a vent cut into it, you ...
Water damage?10/28/2009
  Q: I just resently had a tolet flood, and when it flooded a lot of water got into the heating vent next ...
  A: William, Will need a lot more info to even venture a guess. Is the water closet directly above ...
Sticking Fan10/27/2009
  Q: At times the fan on our a/c unit won't spin. When we push the fan even a little bit it starts back ...
  A: Kathy, The problem is the run capacitor. That is a PSC ( permanent split capacitor ) motor. The ...
Heating System10/26/2009
  Q: My daughter just bought a townhouse and moved in about 3 weeks ago. She has electric forced hot air ...
  A: Susan, she can turn the temp wherever she wants, I don't know what yahoo told her that. And if the ...
Gas furnace10/25/2009
  Q: Tried to start the gas furnace but it will not light. I have checked all the safety ...
  A: Roger, Depending on the furnace, you will need to look at the schematic....the safties and ...
Gas furnace10/24/2009
  Q: Tried to start the gas furnace but it will not light. I have checked all the safety ...
  A: Roger, So, you did not say....does the ignitor lite up? if so and you have checked the gas ...
Low cfm/velocity problem10/24/2009
  Q: Could having too much cold air return(16x32 cast iron floor grate over two floor joist cavities 8x15 ...
  A: Ryan, Having a bit of a problem with your descriptions. But you cannot have to much return air as ...
temperature set on thermostat not recognized10/23/2009
  Q: The tenant called me and said that after one of the big storms when the power went out, they came ...
  A: Laura, Thanks for the compliments, but I need more info than that. If it is a heat pump the ...
Calcium build-up on brand new HVAC?10/23/2009
  Q: Our new 3.5 ton HVAC system was installed January, 2009. We used the heater from January through ...
  A: Joan, OK, first let us address the load calculations. Who did them and by what method? If they ...
Calcium build-up on brand new HVAC?10/9/2009
  Q: Our new 3.5 ton HVAC system was installed January, 2009. We used the heater from January through ...
  A: Joan, At your furnace location is the indoor coil. Hopefully they used a cased coil, which has a ...
Calcium build-up on brand new HVAC?10/8/2009
  Q: Our new 3.5 ton HVAC system was installed January, 2009. We used the heater from January through ...
  A: Joan, That seems extreem yes. But, the water that is condensed on the coil that would leave the ...
furnace return air10/8/2009
  Q: I have a high efficiency furnace and it has the PVC inlet and exhaust directly vented to the ...
  A: John, That is called make up air. Homes are built so tight now that we must introduce fresh air ...
Heil furnace not providing heat/running properly10/7/2009
  Q: I have Heil condensing gas furnace, model NTG9075FGA3 (manufactured by International Comfort ...
  A: Jason, If you didn't remove all the rocks from the pvc flue the pressure switch will not make. ( ...
superheat/subcool10/6/2009
  Q: I have just entered the a/c trade and I am attending school. We have been going over the ...
  A: Kaleb, First there is no 30 inches only 29.96 and service gauges are way off. Remember that when ...
superheat/subcool10/6/2009
  Q: I have just entered the a/c trade and I am attending school. We have been going over the ...
  A: Kaleb, VERY GOOD....one of the only opposites in physics is heat as there is no opposite, just the ...
superheat/subcool10/6/2009
  Q: I have just entered the a/c trade and I am attending school. We have been going over the ...
  A: Kaleb, Very good question. I love to help students of our field. You are correct in your ...
HE Gas furnace10/5/2009
  Q: We moved into a house that has a high efficiency forced air, natural gas furnace installed. The ...
  A: James, Good job on the filter. Do yourself a favor and get the cheapest pleated filter made and ...
Heat Pump Not Dehumidifying10/5/2009
  Q: The following is a summary of questions remaining after 2 "best of phoenix" ac companies, with clean ...
  A: Lisa, sorry got the last one first. Secret??? Demand them you paid for the job. And it sounds ...
Heat Pump Not Dehumidifying10/4/2009
  Q: The following is a summary of questions remaining after 2 "best of phoenix" ac companies, with clean ...
  A: Lisa, A TXV is simply a valve that slides one way to restrict the flow and the other to open the ...
ice build up on outside unit10/4/2009
  Q: I have a goodman central air anda heat for house in florida. this morning i heard a strange noise on ...
  A: Pat, Your filter??? It is probably clogged solid, if so change it and turn on the fan. If air ...
Burner cuts out fan stays running10/4/2009
  Q: Ducane gas furnace with Smart Valve and HSI pilot/sensor...draft inducer fan comes on, ignitor will ...
  A: Tim, It is not supposed to keep the HSI lit. A volt meter needs to be used on the valve to see ...
what size and type10/3/2009
  Q: i bought a home in eastern ky. complete remodel. 2 story. 1577 sq. feet each floor. the front of ...
  A: Will, I can't help you with the power bill either....lol I am not familiar with ky weather. If ...
my heater is no working10/2/2009
  Q: I have a Philco heating and cooling product model G6RA 072C-12A. The AC is working fine but I can ...
  A: I am unfamiliar with the type of lighting system that furnace uses, but if it is less than 15 ...
FURNACE NOT STAYING ON10/2/2009
  Q: I HAVE A CARRIER FURNACE THAT WILL NOT STAY ON. I HAVE CHECKED AND CLEAN WITH SAND PAPER THE FLAME ...
  A: Here is a link to get an owners manual to help with the fix ...
RHEEM 80 Imperial10/1/2009
  Q: I have just purchased a house and the HVAC unit is a RHEEM 80 Imperial. It has worked well all ...
  A: George, It is possible the pilot is plugged, but the majority of the time, that is the way the ...
Smell from furnace10/1/2009
  Q: I turned my forced air gas furnace on for the first time this year, and there is a strange smell ...
  A: Erica, Generally the first time you fire off the furnace the heat exchanger is coated with dust and ...
Air conditioning question10/1/2009
  Q: I am a bally's (gym) instructor and also an amateur at home building. Being a san diego resident i ...
  A: Leah, You have a couple problems. First you have a mis matched system it should be a 2 ton coil. ...
Residential Heat Pump9/30/2009
  Q: We are older folks renovating an even older two story home in Maryland. The house in about 2500 ft2. ...
  A: Leo, Before you make that decision on the radiant heat you should check out these boilers, they ...
Thermostat and auto changeover9/30/2009
  Q: Have a functioning system in either heat or cool mode, but in auto mode it will only respond to the ...
  A: Steve, First of all if it is the thermostat don't get a hunter, get a honeywell, only a few ...
Thermostat and auto changeover9/29/2009
  Q: Have a functioning system in either heat or cool mode, but in auto mode it will only respond to the ...
  A: Steve, I would call the owner of that company and insist on them making it right with you. Have ...
Rudd Air Conditioner about 6-8 yrs old9/29/2009
  Q: My air conditioner will not turn on, if I push down on the contact points it runs, as soon as I let ...
  A: Geoff, It sounds like best case you blew a 3 or 5 amp fuse on the circuit board inside the blower ...
new furnace9/29/2009
  Q: I live in N/W Indiana and have a 32 year old 100,000 BTU natl. gas furnace made by Rheem that still ...
  A: Jurgen, If you look your old furnace was 100,000 btu input and probably 70, 000 or so " bonnet " ...
AC compressor9/29/2009
  Q: My outside unit is 17 years old and the compressor has shorted out. I have a home warranty and it ...
  A: Charles, It depends on your warranty coverage. I would be amazed if it covers all costs of a ...
Heat Pump in Midwest9/29/2009
  Q: I've heard a lot of negative things on heat pumps in the mid west. I live in Topeka, KS and am fully ...
  A: Travis, Whoever is bidding the equipment should supply you with a worksheet that comes up with a ...
outdoor central a/c unit9/28/2009
  Q: Hello there. Okay...I am renting a mobile home in Alabama. My landlady lives in Virginia, and ...
  A: Shannon, That radiator thing is called the evaporator coil and if you look at it when the pipe in ...
Trouble with new A/C9/28/2009
  Q: I got a new airconditioner about a month ago. Since then, it doesn't work the way my previous (22 ...
  A: Tim, If when you lost power, you went into a brown out, or low power before it dropped out it is ...
AC motor9/28/2009
  Q: We installed a new 5-ton A/C unit about six years ago. Over the weekend the capacitor blew and it ...
  A: David, A potential problem in the future?? What the heck does that mean? and that motor only ...
aircon compressor loading9/28/2009
  Q: Mike , i am involved in a green building information , education and supply operation on the island ...
  A: You are asking questions that would take a great deal of my engineering skills, much more than I am ...
Rudd Air Conditioner about 6-8 yrs old9/27/2009
  Q: My air conditioner will not turn on, if I push down on the contact points it runs, as soon as I let ...
  A: Geoff, I will assume that the wire was outside, that is usually where puppys like to chew them. ...
ac unit in condo9/26/2009
  Q: I have an intermittent cooling problem - Compressor is on roof and installed in 2001, along with ...
  A: Lylah, Tell your friend that it is a possibility that the condenser motor is going bad and that it ...
coil matching with heat pumps9/26/2009
  Q: I have a thermo pride 106,000 btu oil furnace (1 year old). I have the local hvac people installing ...
  A: Dragan, you need to tell me if the coil matches the outdoor unit tonnage. If it is a 4 ton then ...
ac advice9/25/2009
  Q: I bought a home with a 4 ton evaporater coil A-SLB484422T+D all style ,this is asplit unit and the ...
  A: Carol, You only have a 2 1/2 ton compressor with a 4 ton evap coil? Yes you have a problem. Low ...
Rheem Corsair Air Conditioner9/24/2009
  Q: I have the above ac unit model# FADC-0305AS. It has stopped cooling at its normal capacity and I ...
  A: Eric, Make sure you have a clean filter and all vents are open. Then after 10 minutes running on ...
Carrier 58MVP -100-F-1-209/24/2009
  Q: install 03.worked thru spring 09.bsmt location.vents thru roof of 2 flr house. lgth and bends ok to ...
  A: Terry, Are any of these techs(?) writing down and reporting to you any physical data and ...
Heat pump Blower Motor9/24/2009
  Q: I have a 1750 sq ft ranch home. 3 ton Carrier heat pump. Blower motor died. Local guy charged $979 ...
  A: Dan, The price you were charged was for a variable speed motor with a motor controller attached to ...
Crawlspace Conditioning9/23/2009
  Q: I live in southwest Ohio, gratefully enjoy all 4 seasons of the year. I recently bought my first ...
  A: Kathy, Probably the simple solution for your problem is when the central hvac system is up and ...
4 ton Trane xl16i isn't doing the job.9/22/2009
  Q: I’ve been thinking a lot about the AC pad and how the condensers are arranged. I measured the area ...
  A: If those numbers are accurate, you have 7 degree's of sub cooling and 37 degree's of superheat, ...
blower9/22/2009
  Q: i have a ruud fuel furnace. not sure what model. it appears to have 2 thermodisc. as it's warming ...
  A: Dan, Without a little more info it is hard to answer this one. As you look at the furnace, behind ...
ac unit in condo9/21/2009
  Q: I have an intermittent cooling problem - Compressor is on roof and installed in 2001, along with ...
  A: Lylah, John Borgman here, got this out of our question pool. It sounds to me like the compressor ...
T-stat mystery9/20/2009
  Q: I have a central a/c system and the temp stays pretty much even with a 1 or 2 degree differential ...
  A: Marshall, John borgman here got this out of our question pool. So when you have it set at 78, ...
Residential A/C question9/17/2009
  Q: I have two identical residential 2ton split A/C units. They are 16 years old, Goodman, and use ...
  A: Tom, I would have the N.A.T.E certified tech check the other unit since he also added to it, it ...
increasing aircon efficiency9/17/2009
  Q: Mike , i am involved in a green building information , education and supply operation on the island ...
  A: Stephen, You are correct about the conduction of water over air, it is 8 times as efficient. As ...
Residential A/C question9/17/2009
  Q: I have two identical residential 2ton split A/C units. They are 16 years old, Goodman, and use ...
  A: Tom, I don't know where to start with you, except, holy cow!!!!! You are so over charged you are ...
Blower works for 30 minutes then locks9/15/2009
  Q: I have a Lennox dual climate AC unit and had issued today with the temperature being warm in the ...
  A: David, You either have a bad condenser fan motor or more likely a bad run capacitor. When the ...
Freon leak9/15/2009
  Q: My upstairs HVAC system has a slow leak. It is seven years old and the evap. coil was replaced in ...
  A: Rene', The freon can leak from anywhere it runs through, but on a unit as new as yours, the first ...
Fixed vs variable speed ac9/14/2009
  Q: I've been given varying opinions concerning fixed vs variable speed ac units. Seems it's a 50/50 ...
  A: Mike, Sounds like you are doing your homework, although, I have no clue as to the lightening ...
Trane XL 1200 super efficiency weathertron heat pump9/14/2009
  Q: About a week ago our outside heat and air unit stopped cooling,and the fan of the unit wouldn't ...
  A: David, Here is a link as an example. Google trane parts for your area and you can find a dealer ...
a/c leak9/13/2009
  Q: I took out the filter to clean it. I had turned off the A/C and had it turned off for several hours ...
  A: Gaby, I assume you removed the filter due to it not working, is that correct? And the filter was ...
Lennox AC unit9/11/2009
  Q: I had a technician come out to my home today. We bought our home new about 2.5 years ago. Our ...
  A: JC, I would not trust this man to work on your equipment. First, his statements about the filter ...
hvac...freon leak9/11/2009
  Q: john, I have an older central a-c unit. it works great, but it has a freon leak. The tech who ...
  A: Mike, If the leak is that big, the only way to do this is as follows. Fill the now almost empty ...
More on residential AC Dye Test/Leak9/9/2009
  Q: I had a local HVAC company come to find out why my Amana 2.5T central AC system was not blowing ...
  A: David, Not a clue as which light because it is the wrong thing to do to a system, so I haven't ...
Low Cost Options to fix compressor9/9/2009
  Q: I have a 2.5 ton Comfortmaker outside system with a frozen compressor. I asked about if I could ...
  A: Clark, You have till January to replace the whole unit with another R22. After that compressors, ...
Brand New Condenser Burned Out9/9/2009
  Q: I really need some help. I bought a new condenser for my house two months ago and it quit running ...
  A: Cheri, Wow. I don't know what to say tactfully. There is no way that a 3.5 ton condensor should ...
Selecting Thermostat for Heat Pump9/8/2009
  Q: I am seeking to replace my existing thermostat which isn't digital. I have a Carrier Heat Pump ...
  A: Mitch, I recommend a t8000 honeywell. It has an adaptive intelligent recovery that controls your ...
Gas Ducted heater lockout9/8/2009
  Q: My Dad has a "Stadt" brand gas ducted heater. Last night it stopped working so I had a look. The LED ...
  A: Greg, Howdy from the USA. Although we do not have that brand here, they all have the same ...
4 ton Trane xl16i isn't doing the job.9/8/2009
  Q: I’ve been thinking a lot about the AC pad and how the condensers are arranged. I measured the area ...
  A: I didn't say 20 percent should be recycled, I said that the air discharged is at least 20 degrees ...
Quote for the new HVAC system9/8/2009
  Q: Good morning John, I am in process of purchasing a new home in Houston, TX and I am in need of the ...
  A: Ismar, You are correct about the R410a and if you plan on being in your home for 15 years, you ...
4 ton Trane xl16i isn't doing the job.9/8/2009
  Q: I’ve been thinking a lot about the AC pad and how the condensers are arranged. I measured the area ...
  A: A.J., 9 or 10 will also work for the 2 ton. Moving them will help, although the 4 ton is still ...
choosing a gas furnace9/8/2009
  Q: Any general advice on choosing among Carrier, Lennox, or (much cheaper) Goodman for a ...
  A: Ted, No Goodman. carrier and lennox are good equipment, personally I put a Trane in my mothers ...
TRANE XL 1200 Humming Noise9/7/2009
  Q: I have an outdoor unit TRANE XL1200 Super Efficiency Air system. All appears to be operating ...
  A: Ben, You should check the model of that unit, because there is nothing in a straight condenser ...
Thermostat wiring9/7/2009
  Q: I am replacing a contour comfort control thermostat with an Ace hardware brand programmable one and ...
  A: Mark, Rh,Rc jumpered=red G=green W=white Y=yellow O=orange....this is your reversing ...
air duct cleaning9/7/2009
  Q: I am planning to have my air ducts cleaned and would like to know how to find a company which will ...
  A: Edward, Your return air should be metal, that is not code and can hold mold in the cardboard. ...
Zone Controller, Low Air flow, and Discharge Temp Sensor9/7/2009
  Q: I just replaced a 10 year old 5 ton York heat pump and air handler and 2 simple thermostats with the ...
  A: Walt, I cannot help you. I work full time and volunteer 20 to 30 hours a week on here and do not ...
TRANE XL 1200 Humming Noise9/7/2009
  Q: I have an outdoor unit TRANE XL1200 Super Efficiency Air system. All appears to be operating ...
  A: Ben, I am going to assume you have the heat pump model as you did not say. As such, it sounds ...
Limit Switch9/6/2009
  Q: I had tried to repair the old one which made the condition much better but it still happened a few ...
  A: Faith, Insist on finding techs that are N.A.T.E certified and this time, if it is not resolved, ...
Zone Controller, Low Air flow, and Discharge Temp Sensor9/6/2009
  Q: I just replaced a 10 year old 5 ton York heat pump and air handler and 2 simple thermostats with the ...
  A: Walt, Before we address your questions......Bad move with downsizing a 5 ton condenser, with a 3 ...
Limit Switch9/6/2009
  Q: I had tried to repair the old one which made the condition much better but it still happened a few ...
  A: Faith, First lets address the first guy that worked on it. There is no such thing as a pain in ...
Trane XE10009/6/2009
  Q: My unit is 12 yrs old and told the coil needs to be replaced - have had a freon leak for many years. ...
  A: Christine, Did they show you the leaks? How did they find them? If they only used an electronic ...
Limit Switch9/6/2009
  Q: I had tried to repair the old one which made the condition much better but it still happened a few ...
  A: Faith, I remember you, yes. So, this is happening when the heat is not being used? Did the old ...
AC?heat pump operation9/5/2009
  Q: When I turn my unit onto heat mode all works fine and heat comes out. Then in a little while the ...
  A: Rich, Your thermostat has 2 stages of heat, the first for heat pump, the second for aux. heat. ...
A/c fan inside will not come on9/5/2009
  Q: The blower in my squirrel cage quit working properly the other day. I purchased a new switching ...
  A: Mike, I don't know what you are describing as a switching relay? Is this an electric or gas ...
Trane XE10009/5/2009
  Q: My unit is 12 yrs old and told the coil needs to be replaced - have had a freon leak for many years. ...
  A: Christine, I assume you are talking about the indoor coil? You should still have 10 to 15 years ...
ac/furnace blower motor9/4/2009
  Q: ..I have an old luxaire pcsu-ld08n065b serial number ecwmo84759. The blower motor when the ac is ...
  A: Jason, Almost all blower motors are 1075 rpm. On the side of the motor there is a name plate that ...
4 ton Trane xl16i isn't doing the job.9/4/2009
  Q: Question; what are some simply thing I can check to insure my systems are providing peak operating ...
  A: AJ, The first thing we want to look at is if they are set up correctly as far as the charge and ...
Outside coil went out9/4/2009
  Q: I have a split system HVAC. My outside coil just went out and I tried the breaker but that didn't ...
  A: No if the disconnect is a breaker and it and the one in the panel are in the on, not tripped ...
Outside coil went out9/4/2009
  Q: I have a split system HVAC. My outside coil just went out and I tried the breaker but that didn't ...
  A: Hey Alex, The outdoor A/C unit is called your condenser. If the indoor blower comes as it should ...
which product9/3/2009
  Q: We need a new HVAC system put in. Which brand is the best. Trane or Carrier? ANSWER: Jan, I ...
  A: Jan, Ask him how he knows that, as this new refrigerant has only been in place for a few years. ...
which product9/2/2009
  Q: We need a new HVAC system put in. Which brand is the best. Trane or Carrier?
  A: Jan, I prefer Trane it is what I put in my mothers house due to the dependability. Cost a little ...
ac/heat thermostat setting9/2/2009
  Q: how should a thermostat be set when a two story house has 2 ac/heating units if we want temp to be ...
  A: The first thing you need to do is change your air filters. If they get too clogged your equipment ...
Air handler-air conditioner9/1/2009
  Q: I have a five year old rheem blower and a 30 year old compressor that is busted. I assume I would ...
  A: Al, Your indoor unit is fine, you should get 25 years out of it anyway. The question to ask ...
cracked pan9/1/2009
  Q: my uncle is an hvac guy - don't know his exact title but he told me I have a cracked pan and we ...
  A: Kelly, Wow, what a nice comment. I hope it works out for you, if not give me a hollar
my centrail air conditioner does not turn on9/1/2009
  Q: I have a comfortmaker snyder general central air. the thermostant works but no cool air coming from ...
  A: Joe, Kinda curious how you decided that the thermostat works. First of all, lets assume it ...
Rheem RGDG Won't Start or Run9/1/2009
  Q: I have a Rheem RGDG Criterion. I tired to check it out this evening, and noticed corrosion on the ...
  A: Scott, I don't remember where on that model furnace it is, but there is a ledger that tells what ...
Goodman Gas Pack9/1/2009
  Q: I have a new Goodman Gas Pack - 14.50 seer. When the compressor kicks on, I hear a vibrating noise ...
  A: Liz, Ok, so you replaced an old unit or is this a brand new install, duct work and everything? If ...
Old Attic Fan8/31/2009
  Q: My house was built in 1941 in Springfield, MO. It is a two-story house and on the 2nd floor in the ...
  A: Linda, You don't see many " whole house " fans anymore, I have only seen one in the last 27 years, ...
Coil Leak--Lennox Elite 12 CB30M8/31/2009
  Q: I had my a/c company come to the house this morning to do their semi-annual a/c maintenance visit. ...
  A: Robert, An evaporator coil does not leak under normal wear and tear in 8 years and if it does need ...
Vent location8/31/2009
  Q: We're about to have some work done in our house and have a chance to relocate our AC exhaust vents ...
  A: Mike, Yes the "supply" vents should be about 6 inches from the exterior walls and over the largest ...
inside coil8/30/2009
  Q: I am buying a 6 year old used 4 ton condenser unit made by bryant and I have forced air I will need ...
  A: Michelle, It depends on what refrigerant it is, what seer rating, if you are going to use a cased ...
single stage vs double stage and...8/30/2009
  Q: -- 30+ yr old house, thermostat on first floor, occupants like a well cooled and dehumidified second ...
  A: Tom, There is only one true way to size your equipment. That is with a manual J heat gain/loss ...
Goodman Gas Pack8/30/2009
  Q: I have a new Goodman Gas Pack - 14.50 seer. When the compressor kicks on, I hear a vibrating noise ...
  A: Liz, How was it checked before it was installed??? If it is brand new the compressor can just be ...
Gas Furnace Recommendation8/30/2009
  Q: I have been getting estimates lately to replace a 30 yr old forced air gas furnace in my home and am ...
  A: Dave, wow lots of questions...smile Unfortunately your contractors haven't done a very complete ...
winterizing the gas furnace8/30/2009
  Q: John I have a high efficiency lennox elite series gas system,I am needing to know from a technicians ...
  A: Steve, First of all nice furnace. With the new inshot burners, heat exchangers do not clog as ...
York AC Unit8/30/2009
  Q: What is your opinion of the York. My AC contractor wants to replace my 20 year old Lenox unit with ...
  A: Marilynn, To be honest York is not one I would recommend. Hardly any one works on them of carries ...
ac not cooling8/30/2009
  Q: My ac unit is about 3 months old, but it works very good at night and early morning, and around noon ...
  A: Yanet, I will assume you are talking about a central air system. Get on the phone and have the ...
air conditioning and t-stat8/30/2009
  Q: I have a couple questions and I am really hoping you can help solve our dilemma. We purchased a 7 ...
  A: Beth, It sounds like you could have a few problems. First with the furnace kicking on and off, ...
Fan motor on the outside unit will not run8/29/2009
  Q: I have a RUUD, Model# UAMB-030JAZ. I looked at the capacitor but it doesn't seem swollen or ...
  A: Marvin, Since that model has a duel run cap, it is most likely the motor itself or the compressor ...
TXV8/29/2009
  Q: We called to have it looked at. The first service tech said the coils are plugged with cottonwood ...
  A: Thomas, Yes, you can fax him the info, although you might delete the word clown, even if it is ...
TXV8/29/2009
  Q: We called to have it looked at. The first service tech said the coils are plugged with cottonwood ...
  A: Thomas, I would call the owner of that company and complain. Obviously they do not know what they ...
heat pump8/29/2009
  Q: I have a package heat pump that one day it can not switch to cool it was working fine then only can ...
  A: Phillip, Still having trouble with the limited info, sorry. If I am following what you are ...
heat pump8/29/2009
  Q: I have a package heat pump that one day it can not switch to cool it was working fine then only can ...
  A: Phillip, Respectfully your question does not make sense. The reversing valve has nothing to do ...
cracked pan8/29/2009
  Q: my uncle is an hvac guy - don't know his exact title but he told me I have a cracked pan and we ...
  A: Kelly, Bryant is a carrier product and since you didn't say I assume that you are talking about ...
Rheem rrka-a0368/29/2009
  Q: I have a 10 yr old Rheem RRKA-A036jk06X A/C+heat unit on my roof. My problem is that I do not get ...
  A: Steven, Since you are handy with a volt meter this will make this easier. The high voltage first ...
CFM requirements8/29/2009
  Q: 2500 sq ft single story, 4 ton A/C required per manual J calc. Currently two 10" round returns, 1 ...
  A: Bob, this is a great web site for tinkering around with lots of questions in the hvac arena. As you ...
A/C Blower8/28/2009
  Q: My A/C blower motor has been coming on intermittently. The condensor is not on, nor is there a need ...
  A: Faith, If you have an older furnace, it might have a fan limit switch that is going out or if you ...
Gas water heater with air return directly behind in unfinsihed upstairs bonus room8/28/2009
  Q: We recently purchased a David Weekly home, finished in '03. Stair from the 1st to 2nd floor lead to ...
  A: Karla, I don not know the codes there but it cannot be legal to have a return air intake next to a ...
air conditioning8/28/2009
  Q: made a room and conected a 6" duct for the main register in the attic got cold air flowing but can't ...
  A: Manuel, It sounds like you need more cooling yes. But just increasing the duct size might not do ...
single stage vs double stage and...8/27/2009
  Q: -- 30+ yr old house, thermostat on first floor, occupants like a well cooled and dehumidified second ...
  A: Tom, In cooling whatever you choose will be on high speed and de humidifiing is part of the ...
Excessive condensation from A Coil8/27/2009
  Q: I have a split upflow central air unit in one of my rentals that yesterday flooded the utility room. ...
  A: Bill, First if you do not rinse that coil completely you will rot it out. Second another reason ...
R410a presures8/27/2009
  Q: I never had air conditioning in my house, so I just had it installed. It's a Trane condenser 3 ton ...
  A: Paul, You cannot go by just pressures on any system. The new R410a units, due to the different ...
Outdoor unit wires8/27/2009
  Q: We were weed eating around the outdoor unit and some wires came loose...we don't want to touch ...
  A: Renae, Going to need more info. First is it just A/C or a heat pump or package unit. Then it ...
Heating a basement8/27/2009
  Q: I have a 6 year old 2,400 sq ft ranch with a basement with 1,400 sq ft finished. I have ceiling ...
  A: Dan, First closing vents is not the answer, unless your duct system was over sized ( which I doubt ...
? no super heat?8/27/2009
  Q: i installed a 2ton heatpump system by bryant about a year ago. and always got 1-3 superheat. about ...
  A: Nick, First of all, you charge a R410a system by sub cooling, the characteristics are different ...
Residential AC Drainage8/27/2009
  Q: I live in a 2-story home built in 1995 with a Lenox AC system. There is some water in the drain pan ...
  A: Lional, That is a second line of defense and it is only used if there is a problem. Either the ...
Luxaire or American Standard HVAC8/27/2009
  Q: We are looking to replace our 17 year old HVAC system and have quotes from 2-contractors. One ...
  A: Joe, The American Standard, hands down. First because of the obvious more efficient A/C which is ...
central air clanging sound8/26/2009
  Q: When my central air turns off (as in when the temperature reaches the thermostat) it makes a sound ...
  A: Nichole, For one thing, if your evap coil was that clogged, now you have a lot more air flow and ...
Outside Central air unit ?8/26/2009
  Q: I have a 10 yrs old Comfortmaker Unit (FBAO36GC) that recently started to make a very loud noise. ...
  A: Yes, do not use it. There is only one way for this to happen on purpose and that is if you are air ...
payne airconditioner8/25/2009
  Q: i have a Payne aircondition unit and a totaline thermostat last night the low battery signal came on ...
  A: Steve, Is it calling for A/C? If so, check the breaker for the outdoor unit. If that's not it, ...
Outside Central air unit ?8/25/2009
  Q: I have a 10 yrs old Comfortmaker Unit (FBAO36GC) that recently started to make a very loud noise. ...
  A: Steve, I don't know if you are talking about the fan for the outdoor unit or the fan for the ...
need for 2 circuit board replacements in one month and frozen A coil8/25/2009
  Q: I have a 2 yr old Amana high efficiency furnace and a/c 3 ton. In June the a/c quit and A/C ...
  A: Jo, There are two reasons for the A coil to freeze. One is low air flow. ie. dirty filters, vents ...
New A/C not as cool8/25/2009
  Q: I just replaced a 20 year old Trane A/C with a new XR-15 Trane. The installers also replaced the ...
  A: Roger, More than likely, they did not evacuate the system properly or charge it correctly. Get ...
leak repair8/24/2009
  Q: I have a 3.5 ton outside carrier unit and a slightly larger Lenex unit inside. Had a slow leak of ...
  A: Sam, I wish you had contacted me first. The way a refrigeration system works and lasts is that we ...
furnace blower whistle8/24/2009
  Q: My gas furnace blower produces a loud whistle when it runs. Usually the whistle fades as the blower ...
  A: Ken, You are describing the draft inducer motor. It could be bearings or the small blower type ...
AC is barely blowing slightly cooled air8/23/2009
  Q: We have an Armstrong Ultra SX80 ac/heat system. In the last 3 days, we've had a dramatic 75% air ...
  A: Debra, Loss of air flow and other problems are from the indoor coil freezing up. It freezes for ...
window AC8/23/2009
  Q: I have been looking for a 220 Volt 8000 BTU Window AC because using a 110 volt overloads the ...
  A: Ed, I dont know the available window units, you might check at home depot as a start. The ...
blower cuts out8/23/2009
  Q: I have a York Diamond 80 res gas furnace. When I set the thermostat to ON the blower will start but ...
  A: Jamie, You are going to cause more damage than you already have if you do not get a tech out to ...
Replacing Drain Pan8/23/2009
  Q: We have a small amount of water leaking at the base of our indoor unit(Philco B3BM-036K) in the area ...
  A: John, Generally the pan does not have to be removed to put a new pan in, unless there is no room ...
Goodman pgb042100-18/22/2009
  Q: Late yesterday afternoon our ac quit working the condensor fan is not turning and the unit is giving ...
  A: Sandra, That is one that you need a .tech to come do some checking. It could be a board or motor ...
Rheem/condensor fan stops compressor still running8/22/2009
  Q: Here is my problem(s)I have a 1 1/2 ton Rheem (split system )installed in 99 my fan was stopping and ...
  A: Robert, There was probably nothing wrong with the other motor. Sounds to me like a bad run ...
410A Pressure Temprature Chart8/22/2009
  Q: I have a technical question about 410A and pressure temperature charts and i really need some help. ...
  A: Yes that is correct, but the 10 to 20 is minimum and maximum of units that are made today. ...
410A Pressure Temprature Chart8/22/2009
  Q: I have a technical question about 410A and pressure temperature charts and i really need some help. ...
  A: Dharmen, That is not the correct method for charging and temperature refrigerant, even under ideal ...
central air unit8/22/2009
  Q: Ok...during the day today me and the wife noticed it getting hot. I thought the air was turned up so ...
  A: Ronald, If all you vibrated by hitting the indoor blower motor was the motor, then it either has a ...
Portable Air Conditions for spot cooling8/18/2009
  Q: I recently purchased a used Sunbeam KY 25Y Portable Air conditioner rated at 9000 BTU. It is three ...
  A: Sharon, How? The leveling part......You will need a small level and then lay it on all sides of ...
_price@yahoo.com8/18/2009
  Q: John I have a carrier central air unit , i push in the contactor the fan and compressor kick on ...
  A: Chris, You work in the field? I love helping other service or installers. Two things....One ...
No air flow when a/c comes on8/18/2009
  Q: my central air outdoor unit comes on like it should when the thermostat clicks it on but I'm not ...
  A: Chris, Do you have a volt/ohm meter and know how to use it? If not you are going to have to call ...
New installation of electric furnace and heat pump8/17/2009
  Q: Asked too many questions. So just one more. You said in your last answer "But, with this new info, I ...
  A: Connie, You did not supply all that info....smile. So, I assume you mean the large copper pipe ...
A/C unit not cooling8/17/2009
  Q: .. I have a Sears High Efficiency Central Air Condition, Model #769-81602. The unit is having ...
  A: Jim, If all the vents in the house are open and you have a clean filter in, let it run for ten ...
Amana problem8/17/2009
  Q: We have an Amana furnace that is about 7 yrs old and isn’t working. We had our vents cleaned last ...
  A: Nicole, Unless it is a fluke, I would suspect the duct guy did something unintentionally ( I would ...
No air flow when a/c comes on8/17/2009
  Q: my central air outdoor unit comes on like it should when the thermostat clicks it on but I'm not ...
  A: Chris, First thing to try is put it in heat mode and call for heat and see if the blower comes on ...
Newly Installed Electric Furnace and Air Conditioner8/17/2009
  Q: I live in a 20-year old, 3 story 1300 sq. ft. condo in Cincinnati, OH. (It has a walk-out basement, ...
  A: Connie, Sorry for the lack of professional help you received. It would not matter how it shorted ...
Newly Installed Electric Furnace and Air Conditioner8/17/2009
  Q: I live in a 20-year old, 3 story 1300 sq. ft. condo in Cincinnati, OH. (It has a walk-out basement, ...
  A: Connie, If you had a 20 year old payne, then the duct work must have been ok for it, to last that ...
air conditioner problem8/17/2009
  Q: my home air conditioner unit only shuts off for 3 minutes at a time, then runs for at least 10 ...
  A: Jerry, If you have an old mercury bulb tstat, the anticipator might need to be set or it is worn ...
Central Air Conditioner Not Working?8/17/2009
  Q: Today we noticed that our house was no longer getting cool. We are "total electric." We have an ...
  A: Carista, The cap could still be bad, even without visual signs, but it sounds like the motor is ...
ac/furnace8/16/2009
  Q: We have a Luxaire furnace that we believe is original to our 1977 house we bought 3 years ...
  A: Kim, Yes the blower motor of that age is an oil port motor. The problem with doing it yourself is ...
heat pump and air handler8/16/2009
  Q: ..we are considering replacing a 31 year old air handler. our american standard 21/2 ton heat pump ...
  A: Jay, Personally I would replace it due to age, even though it will do the same job as a new one. ...
split system ac unit8/16/2009
  Q: recently installed new condenser outside,2 1/2 ton,transformer has tripped several times,it also ...
  A: Chuck, Who the heck is working on your equipment....a roofer. Sounds to me like the old unit ...
placement of heat pump return air vents8/16/2009
  Q: I have 2 return air vents for my heat pump. One at floor level in the hallway wall and one in the ...
  A: Robert, That will not make any difference in your bill. It sounds like you have one of two ...
zone cooling8/16/2009
  Q: Have a Bryant 4 zone perfect plus. It will not respond to inputs. Two zones may be shut out or hold ...
  A: Randy, Sounds like there are some crossed wires to the zone dampers. Here is the easy way to fix ...
3 year old tempstar evap coil8/10/2009
  Q: I purchased and had installed a brand new Tempstar heat pump / AC unit three years ago when I bought ...
  A: Justin, Yes you are. Any tech should have come, gauged up and started the system. If there is a ...
air handler problem8/10/2009
  Q: About 3 years ago I had a problem where the outside air compressor was working (and all iced up) but ...
  A: Paul, You have either and air flow or refrigerant flow problem. All vents open? Clean filter? ...
a-coil selection8/10/2009
  Q: Is it ever okay or desirable to mis-match the a-coil and the condenser unit? Long story ...
  A: Chris, The only time to run a larger coil is with a heat pump using the new r410a refrigerant and ...
Miller Outdoor Heat Pump Unit8/10/2009
  Q: The fan to my outdoor unit will not turn on. You can hear power going to the unit, but nothing is ...
  A: Jenny, Well if you have a new defrost control board, then it is probably the motor or the run ...
air conditioning/furnance8/9/2009
  Q: Sometime this afternoon our house started heating up and we found later that while it sounds like ...
  A: Brian, sounds like your indoor coil is frozen. So, turn off the system switch and turn on the fan ...
t stat question8/8/2009
  Q: I have a trane heat pump unit. I think it has a 15kw heat strip in it. I have a hunter touchscreen ...
  A: Travis, The first thing to do is have a tech gauge up and probably adjust your refrigerant level. ...
Fan motor not running8/7/2009
  Q: I have a 2 1/2 ton Lennox that is making a hissing noise down around the base of the unit and the ...
  A: John, What was done about the line? The hiss can be one of 3 things. First, a leak, which if it ...
Quietest Attic Air Handler Installation8/7/2009
  Q: Good Morning, I will be installing a split geothermal system in a ~ 1500 square foot 1928 colonial ...
  A: John, In theory it sounds nice but air does not move like water. It actually needs the back ...
Furnace door won't stay shut8/7/2009
  Q: I have a mystery regarding the front panel/cover on my furnace. My furnace (air conditioning) has ...
  A: Jesse, Your furnace might have these 1/4 square black pieces where the doors come together with a ...
blower motors8/6/2009
  Q: We recently replaced our blower motor in our gas furnace with one identical to the old one. Here are ...
  A: Chanda, On the small plate that you remove to get to the wiring is a schematic, that shows what ...
Heat pump package unit8/6/2009
  Q: We have a 22 yr. old 3 ton Rheem or Rudd heat pump package unit that we're looking to replace. What ...
  A: Kim, Stay away from the Ammana. You got over 2 decades with the prior equipment, why change that. ...
New AC unit compressor on and off while outside fan running8/6/2009
  Q: We purchased an AC unit of Kenmore model H4A448GKB100 in Jun 2008 and Sears’s contractors ...
  A: Sam, As you have found out, it is not the equipment but the installation that is the problem. In ...
Carrier heat pump8/6/2009
  Q: My a/c unit is not cooling properly. The condenser is running and the fan seems to be running. The ...
  A: Debora, do this test. Remove the air filter ( just for this test ) have every air vent in your ...
heat pump and air handler8/5/2009
  Q: ..we have a 5 year old 10seer american standard 2 and 1/2 ton heat pump, that runs good. our air ...
  A: Jay, Although as of January they will no longer produce equipment using R22, the refrigerant and ...
blinking amber light8/5/2009
  Q: Concerning an american standard freedom 80 single stage gas furnace...there is an amber blinking ...
  A: Patty, If you remove the door on the blower compartment( there are two doors, one for the burner ...
AC CONDENSATE8/5/2009
  Q: Recently I noticed water dripping from the RELECTIX insulation that covers the ducts and coil that ...
  A: Joe, Whenever a system is zoned, as each zone is satisfied and the damper closes, there is a large ...
heat pump low voltage8/4/2009
  Q: i have just installed a new goodman 3ton heat pump with matching coil to a intertherm down draft ...
  A: Scott, TSTAT FURNACE HEAT PUMP R=RED R=RED R=RED C=BLACK ...
Return air grill condensation8/4/2009
  Q: Recently I have noticed that when I get up in the mornings my return air grill is dripping with ...
  A: Mick, It is because of humidity and dew point, the temp drops just below it at night because of ...
cooling problem8/4/2009
  Q: I been having a problem with cooling, I recently graduated from an AC refrigeration school but, I'm ...
  A: Robert, What is you dry bulb return air temp and what is your liquid temp? I dont know where you ...
evap coil drain8/3/2009
  Q: John, Finally lit off our split system (Frigidaire) AC unit to temper the summer heat. The unit is ...
  A: Tim, Yes those things happen. If you fill the drain pan with water with the unit off, you should ...
AC unit Dead8/3/2009
  Q: 2yr 13 Seer Johnson Fraser(YORK International) AC unit dead.The fan outside will not come on. It is ...
  A: Katilina, Phone any company that is reputable for the work. It wont be just the compressor, if it ...
AC CONDENSATE8/3/2009
  Q: Recently I noticed water dripping from the RELECTIX insulation that covers the ducts and coil that ...
  A: Joe, First you say zones? Do you mean area's? Zoning means that those ducts have dampers that ...
wet spots on exterior stucco8/2/2009
  Q: I just recently purchased a 7 year old house. I noticed that whenever I run the AC unit, I notice ...
  A: Rob, If the secondary pipe does not exit the structure it should be finished. I don't know where ...
New AC Unit dead after 2 days - same problem as before.8/2/2009
  Q: I recently had my entire unit replaced through a home warranty claim. According to the tech, the ...
  A: Kirk, I can almost promise you are out of or low on freon. Any " tech " that has trouble sealing ...
Water pouring out of furnace8/2/2009
  Q: We just bought a new house in MD and when we run the AC water flows out from below the furnace. Is ...
  A: David, There are a couple reasons for the water. One would be a clogged drain from the drain pan, ...
Central Air unit8/1/2009
  Q: Yesterday I heard water rushing and discovered water coming out of my Central Air Unit (Goodman ...
  A: Angie, The pan can be purchased by itself. It can also be repaired, depending on where it is ...
Isolating 24v transformers8/1/2009
  Q: Was just up in your neck of the woods (Portland) this week ...guess you've been busy with the heat ...
  A: Mike, First of all, yes that is what is called a peanut relay. You had indicated you wanted the ...
Isolating 24v transformers8/1/2009
  Q: Was just up in your neck of the woods (Portland) this week ...guess you've been busy with the heat ...
  A: Mike, Yes if the de-humidifier has its own 24 volt system you will need to isolate it. The ...
AC Unit8/1/2009
  Q: Bought a new house 1 yr ago. Turned on the AC in the house for the first time this summer and it was ...
  A: Matt, Compressor??? What compressor? In your unit? To be honest 300 sounds too cheap. If you ...
Unico loss of cooling8/1/2009
  Q: I am in the construction business and ask this question with a little knowledge of things. We have ...
  A: Dana, I actually guessed that part, kinda. But I am familiar with unico and do not know what to ...
sp80 tampstar7/31/2009
  Q: the fan doesn't come on went you turn the ac or heat on. i have power
  A: James, Are you talking about the blower? It is in the furnace and moves the air in the house. If ...
Air conditiner warranty7/31/2009
  Q: Carrier 2-ton residential ac model 38ckc024340. Installed 4 years ago for use in our small office ...
  A: Judy, Warranty will not cover new unit. And if you have had an electrical burn it could cost as ...
AC Unit7/30/2009
  Q: Bought a new house 1 yr ago. Turned on the AC in the house for the first time this summer and it was ...
  A: Matt, It is very very rare for the outdoor coil to have a leak. I have to assume he came out, ...
LENNOX HP CONDENSER NOT RUNNING7/30/2009
  Q: i have an 11 year old Lennox heat pump. About a week ago, the blower motor burnt up so we replaced ...
  A: Cassie, You should check the breaker for the outdoor unit. There also might be slow blow fuses in ...
Clean an A-Coil7/30/2009
  Q: I know that you can trap the freon in the condensing unit so you can cut the lines and remove the ...
  A: William, You should be bleeding nitrogen when brazing and I would use silfloss or silbraze, then ...
GOODMAN AC HANDLER BLOWER INOP AT TIMES7/30/2009
  Q: MR. BORGMAN, I HAVE A 2 STORY HOUSE WITH 2 SEPARATE AC/HEAT SYSTEMS(I BELIEVE THE AC HANDLER #'S ARE ...
  A: John, If that furnace has a deadman switch ( when you open the blower door it pops out and kills ...
Portable air conditioner shakes and sputters7/30/2009
  Q: I have a portable sunpentown air conditioner, and it does this new thing I haven't seen before. In ...
  A: Carrie, Well, there are only a couple moving parts so it has to be either the compressor motor or ...
Installation of Fan Timer Control Board7/30/2009
  Q: I need to replace the fan timer control board in our Comfortmaker HVAC system. The board is ...
  A: Sam, No hidden power issues with that. Most boards are a wire for wire change, but some boards ...
Compressor cuts out7/30/2009
  Q: I have a 10,000 btu window unit that usually cools my entire (small) apartment. When it gets around ...
  A: Joseph, There is not a lot you can do except to position a mist head on a garden hose and have it ...
new ac7/29/2009
  Q: I am an ac dummy. My home ac unit just went out-compressor I guess. It was 26 years old and just ...
  A: Stephanie, Since I do not know if the indoor air handler is a furnace ( electric or gas ) or what ...
AC system keeps breaking down7/29/2009
  Q: I have a 5 year old home/AC units. The upstairs unit has been breaking down for 1 year. 1.5 years ...
  A: Stephanie, John borgman here, I got this out of our question pool. If it was a return air vent ...
hvac first floor units7/28/2009
  Q: i have a 1940's 3300 sqft property which i am renovating in Houston TX and a hvac rep has ...
  A: Tim, As far as building it in, just make sure that whatever is covering the furnace doors can ...
Clogged AC drip pan7/28/2009
  Q: Can i fix a clogged drip pan on my AC unit relatively easy or do I need to call a professional? ...
  A: Sue, it depends on how the coil was installed. If it is a cased coil, with a factory door, and it ...
Filter7/27/2009
  Q: Our air conditioner has frozen up and I removed the panel to see what things looked like in ...
  A: Cammy, If there is no filter in the furnace or the return air grill, then your indoor coil and the ...
York Heat Pump, Emergency Heat Light7/27/2009
  Q: Good Day: Thank you for your time! We have an old (at least 15 year old) York heat pump with a ...
  A: Brad, you will need a tech to come out. Those Yorks are hard enough for a tech to work on. It ...
heat pump7/27/2009
  Q: For a long time I would have to turn the thermostat on and off several times for it to come on. I ...
  A: Tedd, Get a service tech out there before you burn everything up. You cannot let the smoke or the ...
Window Air Conditioner ducting to furance ?7/27/2009
  Q: I live in Nova Scotia, Canada. I currently have a forced hot air furnace for heating my home. The ...
  A: Larry, you wouldn't get that much done by that method. You would be better off, just mounting a ...
rewiring 3 terminal capacitor to 2 terminal capc.7/27/2009
  Q: I replaced the condenserfan motor which comes with 7.5/370v run capacitor that has two terminals ...
  A: George, The two brown wires are for you run capacitor, which should ALWAYS be replaced when ...
hvac first floor units7/27/2009
  Q: i have a 1940's 3300 sqft property which i am renovating in Houston TX and a hvac rep has ...
  A: Tim, If you asking if a upflow furnace in the basement, to service that floor and the main floor ...
INOP Central Air7/26/2009
  Q: I have a Central air unit that is working but not cooling . the unit outside is on the one in the ...
  A: Nelson, First you need to check the air filter and for this test, go ahead and remove it from the ...
ac intake (return)7/26/2009
  Q: We have a 4 ton central ac and are going to have a 5 ton installed (which was determined by a load ...
  A: Connie, First increasing by a ton is quite a bit. Was this calculated by manual J, room by room ...
Rudd ac unit7/26/2009
  Q: Honeywell FocusPro 5000 set at 70deg. and inside temp. got up to 84deg. yesterday. Fan outside just ...
  A: William, Sounds like you are talking about the condenser fan motor and if it is turning slowly it ...
Air Flow to a Bedroom7/26/2009
  Q: When I had my system installed several years ago, I asked for a little bit of increased air flow to ...
  A: Brian, Probably the easiest way to do what you want is to blank off the collar coming from the ...
Bryant Air Conditioner Unit Installed 19927/25/2009
  Q: Mr. Borgman, I have a Bryant heating and air conditioner system in my house. It was installed when ...
  A: Lewis, So was this tech from the same company? I am still not comfortable with the 30 day thing. ...
refiregrant leak7/25/2009
  Q: I recently found out I had a leak in my system. The system is a year old and I recently had a coil ...
  A: You didn't tell me it was a R410a system. But the numbers you sent me tell me so. Problem is that ...
ac ceiling vent7/25/2009
  Q: We are looking at buying a house and the is one annoying little problem I want to be able to fix to ...
  A: Kate, OK, here is what is up there, when you take the two screws out of the louvered register ...
Air Flow to a Bedroom7/24/2009
  Q: When I had my system installed several years ago, I asked for a little bit of increased air flow to ...
  A: I am thinking, that they on purpose ran that run straight from the plenum to give you plenty of air ...
Air Flow to a Bedroom7/24/2009
  Q: When I had my system installed several years ago, I asked for a little bit of increased air flow to ...
  A: Brian, Was that where the original run was from? I have never heard of 4" unless it is a high ...
AC won't cool/ Freon Leak/Condensing Coil7/24/2009
  Q: About 5 days ago, our air conditioner quit cooling the house. We would set it at 76 and the house ...
  A: Sally, Hi, me again. How did he show you the leaks? If he showed you with an electronic ...
duct cfm7/24/2009
  Q: I was the one asking about charging a sysyem with refrigerent, and yes I'm in thr field, currently I ...
  A: Brian, Practically you cannot. There are some pretty heavy mathematical equations for that, but ...
Whole house fan7/24/2009
  Q: Our whole house fan went out after 18 years so we replaced it with a flow master we purchased from ...
  A: Mary, I really do not know what the right side means. But if you are having an issue with a Home ...
refiregrant leak7/23/2009
  Q: I recently found out I had a leak in my system. The system is a year old and I recently had a coil ...
  A: Vadim, If it holds at 400 psi, then there is not a leak where they are testing. My question would ...
removimg a gas furnace7/23/2009
  Q: I need to remove a furnace and cap off a gas line in order to have a heat pump/air conditioning unit ...
  A: Larry, No, you covered everything. Actually you might get a little smell, but you can dump a ...
PAYNE model PA10, have to keep replacing fuse7/23/2009
  Q: i bought my home in 2003 and had continuous problems with the air conditioning unit since the ...
  A: Joy, If you are having the same problem as you had with the old unit you had replaced, then the ...
Armstrong electric furnace7/23/2009
  Q: I recently purchased a house with an Armstrong EFC12SAA electric furnace. There is a whole house ...
  A: Christopher, If the coil for the humidifier is 24 volts, then you want to wire one side to 24v ...
contactor noise7/23/2009
  Q: The contactor at the outdoor unit growls momentarily before closing. I have 27 volts coming in to ...
  A: John, I am trying to teach you proper electrical troubleshooting , so you can do just that. You ...
sizing house7/23/2009
  Q: I was the one asking about charging a sysyem with refrigerent, and yes I'm in thr field, currently I ...
  A: Brian, For that, the first thing you need to do is get Manual J, either the book or computer ...
air con stopped working outdoor unit7/22/2009
  Q: i have a fuji electric rom-19ua2 outdoor unit and it has stopped working , the fan dont turn and ...
  A: Jim, I am afraid you are going to need a service tech, Jim. The sound could be the overload ...
contactor noise7/22/2009
  Q: The contactor at the outdoor unit growls momentarily before closing. I have 27 volts coming in to ...
  A: John, You mean you placed your lead not leads. And had the other lead where? Also is it a NO or ...
air conditioning7/22/2009
  Q: I have a 3 year old ameristar furnace by american standard and an american standard central air ...
  A: Shawn, OK, here is what we do next. turn off the power to the furnace either at the breaker or if ...
contactor noise7/22/2009
  Q: The contactor at the outdoor unit growls momentarily before closing. I have 27 volts coming in to ...
  A: John, So the low pressure switch on that unit is a normally closed?? You said it does not open ...
Bryant Air Conditioner Unit Installed 19927/22/2009
  Q: Mr. Borgman, I have a Bryant heating and air conditioner system in my house. It was installed when ...
  A: Lewis, I almost hate getting ones like this......You might want to find a real tech to work on ...
Freon leaking7/22/2009
  Q: John, I asked a company to do my A/C tune-up today. The tech told me the freon pressure is low and ...
  A: Yong, The guy is not only very bad at his job, but either does not know what the montreal Protocal ...
Central Air in a Mobile Home7/22/2009
  Q: I hope this is not a repeat question but i have searched far and wide and can't find an answer that ...
  A: Matthew, There is supposed to be a " cross over duct " that connects the 2 sides of the mobile ...
Air Conditioning Won't Cool7/21/2009
  Q: Our house was built in 1998, apparently the builder put smaller units than is recommended. However, ...
  A: Erin, Yes it should work better. First I think that a cooler supply temp can be obtained, if I ...
HVAC New Home7/21/2009
  Q: Greetings: We are building a new home, 3 BR 2-1/2 BA, in Kitty Hawk, NC. Approx. 1900 sq. ft. ...
  A: Denise, With no attic the power exhaust fan is not an option. Sorry if what I said was ...
Freon leaking7/21/2009
  Q: John, I asked a company to do my A/C tune-up today. The tech told me the freon pressure is low and ...
  A: Yong, I apologize for the company that has that tech working there, you might want to phone them, ...
Vert or Horz loop7/21/2009
  Q: John, I appreciate your time. I will try to make this short. Dirt is dug on my property and I have a ...
  A: Chip, No I know of no reason for not going horizontal and respectfully would take a lot more work ...
TRANE Problem??7/21/2009
  Q: We have a 1-2 year old Trane AC and a programmable thermostat. Everything worked great yesterday and ...
  A: Alicia, Call your local Trane dealer asap, Alicia. That Trane has a 5 year warranty at the very ...
follow-up of your ans. to me of 7-13-097/21/2009
  Q: Would your answer you gave be the same if the heat pump Would your answer be the same as to ease ...
  A: Mel, The evap. coil has nothing to do with the water source for the outdoor unit, unless you are ...
HVAC New Home7/21/2009
  Q: Greetings: We are building a new home, 3 BR 2-1/2 BA, in Kitty Hawk, NC. Approx. 1900 sq. ft. ...
  A: Denise, Well the second guy does not know how zoning works and if you use the first guy hopefully ...
Vert or Horz loop7/21/2009
  Q: John, I appreciate your time. I will try to make this short. Dirt is dug on my property and I have a ...
  A: Chip, I guess it is a good thing I am an expert, you gave no clue as to what you building...lol ...
Ac problems7/20/2009
  Q: My outdoor ac unit stopped running a couple days ago and after doing some research we decided to see ...
  A: T, You need to put an amp probe on the motor and see if the amp draw climbs along with the fan ...
Ac problems7/20/2009
  Q: My outdoor ac unit stopped running a couple days ago and after doing some research we decided to see ...
  A: T, It sounds like you wired it wrong and got two of the leads reversed, although that wouldn't ...
flame sensor location7/20/2009
  Q: Where is the flame sensor located on a 10 ton gas pac lenox ac unit
  A: David, John Borgman here, I got this question from our question pool. I am assuming you are a ...
Carrier control board7/20/2009
  Q: I have the info you ask for on the control board, remember I bough a control board with only one ...
  A: Robert, The BDP part number is .... CES0110057-02 If you do run across a situation where the ...
home a/c unit on roof7/20/2009
  Q: fan motor seized, got it replaced. unit then only cooled for about 20 min. was told compressor is ...
  A: ask your other person what an overload devise is and how it works. It is for emergency only and ...
thermostat7/20/2009
  Q: i have an Evcon unit about 2 1/2 years old. today my thermostat started blinking the following ...
  A: Ken, I do not take private questions and I did not know Evcon made a thermostat and I have no idea ...
HVAC sealed combustion return air7/20/2009
  Q: How close can a cold air return be on a sealed combustion unit?
  A: Brad, Are you talking about one that gets its combustion air from outside or in the room it is in? ...
water leaking in basement around heater / ac unit7/19/2009
  Q: Why is water leaking around our propane heater /AC unit??
  A: Lynne, It could be a number of things, from a clogged drain line, to a faulty condensate pump, to ...
wiring7/19/2009
  Q: hi john im not sure weather u can help but its worth a try i can build small windturbines with no ...
  A: Fred, Are you watching the OPEN? Would love to come visit our mother country someday. There are ...
iced coil7/18/2009
  Q: Today I discovered that my indoor coil of my central air unit was heavily iced after running for a ...
  A: Vadim, Ther are 2 things that will cause the indoor ( evaporator ) coil to ice over. Low indoor ...
humidity7/18/2009
  Q: I noticed a question about cfms and you said that in a humid climate a small amount of cfm would be ...
  A: gerald, I don't think you read what I wrote correctly, if it was me. I answer hundreds of ...
air conditioner split system7/18/2009
  Q: I have a Coleman Evcon 3 ton R22 split system unit, this system is 10 years old. It is not cooling ...
  A: Steve, I would be glad to help you, but you need to give me better measurements. I need the ...
home a/c unit on roof7/18/2009
  Q: fan motor seized, got it replaced. unit then only cooled for about 20 min. was told compressor is ...
  A: Mike, 10 years is the cut off to look at a case by case business, but doesn't mean it can not be ...
heat pump gets ice7/18/2009
  Q: I answer on allexperts in 5 other categories, but am not an expert on HVAC. My heat pump worked fine ...
  A: Dave, Probably Dave. Low air flow or low refrigerant flow are the 2 reasons for that. With the ...
imbalance of air flow7/18/2009
  Q: we have a couple vents that are blowing very hard and barely any flow going to the rest of house. I ...
  A: Robert, You really need a tech there to get that straightened out. Air does not flow like water ...
multimetering7/18/2009
  Q: first it seems like my t-stat when i change something is turns off and then maybe turn back on, like ...
  A: Kenny, Your step down transformer gets 120 volts from the grid and supplies 24 volts to the hvac ...
a/c compressor7/18/2009
  Q: unit o/s 21/2 ton, air handler 3 ton i notice the o/s unit starts without the compressor but ...
  A: Len, You cannot change the motor, first they all come in the same rpm 1075 and if you reduce the ...
AC return air location7/17/2009
  Q: I am trying to determine is the building dropped ceiling hot air return vent is in the right ...
  A: Debbie, Since the A/C was not sized for the heat from a server room, no. You should let the spot ...
AC not removing humidity7/17/2009
  Q: John, I have a 20 year old Trane AC unit which recently had 3lbs of freon added. After that for ...
  A: Robert, What does high amps mean? There is a clearly marked rating on the name plate of the ...
thermostat not shutting off AC7/17/2009
  Q: Two days ago had the outdoor condenser of refrigerated AC moved to roof due to a coolant leak ...
  A: Jeannine, Why in the world did you move it to the roof...because of a leak?? Never heard of such ...
Tuneup on a AC Unit7/17/2009
  Q: I bought a house 2 years ago and the ac unit is 8 years old, I am looking at getting a tune up on ...
  A: Marc, You need to have a tune up and I would be surprised if the contactor is still good, but ...
propane heater7/16/2009
  Q: My neighbors burner on her heater for her house seems to plug up with some sort of foreign stuff. ...
  A: Pete, No, propane is usually as clean as natural gas. The burner gets plugged either by a not so ...
AC compressor will not shut off7/16/2009
  Q: I have a 10 year old, 3 ton, electric AC unit. I had a small leak in the outside unit about a ...
  A: Krista, It is one of two things. Less likely your low wiring is either not wired correctly at the ...
clicking in our central heating and air7/16/2009
  Q: I read a questions from someone else that sounded alot like my problem so here goes. Our mobile ...
  A: Sue, You are going to have to provide me with more info than that. Where is the clicking? What ...
gas heating7/16/2009
  Q: I have a 24 x 30 garage with 9' ceilings that I want to heat with natural gas. Could you please tell ...
  A: Robert, Yes and that is assuming you have very little or no insulation everywhere else besides the ...
Wiring new Condensor fan motor.7/16/2009
  Q: I came across this forum as I was digging through information on replacing the condenser fan motor ...
  A: Kevin, Do not run it that way you will burn up the motor. You do not have the run cap working and ...
gas heating7/15/2009
  Q: I have a 24 x 30 garage with 9' ceilings that I want to heat with natural gas. Could you please tell ...
  A: Robert, It depends on the insulation and if you have a standard opening garage door for the size ...
Wiring new Condensor fan motor.7/15/2009
  Q: I came across this forum as I was digging through information on replacing the condenser fan motor ...
  A: Kevin, Actually it is refreshing to get more than " my a/c quit whats wrong...lol" The first ...
hvac air flow7/15/2009
  Q: 3rd yr in a row my hvac runs all day til evening, then sweats & leaks under coil & sometimes after ...
  A: Jen, I understand your frustration, believe it or not I feel the same way on calls I go on and ...
hvac air flow7/15/2009
  Q: 3rd yr in a row my hvac runs all day til evening, then sweats & leaks under coil & sometimes after ...
  A: Jen, You only gave me a rating of 8 on knowledge?
A/C frozen coil/bad compressor/TXV7/14/2009
  Q: We have a Trane heat pump, new 3.5 years ago (installed to heat/cool an addition to house). Two ...
  A: Sybil, First, In an air conditioner, the indoor coil sits in the air stream and liquid refrigerant ...
increasing hvac air flow on existing unit7/14/2009
  Q: I just purchased a single story home 1700 sq ft with a 5ton unit in the attic and 5ton condensing ...
  A: Spencer, I need more info to help..1000 cfm return???? I need to know the return air plenum size, ...
Location of return air duct.7/14/2009
  Q: My house currently has 8 (13.75" x 7.75") return air ducts, 4 each on the first and second floor. My ...
  A: Cutting a hole in it will not increase its size!!! And if your duct work collapses now, more air ...
Location of return air duct.7/14/2009
  Q: My house currently has 8 (13.75" x 7.75") return air ducts, 4 each on the first and second floor. My ...
  A: Kim, First, how did your old equipment do before it failed? Second if you increase the tonnage ...
Trane Air conditioner unit7/14/2009
  Q: I broughta Trane 2TTX5030A1000AA heating and airconditioner unit from a local company in arkansas. i ...
  A: I am assuming you might have a duct problem, as, the dripping copper pipe says that the air flow and ...
Bryant central unit-Ruud outside fan7/13/2009
  Q: Outside fan works but I do not know how to tell if the air is warm enough coming out of it off the ...
  A: Don, No, it sounds like you are describing a problem with the blower motor. Do Not turn it on ...
HVAC works, inside fan motor will not come on7/13/2009
  Q: I recently went into the furnace, pulled the covers and changed the filter only. Put the covers back ...
  A: Steve, The outdoor unit does not blow air inside, it moves refrigerant inside. The motor below ...
Freon Problem?7/13/2009
  Q: Hey I have a VEXAR Coil unit heating my mobile home. I paid a guy $100 to come out and fill my unit ...
  A: Chad, I don't have a clue what the guy did I was not there. It is not filled inside the house. ...
Trane Air conditioner unit7/13/2009
  Q: I broughta Trane 2TTX5030A1000AA heating and airconditioner unit from a local company in arkansas. i ...
  A: I am sorry to inform you that the tech is lying to you. There is no physical way your equipment ...
Settings for 2 level home?7/13/2009
  Q: I have a general question about cost control in a 2 level house. I live in Arizona and currently we ...
  A: Alex, The first thing you should consider is a tstat controlled power attic fan, if you have an ...
Freon Loss7/13/2009
  Q: I believe that my unit is a heat pump, as it provides my heating and air conditioning. My question ...
  A: Rick, You need to crawl under your home and secure the cross over duct work, it is flex duct and ...
Freon Loss7/13/2009
  Q: I believe that my unit is a heat pump, as it provides my heating and air conditioning. My question ...
  A: Rick, There is no such thing as magic, a phrase from my engineering teacher of old. Why would you ...
rv a/c no leaking water on outside of trailer7/13/2009
  Q: my rv a/c is not leaking water on the out side of the trailer what could be the problem ANSWER: ...
  A: There are a lot of things that can cause it to not condense water from the air, including a little ...
Maytag fridge cooling fan issue7/12/2009
  Q: I have a fridge (Maytag MTB2456gew) that started not working properly, so I tried to troubleshoot. ...
  A: Mark, FYI, I am just an expert volunteer on here. Looking to build my portfolio for making this ...
Ruud air conditioner/blower issues7/12/2009
  Q: I have a Ruud model #UGDA-12EA-ER furnace with outside air conditioner unit. I turned the AC on this ...
  A: Jerry, Pull the front door from the furnace. To the right of the vent pipe there is a brown door ...
refrigerant escaped from a/c.7/12/2009
  Q: We have separate Command a/c for 1300 sq. ft. condo unit in South Florida, built 1991. Responding to ...
  A: Mel, Did He show you the leak? A coil leak be it indoor or out, can easily be repaired. I have ...
AC fan stays on when AC is off7/12/2009
  Q: Replaced an old t-stat recently with a new programmable t-stat (ritetemp model 6025). Initially had ...
  A: Kevin, http://www.ritetemp-thermostats.com/6025.html Unless there is a program set up for the fan ...
Filter turning black7/11/2009
  Q: I have an electric heating and cooling system and about a month ago we noticed that our air ...
  A: Toni, It is not coming from your furnace. It is coming through the duct system. Could be a duct ...
air handler bower motor7/11/2009
  Q: I recently change my fan control board for my inside AC unit. The original circuit board had a place ...
  A: Robert, If you get me the product code number off that unit I can get you the part number for the ...
two-stage vs. single-stage A/C7/10/2009
  Q: We are looking to replace our A/C and furnace. One guy told me that a two-stage A/C is more ...
  A: Claire, It really depends on your duct system and that is something that the contractors should be ...
Getting heat in summer7/9/2009
  Q: I have a GE heat pump/ac system at our beach home. When we leave the area I turn off the system at ...
  A: Rob, It sounds like the outdoor unit is staying on, maybe the contactor is frozen shut. It does ...
Installation of AC/Heat7/9/2009
  Q: Our heat pump went out last year and we are currently getting bids on a replacement (regular AC/Heat ...
  A: Jeri, The tax credit is very high for 410a high seer rating. I agree with both carrier and ...
American Standard AC frosting at gasline service valve7/9/2009
  Q: Model 7A0018-042A. This is a new behavior on a 6 yo system. When the unit starts, the frost appears ...
  A: Rod, First lets assume that it was charged correctly and no leaks. Change your air filter or pull ...
two-stage vs. single-stage A/C7/9/2009
  Q: We are looking to replace our A/C and furnace. One guy told me that a two-stage A/C is more ...
  A: Claire, Go with the Bryant which is a carrier product. The outdoor high seer unit is so quiet you ...
Geothermal HVAC systems and problems7/9/2009
  Q: I am considering replacing my nineteen year old HVAC system with a geothermal system. Would you ...
  A: Bob, First downside is there will need to be a back up heat source unless you don't mind waiting a ...
air handler bower motor7/9/2009
  Q: I recently change my fan control board for my inside AC unit. The original circuit board had a place ...
  A: Robert, At the very least you need to change to high speed, right now with a dirty filter you will ...
Squeaking noise from AC7/9/2009
  Q: I have a 5 year old Carrier Central AC. It runs OK, but about 30s after the AC stops, it give out a ...
  A: That could be done by replacing the external equilizer tube on the metering device, which means a ...
charging system7/9/2009
  Q: I was the one asking about charging a sysyem with refrigerent, and yes I'm in thr field, currently I ...
  A: Brian, Cool. The most important thing to do first is pressure test with nitrogen after all joints ...
AC evaporator & filter7/9/2009
  Q: 2.5 yr old Summit evaporator leaking needs replacement - rest of system is Carrier - Houston, TX ...
  A: Joseph, They are wrong. Not only have I done many without a problem but they can put wet rags or ...
hvac fan issue follow up7/9/2009
  Q: the fan starts and stops all of the time. the hvac side the the t-stat is off and the fan is set to ...
  A: Curt, I missed the comment about the fan switch in the on position....my bad. I might need to ...
FUSE7/9/2009
  Q: I HAVE A RUUD 96% FURNACE, I JUST IN STALLED IT AND WHEN THE SAFTY SWITCH IS PRESSED THE POWER ...
  A: Cliff, Unhook the low voltage wires from the board , That come from the transformer. If you still ...
hvac fan issue7/9/2009
  Q: the fan starts and stops all of the time. the hvac side the the t-stat is off and the fan is set to ...
  A: Curt, Is this an old furnace? what kind? If you are willing to go through some trouble shooting ...
FUSE7/9/2009
  Q: I HAVE A RUUD 96% FURNACE, I JUST IN STALLED IT AND WHEN THE SAFTY SWITCH IS PRESSED THE POWER ...
  A: Cliff, You have a low voltage ground somewhere. Put your meter on ohms scale and with ALL low ...
Fan on AC unit won't start7/8/2009
  Q: The fan on my AC unit won't start up. The condenser appears to be ok, it makes the typical humming ...
  A: Jason, You probably need a new run capacitor, it is a duel capacitor and it also runs the ...
Condensor fan7/8/2009
  Q: I awoke this morning to a warm house of 76 degrees, when my thermostat is set at 68. As i began my ...
  A: Trey, Hi, spent some time in ft polk I know hot it can be there. Since you heard nothing run, it ...
Room will not cool down below 96 degrees.7/8/2009
  Q: I live in Texas. My second floor is on a separate A/C unit. I have replaced it twice because it ...
  A: Lynne, First lets make sure the unit is running correctly or nothing else is even worth looking ...
air handler bower motor7/8/2009
  Q: I recently change my fan control board for my inside AC unit. The original circuit board had a place ...
  A: Robert, You need high speed for cooling and a lower speed for heating. Give me model and serial. ...
heating up the cold side of a heat pump7/8/2009
  Q: My home uses a heat pump. In the winter the outside temp is about +32 f , here in Vancouver B.C. . ...
  A: John, I suppose if you built a football stadium and heated the air to 100 degrees that would work. ...
Attic verses crawl space.7/8/2009
  Q: I'm replacing my 15 yr old 4 ton heat pump system. My current system has the air-handler in the ...
  A: Sorry if I didn't make myself clear Dean, I said to put the one air handler in the space in the ...
Ruud vs Carrier vs Goodman/Amana7/7/2009
  Q: My 20 year old Rheem 3.5 ton and 3 ton central system are about to stop running. I live in Texas and ...
  A: Charlie, Carrier is also bryant day&night, and payne, all the same equipment with the same parts. ...
hvac/central air7/7/2009
  Q: I had a frigedaire furnace with central air unit and honeywell emm-3 minizone panel. I tried to ...
  A: Howie, Is this something new that has happened or an existing problem? From the small amount of ...
heatpump l/v wiring7/7/2009
  Q: old t.stat old furnace (electric) set up for heatpump, condensing unit being replaced its a ...
  A: Norm, I do not get any compensation, I volunteer before and after work. The orange wire should be ...
2 thermostats, 1 heat pump7/7/2009
  Q: I'm currently renting a two story townhouse (1500 sq ft); 2 therostats with 1 heat pump. Unit ...
  A: John, I would hope you have a 2 zone system for those 2 tstats or it will never work right. The ...
AC going on, off,on,off7/7/2009
  Q: I have an American Standard split system (propane). Condenser outside the rest in the attic. 5 ton ...
  A: Shawn, If it is contaminated then yes, it must be removed, evacuated properly and recharged. If ( ...
AC going on, off,on,off7/7/2009
  Q: I have an American Standard split system (propane). Condenser outside the rest in the attic. 5 ton ...
  A: Shawn, Your unit is cycling on high head pressure trying to protect itself. I am sorry for the ...
Fried contactor wire7/7/2009
  Q: Good evening Tim, Thanks for taking the time to help me out. I own a Goodman CE 30 !HB residential ...
  A: Terry, John Borgman here, got your question out of the question pool. It could be both or just a ...
Trane A/C compressor and coil7/7/2009
  Q: .. My Trane 1.5 ton 11 seer with 2 ton cased coil 14.5 w was put in January of 2005. The coil is ...
  A: Martha, If they find out it is dog urine, gonna be hard to hide it will not be under warranty , as ...
Air conditioner contracts7/7/2009
  Q: Trying to help out my elderly father down in Fla. He is asking me about getting a service contract ...
  A: Matt, A service contract is a preventative maintenance agreement that usually gives a discount for ...
Tech question on pressures7/7/2009
  Q: I have a quick question. question is: I have a 4 ton Comfort maker air conditioner that I changed ...
  A: Arric, You need to check for a txv and if you have pressure on the high side and none goes through ...
Central AC Unit Blower will not cycle on and off7/6/2009
  Q: I have a central AC unit, a Trane 5 ton. I set my thermostat to a specific temperature. The unit ...
  A: Sean, It is not uncommon for a fan switch to hang up. What I recommend is to pull off the door at ...
FUSE7/6/2009
  Q: I HAVE A RUUD 96% FURNACE, I JUST IN STALLED IT AND WHEN THE SAFTY SWITCH IS PRESSED THE POWER ...
  A: Cliff, You have a low voltage ground somewhere. First thing to do if your not real good with a ...
Tech question on pressures7/6/2009
  Q: I have a quick question. question is: I have a 4 ton Comfort maker air conditioner that I changed ...
  A: Arric, I doubt it is the compressor, more likely the txv at the indoor coil. To check the txv, ...
new units?7/6/2009
  Q: John -we live in Phoenix & have 2 Trane heat pump units that are 13 yrs. old w/seer rating of 11/12. ...
  A: Marcia, You can easily get another decade from your equipment if you have some preventative maint. ...
AC evaporator & filter7/6/2009
  Q: 2.5 yr old Summit evaporator leaking needs replacement - rest of system is Carrier - Houston, TX ...
  A: Joseph, Hi, this is John Borgman, got this question out of our question pool. The coil is not ...
Furnace Hums7/6/2009
  Q: 1984 ICG Gas Furnace. Occasionaly thermostat calls for heat, burner comes on but when motor should ...
  A: Ray, No need to check the transformer, it supplies 24 volts for the entire system and is always ...
T-stat temp is not met7/6/2009
  Q: Im a 5 yr. tech with my class 1&2 card, residential and comercial experience. Im helping with a unit ...
  A: Rene' Sure I would be happy to help a tech any time you have a problem. First when asking me a ...
Humidistat7/6/2009
  Q: I recently moved into a house that has a carrier humidistat next to the AC control, it looks fairly ...
  A: Cheril, There will be a unit attached to the side of the furnace like the ones in the picture with ...
Ac Thermostat-Inside House Blowing semi -cool7/6/2009
  Q: We had a power outage the other day, and we had to reset the S3000 Thermostat for our A/C Unit. Now ...
  A: Cindy, Actually the A/C unit is on the roof. You probably have an air handler in your ceiling. ...
AC not cooling enough - keeps running7/6/2009
  Q: I have 11 year old 5 Ton Carrier split-unit, just got 5-lbs Freon added, at least that's what the ...
  A: Paul, Drive around the back of any Ma and Pa store and see equipment that is 40 to 50 years old ...
heat pump7/6/2009
  Q: My YORK heat pump cooling system is not working efficiantly. I have it set at 73 degrees inside and ...
  A: Shawn, First turn the system off and run the fan in the ON position. This will thaw the indoor ...
AC not cooling enough - keeps running7/5/2009
  Q: I have 11 year old 5 Ton Carrier split-unit, just got 5-lbs Freon added, at least that's what the ...
  A: Paul, First Paul, if it was that low and had been added to last year they did you a disservice by ...
Ac Thermostat-Inside House Blowing semi -cool7/5/2009
  Q: We had a power outage the other day, and we had to reset the S3000 Thermostat for our A/C Unit. Now ...
  A: Cindy, It sounds like your outdoor unit has stopped running, have you looked at it and checked? ...
Daughter's Heat Pump7/5/2009
  Q: I just wanted to update you on my daughter's heat pump. We stayed with the same company since the ...
  A: Dorthy, I would like to thank your appreciation, I have just written a letter to the admin. of ...
trouble codes7/5/2009
  Q: York Diamond 80 model G/UA036A single flashing light= Lockout-check furnace...any help with what ...
  A: Vince, John Borgman here, got your question from our question pool. That means your equipment has ...
condenser shuts off but can restart7/4/2009
  Q: Our condenser unit will shut off after a few days. The house fan, [squirrel cage] keeps running. I ...
  A: Jerry, If it is the high pressure switch then your problem would have gotten worse after adding ...
Armstrong BCZ36B12N00A-3 condensate drain pan leaking7/4/2009
  Q: My drain pan slope is towards the back of the unit now, and it overflows and leaks into the ground ...
  A: Chase, It just needs to be shimmed at the back, it is not usually screwed in to anything, it sits ...
AC7/4/2009
  Q: 2 months ago we had work done to our Goodman AC unit- The first repairman cleaned coils and added ...
  A: Larry, You should not have had to pay for the first call, as it did not solve anything and how ...
Outside AC Unit stopped running7/4/2009
  Q: We have Train XR 11 outdoor ac unit (almost 6 years old) that has been working fine until this ...
  A: Derek, Check your breaker and next there is a fused disconnect on the house next to the outdoor ...
Starter kits7/4/2009
  Q: My service tech told me the capacitor for my unit is $259.00, I found it on line for $88.00 bucks. ...
  A: Warren, First you must understand that a business must make money on labor and parts mark up that ...
Furnace Hums7/3/2009
  Q: 1984 ICG Gas Furnace. Occasionaly thermostat calls for heat, burner comes on but when motor should ...
  A: Ray, First thing would be to check the amp draw of the motor, it should be about 70 to 80 % of the ...
rheem heat pump, outdoor fan and compressor not start7/3/2009
  Q: I have a Rheem heat pump. model no is RMPC-024JAZ. when call for heat or cooling, the compressor ...
  A: Yves, It sounds like you either have a bad run capacitor or you have a power problem. Next to the ...
Heat Pump Air Handler7/3/2009
  Q: I live in the Phoenix Az area where most homes have a Heat Pump. Original Owner of my home for over ...
  A: Sorry...furnace means you have either a gas back up or electric, both are called a furnace, the term ...
Heat Pump Air Handler7/3/2009
  Q: I live in the Phoenix Az area where most homes have a Heat Pump. Original Owner of my home for over ...
  A: Marty, That's a good one and I can tell you right now it will take some one there with eyes on and ...
Temperature of air out a supply vent7/2/2009
  Q: What is the temperature at a supply vent for a home a/c? Mine is 58-59 degrees. The temperature at ...
  A: No, 20 degrees is the rule of thumb, you might have a dirty filter or a few ounces low on charge, I ...
Carrier A/C issues7/2/2009
  Q: I have a 3.5 ton carrier a/c unit that was installed three years ago. My house was built three ...
  A: No Jeff, the blower wheel is way heavier and has more static pressure than the fan blade. Did you ...
AC Coil replacement7/1/2009
  Q: The AC 1st main drain line goes to the main master bath under the sink. The 2nd drain now ...
  A: The first drain is the rusted drain pan and the color that the water is tells that they are correct. ...
2nd Opinion7/1/2009
  Q: Greetings from another Expert at allexperts.com (I'm in the Excel and Geocaching categories)! My ...
  A: Two sizes copper pipe, it gives with the gauge pressure what we call superheat and sub cooling, ...
Choosing a High Seer Central Air Conditioner7/1/2009
  Q: John, I live in LA. Have had a contractor determine that i need a 5 ton unit. I know want to ...
  A: Marlon, Carrier, bryant, day&night, payne are all the same unit and all of their 410a equipment is ...
2nd Opinion7/1/2009
  Q: Greetings from another Expert at allexperts.com (I'm in the Excel and Geocaching categories)! My ...
  A: Nathen, Something does not add up. If you have a 5 ton fan and duct system the evaporator coil ...
air conditioner7/1/2009
  Q: my breezair evaporater,the motor heats up after working for two hours only why.the other ...
  A: Mulowoka, All motors heat up, but should never heat to 30degrees c temperature rise above the ...
Ductless A/C7/1/2009
  Q: John, am in the process of planning our retirement home to be built in the Texas hill country. Am ...
  A: Ron, How well they work will depend on windows , insulation ect. If you do have a cold spell I ...
Carrier A/C issues7/1/2009
  Q: I have a 3.5 ton carrier a/c unit that was installed three years ago. My house was built three ...
  A: Jeff, Yes you have some issues, either the unit is not sized correctly and or your duct system is ...
Condenser in furnace froze and now..7/1/2009
  Q: I replaced the filter in my furnace about a week ago. I usually keep the AC in the house around ...
  A: Gary, that is why it is frozen in your evaporator, the fan isn't running. It will use the black ...
Water Source Heat Pump6/30/2009
  Q: To qualify my position I have a background in A/C & Refrig. but have been out of that business for ...
  A: John, First thing you do is reverse the flow in heat mode and that will eliminate the metering ...
Sealing return air vent6/30/2009
  Q: A neighbor suggested the following tip passed on from an HVAC technician to improve cooling on the ...
  A: Raf, Tell your neighbor not to do that, unless somehow( and I would bet not ) they over sized the ...
TXV Valve install6/29/2009
  Q: I have a 3 yr old Trane unit that has been diagnosed with a bad TXV valve. The part cost is covered ...
  A: Bill, Standard practice is to pump the refrigerant to the other coil , lock it down and re use it. ...
a/c question6/29/2009
  Q: I have no low voltage to my outside unit.tried the volt test at thermostat from common to red wire ...
  A: Doug, Next to your furnace is there a condsensate pump, it has the pvc from the coil dumping in ...
What kind of info/testing should be done to determine replacement AC?6/29/2009
  Q: I live in Kansas, where it's hot and humid in the summer, dry and cold in the winter. My home is ...
  A: James, Take advantage of the contractors coming to your home, who can see what you have in the way ...
Drip Pan on furnace6/29/2009
  Q: Where is it located? Can mold be found in it? We have a new Trane AC unit and a Trane 2 stage ...
  A: Fred, John borgman here, got this question out of the question pool, I think in my hurry I ...
is this system overcharged6/28/2009
  Q: the outdoor ambient temp is 90 the indoor ambient temp is 74 the suction psi is 61 the line temp at ...
  A: Then everything is as it should be. Your in a high humidity area and the tstat should be set at the ...
Geothermal HVAC systems and problems6/28/2009
  Q: I am considering replacing my nineteen year old HVAC system with a geothermal system. Would you ...
  A: Bob, John Borgman here, got this out of our question pool. Lets start with if you cannot find ...
is this system overcharged6/28/2009
  Q: the outdoor ambient temp is 90 the indoor ambient temp is 74 the suction psi is 61 the line temp at ...
  A: Terry, First when asking this question the proper terminology is suction line temp and liquid line ...
AC variations6/28/2009
  Q: My wife has a problem with the bedroom temperature in the summer. She is complaining that our AC ...
  A: Alex, The thermostat controlled attic fan will do wonders for the small expense it requires, it ...
A/C6/28/2009
  Q: I am installing a Goodman 4 ton 16 seer and we are moving it to the back of the house and it will ...
  A: Frank, Your first step is to have a licenced tech come and pump the refrigerant into the outdoor ...
Problem with leak checks/coils6/27/2009
  Q: Last summer my air conditioning unit in my house stopped cooling. We have a home warranty, so we ...
  A: Fred, You should find a company that is not trying to milk insurance money. First of all, neither ...
My HVAC unit sweats6/27/2009
  Q: My ac sweats when its nice and hot outside which I assume is normal but when I checked it today it ...
  A: Johnny, Is this a heat pump in the heating mode? I am assuming so, because you cannot see the ...
Air Diffusers for exposed ducts6/27/2009
  Q: I live in an authentic open concept loft with 11 foot ceilings and 3 large windows along the main ...
  A: Mariana, Hi, John Borgman here, got this out of our question pool. The main heat gain/loss in ...
can't feel air coming out of ceiling vents6/27/2009
  Q: we just bought our first home yesterday and realized we can't feel air coming out of the ceiling ...
  A: Mary, You need to get someone to your home that knows what they are talking about to look at your ...
estimated coet of ac (leak) repair6/27/2009
  Q: my ac unit in attic is leaking water. i noticed when water begin dripping through ceiling in ...
  A: John borgman here got this question from our question pool. Whatever the cost it will be less than ...
Trane Air conditioner unit6/27/2009
  Q: I broughta Trane 2TTX5030A1000AA heating and airconditioner unit from a local company in arkansas. i ...
  A: Vernita, There really is no lemons in this industry, just poor installation and service work. ...
Coleman ac unit put newfan on outside unit6/26/2009
  Q: My husband just put a new fan on the outside unit and now the compressor will not kick on. what ...
  A: Shannon, You are going to need a service call. That does not sound good at all, the compressor ...
a/c fully charged and running but not getting cold6/26/2009
  Q: I am fully hvac certified I have a unit that is running and the right preasure but the suction ...
  A: Rev, Give me the following info and I can tell you ( if the evaporator was clogged you would have ...
cooling problem/air in line6/26/2009
  Q: I live in NC and have an 11 year old Carrier split system for my upstairs. Recently, the system has ...
  A: Greg, Sounds fishy, if there were non condensibles ( air ) in the lines it would have been fro the ...
heat pump6/26/2009
  Q: The air conditioner blows hot. During the winter it would work ok but the little return line was ...
  A: Lyle, John Borgman here, got this from our question pool. The large insulated copper line should ...
hvac replacement6/26/2009
  Q: We have a Carrier Weathermaker 9200 gas furnace and a 2 1/2 ton airconditioner that were installed ...
  A: Fran, It really all depends on how well the furnace was maintained, as far as how much life is ...
drip pan for tempstar furnace6/26/2009
  Q: My Tempstar furnace is leaking around the bottom of the drip pan. What do I need to do? mdl# ...
  A: Anthony, Usually this is a result of the coil freezing up in the indoor coil and when the ice ...
A/C wont cool6/26/2009
  Q: Let me preface that I'm an auto tech by profession, so forgive me if my terminology is incorrect. ...
  A: Dusty, Yes a little mix up.Your low side psig reading is a little low and the way to set the ...
A/C wont cool6/26/2009
  Q: Let me preface that I'm an auto tech by profession, so forgive me if my terminology is incorrect. ...
  A: Dusty, You are way low on refrigerant.Your head pressure at that ambient temperature should be in ...
airconditioning problem6/26/2009
  Q: My thermostat is set at 78 degrees, yet the temperature inside reaches 85 degrees. I change the air ...
  A: Michael, If your filter is clean and vents are open, go check the large copper insulated pipe that ...
evaporator coil6/25/2009
  Q: Our AC unit was no longer blowing cold air through the vents in the house, so we called a service ...
  A: Tiffany, You had to have been without cooling or air flow for a long time for it to have made a ...
new coils or new furnace?6/25/2009
  Q: We replaced or home condensor 8 years ago. Last spring or pressure was low and was checked again ...
  A: Lynette, John Borgman here, got this question from our question pool. Yes to can units be ...
Squeaking noise from AC6/25/2009
  Q: I have a 5 year old Carrier Central AC. It runs OK, but about 30s after the AC stops, it give out a ...
  A: What??? Tell that tech to go back to school. You are hearing the system equalize its pressures ...
HVAC6/25/2009
  Q: Coleman hvac,blower inside will come on and go off continuously once set temp is reached. Outside ...
  A: Bill, Hi John Borgman here got this from the question pool. You have an issue in the furnace. ...
Brand new unit (fan runs all the time)6/25/2009
  Q: Brand new 4 ton 15 seer pkg Goodman heat pump fans runs constantly. Ex: temp set 75 degrees, ...
  A: Yes, The fan should cycle off at the end of a call for cooling., unless the fan is set up by ...
a/c has a leak how to find it.6/25/2009
  Q: i have a 2.5 ton bryant heat pump that loses alot of freon. it holds 8 pounds and i put 6 pounds in ...
  A: Terry, Since none of the techs that were there adding freon noticed oil dripping everywhere and ...
a/c has a leak how to find it.6/25/2009
  Q: i have a 2.5 ton bryant heat pump that loses alot of freon. it holds 8 pounds and i put 6 pounds in ...
  A: Terry, That is an incredible size leak. First of all do not use it any more till you get it ...
Fan/motor not running out outside TRANE unit6/25/2009
  Q: This is probably a typical problem, but I thought I would ask. The inside fan is running, so power ...
  A: Julian, You have an upstairs and downstairs with both air handlers running off the same breaker? ...
Furnace Return Make-up Air Questions6/25/2009
  Q: I am installing a 40K btu 92% nat gas furnace (horizontal mount). I have a concentric vent/supply ...
  A: Jason, Make up air is fresh air brought in because homes are built so tight now that we breath all ...
Trane AC6/25/2009
  Q: I have a trane 4ton unit that was made in 2000. Sat I started action up and the compressor wasn't ...
  A: Jim, I am sorry I really cannot understand what you are asking? I know of nothing that is a prv?? ...
Rheem6/24/2009
  Q: I am looking at a 3 ton rheem its about 12 years old.It will not take any freon my suction is at 45 ...
  A: Joe, At 45 psig it should take refrigerant, because your jug should be about 100 psig. You might ...
AC tripping circuit breaker6/24/2009
  Q: My older AC compressor unit is drawing too much power on start up and tripping the breaker. ...
  A: Sue, It really shouldn't be able to start a fire, but it can be damaged and need to be replaced, ...
A/C return vents6/24/2009
  Q: I am replacing my old return vent with a larger one. This is the only one in the home that i know ...
  A: Matthew, Yes to a.) and the return size of the vent is only critical that it is not fewer square ...
Hot second floor. Need an air return?6/24/2009
  Q: I have a 100 year old 2 story home. The main floor is adequately cooled, but the second floor is ...
  A: Steve, One of the things you should consider, regardless of every thing else is a thermostat ...
Stop Smoke in Dual Zone System6/24/2009
  Q: I have a duplex rental with one HVAC system. Each unit has a thermostat and a return. One tenant ...
  A: Eric, You can install an activated charcoal filter to control odors. The problem with them is ...
Keeprite central air6/24/2009
  Q: We are new to owning a house and have never had central air before. So I was wondering how to turn ...
  A: Crystal. No, Crystal it runs off electricity. The thermostat has a system switch that has a cool ...
Residential Air Conditioning/Furnace6/24/2009
  Q: After I put on the AC it only runs for about a minute and then shuts off, without bringing the ...
  A: Tim, turn the "Fan" switch on the thermostat to the ON position by itself and see if the blower ...
plastic drain pan leak6/24/2009
  Q: we had an A/C company out last week to clear a clogged line. he cleared the line but then told us ...
  A: Mark, If the tech sealed up the crack there is no reason to replace it. Does the aux. pan have a ...
Air conditioner6/24/2009
  Q: My air conditioner will not cool below 75 degrees during the hottest part of the day. Please advise ...
  A: Nodea, I already answered this question, why didn't you check the insulated copper pipe where it ...
Residential A/C Dye Test6/24/2009
  Q: John - our A/C Company said we are leaking freon and just did a dye test for almost $100. I ...
  A: Brian, You are asking the wrong person because.....it will get me on my soap box. As a ...
Air conditioner6/24/2009
  Q: My air conditioner will not cool below 75 degrees during the hottest part of the day. Please advise ...
  A: Nodea, The way to tell if your A/C is close to being set up correctly is as follows. First make ...
Gibson heat pump not cooling6/23/2009
  Q: I have two Gibson units for my home, one for upstairs and one down. Both installed in 2003. The ...
  A: Steve, The click you heard was the contactor pulling in, which is good it is supposed to on a call ...
Gibson heat pump not cooling6/23/2009
  Q: I have two Gibson units for my home, one for upstairs and one down. Both installed in 2003. The ...
  A: Stave, Yes another tech that knows his job. at the outdoor unit, there is a large copper pipe ...
cooling temperature control6/23/2009
  Q: cndMy wife sets the t-stat about 5 degrees higher when we leave in the morning (and we argue about ...
  A: Bill, I don't like to get in marital disputes....lol An A/C by design is ment to hold temperature ...
Blower always running6/23/2009
  Q: Alright last winter the heat on my unit wuit working, the blower and the inducing fan always are ...
  A: Christina, John Borgman here, I got this question from our question pool. Could you provide me ...
HVAC system6/23/2009
  Q: We installed a new frigidaire hvac unit in 2004. We have had nothing but trouble w/ the temperature ...
  A: If the outdoor unit is not running and the indoor is, check the tstat. Is the fan switch set to the ...
TXV valve6/23/2009
  Q: My downstairs air conditioning stopped cooling a week ago. It is a Bryant 5 ton system that is only ...
  A: Steve, I don't have a cross reference guide to tell if the replacement was correct, but it ...
AC Unit6/23/2009
  Q: I went outside to check Ac the fan wasn't runining and it was real hot on back of fan motor. The ...
  A: Charles, Hi John Borgman here got this from our question pool. With the power off to the outdoor ...
HVAC system6/23/2009
  Q: We installed a new frigidaire hvac unit in 2004. We have had nothing but trouble w/ the temperature ...
  A: Jennifer, Wow, what a horror story......You have a freon leak, but it is not at the indoor coil ...
Outdoor A/C no longer functioning with new furnace.6/23/2009
  Q: We recently had our old (Olson Duomatic) mid-efficiency furnace replaced with a Trane Xv95 (model ...
  A: Renay, Just curious where in Europe are you? Anyway the thermostat will send a signal through the ...
home ac unit6/23/2009
  Q: i have a heating and cooling guy out here now.had ac installed two years ago and the system looses ...
  A: Mike, If he took it to 400 psi and it held there is no leak, at least not one that could happen ...
poor airflow in finished attic6/23/2009
  Q: I have a small home built in the 1940s that has been expanded twice. The original house is about ...
  A: Dave, The inline blower would create as much resistance as it produces. My biggest question is why ...
Air handler and compressor not turning on6/23/2009
  Q: I have a spacepack a/c system and a hot water boiler as my HVAC system in my house. I replaced the ...
  A: Benjamin, When a thermostat has an Rc it also has an Rh. Those two need to be jumped for heat and ...
York Diamond 80 - 9 Flashes6/23/2009
  Q: I have a York Diamond 80 heating and central air conditioning unit. When I turn it on, it flashes 9 ...
  A: Donald, John Borgman here got this from our question pool. It means that something has gone to ...
Bryant vs Payne 3 ton 13 SEER heat pump/ac unit6/22/2009
  Q: Our Bryant 3 ton 13 SEER heat pump/ac unit went out and we had to fight with FirstAM Home Warranty ...
  A: Linda, Payne, Bryant and Day and Night are all Carrier, they give different names and different ...
price of central air6/22/2009
  Q: i have a 1976 model 14x70 trailer house. it has cental heat but not air. a family member of mine ...
  A: Joseph, No, only one per breaker, those are run load amps. When the window unit starts it pulls ...
Which air units to buy6/22/2009
  Q: John, Help, our air conditioning went out this weekend and we have had 3 people trying to sell 3 ...
  A: Kim, The Trane would be the $5,700 it is always the most of those three, Payne is the middle of ...
Hard Start Kit for small A/C system6/22/2009
  Q: I have a small ductless mini split system (Heat Controller, Inc.) that conditions a room over a ...
  A: Ron, Cost of call was reasonable, as far as the rest, no way to tell without, being there and ...
ac window unit cycles compressor on off6/22/2009
  Q: we have a small ac window unit that has begun to cycle the compressor on and off every 5 minutes or ...
  A: Keith, The problem with window units is that since you can get a brand new one at home depot for ...
Intertherm A/C Leaking6/22/2009
  Q: We have an Intertherm A/C and heat pump in a double wide mobile home. The inside unit is leaking ...
  A: Claudette, A couple of questions for.....All vents open and not covered? Is your filter clean? ...
residential a/c6/22/2009
  Q: what should the proper pressures be (high and low side) on a 410A system thanks ANSWER: Woody, ...
  A: Woody, In looking over your numbers briefly, I need to know if in fact the supplies and the ...
Air Conditioning: Keep basement door shut?6/22/2009
  Q: We have a carrier system that is about 7 years old installed to cool main floor and walkout ...
  A: Connie, No, shutting down vents is never a good idea as far as efficiency and longevity of your ...
added misters to AC6/21/2009
  Q: I ran a 3/8" water line up to my roof mounted AC/Heat pump and installed misters above the intake ...
  A: Allan, I wouldn't recommend the mister due to the affect it has on the head pressure of your ...
expansion valves6/21/2009
  Q: what are the steps to change them out
  A: Robert, All refrigerant must be recovered or pumped to the other side of the service valve from ...
air conditioning6/21/2009
  Q: How to reduce the static pressure like form 0.35wc to 0.25wc,and is that mean I have problem with my ...
  A: Sam, The static pressure would increase with fan speed, the filter could be dirty, the duct system ...
Attic heat re-circulation...6/21/2009
  Q: ..my attic is obscenly hot while my house is too cool. I'd like a solar-powered (12v) duct inline ...
  A: David, Answer is the same and I have had a couple of people that I spent good amount of time re ...
Adding R-410A6/21/2009
  Q: I used to charge my home AC system when R-22 was common. I've added R-22 in both liquid and gas ...
  A: Don, That is a HUGE leak and your service company are very incompetent . I could find that leak ...
ruud central a.c.6/21/2009
  Q: I have a ruud central a.c. older model maybe 30 years old. About a week ago it started noticing that ...
  A: Ed, you will take a huge chance on damage if you continue to use the A/C. Could possibly take out ...
ruud central a.c.6/21/2009
  Q: I have a ruud central a.c. older model maybe 30 years old. About a week ago it started noticing that ...
  A: Ed, It is physically impossible for the refrigerant to flow into the condenser when the compressor ...
Adding R-410A6/21/2009
  Q: I used to charge my home AC system when R-22 was common. I've added R-22 in both liquid and gas ...
  A: Don, The reason for not trying to add 410a on the high side is that, the standing pressure in your ...
residential a/c6/20/2009
  Q: what should the proper pressures be (high and low side) on a 410A system thanks ANSWER: Woody, ...
  A: Woody, Are you sure that you are on a 410a system? Something is terribly wrong if you are. The ...
Time to Replace All6/20/2009
  Q: House is 25 years old and I suspect unit in attic is that old. Coleman blend air system upstairs and ...
  A: Francis, John Borgman here, got this out of our question pool. If you replaced the duct system ...
white-rodgers digital thermostat6/20/2009
  Q: the thermostat often shows the temperature as getting warmer as the air conditioner is running. It ...
  A: Karen, Yes the pipe will drip there more than other area's due to the high humidity. If it is ...
Solder or braze AC outdoor unit repair6/20/2009
  Q: York central air outdoor unit approx. 2 years old. AC stopped cooling. Repair tech found no R-22 in ...
  A: Ken, Actually I appreciate the long response, gives me a lot more to go on. oxy/acetylene is the ...
Corroded Coils?6/20/2009
  Q: I have a Day and Night residential 3 ton unit and the unit is ground-mounted on a cement slab next ...
  A: Jim, Yes urine can do that....bad dog. But just because the techs electronic detector sounded, ...
Attic heat re-circulation...6/20/2009
  Q: ..my attic is obscenly hot while my house is too cool. I'd like a solar-powered (12v) duct inline ...
  A: David, It doesn't work that way, David. Even if you have no insulation under your home, that ...
ac unit won't cool6/20/2009
  Q: I have turned on my unit, which is 8 years old, and it runs but doesn't cool at all. I assume it ...
  A: Ken, I will assume you mean that just the A/C is outside and that you have and indoor furnace/air ...
Insulation on Return Air Ductwork6/20/2009
  Q: Mr. Borgman, I live in northwest Florida. The humidity and heat here are often very high. My home ...
  A: Shawn, Call your local utility company and ask that question. The reason for this, is, they might ...
white-rodgers digital thermostat6/20/2009
  Q: the thermostat often shows the temperature as getting warmer as the air conditioner is running. It ...
  A: Karen, First you shouldn't have any type of devise pulling hot air from the attic. Are you saying ...
Frigedaire central air conditioner6/20/2009
  Q: what causes the inside panel to fry, and how hard is it to replace? my air conditioner didn't work, ...
  A: Karen, Got this question from our question pool. A lot of things can cause the " board " to burn ...
central AC noise inside unit6/20/2009
  Q: While running it sounds like a fan is rubbing under the inside coil. Unit is 2 years old
  A: Jim, The set screw that holds the blower wheel onto the shaft of the blower motor sometimes is not ...
Solder or braze AC outdoor unit repair6/