| Subject | Date Asked |
|
| A/C Question - Goodman CK-42-1B | 7/12/2009 |
Q: when that satisfying sound of the compressor springing to life stopped happening and just the fan ... A: Well hello again Don. I have been in this business since 1973 & it has always been fun(well most of ...
|
| AC fan stays on after AC is off | 7/12/2009 |
Q: Replaced an old t-stat recently with a new programmable t-stat (ritetemp model 6025). Initially had ... A: The O is not to be connected to O. Is this a heat pump ? Doesn't seem to be. The white is for heat, ...
|
| A/C Question - Goodman CK-42-1B | 7/12/2009 |
Q: when that satisfying sound of the compressor springing to life stopped happening and just the fan ... A: nice to have good info like yours. Need to test the run capacitor for the compressor first.May be a ...
|
| Raindown furnace flu | 7/11/2009 |
Q: Howard. I'm having a problem with rain coming down the "inside" of my Gas furnace flu. I have tried ... A: wishyou would send the rain over here in TX. We are 106 every day, no rain, Only thing I can imagine ...
|
| air running (not continuous) - apt humid! | 7/9/2009 |
Q: Livingston, Thank you so much for being there for all of us who are out here (literally)sweating ... A: Gladto "try" to help your not=to=good situation. Hope for your comfort & recovery. I have ...
|
| attic fan | 7/9/2009 |
Q: I am planning installing an attic fan in my 2-story house. My attic size is approximately 1200 ... A: The soffits vents will work === but if you remove one you will probably see a much smaller hole has ...
|
| Air Conditioner kicks off breaker | 7/6/2009 |
Q: As the weather warmed we noticed our AC was not working on the main floor (we have a separate unit ... A: Could be a bad capacitor on the outside unit fan. Have you watched the unit while it was running ?? ...
|
| No Cool Air After PG&E Smart AC Program | 7/5/2009 |
Q: My question is... My central AC worked great until last Tues. afternoon when during the sweltering ... A: Oh Jennifer, never saw so much ineptitude in one place !! The guesswork on the 50 amp breaker shows ...
|
| carrier unit condensor valve cores | 7/5/2009 |
Q: Do older Carrier units have a valve core on the suction side that cannot be removed if they are ... A: Been at it since 1973 & have never seen a unit without removeable schrader valve. What can happen is ...
|
| Roof top AC | 7/4/2009 |
Q: I have a 1976 Coleman rooftop AC unit on my Motorhome, It runs OK, not the coldest, but after a ... A: sually there is not a service valve on those things. But you can buy a clamp made for the diameter ...
|
| Roof top AC | 7/4/2009 |
Q: I have a 1976 Coleman rooftop AC unit on my Motorhome, It runs OK, not the coldest, but after a ... A: 33 years old !!!! They made good stuff then. Not anymore. Fan motors is the favorite thing to ...
|
| Goodman GMP07-3 | 7/3/2009 |
Q: my Goodman unit's inside fan is running constantly. The outside unit will not turn at all, no fan, ... A: Manually press in the contactor in the outside unit & see if it runs. Test the freon to see if has ...
|
| tapping into air ducts | 7/1/2009 |
Q: I finished our basement a few years ago and did not think we needed to tap into the ducts for air. ... A: you can do it. Whatever size duct you tap into you would need a Y fitting with a 45 deg side outlet ...
|
| Carrrier Furnace 58XTS070 placement | 7/1/2009 |
Q: We got this Carrrier Furnace 58XTS070 last year when it was installed in downflow format. We are ... A: I presume the furnace is electric heat ?? The coil drain pan & drain lines is the problem. I don't ...
|
| New AC Unit tripping breaker | 6/30/2009 |
Q: We have a 14 seer Goodman unit that is 13 months old. On Saturday we noticed there was no cold air ... A: I would start off replacing the circuit breaker. They can fail like everything else. Did the tech ...
|
| Iced Pipe on Trane Unit | 6/29/2009 |
Q: We have a Trane XL19i Super High Efficiency heat pump that was installed in 2004 that doesn't seem ... A: Hate to say it but these evaporator coils they make nowdays can start leaking in a couple of ...
|
| SWAMPED PACKAGE UNIT | 6/29/2009 |
Q: I probably have a wild question, but I'm looking at 2 International Comfort Package units: ... A: Look at the serial number for a year date in it. Like 184702432. See the 02 ?? I'd think if they are ...
|
| AC variations | 6/28/2009 |
Q: My wife has a problem with the bedroom temperature in the summer. She is complaining that our AC ... A: I would suggest a new thermostat, like a Honeywell gold round one from Home Depot or elsewhere. They ...
|
| Central air | 6/26/2009 |
Q: Help! On house is on the market and we just realized our central air isn't working. We want to fix ... A: Got my email ?? Its a control circuit problem. !!! So lets carry on with the diagnosis. It can be ...
|
| low voltage problem | 6/26/2009 |
Q: okay let me start by saying i am a residential/commercial service tech. my question is one, more for ... A: Are you getting 24 v between Y & C on the board WITH THE RED & WHITE wires to the outside unit ...
|
| Evaporator Coil/Furnace | 6/25/2009 |
Q: I had and two ton condenser installed last year. When I turned the air on this year, the thermostat ... A: 1. Only if enough oil has leaked out with the freon. Generally does. 2. Look below the burners for ...
|
| hvac | 6/25/2009 |
Q: Our air handler is (Friedrich) over 22 years old and the compressor is dated 1991, very few problems ... A: Florida is the best place in the country for heat pumps. You hardly EVER use the electric heaat. Its ...
|
| Evaporator Coil/Furnace | 6/25/2009 |
Q: I had and two ton condenser installed last year. When I turned the air on this year, the thermostat ... A: 1. Yes just find one that fits the case. 2. Not unless the heat exchanger is rusting out. 3. Usually ...
|
| Heating, Air Conditioning HVAC - Rheem Classic 10, fuse | 6/25/2009 |
Q: Everything (heating or AC) was working before. I turn on AC this year, control board fuse always ... A: Now its getting wilder Steve. I would disconnect the 2 wires to the outside unit at BOTH ends. With ...
|
| hvac | 6/23/2009 |
Q: We installed a new frigidaire hvac unit in 2004. We have had nothing but trouble w/ the temperature ... A: Reminds me of a problem with 2 heat pumps 2 friends had installed themselves. Both had compressors ...
|
| GMC Furnance | 6/22/2009 |
Q: Last year the AC tubing(copper)had ice on it. Had it checked to see what was causing the freeze up. ... A: It's 103 down here in Texas now Ramona, cooling is valuable, right ? The place to start on the unit ...
|
| HVAC Dual Zone | 6/22/2009 |
Q: My father-in-law has a dual zone system in his house. The house is about 1500-1600 square feet on ... A: Common problem with 2 story houses & an open stairwell. Difficult to fix since the cool air upstairs ...
|
| hacv | 6/19/2009 |
Q: Had my system repaired,condensing coil,blower motor and fin,charged system. -This is a slit system ... A: New repair parts work as good as old parts. If you have an electric furnace the elements can ...
|
| HVAC | 6/17/2009 |
Q: I have a model: E2EB-017HA 4ton unit. Ihave had the inside and outside coils cleaned, the technician ... A: Have you tested he run capacitor for the blower motor ?? How about the current draw when the motor ...
|
| A/C cooling but home is hot | 6/15/2009 |
Q: ! We have a Coleman blend air system - 4 ton in a 1782 sq ft mobile home built in 1996. Over the ... A: This sorta IM, right ? I'm retired so check in often. Keeps my brain active. The return is onthe ...
|
| A/C cooling but home is hot | 6/15/2009 |
Q: ! We have a Coleman blend air system - 4 ton in a 1782 sq ft mobile home built in 1996. Over the ... A: That phrase "it's doing all it can" is familiar. I've used it myself so I would accept that it is ...
|
| Condensation pan shut off | 6/14/2009 |
Q: Our AC shut off because the condensation pan was full. I emptied the pan, found and (hopefully) ... A: You have an emergency float switch on the drain line ??? Either that or a condensate pump are the ...
|
| HVAC air distribution | 6/13/2009 |
Q: I have a RUUD system in my house (Heat pump model # RPKA-031JAZ and air handler # RBHA-17J11NFDAI). ... A: You have an "extended plenum" duct system now. They work if, after each drop to a room the size ...
|
| Circuit Breakers | 6/12/2009 |
Q: In general, can a "defective" circuit breaker fail to pass electricity while in the "on" position ... A: good question. These things can be deceiving.hey will not reset to the ON position. Maybe a little ...
|
| Split AC Not Cooling | 6/11/2009 |
Q: I have a 1 ton videocon split air conditioner at my home. Most of the time it does not cool i.e. the ... A: You need to go see if the outside unit is running when the thermostat is calling for cool. Hold your ...
|
| P traps | 6/9/2009 |
Q: We have an inspector that is telling us that we HAVE to install P traps on A coils on top of ... A: Well I'm not much on codes. They are different in different places. I agree with you after 30 yrs ...
|
| heat pump blower quits sometimes | 6/8/2009 |
Q: I'm running my air conditioner, and I noticed that the blower is quiting at times and sometimes not ... A: The blower is triggered to run by the thermostat on a call for cooling. Check behind the tstat for a ...
|
| Hight pitch noise on the A/C furnace, only on summer | 6/6/2009 |
Q: is my second summer in a row with a high pitch noise coming from the A/C furnace. It only happens ... A: Well, I was going to say air noise but not ! There has o be a restriction in the high side liquid ...
|
| Commercial AC Temp Control | 6/6/2009 |
Q: I work in a 4 story building, 40,000 sq ft/floor. We are working hard to be green. We are in the ... A: Keep the fans running all the time & set the temps up to about 81 - 82. That is comfortable with air ...
|
| Corroded coils on furnace | 6/5/2009 |
Q: An HVAC technician just left after inspecting my upstairs unit, Carrier 38YCC, which is a little ... A: I presume you are referring to the evaporator coils ?? They are normally made from aluminum fins & ...
|
| problem with control circuits | 6/5/2009 |
Q: I have an HVAC degree and i am pretty decent with troubling shooting until it comes to double wides ... A: Electrical skills in this A/c business determines whether you are good or not. I worked with a guy ...
|
| American Standard Freedom 90 blower problem | 6/5/2009 |
Q: I have an American Standard Freedom 90 furnace with a brand new (yesterday) American Standard ... A: When in cool mode the thermostat activates the inside fan when cooling is activated. If you have a ...
|
| Multivolt gas valve | 6/4/2009 |
Q: My son has a gas pool heater that has a White Rodgers Multivolt gas valve with a 250 milivolt pilot ... A: The generator does hold the knob down on the gas valve. Its not producing the 750 millivolts to do ...
|
| Snyder General Fan Won't Stop Running | 6/2/2009 |
Q: Howard, I have a Snyder General Comfortmaker model # GUF100A012AN. The AC and Heating systems seem ... A: all those folks are correct. Your problem is "most likely" a stuck fan relay. You have a circuit ...
|
| evaporator water problem | 6/1/2009 |
Q: I have a trane vertical air handler with the coil at about a 60 degree angle. This system is about ... A: The fins are spaced to retain water. Your fins may look clean but have collected crud over the years ...
|
| AC Unit Float Switch question | 5/29/2009 |
Q: I have a Goodman air conditioner that was installed brand new in my condo in May 2005, when it was ... A: I don't dig the 2 pipes coming from the evaporator coil ? Something different here. Anyway, the ...
|
| Frozen AC pipes and AC runs as heat pump | 5/28/2009 |
Q: I got a new Goodman 5 ton heat pump system in Dec 2006. The system worked well until Jan 2009, at ... A: Looks like a stuck closed contactor in the outside unit. Running with out an inside blower causes ...
|
| AC Unit Float Switch question | 5/27/2009 |
Q: I have a Goodman air conditioner that was installed brand new in my condo in May 2005, when it was ... A: Ah, those float switches are there as an emergency only. Don;'t need them if the drain line for the ...
|
| air conditioner output air temp | 5/27/2009 |
Q: what should the temperature of the air coming out of the room register while the air conditioner is ... A: Good question, Jim but tricky. An eveporator coil operates at 70 deg. BUT, from there a bunch of ...
|
| rotten egg smell | 5/26/2009 |
Q: HOWARD---THIS IS NOT A QUESTION BUT THIS SAME SMELL HAPPENED TO US WHEN WE GOT OUR NEW HEAT PUMP ... A: Are you the one that reported the smell a few days ago ??? I had another question about that & don't ...
|
| Luxaire a/c unit loses all freon 4 years in a row | 5/25/2009 |
Q: The short of the story is this: I had 2 Luxaire Outdoor Split-System air conditioners installed in ... A: Freon leaks can occur ANYWHERE !! A 7 day leak should be able to be heard 100 ft away. But I have ...
|
| No Power | 5/25/2009 |
Q: we have a Heil DC 90 Ultra High Efficiency with model # beginning with NTGM. We have not used our ... A: Wait to call a tech. This is for free. Look for a 3 amp fuse, automobile type, plugged in to the ...
|
| restart eletronic furance | 5/24/2009 |
Q: windy weather,so the gas furance and water heater went out. started the water heater,no problem. ... A: How about 85 in Texas.Gas pilot lights are blown out by high winds bacck pressure down the flue ...
|
| Somewhat of a rotten egg smell emitted out of a brand new system | 5/24/2009 |
Q: Howdy sir. I will try to use to use all the technical lingo I can, and what I have tried so far to ... A: Jon, I have the answer !!! Just got a reply from "Shirley" that solves the problem. The rotten egg ...
|
| Central Air Install/Quotes | 5/23/2009 |
Q: I have been getting estimates for central air install w/duct for my old colonial home in northern ... A: The only advantage I've seen for variable speed blowers is quiet. If a return air grille faces a ...
|
| Janitrol compressor trips breaker | 5/21/2009 |
Q: I have a Janitrol compressor that occasionally trips the breaker. If I reset the breaker (off and ... A: Good question, difficult to answer. Many things can be the fault. First try tightening all the ...
|
| A/C charge | 5/19/2009 |
Q: should refrigerant be added until the sight glass shows no bubbles?Does this work on all systems?No ... A: It's better than nothing Gregg. But it can show bubbles & be over/under charged. The type of ...
|
| mold in air duct system | 5/19/2009 |
Q: Cladosporiium and another non flower mold was identified to be in my flexible air duct system ... A: Duct cleaning in flexible ducts is no good. Probably will tear them up with that plastic tube. ...
|
| smell of natural gas | 5/18/2009 |
Q: Mr. Livingston, I am hoping you can give me some direction concerning a problem with my Central A/C ... A: Glad its not CO are you'd be a goner. Couldn't smell it anyway. Is the furnace a gas unit ?? You ...
|
| noise from Lennox G40UH xseries | 5/17/2009 |
Q: Howard, thought I might need to change a fan belt or oil a motor but now I see no belt...squealing ... A: Belt driven blower motors stopped many years ago. Sure had to keep many, many sizes on the truck. No ...
|
| Rheem heat pump indoor motor does not run | 5/17/2009 |
Q: Howard, I have a 1991 Rheem 2.5 ton all electric heat pump system. In cool mode, the indoor motor ... A: If the furnace controls is a solid state circuit board the fan replay is a little black box on the ...
|
| Rheem heat pump indoor motor does not run | 5/16/2009 |
Q: Howard, I have a 1991 Rheem 2.5 ton all electric heat pump system. In cool mode, the indoor motor ... A: In cool mode & fan in auto, the thermostat turns on the fan. If you have a digital tstat, have had ...
|
| CO Level | 5/16/2009 |
Q: What level of CO is acceptable in the airstream heating the living area? A: Good question, difficult answer. That's because everybody has different tolerence to CO. Thats why a ...
|
| AC question | 5/15/2009 |
Q: I own a condo with roughly 1500 sq ft of livign space (2 stories). The AC unit (which is a heating ... A: WOW !!!! 10 grand !! Must be awful hungry.Talk to your neighbors or friends for recommendations of ...
|
| temps | 5/15/2009 |
Q: Is there a standard for temp differences from outside to inside to determine how well insulated a ... A: Good question. There is a rule of thumb that is surprising. Here it is. With a good accurate ...
|
| Cold Room Air Flow | 5/12/2009 |
Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ... A: From the installations I have done a 6' line can only cool a small bathroom !! And a 4"ine to a ...
|
| Cold Room Air Flow | 5/11/2009 |
Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ... A: Got a chance to respond today. 20 ft for a 6 " ?? Does the "extended supply air plenum" it's called ...
|
| Cold Room Air Flow | 5/10/2009 |
Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ... A: A 6" duct will not supply very much air more than 10 feet length.Was that room added or is the 6" ...
|
| One room hotter than the rest | 5/8/2009 |
Q: I’m sure you hear this one a lot. I bought my house last summer. It was built in 1995 and is about ... A: It's a shame the duct systems are installed so badly.Air distrubition is so important. It adds to ...
|
| Compressor terminal prong corroded | 5/7/2009 |
Q: I have a Bryant split AC system installed in 1997 (Model # 561CJ030-C). It tripped the circuit ... A: Hope thats all it wasn the burned terminal. Is there ANY stub left on the compressor terminal?? If ...
|
| fan doesnt always come on | 5/6/2009 |
Q: Big fan doesnt always come on when air condition is running on outside gas heat and air? Is this ... A: Whoa ! A different picture ! It's icing over the evaporator coil, blocking the air flow. Probable ...
|
| Carrier Infinity 96, 40000 BTU | 5/5/2009 |
Q: We've just had this unit installed after our old oil furnace went kaput, using the same duct work ... A: Fans has speed adjustments but the increase from one to another is 50 rpm. Not much but can help. ...
|
| A/C Brands | 5/5/2009 |
Q: I think we're going to replace our central air unit this summer. Do you have any preference on ... A: How much money you have ??? I'm a "conservative" ie tightwad. Make sure the new stuff uses R 410a ...
|
| Outside Unit - Fan & Compressor not turning on - electrical? | 5/4/2009 |
Q: I'm hoping you can help me out with my Bryant Air Conditioner outside unit. The outside unit won't ... A: Start off testing for power supply to the outside unit by pressing in the start relay manually. If ...
|
| Coile and duct work needed | 5/3/2009 |
Q: I have a 5 year old 4 ton system that continues to freeze up. I am constantly told the Freon is ... A: You need more bids. At least 2 more. Ask your neighbors for their recommendation or co workers. Your ...
|
| wiring for 24 volt transformer | 4/29/2009 |
Q: I put a new control or mother board on a goodman heat/air unti, wiring a 110/230 24 volt transformer ... A: Well, the control circuit board controls the heating unit, so the transformer has to connect to ...
|
| Trane XT500C heat pump wiring | 4/29/2009 |
Q: I have a trane heat pump xt500c thermo. and am trying to find out what each wire goes to so I can ... A: Heat pump tstats have changed lately. Have had trouble myself matching the combination terminals ...
|
| HVAC Duel System | 4/27/2009 |
Q: I just bought a home with a Duel zone system, one for upstairs and one down. My question is: when I ... A: hat's a good one, Michael ! Maybe there is a diverter in the ducts somewhere is all I could imagine. ...
|
| Home A\C compressor | 4/26/2009 |
Q: I have a Lennox outside unit and a Comfort air inside unit. The comfort air furnace and evaporator ... A: Sounds familiar. They were welding freon lines on the changeout & a weld is leaking all the freon - ...
|
| weather king AC unit | 4/26/2009 |
Q: My puppy was chewing and yanking on the wires coming from our house to the AC unit. The thermostat ... A: Need to enclose those wires in fence wire. Once the dog chews on them it will not stop. Consequences ...
|
| outside fan want turn on but inside blower want stop running | 4/25/2009 |
Q: when i turn t-stat to cool auto or on the outside fan want turn on you can hear a click in the ... A: Check the circuit breaker for he outside unit first.If OK, manually close the start relay with a ...
|
| Size and distance intake line from unit | 4/24/2009 |
Q: Our exterior 3 1/2 ton heating/air condition unit is current located on the southern exposure, which ... A: Need some clarification. That 16" line is a round duct 16" in diameter ?? That is the return air ...
|
| Rheem RPKA-037JAZ | 4/22/2009 |
Q: The heat pump will not turn on. On the outside of the unit is a reset button. The schematic calls it ... A: That's a high pressure switch. Main cause to trip it is a bad condenser fan motor. Does he fan run ...
|
| venting three dryers in line thru flat roof | 4/22/2009 |
Q: Howard we are renovating a three family house with washers and dryers on each floor to vent the ... A: W hen the 3 vent lines merge, the diameter of the duct should increase to 3 times the area of one 3" ...
|
| air conditioning | 4/21/2009 |
Q: What is the correct way to measure super heat in an a.c. system, wet bulb temp and dry bulb temp? A: The old fashioned way, like me. It is: measure the suction pressure & convert it to temperature. ...
|
| AC unit age and warranty | 4/19/2009 |
Q: I have a Rheem CriterionII. The inside fan stopped working. Is there a way I can find out how old ... A: Nice to have a rough idea of its age to find the date. for 1990 it may read 1469047.hat motor is ...
|
| replace EVAP coil | 4/15/2009 |
Q: Howard, I have a 5 yr old Goodman split heat pump. Two yrs ago i had to add refrigerant an now I am ... A: Where do you live, California ?? Run the guy off with a stick. Try this, there is a liquid you can ...
|
| Split System Central AC | 4/15/2009 |
Q: I have a split system central AC in my condo. Compressor unit is on roof of three story building ... A: Upthere all you need is a block of ice & a fan for cooling ! No problem for the distance between the ...
|
| Split System Central AC | 4/14/2009 |
Q: I have a split system central AC in my condo. Compressor unit is on roof of three story building ... A: Big expensive problem for a 3 story roof! Sometime a crane is necessary to access the roof. Could be ...
|
| a/c installation | 4/13/2009 |
Q: I had a Trane split system installed last week.The outdoor unit is 1 1/4" out of level.The ... A: There is about a qt of oil in the compressor that is oiling the bearings. There is some tolerance on ...
|
| Leaking Evaporator Coil | 4/13/2009 |
Q: I currently have a split Lenox Unit (11 years old) and the Evaporator Coil has a leak. The company ... A: That point of a matching SEER system, in & out can bring about a HUGE discussion! Some brands say ...
|
| seer versus tons | 4/9/2009 |
Q: What is the difference between seer and ton? We are getting ready to get a new system for the house ... A: 1980 !!!! Cheez, that's great ! You can't ever tell how long these things will run. But one thing ...
|
| seer versus tons | 4/8/2009 |
Q: What is the difference between seer and ton? We are getting ready to get a new system for the house ... A: Seasonal Energy efficiency rating = watts/ hours. one ton = 12,00btu.@95 deg. Bet you've heard a LOT ...
|
| bathroom exhausts:energy efficient? | 4/8/2009 |
Q: do bathroom exhausts suck the heat/air out of your house. i always turn them on for white noise in ... A: Uh oh, a family discussion ?? A bathroom exhaust fan moves about 50 cfm.A 1500 sq. ft house has ...
|
| central heat unit | 4/7/2009 |
Q: I have an American Standard central heat and air unit. I am unsure of the size. The air works great ... A: Those switches are around the burners & are small red switches. Sopme have a reset button that pops ...
|
| 24v control wiring to outdoor unit. | 4/6/2009 |
Q: I am having a problem getting 24v to my outdoor unit. there was two transformers on the system one ... A: You have a dog in the backyard that has chewed on the wire ?? Common problem. Can be a mouse in ...
|
| Digital thermostat for Mobile Home | 4/1/2009 |
Q: I live in a 1994 mobile home 16x80 & want to change to a digital thermostat (Honeywell RTH230B) my ... A: The red & white wire was for heat ONLY. Moving the red wire to Rc is OK but the white wire to Y is ...
|
| HEAT PUMPS | 3/31/2009 |
Q: Sir, I would like to ask you if you think a heat pump is recommended for my area for a new AC and ... A: Florida is the best state for heat pumps. Go for it. Just check the run amps comparison between the ...
|
| Proper HVAC size for house | 3/30/2009 |
Q: Howard: we bought a 750 sf, one level, circa 1935 cottage on Va's eastern shore. Crawl space newly ... A: Heat pumps are for Florida, NOT Virginia ! You would be running electric elements most of the Winter ...
|
| Air return sizing | 3/30/2009 |
Q: I have discovered that whoever installed my HVAC system did it in a strange way. There are filters ... A: I have a 3 ton cooling system & have 400 sq. in. grille.But I could use any number of RA grilles as ...
|
| Proper HVAC size for house | 3/30/2009 |
Q: Howard: we bought a 750 sf, one level, circa 1935 cottage on Va's eastern shore. Crawl space newly ... A: Ducts nowadays are flexible stuff but with good insulation(1.5")But would you have any space for a ...
|
| Air return sizing | 3/30/2009 |
Q: I have discovered that whoever installed my HVAC system did it in a strange way. There are filters ... A: Are these returns near the floor in several places around the house ?? There should not be any ...
|
| Furnace problems | 3/28/2009 |
Q: I'm currently having some trouble with my furnace. The Thermostat seems to be working fine. I can ... A: Those switches are pretty standard among most brands. First tho, detremine whether the switch is NO ...
|
| Gas Furnace/White powder buildup | 3/27/2009 |
Q: Yesterday my carbon monoxide detector went off. I had someone from the gas company come out and ... A: Is this a standing pilot type furnace ? Some kind of powder is typical for this type, but not very ...
|
| Furnace problems | 3/27/2009 |
Q: I'm currently having some trouble with my furnace. The Thermostat seems to be working fine. I can ... A: The key here is " it won't even light up".If the draft motro runs on a call for heat, the air ...
|
| Zone vs. Variable Speed Heat and AC | 3/26/2009 |
Q: I have a 3-story house and installing central air. I have been told to get a 2-zone system in order ... A: A 2.5 cooling system will produce only 1000 cfm. Not very much air. Since cold air falls you need 2 ...
|
| Furnace problem with ignition | 3/26/2009 |
Q: My daughter has a Rheem Criterion Gas furnace Model RGDJ 07EAUER Serial # EB50302F400001836. It ... A: Does the igniter glow ? If so, several events are OK. If it does, & there is 24v at the gas valve it ...
|
| HVAC | 3/26/2009 |
Q: I am involved with a Temple, and I am not sure if we are getting the run-around. We replaced all the ... A: Wow, Rick, never heard of that kind of problem. An a/c unit will run in 20 deg weather.Can't think ...
|
| thermostat | 3/17/2009 |
Q: Six month old digital Honeywell thermostat keeps going from "heat on" to "aux heat on" but heat ... A: So your aux heat is for the electrical heat elements.If the tstat is auto shifting to aux heat I ...
|
| Heat Pump | 3/17/2009 |
Q: I have a trane xb10 heat pump, standard airhandler with 1/2 HP motor heat strip BAYHTR 1415 backup ... A: Heat pump in Maryland noi good. That system can only provide enough heat down to about 32 deg in ...
|
| Payne Furnace...no heat | 3/15/2009 |
Q: We have a 14 yr old Payne downdraft furnace up in the attic. It was forking fine until this morning. ... A: Getting closer Albert. Some of those igniters are ceramic & they can develop a small crack from the ...
|
| rheem home central heating & cooling unit | 3/14/2009 |
Q: gas burner on unit wont lite. put new gas valve on but stll no burnner. piolt does stay lit A: An old style furnace, I gather that has a standing pilot ?? Is there any high temperature switches ...
|
| heating | 3/13/2009 |
Q: My emergency heat light will not go off when the heat is running. It worked fine earlier in the ... A: Your elecric bill is up since emergency heat is only electric elements are operating. Does every ...
|
| condensing unit lowside and high side fluctuate | 3/12/2009 |
Q: Please! Help. Last summer I had four units the same problem. 1st Weather King, 2nd Ruud, 3rd ... A: You in the a/c business, nuoc ?? The description you give sounds typical for a dreaded disease ...
|
| thermostat replacment | 3/11/2009 |
Q: i wanted to replace my central ac thermostat with a digital one when i did sparks flared up and it ... A: Something funny here since "normally" those 4 wires are from the same side of the transformer. So ...
|
| Payne Furnace...no heat | 3/11/2009 |
Q: We have a 14 yr old Payne downdraft furnace up in the attic. It was forking fine until this morning. ... A: If the draft motor runs & no igniter glows, it the air pressure switch that's bad. Insure the hose ...
|
| Heating | 3/8/2009 |
Q: I have a Carrier forced air unit for our heating and air conditioning. Everything works fine but ... A: You must have an older gas furnace. If so, the fan/limit switch needs adjusting to control the fan ...
|
| 3600 sq ft ranch in nh-size of furnace needed | 3/5/2009 |
Q: We just put a 1600 sq ft addition on to our ranch to bring total sq ft to 3600 (existing on slab, ... A: Like blowing in a bottle, when the pressure is maxed, no more pressure is possible, So when the ...
|
| Question about HVAC (Gas heat) | 3/5/2009 |
Q: Where can I find the fuse for a tempstar Dc90 ultra high efficiency gas heating system? The system ... A: If there is a fuse on the module it is a plug in auto type, 3 amp. That is only a protection for the ...
|
| 3600 sq ft ranch in nh-size of furnace needed | 3/4/2009 |
Q: We just put a 1600 sq ft addition on to our ranch to bring total sq ft to 3600 (existing on slab, ... A: Easy question Bonnie, difficult to answer. The new way to run a heat load analysis is with a ...
|
| payne furnace | 3/4/2009 |
Q: The furnace was working last nite now over nite it will not come on. Checked thermostat when it was ... A: Does the lighting sequence of: Draft motor runs, air pressure switch closes, igniter glows, burners ...
|
| AC forced air unit leaks freon | 3/3/2009 |
Q: I had to have my outdoor AC unit completely charged w/ freon last spring. My HVAC guy told me that I ... A: 90% of freon leaks are in the evaporator coil.Sometimes a sealer can be added in the system that ...
|
| Furnace working (or not) intermittently | 3/3/2009 |
Q: 3 year old American Standard Freedom 90 Single Stage locks out intermittently (usually at night). ... A: Been at it 30 yrs never heard of "backfeeding" !! Have you tried reversing the power supply to the ...
|
| Furnace | 3/2/2009 |
Q: I have a Lennox G21 pulse furnace. Last night the furnace didn't fire up. There was a humming sound ... A: Sounds like a lemon to me ! I would call the local Lennox sales manager for your area & tell them ...
|
| A/C tonnage rating | 3/2/2009 |
Q: As best as I can determine from the internet, all the manufacturers have a/c in half-ton increments ... A: I did throw you a curve. Yes, you are correct about the Goodman. That is; a 3 ton condensing ...
|
| Furnace | 3/1/2009 |
Q: I have a Lennox G21 pulse furnace. Last night the furnace didn't fire up. There was a humming sound ... A: The last thing you want to do is replace the module. You are resetting the module with the off/on ...
|
| A/C tonnage rating | 3/1/2009 |
Q: As best as I can determine from the internet, all the manufacturers have a/c in half-ton increments ... A: Sometimes the evaporator coils are the same, the expansion device(which is a hole)is just a bit ...
|
| Gaffer & Slatter furnace | 2/23/2009 |
Q: My condo has a G & S furnace. I replaced the old dial style of thermostat with a Honeywell digital ... A: Again. One more clarification. Are the burners still fired up or is it just the blower still running ...
|
| Rudd Silhouhette II Gas Furnace 4 Blinks | 2/22/2009 |
Q: My Rudd Silhouhette II Gas Furnace will not start and the Normal green light is flashing 4 Blinks ... A: Check the air hose from the draft motor to the switch, blowing thru it for blockage. Check the ...
|
| Options for oversized A/C | 2/21/2009 |
Q: Howard, My family just moved into a 3200 sqft house in Houston, which was built in 1993. It has a ... A: Good thinking Bill. In Houston you will need everything you can afford to cut the big electric ...
|
| New construction HVAC | 2/19/2009 |
Q: Is a gas heat/elec AC outside package system less costly than a split system? It seems like a ... A: A package unit is more costly.The unit is more costly & the ducting connecions is more difficult ...
|
| heater not working | 2/19/2009 |
Q: When i turn the thermostat to heat/auto the furnace tries to kick in for a couple mintues then shuts ... A: You've got to do some diagnosing yourself before I can help you. Namely, open the furnace to watch ...
|
| Return size | 2/18/2009 |
Q: I have a 5-ton York split system. My installer put in a 20" x 20" return with a 16" duct. I have ... A: The return air duct is sized to produce an air velocity of 400 cfm or less. I do not have the chart ...
|
| code requirement for supply air filter | 2/18/2009 |
Q: What is the code requirement for installing filters on the return air ducts serving the heating and ... A: Every state probably has there own codes. But there is a Universal Mechanical Code that all states ...
|
| Heil DC90 Ultra High Efficiency Furnace | 2/16/2009 |
Q: I have a Heil DC90 Ultra High Efficiency Furnace which stopped working over the weekend. My Direct ... A: CO can affect different people different ways. Some can die when others are barely affected. Also, a ...
|
| furnace air flow with bigger pulley | 2/15/2009 |
Q: Last summer I had ac installed in my house that did not work properly. My furnace is a Lennox that ... A: Sure can't see the air volume increase will affect the furnace for heat. You may see more affect on ...
|
| furnace won't stop running and sometimes won't fire | 2/15/2009 |
Q: I have a Goodman Gas Furnace. It is about 5 years old. The other day my husband and I noticed that ... A: Replaced in warranty only keeps the original warranty length in place. Some can be expensive, some ...
|
| AC Unit Hard Start Kit for Dimming Lights | 2/13/2009 |
Q: This is the second home that I have had on this property. The first home I went through two ... A: Powersupply to the house is inadequate. Somewhere in the electrical power circuit the wire is too ...
|
| Location of Filter for RUUD AC Model UENB 1008 BDS | 2/12/2009 |
Q: I am visiting my 96 year old mother in Florida and opened up her AC unit to replace the filter. I ... A: I presume the furnace is NOT in the attic ?? If it is an uplow in a closet the filter would be at ...
|
| Residential Gas Furnace | 2/11/2009 |
Q: Is it ok to continuously run the fan on a residential gas furnace? We have a large expanse of ... A: Continuous fan is good for circulation for large homes. If you have a 2 story house the hot air ...
|
| obsolete circuit board replacement | 2/10/2009 |
Q: Livingston, I am getting a bit of a run around from various HVAC guys and am looking for some ... A: Good for you, Elaine. You will have to rely on the schenatic posted somewqhere on the furnace.Use ...
|
| Furnace to coming on | 2/9/2009 |
Q: I do home repairs for a living and have a little experience with heating and I'm pretty good with ... A: Sure don't have an idea what's going wrong.Those code flashes on the led's sre generally OK for ...
|
| Thermostat | 2/8/2009 |
Q: I am changing from a Chronotherm III to an Emerson 1F95-1277 thermostat. Current wires on ... A: New kinds of thermostats for heat pumps can be difficult. Can only say what is "normal" for the ...
|
| Kenmore Heating and air unit | 2/8/2009 |
Q: i have a Kenmore model NTC6100GFA1 system that was installed 9 years ago.I recently have lost heat ... A: Several problems at once. The fan circuit is on a timed cycle with the heat. Think the fan relay on ...
|
| ac air return | 2/7/2009 |
Q: I live in the Northeast. My AC is in the attic, (heat is baseboard so no connection)Home is 5 years ... A: Air doesn't move withou a pressure differential. Most likely that is occuring between the return air ...
|
| Gaffer & Slatter furnace | 2/6/2009 |
Q: My condo has a G & S furnace. I replaced the old dial style of thermostat with a Honeywell digital ... A: Steven. When the furnace is set to run on the thermostat, let it stabilize for a bit. Then urn the ...
|
| carrier gas furnace | 2/3/2009 |
Q: I have a carrier gas furnace plus 90 that was installed in 1993. The furnace is a sealed system so ... A: Doesn't that furnace have an led trouble light that flashes codes that can tell you where the ...
|
| obsolete circuit board replacement | 2/3/2009 |
Q: Livingston, I am getting a bit of a run around from various HVAC guys and am looking for some ... A: Don't know about D & L Supply, but I would relay on the local RUUD supply house to sell me the ...
|
| No Heat. | 1/16/2009 |
Q: I came home tonight to find no electricity in my apartment. After I fixed that I noticed that my ... A: Turn on the fan to"on". Does the fan run ?? That's a test for power, low & high. Is there a pilot ...
|
| furnace exhaust blower condensation | 1/16/2009 |
Q: This is about 18 years old Heil furnace.I've replaced noisy exhaust blower, cleaned all drain tubes. ... A: This condensate problem is a difficult issue.A hot exhaust moving thru a cold pipe is hard to stop ...
|
| heating and air | 1/14/2009 |
Q: i got a loud noise from my ac unit outside, i have electric central heating and air, i went outside ... A: You must have a heat pump. The ice formation is natural & is thawed by a defrost cycle in the ...
|
| wiring | 1/12/2009 |
Q: i have zone heating. 2 stats. need to know how to wire control board. red. white wire coming from ... A: the heat contro; wires are red & white. The rest are for cooling & a fan.If each stat uses a red & ...
|
| Air Handler Fan Will Not Run | 1/10/2009 |
Q: I have a 1990 Amana Heat Pump. The inside unit blower fan stops running intermittently..... about ... A: I did not respond about the delay knnob since an ajustable knob would be a coil of wire with a ...
|
| no power to furnace | 1/6/2009 |
Q: My reheem furnace (model rgdg07eauer)is all of a sudden powerless, I check the circuit breaker,no ... A: There is a fuse on the board, generally. Its like an auto fuse & just plugs in. Usually a 3 amp. If ...
|
| Central heat/ac unit that cools from a well? | 1/5/2009 |
Q: I am looking at purchasing a house, that has a central heat/ac unit that cools from a well. I think ... A: The model number hides the tonnage, like ABC3602516. That 60 is 60k btu & a 5 ton.A 1600 sq ft may ...
|
| Payne Force Air System | 1/5/2009 |
Q: Fan is set on auto but when the unit is set to HEAT, the blower does not turn on. Angela A: The circuit for the heat fan is different from cool fan.Now, if you have a circuit board controlled ...
|
| error code on armstrong furnace | 1/3/2009 |
Q: My 8 year old furnace will not fire up by thermostat, unless i go to the side of the furnace turn ... A: Pull off the 2 wires at the pressure switch & ohm across the terminals to test.Thats a reset you're ...
|
| Resize central hvac system | 1/2/2009 |
Q: been awhile since I've talked to you.I installed a 3ton.Goodman 13 seer straight cool matched system ... A: The reversing valve is the question. Since heat is more important than cooling for people, the ...
|
| Electric Baseboard/Thermostat | 12/31/2008 |
Q: Howard: I just installed 220 volt hydronic baseboard units (TPI)in an atrium (the rest of the home ... A: Running late due to the holidays. The green ground wire goes to a bare ground wire, or to a water ...
|
| Loud "bang" from air handler on Heat pump | 12/30/2008 |
Q: I have a 1 1/2 yr old 4 ton Rheem seer 13 classic heat pump coupled with a rheem prestige air ... A: Could it be the blower motor inside ??? Quick test, turn on fan to on only, when up to speed turn it ...
|
| Ignition Failure, Gas Forced Air Furnace | 12/29/2008 |
Q: I have a Frigidaire FG6RA 072C-12A - Nordyne. There is a red light that blinks 4 times. The ... A: Ground wires screwed to a metal surface can corrode. Sand off the metal at contact. Just watch the ...
|
| refrigerated air conditioners | 12/28/2008 |
Q: I want to start investigating refrigerated air conditioners. I have searched the Internet and can't ... A: Happy New Year Sharon!Hope your Christmas was great. A rule of thumb to size is 500 sq ft /ton ...
|
| Direct vent propane wall heater | 12/27/2008 |
Q: I have a 1 yr old Cozy direct vent propane wall heater. It works well, but only stays on for about 3 ... A: There is a hidden overheat switch somewhere near the top of the heat exchanger that may be tripping. ...
|
| hi howard | 12/27/2008 |
Q: i have a clare megasave furnace. the motor went on in las t night. go figure huh christmas and all. ... A: This furnace has spark ignition to a pilot light ?? If so, you may have a stopped up pilot orifice ...
|
| no heat jus air from roofmount fau | 12/26/2008 |
Q: MERRY CHRISTMAS HOWARD. I have a roof mounted fau the fan comes on but no heat . I looked and ... A: Test the air pressure switch by jumping across the 2 terminals. The ignitor lights after the ...
|
| T-1250 pool heater | 12/25/2008 |
Q: I bought this unit used and the person who had it never used it. I got the unit hooked up and the ... A: There is an axiom in the service business, Werner, "if you touch it you're married to it " That's ...
|
| Thermostat OFF, heat still ON | 12/25/2008 |
Q: This senior citizen is ignorant when it comes to heating. Have 3-year-old Weil-McLain Series 3 ... A: Well, Santa Claus may be watching if you strip !! Turn off the power at the boiler to kill the heat. ...
|
| Propane furnace gas surge | 12/25/2008 |
Q: I have a Conquest 90 furnace (installed 1995) that started surging the flow of gas tonight. The ... A: Yes, there is a filter at the inlet to the gas valve. You know that condensate is possible in the ...
|
| Heat Pumps | 12/24/2008 |
Q: How can I tell if I have a bad reversing valve or a compressor issue.or maybe check valves The head ... A: It could be an electric heat element on, leaking seals in the reversing valve. Does a test of the ...
|
| Furnace has to ignite several times to light | 12/24/2008 |
Q: I have a Nordyne model#M3RL080ABW furnace that tries to ignite up to 4 times, which then shuts ... A: Is the ignitor glowing red ? And if the gas ignites on the main burner just a bit the flame sensor ...
|
| goodman air handler and heat pump | 12/22/2008 |
Q: Howard, My wife and I recentley purchased a older farm house. It was built in 1942. It has the cape ... A: Hope you live in Florida, or the South considering a heat pump. The heat from the compressor(1st ...
|
| 13 Seers vs 14 Seers | 12/21/2008 |
Q: Howard, First off thanks for your time and making yourself available. I've got what i hope is a ... A: WOW, $480 !! No way. Know the formula for SEER ?? Its btu's per season divided by watts per ...
|
| heatpump | 12/21/2008 |
Q: I have a split heatpump when I turn the t'stat to heat and fan to auto only the indoor blower is ... A: Good info Phil. Has the freon been tested?? First thing to do on a heat pump. May be off from a low ...
|
| Rheem Gas Furnance - Blower won't start | 12/18/2008 |
Q: My Rheem furnance goes thru the start cycle and ignites but the blower wont come on...20 seconds ... A: Test the motor run capaictor first. You know how with an ohm meter ?? Then if it's OK, test the ...
|
| Internal fan won't turn on unless U hard wire it/. | 12/18/2008 |
Q: I have a Coleman downdraft furnace, the internal fan won't turn on, I tested the wires and there is ... A: Sorry, can't help you on those code signals. Are they not indicated on the manuals? Maybe on the ...
|
| limit switch | 12/16/2008 |
Q: My furnace is 11 years old, and i had to replace my limit switch because the electric pilot light ... A: Guess you are talking about the high temperature limit switches ?? Are those manually resets ?? If ...
|
| Heat pump/electric furnace | 12/16/2008 |
Q: Have older TempStar Heat pump w/electric furnace. Fan on heat pump working ok (but is running ... A: Generally. the output of the compressor heat(first stage) poops out around 32 deg. At that time the ...
|
| heating | 12/16/2008 |
Q: We have a newer two story home, but half of the 'second story' is a vaulted ceiling from the first ... A: The best answer, Matt is to have had 2 units installed, 1 up,1 down. Your on track to have ceiling ...
|
| Furnace Operates Correctly in All Ways Except... | 12/15/2008 |
Q: ... the heat output is low. [LIST] [*]Centurion Gas Furnace, 75,000 btu., with AC [*]Thermostat ... A: Wow, never got such detailed info in my 1860 questions I've answered !! Good for you.My big surprise ...
|
| Electric HVAC | 12/14/2008 |
Q: i recently had service done on my Electric furnance. The tech said that i am using only half(5 KW) ... A: If there are wires running to the elements & is connected to 240 volts you are getting full power. ...
|
| gas furnace | 12/14/2008 |
Q: have gas furnace with electric start-appears that it takes 5 or 6 times for furnace to light(Clicks ... A: Maybe needs a little cleaning around the spark ignition. Or can be a partially blocked pilot gas ...
|
| No heat when it gets below 30 outside | 12/13/2008 |
Q: Let us begin with, we have an Amer. Standard heat pump and for the 10 years we have been here, we ... A: Wow, Stephanie, you ought to go into a/c service work after all that good info !! Now let's see if I ...
|
| Moving burners on York 4 burner unit | 12/13/2008 |
Q: I have an York package unit, the heating component has four heat exchanger ports but only uses two ... A: So the top burners heat exchanger is good ?? Yes, move the burners & block off both top & bottorm ...
|
| Furnace | 12/12/2008 |
Q: I have a York Furnace about ten years old,it blows out cool air when it first starts.Is there ... A: That fan needs a delay to stop that. You may have little switches on the circuit board that can be ...
|
| HVAC tandem units | 12/12/2008 |
Q: A friend has a large open loft space in a seaside community. The building is brick and concrete. The ... A: Well, ya know the humidity is 100% all the time on the seashore. Every crack needs to be sealed. ...
|
| Auxiliary Heat | 12/10/2008 |
Q: I have an electric heat pump. My auxiliary heat keeps kicking on. I have my temp set at 65 degrees ... A: Some heat pumps have a thermostat in the outside unit which turns on the aux heat. Some are ...
|
| heating | 12/9/2008 |
Q: ..I have a furnace that is at least 20 years old. I had it checked out last winter and it checked ... A: Probably have a thermostat with a heat anticipator in it that needs adjusting to a "longer" cyle ...
|
| Rudd Forced Air Gas Furnace | 12/9/2008 |
Q: Having a problem with my furnace turning on. The system seems to work properly when I flip the ... A: You are resetting the circuit board that is acting up killing the power. Do you get the LED trouble ...
|
| heating schematic | 12/9/2008 |
Q: I have a very old package unit gas heat that the fan will not turn on inheat mode. There is no name ... A: You have a thermostat with a heat anticipator ?? Maybe it needs adjusting. It is a dial with an ...
|
| Guardian furnace Pressure Control Switch | 12/8/2008 |
Q: My pressure control switch on my new 95.5 efficiency gas furnace keeps filling with ... A: Well well. found the problem! You need a "P" trap, (not "S") on that horizontil run to catch the ...
|
| trane induction fan | 12/7/2008 |
Q: I have a trane 2.5 ton unit with gas pack that is about 12 years old not sure about the model ... A: Yes there is John.Locate the transformer & press on it & see if it changes sound. They develop a 60 ...
|
| Guardian furnace Pressure Control Switch | 12/7/2008 |
Q: My pressure control switch on my new 95.5 efficiency gas furnace keeps filling with ... A: That moisture would only come through the induced draft motor. That water may come from the flue ...
|
| Rudd 5 ton heat | 12/6/2008 |
Q: Howard: It's 4 years old. Have replaced compressor, 2-3 fans, it freezes up and quits, just recently ... A: Gather all you're service orders plus any other happenings. Call you're local Ruud supply house & ...
|
| Heater blowing cold air | 12/6/2008 |
Q: I have an electric heater, I noticed today that the house seemed cooler then normal. I was in and ... A: Those elements can drop off one at a time & you won't notice it till it gets real cold. Each element ...
|
| Heater Problem | 12/6/2008 |
Q: I have a Day & Night split unit with the fan coils in the attic and the condenser outside. The unit ... A: It could be caused by a digital thermostat. Also the heat fan is a separate circuit & for an old ...
|
| A/C | 12/5/2008 |
Q: I have a 28 year old Lenox central A/C system in a 1400 square foot Townhome. The outside condensing ... A: Let the buyer beware! Caveat Emptor. This equipment usually does not like to work in a different ...
|
| heat pump compressor noise | 12/5/2008 |
Q: Our"Thermal Zone" heat pump works fine in the summer ,but as soon as it turns cold out 40 degrees or ... A: Wonder you're still alive !! Must be good neighbors.Main thing differemce between heat & cool for a ...
|
| Ducane | 12/4/2008 |
Q: We have a Ducane heater. When it is super cold out side it completely turns off. The heater heats ... A: some of these heaters have several rollout switches.Some can be manually reset by resetting a button ...
|
| PGCJAA/MAA cycling on-off in heat mode | 12/4/2008 |
Q: in the heat mode, the unit cycles on and off, will not stay on to reach the temp needed to shut off, ... A: I presume this is a gas furnace. Don't recognize those letters.If this is a pretty old furnace ...
|
| Furnace inducer problem | 12/3/2008 |
Q: I have a 4 year old new construction house with an 80+ single furnance. The inducer had been making ... A: Naw, that's like stockpiling a compressor. You have one spotted so I'd keep oiling the shaft end ...
|
| Furnace inducer problem | 12/2/2008 |
Q: I have a 4 year old new construction house with an 80+ single furnance. The inducer had been making ... A: the bearings in those motors are just sleeve bearings. Was there oil ports on the motor?? Both ends ...
|
| heating unit | 12/2/2008 |
Q: My heat unit outside doesnt always run with the fan going, is this normal? But the thermostat, it ... A: Sounds like this is an electric furnace ?? If so the hea fan is run on a time delay relay & that ...
|
| Comfortmaker gas pack issue | 12/1/2008 |
Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ... A: We did have a good Thanksgiving with the family at a lake house owned by my daughter & husband. ...
|
| AC blower cycling on and off | 11/30/2008 |
Q: Ruud model UCBA100C, Propane furnace, Age not sure but if it is original it's pushing 30 years. ... A: A 10% allowance for a capacitor is the limit. So replace it with a 10 mfd size. Sounds like the ...
|
| Booster Fan | 11/30/2008 |
Q: I have a Carrier furnace with a Tjernlund duct booster fan on one of the branches. Previously, ... A: The booster fan ought to be 120v. Follow the 2 wires from the fan & see if they are not connected t ...
|
| fan blowing, but no gas or ignition | 11/28/2008 |
Q: I have a 10-15 year old Amana furnace. About a year ago, it started blowing cold air. The heating ... A: Could be the flame sensor, Roger. Needs cleaning. Remove it & clean with a rag. Could be the air ...
|
| Gas Valve question | 11/28/2008 |
Q: My Gas valve went bad on my Payne central unit. PY1PNBO30060AAAA series B LP converted Unit! I ... A: Does the flames look all blue, Jeff?? That's the sign of complete combustion on LP. And as you know ...
|
| Comfortmaker gas pack issue | 11/28/2008 |
Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ... A: That would be OK to plug the 2 bad bays in the heat exchanger. Gas pressure not affected.I would ...
|
| Comfortmaker gas pack issue | 11/27/2008 |
Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ... A: I'm not sure which model that is. You have 4 burners on that model? Does sound like a hole in the ...
|
| Payne gas hot air heater | 11/26/2008 |
Q: I have a Payne gas hot air heater. When heat is called for the exhaust blower starts for 15 seconds ... A: Gosh, Fran that's a crud problem, maybe. ! Let's see,you could have dirt or something clogging the ...
|
| wiring for new thermostats | 11/26/2008 |
Q: I bought the Honeywell rth6300b thermostat to replace the old mercury thermo that I'm sure came with ... A: Well, Don this proves that the heat pump thermostats will not work with an older model heat pump. As ...
|
| Goodman Heat Pump | 11/25/2008 |
Q: Howard, I have a 7 year old Goodman PHK024-1 heat pump. Last night the heat stopped running. The ... A: Yes, the compressor is supposed to run for first stage heat, as is the outside fan. Sounds like that ...
|
| Condensation on Ceiling | 11/25/2008 |
Q: I bought a house in April and it is on a concrete slab. At closing the seller told me he gets ... A: You're plumbing is under the slab & can leak anywhere. They find it by listening with headphones on ...
|
| elctronic fan timer control board replacement | 11/25/2008 |
Q: My System is keeping the fan on constantly. Both the heater and the AC will not engage....I suspect ... A: Sounds familiar. Try tapping on the little black boxes on the circuit board to see if you can ...
|
| Carrier Gas Furnace short cycle | 11/24/2008 |
Q: I am a novice and will try to explain what is going on and see if you can help me out. I just bought ... A: los of good info. I'll take it on one at a time. Don't understand what's the connection between the ...
|
| wiring for new thermostats | 11/24/2008 |
Q: I bought the Honeywell rth6300b thermostat to replace the old mercury thermo that I'm sure came with ... A: The wires used on the old tstat do not indicate a heat pump.W2 was used for heat.Don't lnow why C ...
|
| Condensation on Ceiling | 11/23/2008 |
Q: I bought a house in April and it is on a concrete slab. At closing the seller told me he gets ... A: Wow, Denise something funny here ! The condensation pump is to drain the condensate water generated ...
|
| how to wire a honeywell fan and limit switch | 11/22/2008 |
Q: i need to know how to wire a fan and limit switch to the blower A: A limit switch is usually a high temperature device & it is connected to the gas valve, in series. ...
|
| heil model nuge080kg01 | 11/21/2008 |
Q: if I start the unit up the pilot lights and the unit will run till it reaches the set temp then when ... A: Not a place to have furnace problems ! Check the voltage across the gasvalve 24v terminals & see if ...
|
| caloric LP range | 11/19/2008 |
Q: we bought it used, converted to LP. The burners work fine, however the oven and broiler do not. ... A: Usually not involved with stoves but I think you're problem may be is the pilot orifice is stopped ...
|
| pulse 21 furnace 6 years old horizontal unit with moisture in blower compartment | 11/18/2008 |
Q: pulse 21 furnace 6 years old horizontal unit with moisture in blower compartment. The furnace runs ... A: Sounds like condensate problems.Was the filter pretty dirty when you changed it ?? I would check the ...
|
| furnace | 11/18/2008 |
Q: I have a 3yr old Tempstar upright furnace.The 5amps fuse on the circuit board keeps on blowing. Any ... A: You have a dead short in the low voltage control circuit. Got to find it. Sometimes can be in the ...
|
| Heating Airflow problem | 11/16/2008 |
Q: My parents live in a townhouse that was constructed poorly because when they turn on the central ... A: Town houses are notoriously bad for a/c installations. Most likely there are too many jigs & jogs in ...
|
| Electric Furnace Sequencer/fan control problem | 11/15/2008 |
Q: I'd like to start with thanking you for your time in advance. Now, help me impress my new wife with ... A: I better move fast Mark to keep you out of trouble with all those kids, wife too. You really have ...
|
| Transformer got burned | 11/15/2008 |
Q: I cleaned the blower, burners and heat exchanger for my furnace and in order to do so I took out ... A: That was caused by a dead short in the 24v control circuit.You need a 40 VA with 120/24 ...
|
| lennox g40uh(x) series furnace gas | 11/13/2008 |
Q: both led lights on furnace blink slow together when furnace is turned on the led lights blingk fast ... A: You should have in you're instruction a list of codes that tells what the problem is. If you don't, ...
|
| My Ruud heater | 11/13/2008 |
Q: I have a Ruud Heater/ac unit in my house I just bought. It runs fine in the summer and the ac unit ... A: Now,you need to check & see if the outside unit is turning off when the cold air starts.Or is the ...
|
| lennox gas heat and air unit | 11/13/2008 |
Q: I have a lennox gas heat and air furnace model gsc16. its a 93 model. Anyway when it started cooling ... A: That blower motor only draws about 3 amps, or it should. You have a clamp on amp meter ?? With the ...
|
| Ignitor fires early or gas valve turns on too late... | 11/12/2008 |
Q: Here is the sequence I see. I ask for heat. The combustion exhaust fan comes on. The ignighter ... A: I think the problem is low propane pressure. The gas valve ought to open pretty fast after the ...
|
| heating and cooling workshop | 11/10/2008 |
Q: I am converting a 14 x 20 freestanding potting shed into a craft studio. I'm adding insulation and ... A: Been on vacation so running late on my answers. I suggest a window unit with heat. I could be a heat ...
|
| question on furnace | 10/30/2008 |
Q: I went to a friends house and the furnace was in a flood. No LED lights came on whe I turn on the ... A: The blower motor is on a timed circuit & will delay AFTER the burners are on. Try jumping across the ...
|
| Carrier Robertshaw Unitrol Valve | 10/29/2008 |
Q: I have an older furnace, I'd say approx. 20 yrs old. It say 1985 as the year on it, but I'm not sure ... A: You have a 60 cycle hum from a 24v coil. I'm not sure what the part is as a "regulator valve" or " ...
|
| Thermostat Replacement | 10/29/2008 |
Q: Have a Trane electric forced air heat pump and air conditioning system with a Trane Baystat 239 ... A: Head for Home Depot & look at the round Honeywell tstats with a lcd screen on it. I think those are ...
|
| gas furnace | 10/27/2008 |
Q: My gas furnace is not lighting. In checking the electronic gas valve I see that the solinoids are ... A: A sensor needs to detect the igniter before the gas valve will open. So it seems the circuit board ...
|
| Furnace won't ignite | 10/27/2008 |
Q: I have a residential gas furnace g6rl 90+ downflow, it tries but won't ignite. This is my first yr ... A: Follow this cycle to check what is NOT happening. On a call for heat with the gas valve turned to ...
|
| Heating | 10/26/2008 |
Q: I have a Rheem RGRA series heater. The gas valve is not opening, when the furnace should be calling ... A: I'm not sure what all those acronyms mean. I don't know what the LED flashes mean, not having any ...
|
| gas pipe | 10/25/2008 |
Q: we have a huge vibration in our gas pipes in our home specially in one room where the pipes go on ... A: Gas pressure in the line is so low you may have a problem in the regulator at the gas meter to cause ...
|
| heating unit filters | 10/24/2008 |
Q: I have a Carrier 2800 gas heating furnace. It heats very well, but there are no air filter on any of ... A: Look at the return end of the furnace case.If there is a small door there that is the place for the ...
|
| American Standard Freedom 90 - 4 Flash Code | 10/24/2008 |
Q: It looks like I need to press the reset burner box temperature limit switch which is located at the ... A: That is a strange name for a heat exchanger. I think that is what that term means. There usually are ...
|
| no power to furnace | 10/24/2008 |
Q: I recently moved my thermostat from one side of the room to the other side,but I did,not turn off ... A: Wow, no wonder no power ! That 3 amp protects the 24v control circuit. The 20 amp should not have ...
|
| heil model nuge080kg01 | 10/23/2008 |
Q: if I start the unit up the pilot lights and the unit will run till it reaches the set temp then when ... A: Since you have replaced the pilot sensor it indicates the module is not responding to open the gas ...
|
| Carrier PAV 58 - Fan won't turn off | 10/22/2008 |
Q: The furnace heats and everything else works..no failure codes, however the fan stays on. It turns ... A: Are there any small switches on the circuit board that sets the fan on time ?? They are called dip ...
|
| furnace repair | 10/22/2008 |
Q: I have an Empire direct vent wall furnace, propane, no fan 5 years old. The pilot went out, but now ... A: Is this a millivolt unit ? Sounds like it is. If so, need to test the voltage output with a strong ...
|
| the basement | 10/14/2008 |
Q: Sir, I am renting the pretty garden flat in the most prestigious location in London...but, alas, it ... A: I'm still here till Friday Jimmy. Fire away.
|
| burners won't ignite on older ruud furnace with a gas pilot | 10/14/2008 |
Q: I lit the pilot,turn on the heat but the burners did not ignite OK so i installed a new pressure ... A: Is the draft motor air flow blocked ? The air pressure switch is activated by positive air pressure, ...
|
| HEATER NOT WORKING | 10/11/2008 |
Q: I HAVE AN EVCON HEATER/AC THAT DOES NOT PUT OUT HEAT NOW. BLOWER WORKS, BUT NO HEAT. SOMETIMES IT ... A: Not enough info, Bill but I can make a guess. Main thing to know if this is a circuit board ...
|
| trane gaspack furnace | 10/11/2008 |
Q: unit has been cleaned and inspected but yet in am when it is not too cold out the heat seems to fire ... A: Wonder if you have low gas pressure ?? The flame sensor may not be sensing flames that are too weak. ...
|
| Airflow into center of finished basement. | 10/11/2008 |
Q: I don't think I have enough air getting into the room which houses 2 H/W/H, and a 100k btu furnace. ... A: A stopped up flue pipe can cause this, Nick. Don't run it with yellow flames. That creates soot, ...
|
| Air Conditioning | 10/10/2008 |
Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ... A: You do it with a garden hose & an oil can using about 5 drops of oil at the start of every Summer. ...
|
| Tempstar DC90 - Thermal Limits switch trips | 10/10/2008 |
Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ... A: If dirt or soot has accumulated to plug up the heat exchanger or the flue pipe, the flame, or too ...
|
| Tempstar DC90 - Thermal Limits switch trips | 10/9/2008 |
Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ... A: Is there any flames rolling from the burners ?? Is this switch one of those little red manual reset ...
|
| HVAC / Evap Cooler Lockout Circuit | 10/9/2008 |
Q: Does anyone make a "lock-out" circuit for an HVAC unit, such that it will not come on if an evap ... A: Boy, Don, that's a good one ! Swamp cooler & a/c going at the same time !! Don't know of anything on ...
|
| Furnace | 10/8/2008 |
Q: I currently have a Thermopride 1995 oil furnace and am thinking of switching to natural gas. I have ... A: Variable speed motors are quiet, but blow the same amount of air as a common motor. They do ramp up ...
|
| Air Conditioning | 10/8/2008 |
Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ... A: Not yet. R22 is phasing out in 2010, R410 replacing it. BUT, recycled R22 will be around awhile yet ...
|
| AC control | 10/7/2008 |
Q: I have a control problem that I could solve with an embedded controller, a small Visual Basic ... A: Interesting point, John. Just think that startup load is about 175% of run load & I could imagine ...
|
| furnace wont light | 10/5/2008 |
Q: The furnace will not ignite. It has electronic ignition and you can hear it click to try to ignite ... A: Most likely the pilot line is plugged. Can you try to light it with a match while clicking ?? ...
|
| Bypass Humidifier Installation | 10/3/2008 |
Q: I am installing an Aprilaire 600A unit on my Lenox Furnace and am wondering if the bypass ducting ... A: Is this an electrical furnace ?? The heat from that is only about 90 deg & not hot enough to ...
|
| HARD START | 10/3/2008 |
Q: You had asked me a couple of questions so as that you could better understand the problem. I ... A: FOURTEEN POUNDS !!! WOW !!! Do you have a 100 ft liquid line ?? The amount of the charge is based ...
|
| gaffers and sattler forced air furnace model # S80FEF | 9/30/2008 |
Q: my forced air furnace is located on the second floor in the closet. when i had the gasman come to ... A: Presume you use natural gas. Typical problem. The gas man was wrong. Soot doesn't mean a cracked ...
|
| HVAC | 9/30/2008 |
Q: we have a 4ton rooftop carrier unit, evaporator is clean condenser is clean condenser fan is running ... A: Sounds familiar.The compressor bearings are wearing causing a bit of heat. Then on a cold start the ...
|
| Lennox Furnace on a Generator ? | 9/26/2008 |
Q: Can I run my newer (2004) NG Lennox Furnace on the Generator?? Sorry I don't have the model # but I ... A: Not acquainted what a "Manual Transfer Switch"does. I wouldnt use the generator with a solid state ...
|
| Heating | 9/25/2008 |
Q: My furnace HEIL DC90, model NTGM 100 EHA2 runs a small fan continuously. The fan does not stop even ... A: Could be a short in the control circuit for heat.Remove the thermostat wires. Fan still run ?? Look ...
|
| Lennox Furnace on a Generator ? | 9/25/2008 |
Q: Can I run my newer (2004) NG Lennox Furnace on the Generator?? Sorry I don't have the model # but I ... A: You didn't say cooling. Just the furnace ?? If it's electric, probably not. One element is too much ...
|
| gas furnace won't start | 9/25/2008 |
Q: I have a gas furnace that has what my husband calls an electric start pilot light. The furnace was ... A: Aw, don't need model numbers, they are all alike. $180 !!!!! Wow. I'd ask the neighbors who they ...
|
| no return register, stale air | 9/24/2008 |
Q: I have a 3 story house. on the third floor, there are four floor registers but no return register, ... A: Where is the nearest register ?? I would say the return air was expected to be thru the open ...
|
| match condensing unit w/ gas furnace | 9/23/2008 |
Q: Right now I have a Lennox G26Q3/4-100-1 model gas furnace matched to a Lennox condensing unit ... A: Either inside or outside can be changed separately. Just has to match tons of cooling to provide the ...
|
| condenser fan | 9/23/2008 |
Q: two bladed fan slaps air and makes to much noise..uaka036jaz ruud, tried a three bladed 27degree but ... A: You are correct, cheaper. A shop that sells blades will have cfm values for blades.But the amp draw ...
|
| No power to AC | 9/22/2008 |
Q: The ac was running normally this morning when it stopped just as if it had reached the set point. I ... A: Go outside & remove the control area panel. With a screwdriver press in the contactor points.If it ...
|
| HARD START | 9/21/2008 |
Q: I HAD JUST PURCHASED AND INSTALLED A 14 SEER GOODMAN ALONG WITH NEW GAS FURNACE. I SAVE CONSIDERABLY ... A: He ain't worth $75/hr.R22 Freon sells for $7/lb so go figger.Or was this R410? Wonder what the sound ...
|
| york furnace | 9/20/2008 |
Q: ..I recently bought a house without central air/heat. Central air is going to be too pricey for us ... A: Sounds good way to go Justin, except for the York. Try a Comfortmaker, American Standard or similar ...
|
| air handler/heaters | 9/19/2008 |
Q: do you have to match the seer ratings of the handlers to the compressors (ac) eg can i replace a ... A: Wow, that is a arguable subject Jack.I have polled a bunch of the experts on this site & the ...
|
| york ac unit | 9/17/2008 |
Q: I recently bought a house with a York unit that was manufactured and installed in 1993. It ran fine ... A: First, install a good surge protector on the furnace power supply. Next, I think it may be the ...
|
| Air vent noise | 9/15/2008 |
Q: recently, I have notices a dripping/clicking noise in our upstairs air vents. At first, I thought I ... A: Sounds like condensate on the humid days is backing up water in the drain pan & maybe the fan is ...
|
| thermostats | 9/15/2008 |
Q: I have what is probally a dumb question. I was looking to buy a 7-day programable...it has 3 stage ... A: There are no dumb question, Nick. A heat pump has 2 stages for heat. 1st is the compressor heat,2nd ...
|
| compressor problems??????? | 9/14/2008 |
Q: What could cause a compressor to operate under the conditions listed below? Liquid line pressure ... A: Is there a liquid line filter installed inside the outside unit ?? Or one outside the unit on the ...
|
| New Air Unit | 9/13/2008 |
Q: i just bought a home that was made in 1982. The air conditioning unit has went out. I found a nice ... A: Yes, you can change either in or outside separately. There is a "situation" happening about SEER ...
|
| NEW HVAC SYSTEM | 9/12/2008 |
Q: I have a home that was built in 1977 in southern California. There is a 5 ton Original Lennox ... A: Hey Ike, You remind me of a hurricane I knew! Sure is slamming Galveston right now. 22ft surge ...
|
| Carrier Furnace | 9/12/2008 |
Q: my fan won't kick on (buzzing at me) on my Carrier furnace. The LED light kicks on and is one solid. ... A: Spin the blower wheel to test the motor bearings. Test the motor run capacitor. If both OK,tap on ...
|
| ticking noises coming from heating ducts | 9/11/2008 |
Q: I have a 2 yr old trane system. In the last 2 months I have started to hear snapping noises coming ... A: I am really puzzled with this one based on the fact that it occurs even when the unit is not ...
|
| hvac | 9/11/2008 |
Q: My son has a 13 seer a/c unit, a payne, that is 1.5 years old and is no longer working. He had ... A: Sounds like bull to me, Jim. Current is current. Small difference between the power needed between ...
|
| Central air frigidaire B4VM-X36K-B | 9/7/2008 |
Q: I added a 6in duct booster and got a Packard PR293Q relay but I can't figure out how to wire it to ... A: Get a 24v coil, single pole, double throw relay.( NO)I assume the fan motor is 120v. Find a 120v ...
|
| HVAC | 9/6/2008 |
Q: I REMOVED A LEAKING R-22 EVAPORATOR "A" COIL AND I WAS GIVEN A CARRIER "N" COIL FOR REPLACEMENT. I ... A: I would use the old ear trick to set the charge on the TXV. Place a screw driver end on the liquid ...
|
| a/c unit does not turn on | 9/6/2008 |
Q: Goodman AH1826-1 Last week, the unit responded properly, but now the unit no longer functioned. ... A: OK, you've got a dead short in the 24v control circuit somewhere. Have a dog in the backyard ?? ...
|
| Central air unit impacted by rain. | 9/6/2008 |
Q: Howard, We live in a 6 year old condominium building with separate central air/heating units. Each ... A: After 30 years I thought I had heard everything !!! Not so, that's the strangest thing I have EVER ...
|
| Yearly Cleaning on Regency Gas Fireplace | 9/4/2008 |
Q: Wow... this is the first time I've been to this site! What a fabulous idea! People, such as ... A: Pat for the very kind words. I have semi retired after 35 yrs & this sure keeps my mind ...
|
| Condo Wiring Issue? | 9/4/2008 |
Q: We appear to be having an electrical issue in our condo. Awhile back our AC was icing up, freon was ... A: When it rains it pours is true, right ?? Icing is caused by several things: dirty filter, stopped up ...
|
| variable speed furnace/motors | 9/3/2008 |
Q: I am purchasing a new furnace and like the idea of a variable speed motor for comfort and savings. ... A: The variable speed motor ramps up from 50 rpm to about 1100 rpm for cooling, the common speed. So ...
|
| Tripping CB in afternoon on start | 9/1/2008 |
Q: My AC has been tripping the CB only in the afternoons during start up. I can reset the CB and it ... A: Where do you live in Phoenix ?? Your problems can often occur when the circuit breaker box is on a ...
|
| Bryant 90 plus RED LIGHT and NO AC | 9/1/2008 |
Q: My A/AC was working fine until today. The outside A/AC just stops running and upon opening the ... A: Insure there is power outside, check both breakers. Then check the contactor after calling for ...
|
| Blown 50 amp fuse | 8/30/2008 |
Q: Came home from store found A/C not running first thing I did was check the A/C disconnect,but could ... A: When that happens, Eric, it's usually the compressor shorting to ground. Disconnect all 3 wires to ...
|
| A/C problem | 8/29/2008 |
Q: Residential 3 ton R-22 A/C unit about 13 years old in Dallas. T'stat calls for cooling. 24V and ... A: Sounds like(my favorite term) the compressor has a locked rotor. Have you measured the locked rotor ...
|
| Air conditioning | 8/27/2008 |
Q: I have a two story home in FL my kids have moved out to school and we do not use the 2nd floor. I ... A: If it's possible to shut down the upstairs I would. The heat load from upstairs moving down stairs ...
|
| noisy air conditioner inside | 8/22/2008 |
Q: my ac makes a bit of a loud noise when it turns on - it blows loudly while it's on - it makes a loud ... A: Try this, with a pair of needle nose pliers, bend each fin on the return air grille open a bit ...
|
| Lemon A/C??? | 8/22/2008 |
Q: I closed on my home 12/31/2003 (brand new, 2 story, 1600 sqft). Since then, at least twice per year ... A: Candice,Not a good deal at all. You need to push real hard on the manufacture of the equipment. Talk ...
|
| poor air flow with newer home | 8/20/2008 |
Q: I just moved into a new home. It is about a year and a half old. The builder lived in it for about ... A: Just a bad installation, Tim. If those are flex ducts the air resistance is high so the ducts need ...
|
| Installation of Honeywell Programmable Thermostat with Bryant Puron HVAC Syster | 8/19/2008 |
Q: I have purchased the Honeywell 7-day Programmable Thermostat, Model # RTH7500, to install for my ... A: Wow, Mary Sue, that's mind boggling!Let's go back to the basics, then rebuild the thermostat. The ...
|
| AC issues | 8/16/2008 |
Q: I noticed that my ac unit was blowing warm air so I looked downstairs and noticed that the fan was ... A: RIP OFF, RIP OFF! That's probably an $8 relay. Well, that thing being a heat pump I'm not sure how ...
|
| running fan on central air | 8/15/2008 |
Q: I live in FL and use A/AC all year. I'd like to be as efficient as possible. I recently had to ... A: Only need to run the blower all the time if you live in a great big house with high ceilings. Better ...
|
| Carrier compressor noise | 8/15/2008 |
Q: We recently purchased a home that is 2 years old that has 2 Carrier AC units. The model numbers ... A: Have the compressor mounting bolts been checked for tightness ?? The rubber mounting pads been ...
|
| AC not working with fan in auto | 8/14/2008 |
Q: Central home AC does not start with fan on auto mode. When fan is set to on mode, blower starts but ... A: Insure that the wires to the thermostat are not shorted. Carefully separate them & retry.If this ...
|
| Air Handler Replacement | 8/14/2008 |
Q: First, thanks for taking the time to answer the readers' questions. It is appreciated. Is it OK to ... A: Well thank you Al, I really enjoy helping you all with your questions. Keeps my brain active. Is it ...
|
| Ductless Air Conditioners | 8/13/2008 |
Q: I have two 9,000 btu air conditioners connected to a compressor outside for which is for up to ... A: An air conditioning unit requires a blower fan to transfer heat to the evaporator coil.So I would ...
|
| trane compressor | 8/13/2008 |
Q: When my a/c shuts down, it makes a loud, vibrating noise. Was told that compressor is shot. My unit ... A: Having a Trane unit changes the answer on a compressor. Trane's are about 3 times the cost over all ...
|
| HVAC Design-best control system? | 8/12/2008 |
Q: I am planning to replace my Apollo furnace/AC system with a Goodman heat pump/gas furnace system. ... A: A Trane compressor is about 3 times as expensive as all others.The tubing in the coils is aluminum, ...
|
| duct size | 8/12/2008 |
Q: I don't think my duct is sized right please help me. I recently added on to my house and up sized ... A: Duct sizing is based on Bernoullis Equation for airflow.This is converted to a circular sliderule. ...
|
| a/c not blowing very cold | 8/11/2008 |
Q: i have a 4.5 ton a/c split system that is not blowing very cold. the unit runs all the time and has ... A: Looks like you have a restriction in the system. Too low, & too high. pressures. First thing, was ...
|
| freon vs puron system - effect of reusing lines? | 8/9/2008 |
Q: I need a total Heat pump HVAC system. The compressor is in the back of my townhouse,which is on a ... A: R-22 will no longer be made after 2010. So now is the time for R-410 for you. There is a flushing ...
|
| Variable speed furnace operating with standard AC Unit? | 8/7/2008 |
Q: I am in the process of doing a complete HVAC install on both my existing units that are 21 years ... A: First off, you ought to be installing systems using R-410a. Thats the new, high pressure stuff ...
|
| Garage door opener | 8/7/2008 |
Q: Recently my wife plugged in my large air compressor to inflate a raft! Well she heard a loud pop at ... A: WOW, what a blast ! No telling what happened with the breakers being rearranged ! Going to have to ...
|
| Heat pump problem. | 8/7/2008 |
Q: My home has three heat pump sytems which are about 15 years old - Seer 11. Recently, the MBR unit ... A: Sounds familiar for a compressor getting too hot over a period of time & shutting down, till it ...
|
| Payne PA10 central air conditioner | 8/6/2008 |
Q: My Payne PA10 air conditioner has suddenly quit working. The problem seems to be at the outside ... A: On the capacitor the 3 terminal are marked C, HERM, FAN.Cut the power, pull the wires off. With an ...
|
| no a/c | 8/5/2008 |
Q: the house is reading 85.no cold air.repairman was out 2 weeks ago.said i was low on freon.put some ... A: How much freon is "some" That sealer is best for a small leak. Say not more than 2# added to fill ...
|
| carrier condenser motor replacement | 8/5/2008 |
Q: outside condenser unit 38CKC036-340 says 1/5 hp 1.4a what my a/c repair man put in is an Emerson ... A: 69 avg days above 100 !! Couldn't handle that. I live in arlington,tx & we are having a string of ...
|
| evaporator fan inop | 8/5/2008 |
Q: This is trane airhandler a couple of years old with variable speed. If I turn on power to it, after ... A: Hey Paul, sounds just like a bad run capacitor on the evap motor. Test it with an ohm meter on the ...
|
| Thermostat problem or . . . | 8/4/2008 |
Q: In North Texas we are experiencing a significant heat wave of over 100 degrees for several days now. ... A: Need a freon test for capacity check. Just feel the suction line outside or inside in the afternoon ...
|
| Circuit breaker keeps triping | 8/2/2008 |
Q: I have a Central Lennox airconditioner installed in my home about eight years ago. I recently ... A: Running late on answering, sorry. It could be as simple as a loose terminal on the power circuit. Or ...
|
| Dual Zone - Electronic vs manaul | 8/1/2008 |
Q: We currently have a Electronic Dual Zone system that seems to have went bad after 12 years the other ... A: Zone control is sure good for multiple level homes.Being able to set 2 thermometers different in ...
|
| White Rogers Thermostat | 7/30/2008 |
Q: I recently purchased a property that I am renting out. There was an old white-rodgers thermostat ... A: An inexpensive thermostat can be a magnetic switch control.The White Rogers is good, mercury ...
|
| mold in air handler | 7/29/2008 |
Q: About 4 years ago I had a new ac system put in my 13 year old home. The old system failed and mold ... A: I'd say if you have a family with breathing difficulties get a UV light. I wouldn't pay $1800 for ...
|
| HVAC Design-best control system? | 7/29/2008 |
Q: I am planning to replace my Apollo furnace/AC system with a Goodman heat pump/gas furnace system. ... A: Hate to tell you but Goodman used to be Janitrol & we nicknamed it "Junkatrol" Used to be named GMC. ...
|
| Air conditioner | 7/29/2008 |
Q: We just had a power outage of 1-2 seconds. Our thermostat is working as is the blower. The A/C unit ... A: That outage is hard on compressor's. Refrigerator compressors too. If it is running when that ...
|
| Time delay relay on outside Compressor | 7/28/2008 |
Q: I have a Carrier 38CK036320 split unit hvac system. After having different issues with the air ... A: From adding freon last year, that's where I would start testing. That Carrier probably has a low ...
|
| Freon/Puron Conversion Kits | 7/27/2008 |
Q: I have a 6 yr old freon-based heat pump that needs replacing. In the process of getting quotes, one ... A: Sounds like he's blowing smoke at you, Mike. Never heard of a "conversion kit" before.It may be wise ...
|
| AC not working | 7/27/2008 |
Q: Mr. Livingston, I am hoping you can give me some guidance. Our home is only 2 years old, a modular ... A: 2 105 days ahead. That was very nicely worded question. Thank you. These things can break at any ...
|
| AC Mold/mildew smell from ductwork | 7/26/2008 |
Q: We live in South Florida and have a moldy smell in our house, which is probably originating from the ... A: Vacuum out the dust & dirt all you can from the supply air plenum. Then vacuum around the evaporator ...
|
| AC Blower won't stop before & after New Blower Relay | 7/24/2008 |
Q: 30+ y old Singer AC - The Blower motor turns on & after the compressor cycles off the Blower turns ... A: The cool fan circuit is different from the heat circuit, that you may know. Also, with the ...
|
| thermostat swing | 7/23/2008 |
Q: I have a question about the frequency of cycling of a Lux TX500 programmable thermostat which I ... A: I can't imagine you can satisfy both settings of cycle time & temperature !! A well balanced cooling ...
|
| Goodman Heat Pump | 7/23/2008 |
Q: I have a Goodman Heatpump and 2 days ago I started smelling a smell like the heat had kick on. I ... A: Don't know whether that Goodman has this but some heat pumps auto turn on heat elements on a defrost ...
|
| Broken compressor | 7/21/2008 |
Q: I would like to ask you a question. We have lived in an apartment 9 months and have one cat. Our ... A: Usually don't answer questions about friidges, but yours is easy.When the coils are pretty clogged & ...
|
| ac not blowing but compressor runs | 7/20/2008 |
Q: we have ac/heating unit lenox g-26 series.few days ago we noticed that the compressor runs outside ... A: Women are sure a target, Janet.I hate that.Fan control on "auto" comes from the thermostat. Do you ...
|
| Gas Heater | 7/20/2008 |
Q: I have a problem with my upstairs HVAC system in my house. The house was built in 1994 and has the ... A: Tricky question, Mike.I know of nothing that would interrupt power to the thermostat. There ...
|
| crack combustion chamber | 7/19/2008 |
Q: I just bought a house and had the oil furnace serviced for the winter and the person who conducted ... A: Cracked heat exchanger usually condemns it. But if he sees a crack so can you. That's an easy way to ...
|
| A/C Capacitor | 7/18/2008 |
Q: We had a service call (on our 2.5 ton Trane) a month or so ago (because only warm air was blowing ... A: WOW, $139 for a service call !!! $75 would be better.There is a 10% allowance from the capacitance ...
|
| Central air units | 7/17/2008 |
Q: Just returned from Iraq to find that the basin for one of two HVAC units in my house is full of ... A: The open one is a secondary drain line, needed when the primary drain plugs up. Someone was lazy.If ...
|
| Air conditioner and water heater | 7/16/2008 |
Q: When my air conditioner is running and the hot water heater turns on the exhaust from the hot water ... A: OOnly other thing I can think of is the heat exchanger in the furnace has a big hole in it. When the ...
|
| a/c is blowing warm air. | 7/15/2008 |
Q: I live in a mobile home. I have a "split system" ( a/c outside, electric furnace and blower ... A: Anything can happen anytime to this stuff, Anthony ! Warm air indicates the compressor is not ...
|
| Gibson Furnace | 7/15/2008 |
Q: Howard, I am attempting to solve two minor problems on a heat only central system located in a ... A: Wayne, Metal ducts I presume ?? #1. A multiple speed motor can have 2 brown wires for a capacitor,2 ...
|
| Two Stage AC Wiring | 7/14/2008 |
Q: I have a two stage 5-Ton Goodman condensing unit, single stage variable speed Goodman furnace/air ... A: the most complex circuitry I have ever seen is on a 2 stage compressor.Lennox has had those 2 stage ...
|
| Question about Purely-Radiant Cooling? | 7/13/2008 |
Q: I thinking of a cooling mechanism for houses and buildings in which the cooling -- in the direct ... A: I like you're thinking, Green! My counter to that idea is one of the laws of physics, heat flows ...
|
| York heat pump not running | 7/13/2008 |
Q: I have a york heat pump at home and it has stopped running. If I force the breaker in the unit ie. ... A: A control circuit problem.Can be a bunch of things to cause that. Low on freon,broken wire ,24v, to ...
|
| SEER | 7/12/2008 |
Q: The condenser on my split system failed (fifteen years old - we bought the house eight months ago). ... A: You touched a raw nerve, Bob about a mismatched SEER equipment.There is a lot of disagreement about ...
|
| trane a/c compressor stops, will start backup | 7/12/2008 |
Q: Our Trane is about 10 years old. It did this last year and stopped. The compressor will stop and ... A: Better test the compressor. After the unit stops, lay your hand on top of the compressor. Is is too ...
|
| Leaking AC needs freeon?? | 7/11/2008 |
Q: About a year ago my AC was not getting cold. The company came and added freeon and it was fine. ... A: Lack of freon can cause lots of ice on the evaporator coil. As it melts you can have a flood. But if ...
|
| York Heat Pump Error code 4 | 7/11/2008 |
Q: I have a York heat pump that is functioning properly for about an hour (starts to cool down the ... A: Sounds like a hot compressor. Need to let it run until it stops, then open the top & lay your hand ...
|
| pricing/labor | 7/9/2008 |
Q: My AC was not working properly and water was leaking around the outside unit. I called a repair man ... A: DON'T EVER PAY UP FRONT SHELLY. I changed a 4 ton coil & it was $875 total. Tell the guy to give you ...
|
| fan problem | 7/9/2008 |
Q: i have a ten yr old heat pump/ac it's a 3.5ton janitrol/goodman the problem is spuratic? maybe 2X's ... A: With the fan in the "auto" mode on the thermostat, the thermostat turns on the fan when cool is ...
|
| Janitrol compressor problems | 7/8/2008 |
Q: I have a 13 year old goodman janitrol heat pump with a bad compressor. It shorts out inside and blow ... A: That's a problem nowdays. The a/c supply houses require a license to buy parts. You might call a ...
|
| pulled small wire from outside a/c unit | 7/6/2008 |
Q: I accidentally pulled a small wire from my outside a/c unit while weedeating. It contains 2 smaller ... A: Oh, how much money have I made fixing those wires !! Best thing is to splice those wires back where ...
|
| Return Air Vents | 7/6/2008 |
Q: I am considering purchasing a new home still under construction, but we have concerns over return ... A: Did your current house have only 1 unit ?? Bet it did with multiple RA grilles.Now, the new house is ...
|
| AC | 7/5/2008 |
Q: We moved recently- Have a -Trane I believe- from an old bill- "Unit- ICPC- Model NFCX480062" , "ICPC ... A: Sorry about the delay, Fred. A busy weekend. Back to the contactor. Check the points to see if they ...
|
| Air Flow | 7/5/2008 |
Q: I recently ran an 8" air duct from the main duct of our swamp cooler to the master bedroom. ... A: If there is a supply air plenum with other ducts of various sizes connected to it & you add a duct ...
|
| Mystery Duct | 7/3/2008 |
Q: This is a receipt for a question you recently asked at allexperts.com of Craig HVAC Expert. You ... A: Did Craig answer your question ? Your link to the drawings is invalid.I will just make a guess about ...
|
| Leak in the Compressor Area | 7/2/2008 |
Q: "Hi, We have a Carrier 5 ton AC that's manufactured in 2001 for our home. We had an AC technician ... A: All good service folks have a H-10 leak detector which can measure leaks down to 1/2 ounce PER YEAR ...
|
| 24-V / 3 amp fuse | 7/2/2008 |
Q: Having issues with my HVAC. At the forced air unit, there is a 3 amp fuse that blew, which caused a ... A: Right, Ken, you have a dead short in the 24v control circuit. You can fins it. It can be in the ...
|
| air flow | 6/30/2008 |
Q: I have a dual HVAC system and had the upstairs system replaced. i contracted a guy who was to ... A: Air flow can be affected by the evaporator coil only if it is making ice & blocking the air flow. 17 ...
|
| A/C UNIT WILL NOT TURN ON | 6/28/2008 |
Q: Two days ago I shut my a/c unit off(while running) from the Main circuit breaker and tried to turn ... A: Those breakers can be ornery. Once you've tripped them they may not reset, even tho you moved the ...
|
| Rheem Criterion 2 cooling problem | 6/27/2008 |
Q: I can feel the sheetmetal become ice cold but the fan blower motor is not spinning. Is that a bad ... A: Turn on the fan only. No cool. Does it run ?? Test the run capacitor first. OK, bad motor. But next ...
|
| 4 speed to 3 speed conversion | 6/26/2008 |
Q: I have an older Frigidaire (Heil?) furnace with a 4 speed blower motor (low, med-low, med-high, ... A: little late responding. Phone has been down for 3 days. For heat & cool you need low & high speed ...
|
| A/C compressor not always starting | 6/23/2008 |
Q: I have a brand new Rheem Classic 90 (410A refrigerant) split system that works great 90% of the ... A: Sounds like you have a "sticky" compressor.How long is the warranty on it ?? 5 or 10 yrs ? Need to ...
|
| Control Panel Wiring | 6/23/2008 |
Q: My outside unit had water on the ground and iced up tubing leading into house. I opened express ... A: Can't see any missing wires in the photo, Dereck. That's a piece of the wire laying in the box ? ...
|
| Carrier Heat Pump | 6/22/2008 |
Q: Sir, I have a Carrier 38YMA which is 14 years old. The unit has been working extremely well. Last ... A: I would like to hire you to do my service work ! You good !!Fan motor windings do not have start ...
|
| A/C system in Florida | 6/22/2008 |
Q: I had an A/C system changed out in my Florida 1920's bungalow in 2002. I am embarrassingly young and ... A: Well, your question comes to a person that hasn't had a license for at least 10 years !!! I work ...
|
| central heat/air | 6/21/2008 |
Q: we bought a house last year-it's about 10yrs old- and the central air return is under the house in ... A: I live in North Texas. You too?? That's the way houses were built way back in the 50's & 60's here. ...
|
| Furnace Clearance | 6/19/2008 |
Q: I want to rearrange a few things in my basement and as part of that i want to put a door for access ... A: is this a gas or electric furnace.?? For gas you need 6" from the front to the door. The door needs ...
|
| Need help on HVAC usage costs. | 6/19/2008 |
Q: I have an an interior room in my house with no exterior walls. The central A/C for the house cools ... A: I'll get out my slide rule & figure that out ! Wish we had electricity that cheap in Texas. ...
|
| Lennox heat pump (10HPB48-10P) | 6/18/2008 |
Q: I have almost the same question as what was posted in the post "Trane heat pump xl1200". I turned ... A: Easy test for capacitors is with an ohm meter set on it's highest reading. With no wires attached, ...
|
| air condioning | 6/18/2008 |
Q: With air-conditioning season starting so has the debate as to leaving the air on and doors and ... A: The first thing cooling does is remove humidity, 2nd is the temperature of EVERY OBJECT in your ...
|
| Heil heat pump | 6/17/2008 |
Q: I have a Heil system that does not cool. The capicitor, reverse valve and compressor are good. It ... A: The service valve on the suction line has a Schrader valve in it. Sometimes the hose connection ...
|
| wiring | 6/17/2008 |
Q: I replaced the condenser fan motor on our churches a/ac package unit. It's running the correct ... A: Capacitors are NOT directional. Either way. Maybe test the capacitor. There sorta cheap these ...
|
| Trane heat pump xl1200 | 6/16/2008 |
Q: I suspect that the cooling fan in the condenser unit is bad.I had ac on all night and awoke to warm ... A: Test the run capacitor first. If OK, it's the fan motor.2 speed condenser fan motors went out a long ...
|
| Honeywell Vision Pro 8000 wiring | 6/16/2008 |
Q: I am installing a totally self-contained heatpump system in a trailer, and want to hook up a vision ... A: Yes, remove the jumper from R & Rc. What I don't know is the use of E for that tstat.It is usual for ...
|
| Heat pump size/efficiency | 6/15/2008 |
Q: I have a 5 y/o, 1300 sq. ft ranch. It came with a 2.5 ton heat pump. I live in NC where the high ... A: Used a/c stuff has little market. They are good for garage cooling or a landlord looking for cheap. ...
|
| Weird Smell From Air Conditioner | 6/14/2008 |
Q: There is a weird smell coming from the air vents - I would like to say it smells like a super ... A: Not too uncommon to smell something from the vents. Main that that could create a smell is the ...
|
| Electrical Problem (?) with Bryant AC Unit | 6/10/2008 |
Q: On very warm days when my AC unit has to run for ~90 or more minutes in order to get/keep the house ... A: First, I would test the accuracy of the thermostat. Got another thermometer to lay on the thermostat ...
|
| fan relay | 6/9/2008 |
Q: 95 year trane unit, air handler fans runs non-stop, can the orignal relay#9100211Q132 be replaced ... A: I don't have catalogs to know what those numbers mean for a fan relay.I can say the coil voltage ...
|
| Residential AC | 6/9/2008 |
Q: I have 2 zones with a 3 ton air conditioning unit. The bottom zone is Central air with a propane ... A: Oscar. I'm a little late responding as fast as I like. Got to admit we had our 60th anniversary ...
|
| a/c not real cool | 6/8/2008 |
Q: I HAVE A TRANE WEATHERTON XE1000 WHEN WE MOVED INTO THE HOUSE THE AIR WAS REAL COLD NOW 3 YEARS ... A: It's possible but... Does the compressor still run ?? Sounds like the problem may be just needs ...
|
| AC not blowing cold | 6/7/2008 |
Q: I have a Raheem HVAC system. After noticing that the air is not blowing cold, I went outside to find ... A: Without that outside fan running the freon pressure goes nuts & kills the pressure switch. First, ...
|
| Lennox Central Home Air Conditioner No Cool | 6/5/2008 |
Q: Almost identical to another current question on this site. My system turns the distribution fan on, ... A: The breakers are only one of many causes for nor cooling. More are a burned contactor points. Or low ...
|
| HVAC split unit | 6/1/2008 |
Q: I have an HVAC where the compressor is on the roof and the heater is in the hallway. The model of ... A: Are you using the green horsehair media ?? Some horizontal furnaces just lay the filter against the ...
|
| Rheem Split Unit | 6/1/2008 |
Q: I have recently purchased a rehabbed home that was built in the 40's. The seller claimed that the ... A: These things cab act up at any time !! Usually on the weekends in Summer. Does the inside fan run ...
|
| heating | 5/31/2008 |
Q: I was having a talk with a friend and we discussing heating and how to save money this coming ... A: A chart I have compares the amount needed to produce 1 mil btu's. It says it takes 293 kwh & 10.9gal ...
|
| help | 5/30/2008 |
Q: heater work great all winter.except had to replace thermostate.turn on air cond. and blower would ... A: Where did you find all those bad people ?? Starts off with a bad motor & ends up changing a ...
|
| question on appropriate heat pump size | 5/29/2008 |
Q: I have a 3200 sq ft home in Washington state (pretty mild weather). My furnace is a Rheem Criterion ... A: A couple of questions first. Is this a replacement deal or a new house?? (Replacement would give a ...
|
| Hard start kit question | 5/29/2008 |
Q: Recently my a/c company installed a new evaporator coil with a TXV. Later they realized the coil was ... A: That lesson about using a start capacitor on a TXV valve coil is learned early on in this business. ...
|
| Neither AC nor fan will come on | 5/27/2008 |
Q: We tried to turn our AC on last night for the first time this season. I set the thermostat to cool ... A: Check the wires behind the thermostat. red wire on R, green wire to G, white wire to W, blue or ...
|
| a/c compressor | 5/24/2008 |
Q: I have a Bryant package unit, keeps blowing breaker. I think it could be compressor, removed black, ... A: Burned out motor windings for common & run windings. The freon ought to smell burned also.Add liquid ...
|
| TRANE XE1000 HEAT PUMP THERMOSTAT | 5/24/2008 |
Q: EVERY ONCE IN A WHILE, OUR A.C. AUXILIARY HEAT "LIGHT" GOES ON WHEN WE LOWER THE COOLING SET POINT, ... A: Some control circuit wires crossed up for that to happen. Suggest checking the wires behind the ...
|
| Heil Air Conditioning Unit | 5/23/2008 |
Q: My unit is 6 years old and I have had an issue with it eery summer for the past 4 years. The most ... A: I've experienced that problem before & was totally unable to stop it ! It was a small, short wire ...
|
| 2 year old Carrier evaporators are leaking | 5/22/2008 |
Q: In May of 2006 we replaced our entire hvac system with all Carroer equipment. Recently the system ... A: Different vents will have different temps due to the heat load in the attic & different length runs. ...
|
| noise in Luxaire 12 EER | 5/22/2008 |
Q: About a year after we got it, our outside unit started making a loud noise when it kicks on, ... A: If you have a mercury controlled thermostat & it is not level on the wall the mercury can roll back ...
|
| Thermostat | 5/22/2008 |
Q: My AC quit working. The thermostat is not showing any readings. I checked the transformer voltage ... A: That thermostat use batteries ?? Test for 24v from red to all other connection on the thermostat. ...
|
| A/C age + compatability ? | 5/21/2008 |
Q: My current a/c unit is as old as my home (1976) and is still hanging on by a thread, but just ... A: That is a 1992 model
|
| 2 year old Carrier evaporators are leaking | 5/21/2008 |
Q: In May of 2006 we replaced our entire hvac system with all Carroer equipment. Recently the system ... A: Hey Jennifer, You said "both evaporators". You have 2 systems ?? Both leaking ?? I have not heard ...
|
| motor replacement to air conditioning unit | 5/21/2008 |
Q: Our unit is 25 years old. Within the last month it would work for an hour and then the blower would ... A: Makes me sick for someone to charge a fee like that !!I am assuming that the "blower" is usually the ...
|
| YORK MODEL SJ - Not as cool as it should be | 5/20/2008 |
Q: We just installed a YORK Model SJ unit in our mobile home: Latitude Series, R-22, 13 Seer, ... A: Mobile homes are not known for good insulation. 1# of freon shouln't make much difference in ...
|
| Lawnmower Sound From Heat Pump | 5/19/2008 |
Q: Okay, I have had my installer out four times to evaluate this problem. I have a 4 ton American ... A: Only thing on the inside unit possible is the blower wheel & motor. Sometimes the freon rushing in ...
|
| hvac | 5/18/2008 |
Q: I am getting ready to install a new HVAC (air conditioner and air handler) in my ten-year old, ... A: Always a good question, Don. This tho is only my opinion of coarse. Scroll compressors are good ...
|
| Payne Warranty on Compressor | 5/16/2008 |
Q: We bought a new house that came with a Payne A/C unit. The unit was serviced because it was not ... A: WOW ! You was ripped ! $60 OK. 2.75 hrs OK. $165 filter NOT OK. That's a $35 filter !!.No ...
|
| Carrier motor problem? | 5/16/2008 |
Q: The tech wants to replace my blower motor for $450, but I'm not convinced that it's the problem. ... A: Never heard of condemning a motor for those causes in 35 years !! If one piece of the continuous ...
|
| Frozen AC | 5/14/2008 |
Q: We live in TX where our Summers are always above 90. We just moved into a home with a central ac ... A: Ice forms when these things happen to the cooling system: Dirty filter, dirty blower wheel, dirty ...
|
| need heat pump advice | 5/12/2008 |
Q: I need some advice about heat pumps. My parents home is in West Central Florida ( Hudson ) where the ... A: Nw that's some good info, Ken. Usually the other way.Bet the R value od cinder blocks ain't too good ...
|
| question about the fan | 5/12/2008 |
Q: my question is about the fan. I noticed it was on this morning, even though it was on auto and the ... A: No need to worry, Angelique. There's lots of safety stuff on this equipment, plus circuit breakers. ...
|
| Payne Interior unit problem | 5/12/2008 |
Q: The distribution fan in the interior unit is receiving voltage in all locations except one. I ... A: Capacitor test: With ohm setting on the highest, remove all the wires & test across 2 terminals. The ...
|
| A/C unit is freezing up | 5/11/2008 |
Q: I have pretty fair knowledge of electrical and some a/c components. Limited on funds and down in ... A: Wow, a Chrysler still running !!! Those were really good units. Worse thing happened a freon leak ...
|
| replacing a Condenser Fan Motor | 5/10/2008 |
Q: I have a Ruud Acheiver 10 High Efficiency air conditioning unit. I've been watching this motor go ... A: No problem. Kill the power & remove the motor. Propeller is first tho. Just cut the wires in a ...
|
| Inside Fan Motor stays on - Carrier AC with heat strip | 5/9/2008 |
Q: Issue is blower motor stays on. Even with AC/Off/Heat set to Off, blower motor stays on, regardless ... A: One of the heat element sequencer disks on an electric heater can lock closed & keep the fan ...
|
| Trane XE 80 | 5/8/2008 |
Q: We had a recent power surge come through our house as a result of some tornadoes. It took out 2 ... A: If you don;t have a fried circuit board you're lucky. The 3 amp fuse is an auto type plugged into a ...
|
| Carrier furnace 58ES | 5/8/2008 |
Q: WHERE IS THE FAN LIMIT SWITCH LOCATED? AND IS IT EASY ENOUGH TO REPLACE? IF I HAD AN ACCURATE ... A: Don't have info that you have sent me a question before ?? Anyway, on the old style furnaces(NOT ...
|
| Air Conditioner Brands | 5/8/2008 |
Q: We are looking to replace our AC units. I see information about trane/american standard and ... A: York makes their own compressors & they are way more expensive than other brands. Lennox is good ...
|
| Goodman air/furnace | 5/7/2008 |
Q: I have a HVAC system that is two years old. I went to turn the air on the other day and the system ... A: Sounds like you've lost the control circuit. Turn only the fan switch on to test for fan. If none ...
|
| air handlers | 5/7/2008 |
Q: Are variable speed air-handlers for Central AC worth the extra cost? How has their reliability been ... A: Good question, Steve.The best place to use a VS blower is where you need a quiet fan. Best example: ...
|
| Replacement Coil | 5/6/2008 |
Q: I have a friend who had his air conditioner go out yesterday. He called a repairman, and he said ... A: Replacing the coil indicates it is leaking freon. If this is an "A" coil upflow, there are coils ...
|
| Black specks from air ducts | 5/5/2008 |
Q: Black specks fall from the air duct in the room that is directly below the heating/AC unit in my ... A: This is a difficult question to answer. But not an uncommon question. Only thing I can imagine is ...
|
| 2 HEAT PUMPS 1 THERMOSTAT | 5/5/2008 |
Q: At our church we have a very large room that has 2 separate heat pumps with 2 separate ... A: Yes. Use one of the units transformers to supply control voltage to both of them.So use the 24v ...
|
| e-coil cleaning | 5/2/2008 |
Q: I have some experiance with various hvac repairs. I want to inspect and clean a Rheem evap coil. The ... A: Some coils have end plates screwed in that you can take loose that may give you a peek to the ...
|
| Why did my scroll compressor lock? | 5/2/2008 |
Q: The HVAC man diagnosed a "tightly locked" Benchmark brand 3.5 ton compressor in my heat pump/air ... A: DON'T GIVE UP JARED !!!! 4 to 5 hours !!! 10# freon !!!! I can do those by myself in 2 hrs. No, ...
|
| Carrier heatpump | 5/1/2008 |
Q: Howard, I have a carrier one piece electrical 2 1/2 ton heatpump, 11 years old. The cooling works, ... A: Something fishy here, Ron. When you call for heat, doesn't the heat from the heat pump turn on ?? ...
|
| Quotes, New Purchase | 5/1/2008 |
Q: Right now I have radiant heat and am looking at upgrading to a heat pump system. So far I have ... A: Is that "air purifier" a true electrostatic filter ?? If so, those things are a lot of trouble. I'd ...
|
| Compact Room AC for 12v Mobile Use | 4/30/2008 |
Q: I would like to apply a small room, 115v AC Air Conditioning unit to a 12v DC mobile environment ... A: Don't think they ever made window units smaller than 5000 btu. The compressor start up is usually at ...
|
| HVAC | 4/29/2008 |
Q: Can you replace a 10 ser condensing unit w/ a 13 and not change the a coil, and if so what is the ... A: Yes you can, Bob. Some places cancel the warranty if the coil not replaced but most of us have ...
|
| Lennox 10ACB24-9P | 4/29/2008 |
Q: I was reading one of your suggestions about a hidden switch on my unit. I don't seem to be able to ... A: I was referring to a switch on the outside unit that trips on a fan motor failure - i.e. high ...
|
| Payne Central Unit | 4/28/2008 |
Q: I had a guy come out and look at my unit it was installed in 2001 . Propane heat split unit Payne ... A: I'd replace the gas valve. A familiar story.Furnaces can last 35yrs or more. He was hungry I guess. ...
|
| gunk in a/c condensate line? | 4/27/2008 |
Q: I noticed our unit- which normally cools to whatever temperature we set it at- was not cooling. The ... A: (that's an interesting name !)Ice is caused by several things, like; low on freon, dirty filter, & ...
|
| new Hi eff furnace purchase | 4/26/2008 |
Q: Have quotes on the lennoxG71p, bryant plus 90i, Ruud ultra hi eff furnaces with vs fans, wondering ... A: Best advice is move to Texas, where I live.Those variable speed fans are really expensive but good ...
|
| a/c | 4/25/2008 |
Q: Our a/c unit kicks on and runs for 3 minutes then kicks off for 3 minutes and keeps this steady 3 ... A: First thing to test is the freon amount. May have electrical problems also if freon OK. Could be the ...
|
| short cycling heat pump | 4/23/2008 |
Q: I have a Rheem RPKB heat pump that was installed almost two years ago. It now appears that the ... A: Lack of air across the coils will short cyle on a low pressure switch. If your system is operated by ...
|
| Trying to understand HVAC repair and replacement. | 4/22/2008 |
Q: I am an investor and I’m trying to understand the AC repair and replacement market. I would be ... A: Personal opinions can vary all over the place Robert. Here's mine. I used to have about 700 ...
|
| Lennox A/c issue... | 4/22/2008 |
Q: 2 months ago mid Feb. you helped me solve a heating problem. Your diagnosis was spot on! Now need ... A: The compressor is cooled by the returning freon.But it can also get hot from worn bearings & drawing ...
|
| short cycling heat pump | 4/22/2008 |
Q: I have a Rheem RPKB heat pump that was installed almost two years ago. It now appears that the ... A: Looks like you have lost some freon & it is short cycling from a low pressure switch. Got gauges to ...
|
| Compressor runs but fan doesn't | 4/20/2008 |
Q: My gas ac unit will run for how ever long it takes to get to programmed temp.but during process the ... A: Terry. Now the main thing to test is the run capacitor for the fan motor.You can test it with an ohm ...
|
| Replacing an AC fan motor | 4/19/2008 |
Q: Just wanted to get an idea of how difficult it would be to replace the AC fan motor on a residential ... A: OK, here goes, Wayne. Kill the power. Access the motor & remove the propeller.And that task can be ...
|
| RUUD Filters | 4/18/2008 |
Q: We have a RUUD UBHC 17J11SFF, manufactured 2/04. We're looking for HEPA-like air filters but ... A: Yo J. I like short names ! Don't be fooled by "electrostatic" filters. They are not. It takes ...
|
| Lennox A/c issue... | 4/18/2008 |
Q: 2 months ago mid Feb. you helped me solve a heating problem. Your diagnosis was spot on! Now need ... A: Well hello again Dave! You have been tricked by a typical problem. The outside fan masks the fact ...
|
| blower on furnace will not stop | 4/17/2008 |
Q: Heil gas furnace model EPD5536DC1, then it has another line under it that says d36pa15a1 but not ... A: I presume your furnace is controlled by a circuit board ?? Two things I can think of, Kim. One is ...
|
| Pressure switch in furnace | 4/16/2008 |
Q: My furnace runs too many times at night. Each time it runs less than 10 minutes. Could it be the ... A: The pressure switch closes to tell the circuit board the combustion air blower is working. Actually, ...
|
| Trane XE800 High and low Pressure | 4/8/2008 |
Q: I had noticed the Air Handler running almost constantly in the last month (Outside Temp 30-40 F). I ... A: Heat pumps are tested for freon only on the cooling cycle.The buzzing sound is typically the ...
|
| a/c no start | 4/8/2008 |
Q: I have a Goodman air unit. When I turn the thermostat I hear a click on from the unit and a hum as ... A: Yo Joe, Sounds like the contactor points are burned a bit & won't make good contact. With the ...
|
| liquid cool assist for residential A/C | 4/7/2008 |
Q: I'm trying to detemine if there is some kind of geothermal assist available for a/c units. I don't ... A: Well.Tom, you could dig a deep well in the backyard & run a loop of pipe in & out of it to precool ...
|
| Lennox AC/Heat Pump | 4/5/2008 |
Q: Thermostat lost power...outside unit has power, air handler has power... replaced defrost circuit ... A: Does the fan run when the fan switch on the thermostat is "on"? Thats a control & power circuit ...
|
| Luxaire Evaporator Coil Access | 4/4/2008 |
Q: I have an older home with a 1995ish a/c and furnace unit inside. I am having difficulty getting to ... A: It`s difficult to clean a coil. To do a good job, you have to remove the coils & the difficulty is ...
|
| Duo Therm Roof RV AC | 4/2/2008 |
Q: My '76 GMC motorhome has two roof mount Duo Therm AC units model# 54615-035 and 54515-036 one has ... A: gosh, after 30 years you ought to be used to the vibration !! That is just a flaw in the compressor ...
|
| Carrier AC Problem | 4/1/2008 |
Q: Howard, my AC system is a Carrier for a 2-story 1500 sqft townhouse and is less than 2 yrs old. A ... A: Best guess Tom, the transformer is heating up from a bad coil. A test would be read voltage on both ...
|
| air handler circuit breaker | 3/30/2008 |
Q: I just moved into a really nice townhouse. The air works but I noticed that the air handler switch ... A: Circuit breakers can be an ornery as any electrical device.Also can cause fires too. So when they ...
|
| Rudd Furnace yr1991 | 3/30/2008 |
Q: Furnace starts up with induction motor first and then cycles without the hot surface ignition ... A: Tricky stuff it appears. You can eliminate the thermostat by jumping across the red & white wires at ...
|
| AC/heat pump problem | 3/29/2008 |
Q: Heat runs fine. When you cut the AC on the fan runs but the pump does not run. It does work with the ... A: The one thing that makes the heat/cool for a heat pump is the reversing valve.The inside fan runs ...
|
| Low Flame Sensor Signal | 3/29/2008 |
Q: My Frigidiare 90+ downdraft natural gas has a "low flame sensor signal" indication. Which some times ... A: That ought to mean the electrical signal sent to the flame sensor from the circuit board that there ...
|
| Return Air Flow - Gas Furnace | 3/29/2008 |
Q: Bought this house two years ago. We have been slowly renovating and I just pulled a return air vent ... A: That is a pretty good way to have good circulation, is to use the wall as a return air duct. Return ...
|
| Heat pump not starting up | 3/26/2008 |
Q: I have a Carrier heat pump that stopped working all of a sudden. Even if you put the fan switch to ... A: That's a first, Mohammad, to get a picture ! Circuit board can be identified by the part number of ...
|
| Heating/A/C thermostat | 3/26/2008 |
Q: I live in North Texas ( DFW) area. I have a single story 3000 sq Foot house with two A?c's/ ... A: The digital thermostats have taken over the market & there are a lot of varieties.Stay away from ...
|
| home furnace/ac | 3/23/2008 |
Q: Furnace switches on when thermostat says area is too cool. Runs as it is supposed to, but when ... A: This sounds like a fan running(no heat)since the temperature switch is not satisfied, Ron.If this is ...
|
| American Standard Furnace | 3/19/2008 |
Q: I've had ongoing problems with my 21/2 year old American Standard furnace. The most recent problem ... A: The pilot light or the ignitor has to be proven before ignition, then the flames proven by the flame ...
|
| limit switch settings | 3/19/2008 |
Q: I have a keeprite furnace, it has an intermittent switch I think it's about 10yrs old, anyway the ... A: Ought to shut off the fan at about 90 deg.But, if the furnace is controlled by a circuit board, the ...
|
| Heil DC90 Model# NTGM100EHA2 intermittently blows cold | 3/15/2008 |
Q: I am having the problem in which the draft inducer comes on but the pilot fails to go to full ... A: The flame sensor sanding may have screwed up the sensor. Just need to rub it with a rag to polish ...
|
| Carrier Infinity | 3/13/2008 |
Q: Howard, A Manual J was done on my home and determined that I need: 16,524 BTU's for cooling the 2nd ... A: Well, Brian I am a conservative & over the 35 yrs in the a/c business my opinion goes that way. ...
|
| 1 A/C or 2 ? | 3/12/2008 |
Q: i am in central CA in a 2,000 sq.ft house. half of the house is open plan (almost one big room) ... A: Think the best approach, Rick, would be a separate system in the attic for the 3 br, 2 bath side. ...
|
| frigidaire | 3/11/2008 |
Q: I have a frigidaire model # FG6RA 096C 16B and was moving humidifier wires. The cap came off a wire ... A: Little trouble, huh? Ya never know what happens on a ground fault like that.Do you have a 120v ...
|
| Furnace blower motors | 3/9/2008 |
Q: I am about to upgrade my furnace to a 95% efficient one and add AC at the same time. Is there an ... A: The only advantage that I would see adding a variable speed blower is the quietness. I you have a ...
|
| Goodman GMP100-3 | 3/6/2008 |
Q: I just replaced the blower motor and fan wheel.After I hooked everything up the blower works for the ... A: A blue wire to the gas valve is puzzling since a blue wire usually is the control wire from the ...
|
| Won't keep running NUG9075FGB1/GUM075N12A | 3/5/2008 |
Q: I have an old Keeprite/Comfortmaker which heats my house for the last 10 years very well. It's a ... A: Your`e a good fixer, Bruce.I like do-it-yourselfers, as long as they don`t take too much apart that ...
|
| Concord gas furnace CG80UB150D20D | 3/4/2008 |
Q: Install furnace in November. I notice burner cycling on/off. Works when bypassed. Original limit ... A: There`s no air shutters at the ends of the burners ?? Maybe not with combustion air regulated by the ...
|
| Heater troubles | 3/4/2008 |
Q: I am not sure of brand of heater...It has a diagnostic light on board that flashes three ... A: Wow,John, that`s a killer problem. Does the igniter ever light ?? I presume the LED code is still ...
|
| Concord gas furnace CG80UB150D20D | 3/3/2008 |
Q: Install furnace in November. I notice burner cycling on/off. Works when bypassed. Original limit ... A: Yo Edward,3.5 " water good. Those flames need more air if they are yellowish.You`re on natural gas, ...
|
| Heater troubles | 3/3/2008 |
Q: I am not sure of brand of heater...It has a diagnostic light on board that flashes three ... A: need to remove the hose & insure its not obstructed, nor the opening at the induced draft motor. ...
|
| Comfortmaker high efficiency furnace problem | 3/1/2008 |
Q: I have a 12yo Comfortmaker gas furnace model# NUG9075FGB1/GUM075N12A - For the past month, on ... A: In Texas we draw air from the attic into a sealed closet.The induced draft motor provides the air ...
|
| Comfortmaker high efficiency furnace problem | 2/29/2008 |
Q: I have a 12yo Comfortmaker gas furnace model# NUG9075FGB1/GUM075N12A - For the past month, on ... A: Test for gas leaks with a soap & water mix. Stir it up to make bubbles & wipe across the gas joints. ...
|
| Installing Humidifier | 2/29/2008 |
Q: I have a Trane Forced Air Furnace Model: GUCDA-10-A Type: 174-470-2-A I want to install the ... A: The air flow will only be from the high pressure supply side. So you can mount on the high side ...
|
| Trane XE 90 | 2/28/2008 |
Q: I have a 1995 Trane XE 90 Heat Pump. The diagnostic light blinks 2X, "System Lockout, No Flame, ... A: That is just turning the power plug around to reverse the polarity. No plug, will have to splice the ...
|
| Installing Humidifier | 2/28/2008 |
Q: I have a Trane Forced Air Furnace Model: GUCDA-10-A Type: 174-470-2-A I want to install the ... A: Black is hot, white is ground.Ground is anything that is grounded, so the case, or copper pipes are ...
|
| Gas Forced Air Furnace | 2/27/2008 |
Q: The furnace is an Armstrong Air Ultra V unit. The blower motor starts, but ignition does not ... A: Remove the tube between the induced draft motor & pressure switch. Blow thru it to test for ...
|
| heater will not ignite | 2/26/2008 |
Q: My York diamond try to ignite three times and then goes into lockout mode. The seven flashes of the ... A: Aha, you have an electric ignition for the pilot only,After sensing the pilot, the gas valve opens ...
|
| Rheem Criterion II | 2/26/2008 |
Q: My heater is of electronic ignition control.. When commanded on by thermostat, initial sparking ... A: There is a flame sensor that CAN cause that to happen, Richard. The sensor is usually a metal rod ...
|
| American Standard Freedom 78 | 2/25/2008 |
Q: Howard, I've got a American Standard Freedom 78 in my home that blows cold air from time to time, ... A: So you must have a variable speed blower ?? Assume the furnace is circuit board controlled also ?? ...
|
| Tempstar condensing propane furnace | 2/25/2008 |
Q: Late this past week I noticed sounds from our Tempstar furnace that sounded like the air from the ... A: Furnace problems can echo throughout the house! Open the door to access the blower & feel the blower ...
|
| furnace filter | 2/25/2008 |
Q: sorry if this is a stupid question but i recently moved into my new home and there is a heil ps80 ... A: There are no stupid question, only stupid answersKim. Normally, the filetr is behind the lower door ...
|
| heater will not ignite | 2/24/2008 |
Q: My York diamond try to ignite three times and then goes into lockout mode. The seven flashes of the ... A: Put on a coat, first.Does the igniter glow ?? Does this model light a pilot flame, then the burners ...
|
| miller furnace | 2/24/2008 |
Q: This is my mom's furnace. It is an '89 in a doublewide trailer. If properly working, I see it ... A: Pretty) sure I have seen this on trailers. As the "inferno: (I like that name) starts, it sucks the ...
|
| Lennox heat pump | 2/23/2008 |
Q: we had an issue with the a/c system not blowing cool air we called out a tech who said the system ... A: Adding freon means you have a leak somewhere. Favorite place is the evaporator coil. Need to sniff ...
|
| Powered Humidifier wiring | 2/22/2008 |
Q: How should my new powered humidifier be wired? My brother in law installed it for me. He ran a new ... A: Humidifier only runs when the blower is on. So if the board has an H terminal that ought to do it. ...
|
| induced draft motor | 2/22/2008 |
Q: i have a tempstar 90% furnace that wont run. its only 18 months old. the stat will call for heat ... A: Whoa ! not good, Tony. Typical electronics, acting up so soon.Those code LED flashes are usually ...
|
| Maytag heat pumps | 2/21/2008 |
Q: I am shopping around to replace my existing 15 year old lennox heat pump system. Most of the ... A: A salt water creek ?? Interesting. That explains the stainless steel.First thing, what`s wrong with ...
|
| Furnace Draft Inducer Blower Replacement | 2/21/2008 |
Q: I need to replace the blower, the wheel is wobbling and getting stuck. The gas-pak unit is a: Inter ... A: Hey George, Don`t think I have the answer either.I think the main thing to deal with is the shaft ...
|
| Heater not blowing heat | 2/20/2008 |
Q: I have a dual heat pump. The heating in the attic is working but the unit unit (big fan thingy) ... A: I`m sorta confused, Susan. I`ll quote you as " the heating in the attic is working..." & " the fan ...
|
| TAPPAN FORCED AIR GAS FURNACE | 2/19/2008 |
Q: I have a 30 year old Tappan Forced Air Gas Furnace (Model SGUF 140842 E-7 Series). It has a ... A: NOW your talking good when you said the flames are HUGE> Thats a very good tip that the regulator in ...
|
| intake air vent | 2/18/2008 |
Q: We have a big intake vent which is right next to our tv in our family room (basement of house.) It ... A: No,No. Find some thick, heavy shag carpeting. Glue a piece on the floor behind the grille. Find some ...
|
| Am Std Freedom | 2/18/2008 |
Q: read following question here...We have a Freedom 78 American Standard furnace in our 13 year old ... A: This is sorta a common problem.Has the LED trouble lights flashed? O r does your furnace have a led ...
|
| Setting the thermostats | 2/17/2008 |
Q: We are having trouble learning how to set the thermostats in our just built home (not programming, ... A: Start off by adding a LOT of ceiling fans.Particularly, one in the 2 story foyer.Then another in the ...
|
| TAPPAN FORCED AIR GAS FURNACE | 2/15/2008 |
Q: I have a 30 year old Tappan Forced Air Gas Furnace (Model SGUF 140842 E-7 Series). It has a ... A: Your question, Karen were the burners supposed to do that ? I said no. So now here is possibly your ...
|
| Furnace | 2/14/2008 |
Q: 8 yr. old Bryant heats to temp on stat and then cuts off. A qwik flip of the circut breaker restarts ... A: Could be a bunch of things.Was the circuit breaker tripped, or just reset?? There are several over ...
|
| 15 Year old WaterFurnace | 2/13/2008 |
Q: I have a 15-year old WaterFurnace brand GeoThermal unit that has been diagnosed with a Freon leak ... A: Rush to the local a/c supply house & get a can of "leak sealer". That has hit the market about a ...
|
| Lennox Propane Heater | 2/13/2008 |
Q: I recently had a two-year old Lennox Direct-Vent propane heating unit replaced with a new one. The ... A: Yes, yes, yes you should be concerned with the soot.Not good. Those flames better be all blue, but a ...
|
| Air purifier giving off a smell, may be motor | 2/10/2008 |
Q: Testing your DC motor experience. I have just bought a second hand Sharp Plasmacluster air ... A: I`m not familiar with that kind purifier so I can only guess. My gues would be that thing was ...
|
| HVAC Question | 2/10/2008 |
Q: I'm loosing a ton of warm air generated by my HVAC system this winter because the only return ... A: A return air is sized so the airflow is about 400cfm/min across the grille(s). This ensure the ...
|
| Lennox G60 error codes | 2/8/2008 |
Q: I am having the same problem as Joanne is. Alternating LED's. It happens intermittently, maybe ... A: Didn`t check my answer to Joanne. I`ll just shoot you with what can be wrong with your furnace. It`s ...
|
| Split system approaching its usefull life | 2/8/2008 |
Q: I purchased a used house in S.W.Fla. 4 yrs ago.Came with a 1998 Lennox heat pump 13 seer 3.5 ton ... A: Sort of a common question. I have been an independent for 30 yrs, & a conservative type.So my ...
|
| HVAC residential Compressor related | 2/7/2008 |
Q: ... Generally speaking, if I had a symptom of a tripped 100 amp breaker, a burnt smell, how long do ... A: depending on the locked rotor amps of your compressor it could kick a 100 amp breaker. The locked ...
|
| drain pan and drain pipe | 2/7/2008 |
Q: I have 2 questions: #1 I have a Carrier Model # FX4ANF048 that was installed in late 2001. The ... A: You forgot what material the pan is ! I will presume it is plastic. Puron does not crack ...
|
| Air Quality | 2/5/2008 |
Q: We have an air quality problem I hope you can help me with. When our furnace clicks on we ... A: Thing of it is different people have different smell sensitivity. I have had bad experiences with ...
|
| Furnace Control Board | 2/5/2008 |
Q: Furnace Model # P1UKD12N0401A Problem is the ignitor stays lit all the time, only goes off when ... A: That`s a heck of a problem, Chuck. All of the problems seem to point to the board.It has the control ...
|
| Gas furnace not blowing very hot air | 1/31/2008 |
Q: I have a gas furnace (comfortmaker FBF050B12AA, serial # L002729897)that is 7 years old. When the ... A: I would check the duct system to see if they are OK. With all the burners working that amount of ...
|
| hear pump | 1/30/2008 |
Q: I have a Lennox heat pump that the compressor will kick off about every sixteen hours. I will have ... A: What you really need is a recording amp meter to follow what`s going on with the compressor (if ...
|
| thermal fuse (or what) | 1/29/2008 |
Q: I have a Trane Air Handler and need to replace some old, rusted fuses-took one out and it says ... A: I had the wrong fuse in mind.That`s a second fuse protecting against an overheat situation.Don`t ...
|
| Emergency Heat Inoperative | 1/28/2008 |
Q: Howard, I have a two and a half year old Carrier heat pump system with an electric emergency heat ... A: Wow, Chad that`s a good one !! Have to eliminate things one at a time to arrive at some kind of ...
|
| noma 52-2570-6 thermostat | 1/26/2008 |
Q: Good evening. I've never posted to this forum before but I thought I'd try... I just bought a ... A: You have a heat pump. Is the new one for a heat pump ?? I`m not familiar with that H designation. I ...
|
| burners sometimes don't light on AS Freedom 78 | 1/25/2008 |
Q: We have a Freedom 78 American Standard furnace in our 13 year old home. I assume it's the original. ... A: The blower works on a time delay only. Does the igniter glow each call for heat ?? If so, the flame ...
|
| I think Heat pump? | 1/25/2008 |
Q: I have a carrier model # 38Ycc. The problem has happe three or four times. The outside uit shuts off ... A: Could be several things, Mike. One is the point on the contactor are burned & not making contact. ...
|
| Lennox G60 gas furnace will not maintain heat set on thermostat | 1/24/2008 |
Q: I have a Lennox G60UH-070-02 (2002)gas furnace which has been fine until now. At night or when I ... A: Check the thermostat to be level. Check the heat anticipator behind the front to be set about at .4 ...
|
| Thermostat | 1/24/2008 |
Q: Should you set the heat and leave it alone or adjust it at night. This is a 2 story house. Upstair ... A: Typical problem for 2 story houses with 1 unit ! If all the bedrooms are upstairs I would turn off ...
|
| Heating problem | 1/21/2008 |
Q: We just moved in to a new house that has a fairly new Heil H9MPD heater. It seems to work fine when ... A: Need to run a test on the thermostat.Wonder if it is a mercury or digital ?? If mercury controlled, ...
|
| RE: Tappan furnace wire question | 1/20/2008 |
Q: Howard, I have a Tappan model 100-16, and the product literature that comes with it says that it ... A: There`s only about 50 rpm difference between adjacent speeds. Hi speeds for heating can produce ...
|
| Help me build a ground source geothermal please! | 1/20/2008 |
Q: I am looking for help with building a ground source geothermal this spring. I own a tractor and a ... A: Google it, Jessica. I have worked on them is all the experience I have. Most different thing is the ...
|
| rheem criterion 2 gas furnace | 1/19/2008 |
Q: My furnace fails to start, and I most of the time move the filters around to get it to start again. ... A: My wife used to call me at the office(1 hr away) that the washing machine flooded the place! Sounds ...
|
| Bard Furnace | 1/18/2008 |
Q: My furnace will shut down every 2 or 3 days? when I turn it on and off it cycles again for anothe 2 ... A: Tricky to find source of a problem like that. Start off reversing the power supply to the furnace. ...
|
| Induction gas furnace | 1/18/2008 |
Q: Furnace starts to turn on blower for 30 seconds but cuts off and flashes 6 times for trouble code. ... A: Bet that water has been sucked into the hose from the draft motor to the air pressure switch. Dry ...
|
| Air Conditioning System | 1/17/2008 |
Q: I'm getting ready to build a 2600 sq foot house. R-14 insulation in walls and R-49 in attic. Also ... A: I live in Texas & here 500sq ft/ton is a rule of thumb.I gather this is a 1 story house. If so, it ...
|
| gas furnace location | 1/17/2008 |
Q: mr. livingston i believe i have recieved some bad advice on the location of my gas furnace when i ... A: That flex ducting should have 3" of insulation on it for your location.That attic is as cold as the ...
|
| replacing heat pump | 1/15/2008 |
Q: We are about to replace our heat pump here in Columbus Ohio. There are some differences of opinion ... A: Charlie. I`ll ask you why are you replacing the system ?? Age ?? Still running OK after 10 years ?? ...
|
| new unit vs dehumidifier | 1/14/2008 |
Q: Howard, I was talking with Fred about my problem but he went on vacation. Would you be so kind as ... A: Holy cow, Ed what a discussion ! What a nasty problem.Can`t believe someone screwed up a 1 story ...
|
| Heat pump | 1/13/2008 |
Q: I have had a new heat pump and central air unit installed and I thought my gas furnace was only for ... A: That gas furnace is the secondary source of heat. The compressors supplies the first stage.Look at ...
|
| Gaffers and Sattler Gas Furnace | 1/12/2008 |
Q: I have a wonderful G&S Model CF100-1 gas furnace that has run great in my home for the last 30 ... A: I can still get parts for 50 + year old wall furnaces.True, that parts prices rise for old furnaces ...
|
| Lennox 15CHPX | 1/12/2008 |
Q: The unit (Lennox 15CHPX)was installed September, 2007. This is a split system. We've been dealing ... A: Something fishy here, Malou.You paid high dollar for that Lennox & it no work ?? Is that circuit ...
|
| Burning smell coming out through heater vents | 1/11/2008 |
Q: About two days ago, we noticed a burning/maybe gas coming out through our heater vents. The smell ... A: Furnace smells occur mostly on electric furnaces when something hits the elements when its on. If it ...
|
| Gaffers and Sattler Gas Furnace | 1/11/2008 |
Q: I have a wonderful G&S Model CF100-1 gas furnace that has run great in my home for the last 30 ... A: Don`t mess with it. Let `er run.Those parts like each other & a new part would screw up the ...
|
| aircon fires | 1/11/2008 |
Q: We have an window type airconditioner. A technician says that it has a compressor problem, i.e. ... A: There was a dead short in the wiring, maybe at the compressor, but maybe not.The compressor is a ...
|
| Gas Furnace | 1/9/2008 |
Q: My upstairs furnace is not burning correctly. Spitting out small flames when the gas company turned ... A: If the gas trouble persists for 20 to 30 min.the line would be purged. Now, when a gas line is ...
|
| Trane XE 80 Furnace | 1/9/2008 |
Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ... A: It is a normally open switch. Ohm it when the IDMotor starts up.Have some reports of the hose ...
|
| Trane XE 80 Furnace | 1/8/2008 |
Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ... A: With a good induced draft motor, the next event is the air pressure switch closing completing the ...
|
| lennox elite series cb29m | 1/6/2008 |
Q: Livingston, I have a lennox elite series air conditioner/heating system. The fire damper is closed ... A: Lennox builds strange stuff, Gayle.Complex electronics are the rule.Good stuff tho when the kinks ...
|
| Trane XE 80 Furnace | 1/6/2008 |
Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ... A: Has the induced draft motor ever run in the tests ?? Is that motor good ?? I would separate it & ...
|
| Heater | 1/6/2008 |
Q: I have a Honeywell thermostat set at 68 degrees. I wake up every morning and it shows the heat is ... A: How old is that stat, James ?? No doubt it uses a mercury bulb. Take the cover off & check the roll ...
|
| continually running furnace | 1/5/2008 |
Q: We have an older Steel City standing pilot gas furnace, the problem seems to be is that it is either ... A: I wouldn`t have changed the fan/limit length.The fan settings should be set at about on at 110 & ...
|
| fan running continally | 1/4/2008 |
Q: Forced air, natural gas 18+ years old, had limit switch replaced last year. Unit kicks on, burners ... A: That is a symptom of a stopped up evaporator coil. The dirt accumulations are on the lower side of ...
|
| Ruud Achiever 90 Plus | 12/21/2007 |
Q: We have a 9 year old Ruud Achiever 90 Plus Furnace. Starting toward the end of last winter, I began ... A: You are right on Casey, that is a malfunctioning air pressure switch. Need to remove the hose from ...
|
| part numbers | 12/21/2007 |
Q: I'm looking for a parts number manual for a Goodman GMH950703BXA gas furnace. I emailed Goodman to ... A: Sorry Richard, can`t offer any help.Don`t particularly like this company when years ago they had a ...
|
| Furnace won't Ignite and blower is constant | 12/20/2007 |
Q: I have a 20-25 yr old Bryant furnace which will not ignite and the blower/fan constantly runs. The ... A: Ignition problems caused by several problems. One is a gas pressure problem .The backfire can be ...
|
| carrier gas furnace | 12/20/2007 |
Q: Howard I've been working on a 90 model gas furnace with a spark igniter, 1st problem could not get ... A: With a fan/limit control with a manual knob to pull for on, push for off with the knob missing maybe ...
|
| Furnace won't Ignite and blower is constant | 12/19/2007 |
Q: I have a 20-25 yr old Bryant furnace which will not ignite and the blower/fan constantly runs. The ... A: (that`s what I was called many years ago)The blower is controlled by a relay on the circuit board on ...
|
| Thermostat | 12/17/2007 |
Q: Livingston I just replaced two thermostats with programmable thermostats. I have a combined ... A: Well, well, John, you have the cooling wire from the thermostat in contact with the heating wire. ...
|
| electric heat | 12/17/2007 |
Q: My father has been really ill so I hope you can help me for we don't have much money to call someone ... A: hate to see anyone getting ripped off. I can see he didn`t do any good.Moving wire s wouldn`t solve ...
|
| ID fan & Circ Air blower won't stop | 12/17/2007 |
Q: OK, the equipment is a 1999 Heil DC 90 condensing nat gas furnace with honeywell ST9120C4057 ... A: Wow, Dave, never saw anyone pulling so many wires ! ! I think if I did that I would NEVER get it ...
|
| Adding a central humidifier to an AC only (no heat) system | 12/16/2007 |
Q: We just bought a 1 1/2 story home in Maine with first floor only AC (no air heat) installed in 2001. ... A: Will not do too much good. You need to measure the humidity in the Winter & Google a psychometric ...
|
| Returns | 12/16/2007 |
Q: What is the concern in not having a return in a bedroom. We are on a forced air system? A: The return air path from the house back to the return air grille(s)needs to be just so long. that ...
|
| GMP075-4 no power | 12/15/2007 |
Q: I've got a Goodman GMP075-4 gas furnace that is not getting power. I replaced the ignitor because it ... A: The induced draft motor runs on 120 v as you found out. The quick test for low & hi power is to turn ...
|
| Heat not working | 12/15/2007 |
Q: When we returned home this evening we noted that the thermostat was set for 69 degrees yet it was 64 ... A: I`m gathering Dan, 2 different problems. When the burners have flames & then it shuts off the flame ...
|
| Furnace fan won't turn off | 12/15/2007 |
Q: I have a Lennox natural gas heater that is at least 35 years old and works great. I replaced the ... A: Was the low fan speed used for the heat speed ?? Usually, the red wire is used for that speed. If ...
|
| carrier furnace/air conditioner 1 piece unit | 12/14/2007 |
Q: i have a carrier air/furnace combo, sits outside. my problem; sometimes when i turn the unit on i ... A: Must be a gas unit since you "can hear it running" but no fan. Not possible for an electric furnace ...
|
| Comfortmaker RPJII Furnance | 12/14/2007 |
Q: Symptom: Occasionally and with increasing frequency the temperature in the house drops below the set ... A: to begin with #1: That`s an indication of thermostat failure. If it is a mercury controlled stat, ...
|
| propane supply | 12/13/2007 |
Q: My neighbors propane ran out and when it was refilled the furnace will not restart.Went by ... A: I have seen that happening a lot when I worked on mobile home furnaces. I found that when a tank is ...
|
| Rheem a/c not working | 12/13/2007 |
Q: I am a snow bird and am back in Florida. The a/c was not working when I got back although I had left ... A: Monica, A factor is how old & in what shape is the unit ?? Pretty clean unit?? Works good ?? ...
|
| Rheem a/c not working | 12/12/2007 |
Q: I am a snow bird and am back in Florida. The a/c was not working when I got back although I had left ... A: Lots of things can just happen to this stuff, Monica.First thing is to test the freon, then the ...
|
| Heating Airconditioning Unit has ice on it | 12/11/2007 |
Q: I discovered our unit has ice on the outside of it...what causes this? A: If that is a heat pump that is normal to collect ice on the outside unit. BUT, at some point when ...
|
| Garage electricity will not go back on | 12/10/2007 |
Q: Livingston, Some of my rooms on my first floor bi-level had a short (basically the electricity cut ... A: Just switching breakers doesn`t do any damage. Here`s the catch tho, the breaker switch can be in ...
|
| Carrier/Night&Day Furnaces | 12/9/2007 |
Q: I have five Night and Day Furnaces in my house. Two repeatedly blow their HBC controller and one ... A: When the 3 amp fuses blow that shows there is a short in the low voltage control circuits some ...
|
| Vent Motor | 12/7/2007 |
Q: I have a GDPI series furnace and the vent motor never shuts off. How do I fix it? Please help A: The notor runs from a call for heat thru the circuit board. If the thermostat is not calling for ...
|
| Goodmam gmp100_4 will not continue to run | 12/6/2007 |
Q: The heater will start up and ignite, burners will come on and run for a short time. I have replace ... A: its not vacuum, its pressure. Remove the hose between the induced draft motor & pressure switch & ...
|
| cfms | 12/5/2007 |
Q: Can you tell me how to calculate cfms in flex air duct for a new construction side job.Two story ... A: I have installed only 2 variable speed blowers. Had trouble with one. Had to adjust the switches to ...
|
| Electrical Furnace | 12/4/2007 |
Q: I have a Coleman Central Electric Furnace model number 3500A816, the problem when I call for the a/c ... A: The heat fan circuit goes thru the fan /limit to turn on the fan. Replacing that switch should have ...
|
| cfms | 12/4/2007 |
Q: Can you tell me how to calculate cfms in flex air duct for a new construction side job.Two story ... A: easy question a long answer.You need to go buy a "ductalator" at a local a/c supply house. It`s a ...
|
| heating problem | 12/3/2007 |
Q: mr. livingston, last friday my heating at home abruptly stopped working. i live in a condo with a ... A: Could be a failure of the gas valve. When calling for heat, test for 24 volts at the gas valve. If ...
|
| Problem with Freedom 80 | 12/3/2007 |
Q: Hey Howard. I have a American Standard Freedom 80 model # AUD140C96051 serial # R261WWH2G and I'm ... A: That`s an interesting name. Sure would like to know the interpretation of the LED flashing 4 times. ...
|
| Propane furnace burner problem. | 12/2/2007 |
Q: I have a Tempstar propane furnace. The problem is only one out of the three burners are burning when ... A: Now that`s something you discovered Terry. Somebody never installed the complete conversion kit for ...
|
| colmen gas furnace | 12/1/2007 |
Q: my furnace went out.they replaced the contol board and it ran good for 5 days and quit again.I set ... A: I would remove the tube from the air pressure switch & see if its clean, then check the outlet & ...
|
| Propane furnace burner problem. | 12/1/2007 |
Q: I have a Tempstar propane furnace. The problem is only one out of the three burners are burning when ... A: Wow, Terry, that`s a good one ! Never have experienced that problem. If no gas is coming from 2 ...
|
| rheem heat pump, humidifier install | 12/1/2007 |
Q: I have a rheem heat pump, installing a honeywell 365 powered humidifier, humidifier plugs into 120v, ... A: First off, Norm I wouldn`t recommend a humidifier on a heat pump. Only gas furnaces produce hot ...
|
| Heat | 11/30/2007 |
Q: We just bought our home in Indianapolis it has a Trane XE 78 unit it keeps shutting the heat off but ... A: How much dust was on the filter ?? And, in the area around the blower ?? I`ll bet the previous owner ...
|
| 3 year old 3 ton 12 seer Ruud Heat Pump | 11/30/2007 |
Q: 1. the intesnity of warmth is lacking- milk-toast heating- so runs a long time. I have an April Aire ... A: I hate to see folks ripped off. Happens too often in this business/ Ask your friends & neighbors who ...
|
| furnace... | 11/29/2007 |
Q: I have a 3 yr old modular house in Central NY. It is heated by a 3 yr old Thermopride fuel oil ... A: I live in Texas & we would freeze at 67 deg ! Heard that fuel oil price really increased this year. ...
|
| Furnace air temperture | 11/29/2007 |
Q: How warm should the air be that comes out of the registers A: Easy question, difficult answer Ken. The answer depends on the heat load or loss of heat from the ...
|
| Gas Heater/AC Unit | 11/28/2007 |
Q: The A/C portion of the unit works. However, the heat portion does not. When the unit engages, ... A: Does the spark light a pilot light or light the main burners?? Later models have a glowing ignitor ...
|
| ruud 80 plus intermittent no heat | 11/26/2007 |
Q: I have a 1989 ruud 80 plus unit, model # UGDE-14 ERAJS upflow furnace. I have an intermittent ... A: What you said needs clarifying. "the pre purge sequence starts, the draft inducer motor does not ...
|
| airflow management | 11/26/2007 |
Q: I have a 25+ yr old Freidrich central unit in a house I just bought. Sucker runs like a champ. The ... A: Take care of that Freidrich. Probably have another 8 yrs on it! These service guys see that & all ...
|
| American Standard Freedom 90 | 11/25/2007 |
Q: My furnace is now flashing 3 times (pressure switch problem)per my service paper work. Is there ... A: Running late today Jim. Hope you haven`t froze yet. Need to remove the hose between the induced ...
|
| Rudd Super Achiever 80 series | 11/25/2007 |
Q: According to instructions on outside cover there is supposed to be a Honeywell on/off gas control. ... A: Problem with answering these questions, Virgil is not knowing the details of all these furnaces. So ...
|
| gas furnace filling with water, tripping pressure switch | 11/25/2007 |
Q: Howard, I have a Goodman GMN080-4 90% gas hot air furnace, about 15 years old. When it comes on, it ... A: Boy, Brian, we got a weird one !! Just another wild thought. You have a humidifier on this furnace ...
|
| gas furnace filling with water, tripping pressure switch | 11/24/2007 |
Q: Howard, I have a Goodman GMN080-4 90% gas hot air furnace, about 15 years old. When it comes on, it ... A: Better stop that water quickly,Brian. Rust out the heat exchanger. That isn`t condensate but can`t ...
|
| American Genaeral Freedom 78 furnace | 11/24/2007 |
Q: Furnace heats the house properly ,however ,turns off and on all night and day without stop time in ... A: Usually, on a complaint like that Ken, you are "hearing" the fan noise short cycling, not the ...
|
| breaker | 11/23/2007 |
Q: I have a six year old house. A/c cools great and so does heating. But when i use heater, after ... A: Yea, Mike like last night at 3AM at 35 deg & snow!I live in Arlington. You must have electric heat ...
|
| Carrier combo unit | 11/22/2007 |
Q: Have a 15 year old Carrier combo unit. Last year tech replaced gas valve with new Honeywell unit. ... A: After you bled the air out & you had heat it usually will not have any more air in the lines from my ...
|
| fuse keep blowing | 11/21/2007 |
Q: when i turn my unit on it runs for about 5 Min then the fuse on the inside the air handler on the ... A: There is a short in the low voltage circuit. If you were trying to run the cooling, check the 24v ...
|
| Heat unbearable upstairs in WINTER!!! | 11/20/2007 |
Q: We recently bought house w/Lennox A/C-Heat Pump. Our master bedroom is upstairs over the garage. ... A: Can`t stop the physics law that hot air rises.Cold air sinks.I would close completely off all the ...
|
| Is there a filter on a gas Armstrong 38HWC182-5A furnace/air conditioner? | 11/19/2007 |
Q: .. I have moved into an apartment (first one in 35 years), and it is REALLY dusty. I have opened ... A: Sometimes there was no place provided for a filter in the furnace. It needs a place that can seal ...
|
| Intake Vent | 11/19/2007 |
Q: In the colder months, the first floor of our house seems to get cold as if there is a draft. I ... A: Hey Paul, Are there foundation vents around your house that allow cold air under the house ?? Air ...
|
| goodman gas pack problem | 11/18/2007 |
Q: I AM HAVING TROUBLE WITH A GOODMAN MODEL PGO-60150-1AB-REV E GAS PACK. AT FIRST IT WOULD NOT ... A: Boy, that is a crazy problem. I can think of several things to check out but they are just ...
|
| TRAIN XE 1200 model TTP060C100A1 | 11/17/2007 |
Q: What are some possible reasons that the outside compressor makes a loud humming noise when the heat ... A: Is this unit a heat pump, Yale?? Main thing that can hum in the outside unit is the coil in the ...
|
| Cozy Floor Furnace | 11/17/2007 |
Q: I have an older Cozy floor furnace. The pilot light is lit but I could not get the heater to kick ... A: Wow, Brad, you must feel like a mole! I am thinking the problem may be "resistance" Maybe in the ...
|
| Diamond 80 P3HUA12N06401c Furnace no heat | 11/17/2007 |
Q: I have a Diamond 80 P3HUA12N06401c, when the unit calls for heat the main blower is coming on, not ... A: I`m not acquainted with any particular control boards.The induced draft motor starts first on call ...
|
| Central Heating and Air Unit | 11/16/2007 |
Q: Yesterday my C/ h&a unit seemed to be working fine, minus the fact that my air unit quit blowing ... A: Cooling first: Wonder if the coil has a freon leak to cause the guy to say you need a new one.Now ...
|
| HEAT PUMP | 11/16/2007 |
Q: I HAVE A NORDYNE SPLIT SYSTEM HEAT PUMP #F3TBA 030KA WITH HEATER KIT B3BM 030K AB. MY SON PUT ON A ... A: The new thermostat is for a heaT Pump ??? Sorry, can not provide info to connect the wires since ...
|
| pressure swithc | 11/14/2007 |
Q: i have a question about a Rheem 90 imperail furnace.the heat doesnt appear to be working correctly. ... A: Are you referring to the round pressure switch that has a hose from the induced draft motor ...
|
| Central A/C not responding | 11/13/2007 |
Q: Our A/C is not responding when we turn it on. The outside fan unit does not start. There is no sound ... A: Does the inside fan run when calling for cool ?? Locate the contactor rely in the outside unit & ...
|
| heating flow | 11/13/2007 |
Q: my girl friend has lived in the double wide trailer for a year now and she has had this problem for ... A: Double wides have an interconnecting duct between the 2 sides. Does the cold air come from the same ...
|
| American Standard furnace | 11/12/2007 |
Q: My blower motor on my furnace (model lgf120e100 will not stop running after the house has reached ... A: The length of the probe inside the furnace needs to be matched. Then, does your fan control also ...
|
| flame sensor | 11/12/2007 |
Q: For the umpteen year my Weatherking gas furnace turns on and the ignitor heats up and starts the ... A: The sensor is the small rod sticking into the flame on the burner. Kill the power,remove the 2 wires ...
|
| convert gas pack to heat pump | 11/11/2007 |
Q: I live in Raleigh NC. I want to covert my 3 ton gas pack to a 3 ton heat pump. Is this possible ... A: Can`t convert, Mike. Too much to change.The lowest SEER is now 13. That`s good enough. Don`t get ...
|
| American Standard furnace | 11/11/2007 |
Q: My blower motor on my furnace (model lgf120e100 will not stop running after the house has reached ... A: I am assuming you have the standing pilot type furnace ?? Doesn`t that dial have other temperature ...
|
| Main fan problem | 11/11/2007 |
Q: Carrier model #58SX100-cc-1 circa 1987. When call for heat is made inducer fan works, furnace lights ... A: The fan circuit is different for heat & cool modes as are the fan speeds. Usually, the heat fan ...
|
| Propane AC | 11/10/2007 |
Q: Howard, Do you know of anyone that makes a propane AC unit? I am fortunate enough to have free ... A: Well, hello lucky.I`m paying $2.38/gal !!There used to be gas powered unit made by Arkla Servel that ...
|
| PROPANE FURNACE | 11/10/2007 |
Q: OUR HEIL 7000 FURNACE LIGHTS NORMALLY BUT WILL BACKFIRE UP THE BURNER JET OCCASIONALLY. IT SEEMS TO ... A: Tricky problem. I would test the incoming gas pressure to confirm it`s OK. Is the gas valve fully on ...
|
| trouble starting new York gas furnace | 11/10/2007 |
Q: Just installed a York gas furnace 120,000 btu's 90% downflow unit GY9S-DH. Can't get it to start. ... A: How frustrating !!! Test the induced draft motor & air pressure by removing the hose from the draft ...
|
| lennox gas furnace | 11/9/2007 |
Q: my furnace stays on for a few days then goes off again. i clicked the reset switch and it would ... A: You need to move to Texas. It`s 80 down here. I`m sorry but you didn`t supply enough info to help ...
|
| janitrol gmn100-4 furnace circuit board blinks | 11/8/2007 |
Q: Just installed new circuit board, igniter not turning on (glowing)which was installed a year ago, ... A: Wow, Diane we got to get you some heat, FAST. But sorry, I don`t have the blink codes for your ...
|
| Attic humidity | 11/7/2007 |
Q: I just recently had an thermostatically operated attic fan installed. I was advised afterwards that ... A: You don`t want to remove moisture in the Winter, you want to add humidity. The heat dries out the ...
|
| Rheem furnace 1x2000 | 11/6/2007 |
Q: My Rheem furnaces will trip out periodically and I have to reset one or more of the limit switches ... A: Now that`s an interesting name! Have you removed the flame sensor & drag over it with a rag ?? If ...
|
| Induced draft blower cycling on and off | 11/6/2007 |
Q: I have a 13 year old high efficiency natural gas furnace. I'm having no heating problems with it ... A: That motor turns on with a call for heat only.Sounds like there may be a short across the red & ...
|
| Heat Pump fan operation | 11/5/2007 |
Q: My fan works properly when the thermostat calls for heat, but it doesn't always stop when the ... A: A heat pump blower operates at only high speed. heat or cool. That fan is energized by a time delay ...
|
| Heating balance. | 11/5/2007 |
Q: I have recently moved into a newly built 2 story home. I have the HVAC unit on, at this time, to ... A: Hot air rises, cold air falls. 2 story house have an open stairway that allows that to happen in ...
|
| no light from my smartvalve | 11/4/2007 |
Q: I have a concord 80 plus gas furnace. I had a severe power spike in the neighborhood and the furnace ... A: Does the inside fan run when the fan switch on the thermostat is turned ON ??? The fuse on the ...
|
| gas furnace | 11/3/2007 |
Q: Maybe you can help me. I have a vented floor furnace. It is a Cozy brand. Model number 90P50A. I ... A: Insure the pilot flame is striking the top 1/2" or more of the thermocouple. Did you hold down the ...
|
| Furnance | 11/2/2007 |
Q: Sir: I have a new nat. gas fired furnance in my attic. It takes from 5-8 mins for the blower to come ... A: Gas lines for furnaces up to about 100,000 btu use 1/2" lines. 3/4" above that.The circuit board ...
|
| Burnt electronics smell coming from my registers | 11/2/2007 |
Q: I have a "burnt electronics/electrical" smell coming from my registers when using the heat. This ... A: Wow, Eric that`s a lot of amps for the blower motor!!That`s gotta be the cause of the smell but the ...
|
| Wood Stove | 11/1/2007 |
Q: No basement just a crawlspace. I run my propane forced air furnace blower on low 24/7 with my ... A: Not sure what the problem would be but if you could just install a flex duct from the ceiling of the ...
|
| Furnace control problem | 11/1/2007 |
Q: Howard, I've been having problems with my gas furnace the past few days. Furnace is American ... A: Think the place to start is with the "check line polarity" Turn off the power supply & reverse the ...
|
| American Standard Trane furnace problem | 10/31/2007 |
Q: My gas forced air furnace is not lighting. The fan blows cold, but that's it...it doesn't attempt to ... A: Well, that`s a first John, to get a photo of the furnace!!The 4 blinks for an open switch would be a ...
|
| Gas Furnace | 10/31/2007 |
Q: I got the pilot light lit and it stays on. When I first lit the pilot light the burners started as ... A: Is the gas valve on the gas line all the way on Bryan ??? How about the knob on the gas valve?? ...
|
| white powder coming out of vents when ac unit on | 10/31/2007 |
Q: I have white powder in my apartment when I run my ac unit. It is a very fine powder that covers ... A: The place you can find powder is inside the heat exchanger of the furnace.That`s a natural ...
|
| blower fan for air circulation does not work | 10/30/2007 |
Q: Blower fan for air circulation does not come on in auto or manual. I opened the door to the fan and ... A: Follow the 2 brown wires from the fan to the run capacitor. Need a volt-ohm meter to test it. If ...
|
| centtral issue follow up button not working | 10/30/2007 |
Q: Subject Central air/heat issues new installation Question Howard. My parents recently decided ... A: Well, Gregory what a deal !!! A 110,000btu furnace would have the cfm capacity for the size house. ...
|
| Heil furnace blows cold air, SOMETIMES!! | 10/29/2007 |
Q: Well if anyone can answer this then you did better then the contractor I had come over!! I have a ... A: The induced draft motor that starts the cycle has to blow enough air to close an air pressure ...
|
| Ameristar Furnace | 10/29/2007 |
Q: Can you tell me where to find information on a 2005 Ameristar Furnace? I just had the unit cleaned. ... A: By all means call the guy back.American Standard makes that furnace. Can`t find any info on it on ...
|
| two stage furnace, one stage thermostat | 10/28/2007 |
Q: I just bought a two stage furnace, how do I jumper the control board to still use my standard ... A: I presume your gas valve has high & low output of heat on the one gas valve ?? Or does it have a W1 ...
|
| honeywell rth230b | 10/28/2007 |
Q: I bought this house and when the temperature is really cold in the house, my Honeywell still reads ... A: Put an accurate thermometer on the thermostat for a good read of temperature. Take off the cover & ...
|
| CLEARANCES FOR GAS FIRED HEATERS | 10/28/2007 |
Q: I am rehabilitating an apartment complex in NJ. I am retro fitting each unit to have its own heating ... A: These high efficiency furnace nowadays are pretty small, about 42"high X 17" wide, about 28" deep, ...
|
| gas furnance | 10/27/2007 |
Q: I have a brand new gas furnace (KeepRite C8PN100F14B). It works well for a few days after it is ... A: Have you checked the blinking of the LED on the circuit board ?? It can diagnose the problem for ...
|
| Central AC Fan Motor running at 1/2 speed or less | 10/26/2007 |
Q: We have a 3 ton central unit in our home that is only a few years old. Its gotten kinda cold the ... A: Electric furnaces use 240 v power. One leg on the fan motor bad runs the motor on 120v at half ...
|
| Frost on condenser pipes. | 10/26/2007 |
Q: Howard, I live in dallas and have a Amana heat pump (AC & Heat), just today I noticed that my ... A: Could be several things wrong. Could be the defrost cycle was operating erroneously. You could the ...
|
| Central air/heat issues new installation | 10/26/2007 |
Q: Howard. My parents recently decided to get central a/c. They had their old heater and all duct work ... A: Wow, I hate to hear a story like that,Greg! Those high ceilings need a lot of airflow to circulate ...
|
| replacing... | 10/25/2007 |
Q: I am replacing the a/c heating system in my home in washington dc. the question i have is as ... A: Carrier repair parts are pretty darn expensive as is the equipment. The variable blower is an ...
|
| HVAC Brands | 10/25/2007 |
Q: What can you tell me about the Goodman brand? What brand would you recommend as a replacement unit? A: Goodman changed the brand name from Janitrol to Goodman. Maybe the reason was we used to call it ...
|
| Question about home A/C | 10/24/2007 |
Q: Problem: A/C starts cooling but quits. Have noticed that fan on outside unit starts but stops after ... A: Did the tech check the fan motor run capacitor ?? It could be just a $10 or less capacitor. If it ...
|
| janitrol gmp100-3 | 10/24/2007 |
Q: My furnace will come on the hot surface ignitor will light and the gas will come on there are 4 ... A: Sounds like the flame runner is clogged, or even the orifice on the flashing burner is clogged too. ...
|
| Forced AIr Furnace "Gibson" | 10/24/2007 |
Q: I had a new (Gibson)forced air furnace installed professional two months ago. It is a 90k BTU w/ a ... A: Insulate, insulate, Dave. Can to use duct insulation which is black & really fuzzy on one side, or ...
|
| Heat Blower not comming on. | 10/23/2007 |
Q: Well I went to turn on the heat on my 3 ton HVAC for the first time last night and nothing. The ... A: The blower has 2 speeds, one for heat, high speed for cool. The heat speed is controlled thru a ...
|
| Furnace only buzzes when turned on | 10/23/2007 |
Q: I recently bought a fixed up home with an upgraded brand new gas furnace and hot water heater. The ... A: Easy way to test for power, Anthony, is to turn on the fan switch only. That proves low & high ...
|
| Heating Problem | 10/22/2007 |
Q: This morning it was a little bit cold in my house so I decided to turn on my central electric ... A: During the Summer cooling season dust is bypassing your filter & hanging on the heat elements. Then ...
|
| re:tenant tampering with air conditioner | 10/20/2007 |
Q: I rent out my basement which contains the furnace/electrical box. I think my tenant is tampering ... A: Well, Kelly I could say evict the tenants & you`ll find out !Naw, just kidding. The tenants could ...
|
| Mobile Home Furnace | 10/19/2007 |
Q: I have a Intertherm propane fired furnace. It is about 8 years old and in very good condition. The ... A: Sounds like you have a mobile home model furnace, Jason ?? If that is correct I am unsure that an ...
|
| Amana furnace | 10/18/2007 |
Q: We moved into a house with an Amana Air Command furnace that we think was installed in 1974 or 95. ... A: The filters are somewhere in the return air, Carolyn.Start off looking at the base of the furnace ...
|
| heatpump | 10/18/2007 |
Q: What is proper way to hook up hoses on heatpump in both heating and cooling modes? Which is best way ... A: I presume your talking about the liquid & suction line, Chad.Those lines connect to the evaporator ...
|
| AC won't stay on... | 10/18/2007 |
Q: Our Bryant air conditioner blew it's capacitor (run/start). The repair guy replaced the capacitor, ... A: Sounds like you have a heat pump having an outside sensor.Either way I would run a test at the ...
|
| Hardwiring Air Purifier to HVAC | 10/9/2007 |
Q: I'm installing a UV air purifier in the return plenum of an Gas forced air heating system. The ... A: You could supply the power with a relay that has a single, normally open switch & a 24 volt ...
|
| airflow/black furnace filter | 10/9/2007 |
Q: I had a new Gibson electric furnace installed three months ago. It was adapted to my air ... A: that`s a good question.If your furnace is in a closet sitting on the return air plenum I would ...
|
| Warm Basement?? | 10/8/2007 |
Q: Howard, My basement has been noticeably warmer than the main floor this summer. It use to be the ... A: There was one more thing that it could be. But only if you have an electric furnace down there. It ...
|
| Heating not working on central ac unit | 10/7/2007 |
Q: This morining the heat was turned on (and it worked) then it turned off automatically; but it did ... A: The inside fan works by a time delay, not by heat or the "on" switch.You must have a circuit board ...
|
| Forced Air Heater Pilot Won't Ignite | 10/6/2007 |
Q: When the thermostat asks for heat, the draft fan starts, the pilot light igniter starts arcing, but ... A: Sounds like Mark that the pilot orifice is stopped up.Common problem. Maybe run a test by holding a ...
|
| circuit board short | 10/6/2007 |
Q: "i have a bryant model AC1CN036B that was installed in 1995. my dog bit thru and broke thermostat ... A: If your unit is NOT a heat pump there was only 2 wires on the outside the dog broke. If those 2 ...
|
| furnace not lighting in heat mode | 10/5/2007 |
Q: The ignitor comes on, then after a few seconds it goes out and the blower comes on but the burner ... A: The blower is on a timed circuit so that`s OK.Doesn`t sound like the pilot comes on either. The ...
|
| outside ac unit | 10/4/2007 |
Q: I have noticed my outside unit runs continually. There is also ice on the outside of the unit. Can ... A: You need another contactor in the outside unit. The points are burned & are sticking closed. Your ...
|
| HEIL DC90 not lighting | 10/3/2007 |
Q: I have a HEIL DC90 gas furnace that has stopped lighting. It is about 9 years old. The small blower ... A: Good description of your problem. Thanks. Sounds like the pilot flame is not being proved by a ...
|
| Heating - Furnace | 10/3/2007 |
Q: We have a Rheem Classic 90 high efficiency furnace installed in a garage to heat a garage apartment. ... A: Most of the limit switches have a little button that pops out when tripped. If so, just push the ...
|
| fried equipment | 10/2/2007 |
Q: i recently replaced a tranformer on the indoor unit of a split system, aparently an electrician ... A: Holy cow, Richard !! What a mistake.Could be the contactor coil in the outside unit was fried ...
|
| How to light furnace | 10/1/2007 |
Q: Howard, I have a nineteen year old Lennox furnace. Am confused as to how to light it, although I ... A: The only other kind of pilot control I have ever seen has a separate valve for the pilot.Follow the ...
|
| Furnace turns off too soon | 10/1/2007 |
Q: our furnace turns itself off way before it has reached the desired room temperature. Furnace and ... A: A 3 yrs old furnace is controlled by a circuit board. Some boards have little dip switches that can ...
|
| Transformer Brunt | 9/29/2007 |
Q: I have a Rheem model RBHA 17J10SFAA furnace and heat pump. Yesterday the thermostat screen went ... A: A short in the low voltage power somewhere.Could be the coil on the contactor in the outside unit. ...
|
| condensation pump safety switch | 9/29/2007 |
Q: The compressor would not come but every thing else worked, went out to the compressor to see if the ... A: The condensate pump wiring is simple. There are 2- 24v wires to the condensing unit, usually a red & ...
|
| Poor Dehumidification with Old Furnace | 9/28/2007 |
Q: Howard - I have a Lenox G14 Pulse furnace with a multi-speed blower. Added a new Lenox 2 speed AC, ... A: This a heat pump ?? They run heat & cool at high speed blower. Were the coils replaced when you got ...
|
| central air and heat unit maintenance - coils | 9/27/2007 |
Q: I live in an apartment and it looks like the coils in my system (inside the apartment) are in pretty ... A: Christie, that is the typical rental unit coil you described! It`s all because tenants NEVER change ...
|
| return air | 9/27/2007 |
Q: Howard, I just relocated your answer to me about return in ceiling, but had already posted another ... A: Well, you are a sharp lady, Paula. Always happy to help you. I gave away a lot of time over the ...
|
| Furnace upgrades | 9/26/2007 |
Q: I have an older (1980) electric furnace/heat pump system with a single-speed blower and noise from ... A: Heat pump inside fans need to run on high speed for both heat & cool.That`s what you have.Best thing ...
|
| return air | 9/26/2007 |
Q: Howard, I just relocated your answer to me about return in ceiling, but had already posted another ... A: Now I recall your problem, Paula! That`s goooood info you sent. I live in Arlington, by the way.Did ...
|
| Help! Need a new a/c unit | 9/26/2007 |
Q: Howard. It's 4:30am and I haven't slept all nite worrying about this. I'm in your neck of the ... A: Van. R22 will be phased out in the next few years. The wholesale price has already tripled! BUT, ...
|
| Help! Need a new a/c unit | 9/25/2007 |
Q: Howard. It's 4:30am and I haven't slept all nite worrying about this. I'm in your neck of the ... A: Wow, Van, what a night !! I would stay away from Puron (R410) It`s pretty expensive stuff & higher ...
|
| air handler | 9/24/2007 |
Q: i have a old carrier air handler 230 volt and changed the old t-stat out ive been doing this for 15 ... A: Is there a separate fan/limit switch mounted on the furnace ?? If so, there is a knob on the front ...
|
| Coil and refrigerant lines freezing up | 9/24/2007 |
Q: I have had 4 service calls recently because the coil and refrig lines freeze up. They have tested ... A: Well, well Jamie lets see how many ways can cause these things to make ice! You have a tricky one ...
|
| airconditioner | 9/23/2007 |
Q: I had my two year old 3 ton 13 seer airconditioner fixed ,it had a small leak and now it is not ... A: With 92 ambient temp the suction line should Chilly & even sweating. Did he fix the leak ?? Was it ...
|
| Float switch reset? | 9/22/2007 |
Q: My attic-mounted air handler/evaporator has a switched condensate trap. At the suggestion of the ... A: Never heard of a reset switch on a condensate pump.There, usually, is just a microswitch tripped by ...
|
| HVAC not working | 9/21/2007 |
Q: I came home yesterday to find my a/c not running. I've checked the circuit breaker and confirmed ... A: If no inside fan runs when fan switch is turned on test for 110 volts thru the wall switch or ...
|
| HEIL 90 propane furnace, doesn't ignite | 9/21/2007 |
Q: I have a HEIL DC90 furnace, and just got the propane tank filled, but the furnace won't ignite. The ... A: All that is controlled by a circuit board Ken.Got to have a pilot light first to light the main ...
|
| a/c unit | 9/19/2007 |
Q: I am have an air conditioner unit that is not blowing through the vents in the house, the outside ... A: Yo Cindy,How about a collapsed duct?? Or a blower motor not running at rated speed?? Or an ...
|
| older home hvac | 9/19/2007 |
Q: I would like to know if I can replace my air handler with a smaller unit or get rid of it entirely. ... A: If you have lots of money you could rip out all that stuff & install 1 or 2 or more( 1 per floor) ...
|
| Hvac Coils | 9/17/2007 |
Q: Said i had to also clean the evaporator coils.Seeing how the coils is hard to get to he said about ... A: Yes, Brad. The hot air from the furnace also flows thru the evaporator coils. That`s way too much to ...
|
| Heat pump problem | 9/16/2007 |
Q: When I switched the thermostat from cool to heat, it made a clicking sound and then never came on. ... A: Dead short somewhere.With the breaker reset, turn on the fan only(no heat) at the thermostat. If the ...
|
| Humidifier | 9/14/2007 |
Q: A recent HVAC Rep suggested I install a humidifier as part of a new system (both furnace & A/C). I ... A: Somewhat, John. Heat always dries out the air. Humidifiers will help some. If your family has dry ...
|
| heat...... | 9/13/2007 |
Q: I have a modular home in Northern Ind. where it gets to 0deg. in the winter( a summer home) Can you ... A: Modular houses are not known to be well insulated.You never know how much insulation is in the floor ...
|
| c/a | 9/13/2007 |
Q: The fan on my Bryant High eff. furnace won't turn on, on the heat cycle, but it works for the ... A: The fan for heat is controlled by a time delay on the furnace circuit board. Actuated after flame is ...
|
| Electrostatic filters on HVAC | 9/12/2007 |
Q: I have a Rheem AC that recently failed (6 months out of 5 year warrenty, figures) and I am getting ... A: Have to define "electrostatic" filters, Joe. Does this filter have wires connected to it ?? If not, ...
|
| panel to furnace wiring for air handler | 9/11/2007 |
Q: I just had a heat pump and air handler/electric furnace installed. I noticed that the furnace has a ... A: Those breakers are, most likely just disconnects, Joel. 60 amps for 3 - 5kw heat elements, 20 for ...
|
| Compressor Not Turnig Off | 9/10/2007 |
Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ... A: The points are still not making contact after the cleaning. What you said indicates the thermostat ...
|
| High pitched noise from coolant line | 9/9/2007 |
Q: I have 2 questions for you: 1) We have an ac unit in the attic and the coolant line runs from the ... A: You must be about ready for the funny farm with all those irritating noises ?? Noise #1: Usually, ...
|
| airflow | 9/9/2007 |
Q: the air from the vents is cool but the air is barley coming out had the t-stat replaced a month ago ... A: I presume the air flow has been good in the past ?? That is, this lack of flow is a change ?? Lack ...
|
| New Puron system, not enough air, bad service and design | 9/8/2007 |
Q: Need advice/info: I hired a well-known HVAC company to install central air in my oceanfront, ... A: How many tons cooling was that, Robin?? How many sq. ft. is your house.2 story ?? Big attic ?? High ...
|
| THERMOSTAT WILL NOT COME ON | 9/8/2007 |
Q: MY THERMOSTAT WILL NOT COME ON AT FIRST IT WAS SET 90 DEGREES AND WE COULD GET TO TURN DOWN OR UP. ... A: Now that`s an interesting name, Eboni! Does the inside fan run when the switch is turned on at the ...
|
| Compressor Not Turnig Off | 9/8/2007 |
Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ... A: Those are pretty standard Mike. Go to a local a/c supply house & get a 30amp, 2 pole, 24 volt coil ...
|
| moved thermostat - HVAC won't work | 9/7/2007 |
Q: I'm remodeling and cut the thermostat wire to move the thermostat. I reconnected the thermostat ... A: Is that a digital thermostat that would have both common & hot wires from the transformer ?? That`s ...
|
| Dual wall-mount A/C thermostat | 9/6/2007 |
Q: I have a radio building with dual 3-ton Bard wall-mount air conditioners. This is a 200SF building ... A: Wow, 6 tons for 200 sq. ft. !!! You could use it for a meat locker too. Each one of those units has ...
|
| Compressor Not Turnig Off | 9/6/2007 |
Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ... A: A common problem,Mike! The contactor in the outside unit has burned points & is stuck in the closed ...
|
| Follow up | 9/4/2007 |
Q: This is a follow-up from my previous question (below). The fix is a little above me, so we called ... A: Sorry I`m late Joe. Have been in the hospital for a overnight stay. That`s too much for a circuit ...
|
| Blower fan problem | 9/4/2007 |
Q: Howard. I have a blower fan problem. Originally I thought it was control board problem. Therefore, I ... A: Well done description of your problem, Bill. As I follow the description it seems like your ...
|
| Inside Unit Freezing Up | 9/3/2007 |
Q: "Hi, we recently started having problems with our inside evaporator coils freezing up and not ... A: Freezing is caused by a low amount of freon OR a dirty air filter.Weak suction valves in the ...
|
| goodman heat pump | 9/2/2007 |
Q: I have a goodman package heat pump and homneywell pro 3000 thermostat. I need help with the wiring. ... A: White should be on w1, your heat pump primary heat.I`m not familiar with that stat nor did you say ...
|
| Thermal shutdown problem | 9/1/2007 |
Q: I have a Amana 14 seer RCE, about 2 years new. In a nutshell, the problem is that the cooling fan ... A: After knowing that the motor run capacitor is OK (changing or testing) if the motor fails its the ...
|
| AC Blower will not turn off | 8/30/2007 |
Q: I have a gas furnace, with an AC unit outside the house. We have two separate thermostats, one ... A: Yo Joe, stuck fan relay. Sounds like the relay is a separate relay?? (Rather than having a solid ...
|
| AC/ Coil identification | 8/30/2007 |
Q: I have a carrier split system and have been told the inside and outside units don't match in size. ... A: How in the world did that happen, Jerry ?? That`s a 5 ton(060)inside & 3(036)outside!That evaporator ...
|
| old air conditioner, odor | 8/30/2007 |
Q: At some point the original owner of our circa 1929 house installed in-wall air conditioning units in ... A: Need a little cleaning, Meghan, Best way is to pull the innerds that may just slide out of the case ...
|
| Air Cond. Compressor not Running | 8/29/2007 |
Q: My Goodman A/C Compressor stopped running. Model CK24-1B Serial 951002322B. Furnace & Thermostat ... A: Does it trip the breakers to the outside unit when trying to start ?? But since nothing runs I would ...
|
| AC | 8/29/2007 |
Q: Our power went out yesterday. When it came back on the lights were dim for several minutes, then ... A: That`s an unusual outage! When you turn the fan switch on, does the inside fan run?? That`s a test ...
|
| No blower, Control board change, Bryant 3 ton unit | 8/28/2007 |
Q: Friday a bad storm went through, power flickered on and off (stayed off) and then a couple of bolts ... A: You have a digital thermostat ?? Could have ruined the fan switch with the strike. I would jump ...
|
| Furance/ ac replacement options | 8/28/2007 |
Q: I am planning on installing the following system to heat and cool a two story three bedroom home ... A: Only Carrier uses Puron, that I know of Ron. Puron is just R 410 thats been around a good bit. Works ...
|
| Furance/ ac replacement options | 8/27/2007 |
Q: I am planning on installing the following system to heat and cool a two story three bedroom home ... A: Is the new stuff the same ratings as the good old stuff?? That is: 100k heat, 4 ton cool ?? But ...
|
| Air Conditioner | 8/27/2007 |
Q: I have 1 year old home with TRANE air conditioning unit. It is not working. There is air coming ... A: That was a run capacitor Kristina.God only knows what a service call is where you live. That ...
|
| Air conditioner doesn't cool, inside unit doesn't turn off | 8/26/2007 |
Q: I have a 22 year old unit and earlier this year I replace a few parts on the outside unit and had a ... A: Wow, 22 yrs !! Good stuff, don`t get rid of it till a compressor dies. You`ve most likely got a ...
|
| outside compressor control | 8/25/2007 |
Q: I had a "handyman" do some work on a rental unit. The week before my lawn care person told me that ... A: better find another lawn care! Better test the 24 volt transformer in the furnace first.I gather he ...
|
| Air Conditioning | 8/25/2007 |
Q: Every time it rains, the thermostat quits working on the A/C. We have it set at 74 degrees and it ... A: Wow, Debi, that`s a new one !! Let`s see how many things there are that could cause that ?? A ...
|
| Digital T-Stat Blank Screen and Furnace is not responding | 8/24/2007 |
Q: I woke up this morning to find my digital thermostat with a blank screen. I checked the fuse at the ... A: Well, well, it happens ! Check your furnace controls to see if you have a solid state circuit board ...
|
| Capacitor Blew Out on A/C- Cost to Replace? | 8/23/2007 |
Q: Hot air was blowing inside the house but the Heil outside unit was not running. Called an A/C ... A: Well, Jeannie I`m sorry to hear that. The booster can help kick start a compressor, is what it does, ...
|
| Need to charge A/C? | 8/23/2007 |
Q: I have a very old Duo-Therm Exec 1900. The past 2 weeks it has been so hot and our compressor has ... A: You have access to R-22?? To make it simple add enough so that the suction pressure is about 70 ...
|
| schrader valve leaking | 8/22/2007 |
Q: I have been living in a brand new house for 2.5 years and have had the freon in my downstairs unit ... A: If a schrader valve leaks, just tighten the cap on it & test with soap bubbles. But you may have ...
|
| Rheem Classic 8 | 8/22/2007 |
Q: I foolishly tried to upgrade the thermostat on my HVAC system and now the system is DOA. Nothing ... A: That`s the way we learn, Andrew! One transformer supplies the whole control circuit. If your inside ...
|
| inside blower motor | 8/20/2007 |
Q: i have a trane model # bt724a100bo installed in 1985. my blower motor will run for 10-20 sec then ... A: In the electrical compartment in the furnace somewhere.Kill the power & disconnect the wires. With ...
|
| Condenser cycles on and off | 8/20/2007 |
Q: Our Goodman central air conditioner condenser cycles on and off. We have been fighting this for ... A: Sounds like you may have a bad contactor in the outside unit, the points are not making good ...
|
| replace central A/C | 8/19/2007 |
Q: Please give me your opinion on the best central A/C system. Carrier? Lennox? York? Rheem? ... A: 3 ton should do well in CA. GOT to have good air distribution too. Lennox very expensive but good. ...
|
| What is normally done in this situation? | 8/19/2007 |
Q: Have a 2.5 ton matched A coil I want to put in the discharge of the furnace duct. The duct ... A: Well, sort of, Tim.Normally, the coil would sit on top of the furnace for an upflow furnace. (Is ...
|
| bryant heat pump/air conditioner 8 yr old | 8/17/2007 |
Q: my system doesn't cool in really hot weather. seems compressor kicks off. If i keep it on 60 when 90 ... A: FOURTEEN THOUSAND !!!! How about a piece of the Brooklyn Bridge ?? There is a compressor failure ...
|
| Outside Unit not coming on | 8/16/2007 |
Q: Why is the outside unit not coming on when the AC switch is activated? The air is warm and the fan ... A: Can be quite a few reasons Terence. Low on freon can trip a switch to stop it. Burned contactor ...
|
| clear slime | 8/16/2007 |
Q: My Central air unit doesn't seem to be cooling down the house very well. When I went downstairs to ... A: that`s from the condensate water, I`ll bet. Individual homes can create "crud" of some kind with the ...
|
| AC compressor clicking | 8/14/2007 |
Q: I came home yesterday to no AC. The thermostat appeared dead, so I replaced it with a new one. ... A: Hey Josh, Do you have your manual for the furnace? Need to find out what that single flash of the ...
|
| HVAC - Ac unit | 8/13/2007 |
Q: I own a older townhouse in Boulder City, NV (Las Vegas region)and the upstairs ac unit finally went ... A: what a pity to have to upgrade to the new stuff.That 13 SEER coil is sooo big.Not too good ...
|
| Puron system question | 8/13/2007 |
Q: We installed a Carrier 3 ton Puron system 1 year ago. Our home is a pretty tight 1600 foot house. ... A: From all I know about Puron (R 410) the evaporator coil should provide a 40 deg coil. Therefore a 16 ...
|
| Cold Air Returns | 8/13/2007 |
Q: I have a two story 1550 sq. ft. house and recently had a new compressor and coil installed. They ... A: Where were these returns they closed ?? You have returns to insure return air gets back to the ...
|
| compressor replaced and now not cooling well | 8/11/2007 |
Q: We purchased a 1 story 2500 sq. ft. historic home w/ 2 sep. units. Original unit 2 1/2 ton very old ... A: Now I`ve got the questions! You have had 2 units cooling the house, were they both 2 1/2 tons ...
|
| keeping spare room cool | 8/10/2007 |
Q: I own a two story townhome/denver co. my spare room upstairs faces east and gets morning sun. I have ... A: Ya got to stop the heat from that window. How about a solar screen, or a reflective solar coating ...
|
| Never cool | 8/9/2007 |
Q: I live in an apartment complex forthere are 12 apartments in each building I've called maintenance ... A: Apartments are famous for not-too-good cooling systems.Ducts supplying the air the same. If your ...
|
| simple Comfort 3001 | 8/9/2007 |
Q: we have a simple comfort 3001 and the screen goes on and off, shows 78 degrees for a few minutes, ... A: Not acquainted with that thermostat. Does it use a battery in it ?? If so maybe a new battery will ...
|
| Central AC | 8/8/2007 |
Q: My Fan on the outside unit will not turn and it is HOT! About 1 month ago our unit was frozen over ... A: Well John, Summer has come in Texas also! Sounds like bad motor bearings, but first test the motor ...
|
| Goodman air conditioning unit is leaking water | 8/8/2007 |
Q: We have a Goodman Air Conditioning and heating Unit model GMS8 and it is leaking water. It less than ... A: I presume the white pump is sitting on the floor? That is a condensate pump. It has a float switch ...
|
| a/c electrical???? | 8/7/2007 |
Q: We have been in new home 10mo 14 ton seer unit live in Texas elect bill just keeps going up 1 story ... A: Sounds like your electrical system is at fault, Cathy.Properly sized wiring shouldn`t do that.Only ...
|
| additional information to question (8/6) | 8/7/2007 |
Q: In my original question, i forgot to mention that the unit works and is cooling my house. The ... A: I can`t find your original question, Lisa.But I would guess from your question you may have a bad ...
|
| possible replacement of unit | 8/4/2007 |
Q: My service company tells me it is tine to replace with a higher effiency system preferably a trane ... A: My theory is "run `em till they die" You ought to be washing those outside coils twice a Summer with ...
|
| Outside circuits for A/C | 8/3/2007 |
Q: A disgruntled neighbor has been tampering with my unit outside. Just to fill you in first. This ... A: Call the cops, Melissa !!! That neighbor is BAD !!! He tripped the breaker to the outside unit. Just ...
|
| HVAC Trane XE1000 TTR042C100A2 | 8/3/2007 |
Q: Lead from contactor to dual run cap is burning up. There is no start cap on this unit but this cap ... A: Once the terminals get rusty the wires can melt from the heat generated by the rusty connection. ...
|
| Central AC | 8/3/2007 |
Q: My AC unit will run as though cooling the house although the house is not getting the cool air. ... A: Hey Alice, First thing to check is the freon. Low amounts cause the freezing. Second thing that ...
|
| AC not cooling | 8/2/2007 |
Q: AC was blowing semi cool air so I had a servideman come out. He said he did not see any major issues ... A: Run this test, the hotter the day the cooler the suction line. At about 90 or above that line ought ...
|
| Bryant 561CJ024-D cool/not cold after charge | 8/2/2007 |
Q: We have a dual zone AC/heating system. Our upstairs AC unit is a Bryant 561CJ024-D. It was ... A: Good info you sent.Yes, the temps of the suction lines should be about the same at the same ambient ...
|
| Carrier Compressor | 8/2/2007 |
Q: If my compressor is reading 30 to 350 and the expansion valve is frosting (has been replaced) and ... A: Have you gone to a/c school ?? What knowledge! Something stopped up for sure.That frost at the TXV ...
|
| Lennox Condensing Unit Runs Constantly | 7/31/2007 |
Q: Our Lennox refrigerated air condensing unit sits outside on a concrete pad and the fan is located in ... A: Hey Mark, you`ve got a stuck contactor in the outside unit. Not good to run the cooling without an ...
|
| fishy smell seemingly from HVAC | 7/31/2007 |
Q: We have noticed a fishy odor now that we use the AC in the summer. We have lived in a new modular ... A: (nice name)I get questions like that now & then & it`s tricky to find the source. Wonder if the ...
|
| Very hot compresser | 7/30/2007 |
Q: Sir, Water cooled boat compressor starts and runs for about 10 minutes and then shuts off, the ... A: If water supply is normal , may have bad bearings in the compressor to cause the heat. Or, how is ...
|
| central air | 7/30/2007 |
Q: My central air unit seems to be working fine, however Im having a lot of water pouring out of the ... A: Stopped up condensate drain Everett. Usually, it`s at the mouth of the drain pan under the coil. ...
|
| Warm Air - Compressor Short Cycling | 7/29/2007 |
Q: Howard, We woke up this morning to a warm house (and a complaining 3 year old grandson!). Warm air ... A: That sounds just like a switch tripping off the compressor due to a low freon amount. Best call a ...
|
| Not Cooling After Power Outage | 7/28/2007 |
Q: After a couple of brief power outages, my unit quit blowing cold air. I have tried setting the ... A: Hope the unit wasn`t running when the outage struck. That is really hard on a compressor.It may take ...
|
| Contact Switch Burns Out Often | 7/22/2007 |
Q: I recently replaced a contact switch in my central air unit. After the unit started running again I ... A: I`m thinking the cause of the new contactor failing was the cause of the failure with the old one. ...
|
| can't find a/c leak | 7/22/2007 |
Q: We purchased a home a little over a year ago (3yrs old). It was too cold to properly inspect the a/c ... A: Oh, you bring back not-too-good memories about the same kind of problem you have.And guess where the ...
|
| AC trips circuit breaker often | 7/21/2007 |
Q: I have a Trane xe 1000 unit. About once per day, the two circuit breakers that control the AC ... A: Yes there is, Gerard, Feel the breakers while the unit is running. Are they overly warm to hot? ...
|
| Booster Fan add-on | 7/21/2007 |
Q: Your Question was: I have a ground source heat pump which works well except for our only 2nd ... A: Connect wires to the R & G terminals at the thermostat or at the furnace. Connect these wires to the ...
|
| Furnace pipe plugged | 7/20/2007 |
Q: Today my 3 year old son put a bunch of rocks in one of the pipes coming out of our heating furnace. ... A: And you thought the terrible two`s was over !! Sorry, Erin that I don`t understand what pipe that ...
|
| furnace won't turn on | 7/20/2007 |
Q: okay... here it goes... this may be long and at length... i have a weather king gas furnace and ... A: Electrical problems are tricky but I can give you all the things to test to try to find the problem. ...
|
| New Trane systems not cold | 7/19/2007 |
Q: Replaced two 19 yrs old Carrier systems with two Trane systems five days ago. Same tonage on both AC ... A: Must live in FL for humidity like that! Cooling systems remove humidity first, then the heat ...
|
| Frigidaire window air conditioner | 7/18/2007 |
Q: I suspect that my window air conditioner may need refrigerant recharging. Can I do it myself? The ... A: Those things don`t have a service valve, Wayne. You need to add one that clamps on the suction line, ...
|
| Unit freezes up at night or early morning | 7/17/2007 |
Q: My sister-in-law has a goodman evap unit and ruud condenser. I checked evap. coil found unit on low ... A: You have to have a license to buy parts - usually. Never hurts to try a COD order tho.The fan relay ...
|
| Smell coming out of air conditioning vents | 7/17/2007 |
Q: I bought a brand new 17,100 BTU window unit. Ever since I bought it I have been smelling a plastic ... A: Lousy warranty, Susan.Probably would be difficult finding the problem of the smell. These newer ...
|
| Air handler blower motor | 7/16/2007 |
Q: Last season I called a tech to replace the blower motor in my home a/c. The technician showed and ... A: Most condenser fan motors run at 1100 rpm. But, it`s the amp draw that counts. The 1/3rd motor ...
|
| Unit freezes up at night or early morning | 7/16/2007 |
Q: My sister-in-law has a goodman evap unit and ruud condenser. I checked evap. coil found unit on low ... A: 2-4 deg superheat too low. Too much freon.I use 30 deg split between suction line temp & ...
|
| Sand like white particles when I turn on the AC | 7/16/2007 |
Q: Whenever I turn on my Air Conditioner. There is some tiny sand like white circular particles (it is ... A: Howdy from Texas, Wonder what kind of ducts you have? Flex, metal?? Or plenums?? If the plenums are ...
|
| replaced units in condo with new trane | 7/15/2007 |
Q: contractor replaced all but 1 bottom panel, that hides the pipes underneath, he used existing ones. ... A: Well, I`m stumped. I`m not acquainted with what panel you need.I presume it is a Trane part ?? If ...
|
| Bryany ac heater dual pack | 7/15/2007 |
Q: I have a bryant dual pack ground unit with a hunter digital thermostat, the thermostat seems to be ... A: Hey Mike, Thermal barrier 1st: Heat transfer is instantaneous. So if it is laying on the floor of ...
|
| AC no cooling | 7/14/2007 |
Q: My AC was not cooling three days ago. I called a service company. They checked and changed a Start ... A: A hard start capacitor is generally used to add voltage when the compressor starts when the ...
|
| A/C blowing cool air but not cold air and I can feel the fan blowing even when the unit is off. | 7/13/2007 |
Q: My A/C unit does not blow cold air even when I set the temp. at 70 degrees. The house does not cool ... A: Sounds like you have an electric furnace possibly causing your problem. What can happen is one ...
|
| Hookiing up two thermostats | 7/13/2007 |
Q: I have central air and forced hot air oil burner Thermo Pride. I believe the thermostat is 24v. I ... A: One tstat would use only the red & green wire from the furnace for fan only. The other one would be ...
|
| leaking A coil Interthem | 7/12/2007 |
Q: had tech out charged system, next day iced up 5lbs loss put die in found the leak in A coil the back ... A: Evaporator coils are exposed to heat/cold & that means expansion & contraction. Those coppertubes ...
|
| Central air blower | 7/11/2007 |
Q: Great service, thank you! I have a 4 year old Armstrong Air Ultra V Tech 80 in my home. Since I ... A: The blower is controlled by a circuit board with input from the thermostat. Lets test the fan ...
|
| blower cuts out when a/c is turned on | 7/11/2007 |
Q: working on goodman combo hvac and gas heatpump recharged unit have checked everything and what's ... A: Sounds like the fan shuts down fast, then the ice forms, then the compressor shuts down from a low ...
|
| heat pump | 7/10/2007 |
Q: Our house has a furnace and an outdoor heat pump. Today when the a/c clicked on the heat pump unit ... A: I would start with the contactor having burned points that can`t make contact. Locate it in the ...
|
| Electric vs Propane and what size | 7/9/2007 |
Q: We live in Indiana so we have big temp fluctuations. We currently have a Propane furnace but it is ... A: WOW !! That`s a huge heating bill.You would need about 4 -20 kw heating elements. That`s an 80 amp ...
|
| Blower won't work | 7/9/2007 |
Q: I have an Armstrong Ultra SX 80 furnace and an outside unit.The outside turns on like it should but ... A: ,The blower motor is controlled by the circuit board in the furnace. Does the fan run when the ON ...
|
| carrier unit dripping water from evaporater | 7/9/2007 |
Q: I have carrier unit, the evaporater dripping water into the area behind the intake (return air), I ... A: typical Summer problem.The evaporator coil needs to be removed & cleaned. I use a water hose in the ...
|
| Fan will not start. | 7/8/2007 |
Q: I recently had a radiant barrier applied in my attic. My attic space is very cramped. Three ... A: easy to connect your problem to guys crawling all over your attic but don`t feel that is the cause. ...
|
| Heat pump won't start with temp below about 80 | 7/7/2007 |
Q: I have a Tempstar heat pump, model ch9525vka1, with a Honeywell ct70a1001 thermostat. We bought the ... A: John, I`ve sent your question to the question pool to see if anyone can solve your problem. I am at ...
|
| Freon loss | 7/7/2007 |
Q: I have a Trane XE-1000 heat pump, which is 14 years old. Three weeks ago it started leaking freon. ... A: Is he using a H-10 freon sniffer? They can detect an ounce/yr leak. The coil is usually where leaks ...
|
| AC Follow Up | 7/6/2007 |
Q: 6/26/07 Question I have a HVAC System that was installed in 01. After the AC runs for a few minutes ... A: Only thing I can say is when the thermostat is on auto, it is the thermostat that turns on the fan ...
|
| Lennox 10ACB24-9P split system | 7/5/2007 |
Q: Fan will not start, Compressor will not start, but humming. Contactor approx 230V In/Out. ... A: Ah, Lennox & their hidden switches. Look in the outside unit for a switch with a red push button ...
|
| return supply | 7/5/2007 |
Q: Just had a 5 ton A/C unit put into 2700 sq ft 1 story home. The only return vent is under the unit ... A: That other guy is an expert cause he told you correctly. Return air CAN NOT move 50 to 80 ft across ...
|
| A/C handler in a bad garage location | 7/4/2007 |
Q: I am currently building a 3500 sq ft. house in Caly County Florida and I just noticed that they've ... A: Me again Will, The only thing I can say about that installation is that is a mighty strange place to ...
|
| York AC makes main-house-AC-breaker trips off; new house owner | 7/4/2007 |
Q: when I try with capacitor & turns main house ac breaker on the fan turns one spin & main house ac ... A: Now I got it. The red wire to contactor is the other 220v leg, therefore has the white wire ...
|
| Downstairs Air Conditioning | 7/3/2007 |
Q: There is no air blowing downstairs. The thermostat kicks on and I can hear the compressor/condensor ... A: Don`t run the cooling without the inside fan.Check the auto type fuse on the circuit board in the ...
|
| York AC makes main-house-AC-breaker trips off; new house owner | 7/3/2007 |
Q: when I try with capacitor & turns main house ac breaker on the fan turns one spin & main house ac ... A: Boy, Kong that`s a lot of info!I don`t dig the "White to red to Contactor to C capacitor" The white ...
|
| Rusted pan in air handler | 7/3/2007 |
Q: My air handler has several problems. The 5 Mfd capacitor tests around 1.8 Mfd, and the secondary ... A: WOW ! That capacitor costs $3. Greed wins over all. Now here`s what to do for about $60 +/-. Pump ...
|
| Fan blowing but no cool air | 7/2/2007 |
Q: I have a Trane system. Model TWR036C100A1 I was getting cool air this afternoon, but by evening, ... A: You need some of this rain we are having in Texas. Almost broke a record for a wet June. Had rain 19 ...
|
| goodman elec. ahu | 7/2/2007 |
Q: Goodman parts are hard to come by here locally, can I replace the fan relay that looks like a ... A: Have not changed relays from a 5 pole to 6 pole in a looong time so had to test it again.Terminal 1 ...
|
| Replacing Fan Motor of York HeatPump | 7/1/2007 |
Q: I am replacing the Fan Motor of my York Heat Pump. The old motor had 3 wires (Purple, Brown and ... A: OK,Kamal let`s sort this out.You need to read the printing on the 2 capacitors to see if the mfd ...
|
| York A/C with Gas heat, indoor fan not running. | 6/30/2007 |
Q: The indoor fan motor doesn't kick on. Bought a new motor from A.O. Smith's cross refernce, but the ... A: Brown & brown with white strip goes to either lugs on the cap.Then 2 hot wires to power. One yellow ...
|
| air conditioner | 6/29/2007 |
Q: My house is 1800 sq ft and my unit is Arco Air and is less than 2 years old. The unit was in the ... A: The air temp at a mid range supply grille from the furnace ought to be about 55 deg. Did anyone ...
|
| Inadequate AC unit | 6/29/2007 |
Q: We have a 5200 s.f. house with the main floor being 2000sf, the lower level being 2000sf, and the ... A: The heat load on your house determines the cooling capacity needed to keep the house 30 deg cooler ...
|
| Blower doesn't stop | 6/28/2007 |
Q: I have a Lennox O23 furnace with a Lennox 10ACB condensing unit and C23 coil. About 1 month ago I ... A: You sure the thermostat switch for the fan is on auto ?? (never hurts to ask)Now, since you have ...
|
| Inadequate AC unit | 6/28/2007 |
Q: We have a 5200 s.f. house with the main floor being 2000sf, the lower level being 2000sf, and the ... A: Wonder where you live?? Your heat load is really small for the 6 tons total cooling.Your house sure ...
|
| Air Conditioner Repair | 6/27/2007 |
Q: I had a repairman out last week because central air unit was blowing hot air. He replaced what I ... A: The "start capacitor" he replaced is under HIS warranty. Unfortunately,that charge was a little high ...
|
| low air flow | 6/27/2007 |
Q: I have a Janitrol residential air handler model R43-00 (electric heat and cool) with a 3 ton ... A: Ya never know what maintenance has been performed on that system. Maybe none. Lack of filter changes ...
|
| Air Conditioner not working | 6/26/2007 |
Q: I have a mobile home and my air conditioner used to wotrk.. then after winter I tried to turn it on ... A: To begin, we need to confirm that there is power to the outside unit. Ought to be a circuit breaker ...
|
| HVAC | 6/26/2007 |
Q: I have a HVAC System that was installed in 01. After the AC runs for a few minutes it sounds as if ... A: Ya know, the thermostat is blamed too often & usually is not the problem.Your description of the ...
|
| Blower fan doesn't stop | 6/25/2007 |
Q: I replaced the filter in my A/C unit a few days ago and after putting the cover back in place the ... A: Boy Sonny, that`s a killer question! A key fact may be is this a circuit board controlled unit ?? ...
|
| AC operation | 6/25/2007 |
Q: My year old electric ac unit has a few seconds of fan operation then it hesitates a couple seconds ... A: I say "baloney".What happens if you turn on just the fan switch at the thermostat?? Hesitate ?? Do ...
|
| Goodman and Wires | 6/24/2007 |
Q: I have a goodman unit and the wires that come fropm the house have been chewed up from the previous ... A: You can`t believe how common that problem is with dogs. They will keep doing it for some strange ...
|
| Suction King valve | 6/23/2007 |
Q: I have a Corsaire by Rheem air condtionong unit. It has been running fine until the other night it ... A: Lock tite ??? Never heard of sealing a 175psi system with that !! The valve he was messin` with is a ...
|
| Grinding noise at Compressor startup | 6/23/2007 |
Q: I have a 6 month old matching Goodman 5 ton unit & coil with a 7 years old goodman Gas furnace. ... A: What`s the guy want to replace the inside blower for, the noise is outside! That motor surely can`t ...
|
| AC unit and lightning | 6/23/2007 |
Q: I did have a nearby lightning strike. No outside operation or inside fan. The fuze on the control ... A: Hey Frank, Not too good. Be sure & add a surge protector on the furnace.You have a fuse or ...
|
| Grinding noise at Compressor startup | 6/22/2007 |
Q: I have a 6 month old matching Goodman 5 ton unit & coil with a 7 years old goodman Gas furnace. ... A: I gather that this noise has recently started ??More than likely it would be a fan motor That could ...
|
| Loose wire on outside compressor | 6/21/2007 |
Q: I have a Trane XB1000 HVAC unit. After I opened the outside compressor to clean the coils, I ... A: Let`s start with cleaning the coils. Best way is with a water hose not spraying too hard & squirt ...
|
| RE: Trane XL-80 furnace controls | 6/21/2007 |
Q: I have a trane xl-80 two stage gas heating system with white rodgers 50A51-495 controls. when I try ... A: How about a good ground on the power supply?? Is the low voltage fuse seated in the sockets?? Is the ...
|
| 24 volt control circuit | 6/20/2007 |
Q: unit will not come on checked volts at t stat from red to ground = 0 volts went to transformer had ... A: That`s a doozy of a question, Roy.Got to have some resistance somewhere. Try disconnecting the red ...
|
| not cooling air | 6/19/2007 |
Q: i live in a townhouse and i have a digital thermostat but do not know what brand my unit is, my home ... A: Hotter than Texas ?? You have lost freon. Got a leak somewhere, usually in the evaporator coil. Just ...
|
| Dryer or not to dryer | 6/19/2007 |
Q: I have an old gaffer and Sattler Central Air conditioning/gas heater on my roof. I beleive it is 2 ... A: He didn`t know what he was doing. You had a "burnout" of the compressor motor windings spewing ...
|
| compressor contactor/thermostat | 6/18/2007 |
Q: I have a 5year old Comfortmaker heat pump (scroll compressor) and I am having problems with the ... A: What triggers the defrost cycle? Sometimes it is an air pressure actuated switch sensing ice on the ...
|
| AC power interrupter | 6/18/2007 |
Q: Is there a power circuit interrupter to protect the compressor when the power is interrupted by a ... A: Yes, I`ve got one. It is a Honeywell thermostat sold at Home Depot. It`s round with a digital temp ...
|
| Heating and AC unit | 6/18/2007 |
Q: My new AC and Heating unit does not cycle on and off what is the problem A: Sometimes on a new installation the vibration will crack a weld on the copper piping. Lose some ...
|
| Lennox AC model G23-31-1 | 6/17/2007 |
Q: I have zoned heating and cooling. both units are right next to each other. The G23-31-1 had water on ... A: Not likely that the water would have damaged anything. Need to find out if the compressor is running ...
|
| AC: Varying supply air temperature | 6/14/2007 |
Q: When the AC is running, I am getting different supply air temperature from different rooms. I have ... A: Those attics can be about 120 deg on a hot day. Different length duct runs can pick up more or less ...
|
| A/C Units | 6/14/2007 |
Q: I have a NOMA - 10,000 BTU A/C Unit. I havent had it for more than 2 months & its brand new. Anyways ... A: A/c units produce lots of condensate water & that`s about the only thing that could cause a smell.I ...
|
| Outside unit will not run or runs sometimes | 6/13/2007 |
Q: I have a carrier heat pump. I noticed a few days ago that I would hear a click or several clicks ... A: Did you test the unit by manually closing the contactor?? That test would localize the problem to ...
|
| Air flow from a wall unit | 6/13/2007 |
Q: We have an A/C unit (GE Model) through the wall unit, which blows and cools perfectly in an ... A: Well, well, something else, huh? So if the motor is running at full speed it has to be a stopped up ...
|
| Water from air conditioning unit | 6/13/2007 |
Q: We have a Rheem Classic 90 Plus furnace/air conditioner. Water is leaking from the bottom while our ... A: Typical Summer problem, condensate water leaking. Got a stopped up drain line.Open the panel in the ...
|
| Mismatching SEER #'s | 6/12/2007 |
Q: Can I use a SEER 13 condensing unit(a/c only) with a SEER 10 evaporator coil? If so will it shorten ... A: Good question, Pat. Some a/c companies here indicate the warranty is void unless the evaporator coil ...
|
| Air flow from a wall unit | 6/12/2007 |
Q: We have an A/C unit (GE Model) through the wall unit, which blows and cools perfectly in an ... A: Low voltage in the other apartments could cause that low air flow. Test both places for similar ...
|
| AC not cooling to set temp | 6/11/2007 |
Q: I have a Rheem heat pump unit. My AC blows cool air but does not reach the set temp. For example, if ... A: Wonder how much freon was added last year?? 1 to 2 lbs? small leak, 3 to 5 lbs, big leak.The ...
|
| Rheem AC | 6/10/2007 |
Q: I have an old rheem air conditioner that is working order, my question is I replaced the motor for ... A: You have a short to ground on the motor. Usually this short is in the windings but may be from an ...
|
| Central AC unit --- contactor releasing | 6/10/2007 |
Q: Howard, I have an old Central AC unit about 25-27 years old. I have replaced the fan motor about a ... A: I`ll bet a switch in the outside unit is stopping the unit.You probably have both high & low ...
|
| Lennox GCS fan runs continuously | 6/9/2007 |
Q: The fan on my Lennox GCS20R-411-75-4P runs continuously. The compressor starts and stops ... A: Goofyis the fan switch on the thermostat in the ON position ?? How about exposing the wires on the ...
|
| Squeaky A/C | 6/9/2007 |
Q: We have a 15 year old Luxaire Delux high efficiency unit. Model # PCMU-LD12NO57B (I am not positive ... A: That unit uses a belt ?? Bet it is a direct drive. Assume the motor squeaking is the inside blower ...
|
| Trane XL weathertron heat pump | 6/8/2007 |
Q: I received a used Trane weathertron heat pump with the heat pump feature disabled by rerouting of ... A: Wow, a freebie !! Is there a visible schematic on the access door ?? Suggest get one, if none ...
|
| Heat works but not A/C | 6/7/2007 |
Q: I have a 7 year old Carrier Heater and A/C Went to turn on A/C today and nothing happens. I can ... A: This time of the year when the a/c is first turned on the common problem is low on freon.You need a ...
|
| Trane XE 1000 | 6/7/2007 |
Q: I have a Trane that is almost 10 years old and suddenly it does not blow cold air. The Fan runs and ... A: You need to check it with a set of gages connected to the high & low side to really tell what`s ...
|
| Lennox Model HS19-511-6P | 6/6/2007 |
Q: First off I would like to say thank you for your time in answering this question. Now I bought a ... A: It`s all about money, right ?? These guys nowdays will sell you a new unit even if it`s 4 yrs old!! ...
|
| HVAC | 6/6/2007 |
Q: Here's the thing. I have a uncle who put in a new 2.5ton 13 seer gas pac in his home during the ... A: Some good rules of thumb. For a 1000 sq ft house a 2 ton cooling system is good.A right size system ...
|
| New blower motor trips breaker | 6/5/2007 |
Q: Howard, I have a Lennox dual pack/4 ton unit approximately 20 years old. Replaced the compressor ... A: Hey Rob, That higher amp rating is the permissible amp draw, so the new motor should be pulling only ...
|
| Trane XE1000 - short somewhere? | 6/4/2007 |
Q: Trane XE1000 - Model TTR048C100A2 Noticed no cold air, then noticed that breaker was tripped. Tried ... A: One more try,Eric. Cases like this I drag out my $150 ohm meter(35 yrs ago, analog) & put it on ...
|
| Outside unit will not run or runs sometimes | 6/4/2007 |
Q: I have a carrier heat pump. I noticed a few days ago that I would hear a click or several clicks ... A: Sounds like another switch in the outside unit is the culprit causing the contactor to cycle.One is ...
|
| dual zone systems cost & issues | 6/4/2007 |
Q: I am finishing an attic & the concerned about AC in this third story room. The contractor has just ... A: How much insulation is there on the ceiling of the new room ?? Lots I hope. Figure this: Rule of ...
|
| Heil central air conditioning fan | 6/3/2007 |
Q: Two yellow wires on the outside fan unit on our Heil 10 central air conditioner were disconnected ... A: Those 2 wires are normally the 24 volt connection to the outside unit. They connect to the red & ...
|
| Blower Motor | 6/2/2007 |
Q: The blower motor on my unit has been making strange noises when starting and stopping while running ... A: Classic symptoms of bad bearings on the motor. Best way to tell is to pull the blower assembly by ...
|
| Carrier 58PAV | 6/2/2007 |
Q: I have a Carrier 58PAV Upflow furnace / A/C. The drain was clogged on the primary and the pan filled ... A: Yo Daron,I think you may have a wire in the thermostat shorted to another wire. The draft motor is ...
|
| Trane XE1000 - short somewhere? | 6/2/2007 |
Q: Trane XE1000 - Model TTR048C100A2 Noticed no cold air, then noticed that breaker was tripped. Tried ... A: Little slow responding today. Yard work. You need to ohm the compressor for a shorted motor. Isolate ...
|
| transformer hook-up for 1980 era gas furnace | 6/1/2007 |
Q: We have a singer gas furnace installed in 1980. The original transformer burned out a few weeks ago. ... A: Do you mean 4 wires total from the transformer?? If I dig you right, the 6 wire new one has 2 wires ...
|
| control transformer failure | 6/1/2007 |
Q: I have 3 amana units. One of the units stopped working and I found a blown fuse. I replaced the ... A: you have a dead short in a 24 volt control circuit. Start outside checking the control wires from ...
|
| Air Conditioning outside Unit not Running | 5/31/2007 |
Q: Trane 3 ton XE 1000 AC unit running ok this morning. Came home and noticed no cooling in the ... A: Is that oil below the access panel to the electrical stuff?? Bet so. Remove the panel & check the ...
|
| Humming Sound Every 4 Minutes | 5/30/2007 |
Q: I have an elite 90 gas fired heater by Lennox. While the thermostat is on off position I noticed ... A: A coil of wire that is energized can make a humming sound.That furnace has lots of "stuff" on it so ...
|
| Pkg Unit Blower only works with heat not A/C | 5/30/2007 |
Q: I have a 1 yr old (ICP) Comfortmaker PAM342K00A1 3.5 ton Pkg unit w/ 10kw heat strip. Blower motor ... A: Heat fan & cool fan 2 different circuits controlled by a NO & NC relay on the circuit board. The ...
|
| rheem 6 year old ac unit not running | 5/30/2007 |
Q: i have 3 ac units for my house. the guys that put it in "were not the best" as i have been told by ... A: Need to run several tests that can isolate the problem. One: Turn the fan switch on the thermostat ...
|
| Lennox AC unit outside not responding | 5/29/2007 |
Q: I have a Lennox Elite CB29M unit that recently I noticed was blowing only warm air throughout the ... A: There is a dead short to ground somewhere.Was the compressor running when you went outside to check ...
|
| HVAC outside unit has quit! | 5/29/2007 |
Q: Outside unit has quit running, totally. Nothing. AC will blow air inside, but the outside unit ... A: Remove the access panel on the unit to the electrical controls. Locate & manually press in the ...
|
| Air Conditioner STOPPED | 5/27/2007 |
Q: I have a Rheem 14 seer central system. Than is all I know about it. Yesterday the house was hot ... A: Have a close lightning strike ?? Bet there is a circuit board in the outside unit, they are sure ...
|
| Trane Heat Pump Failure | 5/27/2007 |
Q: Our 3 yr old Trane heat pump failed to provide cold air this week. I is a 4 ton XR12 Trane unit. ... A: Not a un common problem, Jan, but unusual on a 3 yr old system. Fan blade could have been defective ...
|
| Air flow | 5/27/2007 |
Q: I have a Carrier central air unit that runs great in the winter when the unit is heating the house. ... A: Well, that`s interesting, Charles.You have a 3 speed motor there, black wire is high,blue the next, ...
|
| Heat Pump Problem! | 5/26/2007 |
Q: I have a 22 year old Heat Pump (TRANE) brand. Went to turn it on for the AIR Conditioning, for this ... A: good questions.Need to test the freon. Outside fan running can mask that whether the compressor is ...
|
| AC fuse box | 5/26/2007 |
Q: Howard, I have a fuse box located outside (next to my AC unit--central air) that contains two fuses ... A: You brave gal, Diane. Dead short caused the sparks. I`m curious about reversing the fuses.Are the ...
|
| AC - Trane with Honeywell TH8000 Thermostat | 5/26/2007 |
Q: I have a Trane outdoor condenser with in ceiling air handler; Honeywell TH8000 Thermostat. ... A: Expose the thermostat wires & jump across red & green wire to test. I would expect the trouble is in ...
|
| ac blows hot air after circuit breaker trips | 5/25/2007 |
Q: i live in an apartment and my circuit breaker for the ac seems to trip often. i re-set the breaker ... A: When it is running OK, feel the circuit breaker & see if it is hot to the touch. If, not the ...
|
| Dog ate thermostat wire | 5/24/2007 |
Q: Ok, kind of a long story here. My dog chewed the thermostat wire out of the outside central air ... A: I used to make a lot of money fixing wires chewed on by dogs! Once they do that they never stop. ...
|
| blower motor | 5/24/2007 |
Q: the blower will not work, when it calls for it to run it just has a hum. Is the problem the blower ... A: Several things to test. Turn off power to the furnace, remove lwr access door. Manually spin blower ...
|
| Central Air not working | 5/24/2007 |
Q: I turned my a/c on for the first time this year and it is kicking on the heater. It is blowing hot ... A: Not an uncommon problem, Tina. It is usually a shorted wire in the thermostat. Remove the cover & ...
|
| High current draw AC unit off | 5/23/2007 |
Q: With thermostat satisfied, a high amp load (70+ amps)dims the lights in the house for about 2 ... A: I would feel the breaker when the cool is running & see if it `s hot. The loose wire could have ...
|
| heat pump | 5/23/2007 |
Q: Howard I have a goodman heat pump pakage unit Mod #phk024-1 when I put T'stat red and yellow ... A: I led you astray on my last answer. The wires to the contactor do not come directly from the ...
|
| A/C not blowing | 5/23/2007 |
Q: I am a new homeowner with a completely renovated home. I have a one year old Trane air condition ... A: Lack of freon can cause icing of the whole system.This blocks air thru the evaporator coil. If ...
|
| Hvac goodman ck42-1c | 5/22/2007 |
Q: Outside unit quit. Fan motor extremely hot but blades are free. I'm waiting to let it cool down to ... A: Test the run capacitor first. Got a VOM? Use the highest ohm setting & test across the terminal ...
|
| ac problem/son | 5/21/2007 |
Q: my sons Trane XE1200 ac unit's fan works, but outside compressor wont work, reset breaker, nothing, ... A: Need to test compressor run capacitor first. Then retest. Test next after trying to start up, the ...
|
| Ice is blocking the tube | 5/21/2007 |
Q: I turned on the A/C unit and within 2-3 hours the coil is frozen. Therefore no air goes thru the ... A: You have lost some freon Luis. The inside coil is icing also, blocking the air. The tech needs to ...
|
| Goodman CK42-1C | 5/21/2007 |
Q: I live in Houston, and have a Goodmand CK42-1C that works very well overall. I had the coils ... A: I wondered about that word windy,Marc. The freon liquid line going to the coil could make a noise ...
|
| Goodman CK42-1C | 5/20/2007 |
Q: I live in Houston, and have a Goodmand CK42-1C that works very well overall. I had the coils ... A: that is a head scratcher.Something funny about that "windy" sound. I`m thinking that the motor is ...
|
| 220 vs. 110 advantage for thru-the-wall ac unit | 5/20/2007 |
Q: I am about to purchase a 15,000 btu thru-the-wall air conditioner to be installed in a bedroom. My ... A: Voltage is equivalent to pressure in a water hose. The more the pressure, the smaller the motor can ...
|
| Tri-zone LG Multisplit | 5/19/2007 |
Q: Tri-zone LG Multisplit 13 SEER 3 indoor units, one outdoor. Units a and b work fine; spitting ice ... A: Never have experienced a 3 split system so all I could presume is that unit c superheat is off maybe ...
|
| Bryant Plus 90 Furnace | 5/19/2007 |
Q: I am having trouble getting my HE furnace to light. When heat is call for from the thermostat I ... A: First thought, Kyle is that the pilot orifice is plugged.You proved the gas is flowing from the gas ...
|
| Heil air reduction | 5/19/2007 |
Q: We are having an issue with our Heil model H8MPN075F16A A/C (2 years old). On warm days (80F) the ... A: That problem smacks of a freon loss causing icing of the evaporator coil blocking off the ...
|
| ac unit | 5/18/2007 |
Q: We have an trane central air & heating unit installed when the house was built 1999. Last year the ... A: Your description fits the problem of a freon leak. How many pounds of freon was added at the recent ...
|
| compressor contactor/thermostat | 5/18/2007 |
Q: I have a 5year old Comfortmaker heat pump (scroll compressor) and I am having problems with the ... A: The simple test of manually closing the contactor tells you it is a control circuit problem.I`ll bet ...
|
| duct size | 5/17/2007 |
Q: Is there a general guideline on the size of the duct that should be going to each room? That is, 8" ... A: Duct sizing is a function of Bernoulli`s Equation for airflow in ducts. That equation applied to ...
|
| Lennox G40UH(X) series gas furnace | 5/16/2007 |
Q: We have zoned heating/A/C. Over the past couple of days, although we're not heating or cooling, one ... A: If that is the outside unit running all the time you probably have a stuck contactor. Don`t let it ...
|
| evap cooler | 5/16/2007 |
Q: I just replaced my roof top cooler, rewired it like the diagram said, but now when turned on the ... A: Not really acquainted with your cooler but a motor that does that can be a capacitor run & if so the ...
|
| central ac | 5/16/2007 |
Q: I turned on my 7 year old central air for the first time this year and the blower started blowing ... A: Sounds like a locked rotor in the compressor if that was the compressor you heard. Did the hum stop ...
|
| outside unit not working | 5/15/2007 |
Q: My air conditioner wasn't cooling the house, I looked outside and the outdoor fan unit wasn't ... A: Don`t mess with this guy, he wants money.Yes, the outside unit can be replaced separately. A heat ...
|
| Air Conditioner Fan blows but no air comes through the vents | 5/15/2007 |
Q: I have a Heil air conditioner. When it cycles on, the fan is running, but no air comes through the ... A: A rip off at $300. That`s about a $60 motor. Take the motor out yourself. Cut the wires to the ...
|
| 10 year old Nite&Day air cond dead | 5/15/2007 |
Q: I have can see the 220V relay operate correctly and I've replaced the capacitor but still neither ... A: Got a voltmeter?? Test for 240 volts on the inlet side at the contactor & 24 volts at the contactor ...
|
| A/C Compressor Won't Start | 5/14/2007 |
Q: Howard, my wife and I purchased a pre-owned home in January. Due to about 3 feet of snow on the ... A: The fan switch on the thermostat sure should turn on the inside fan when turned on. That is the red ...
|
| central air not cooling | 5/14/2007 |
Q: Ontario and I have a 1.5 ton keeprite central air conditioner that runs steady. My house is 900 ... A: One test you can do may give a clue as to why it runs all the time on cooling. You will need a good ...
|
| AC compressor capacitor. | 5/13/2007 |
Q: I have and ancient "Singer" AC central air unit. Has always worked great. This season when ... A: My philosophy is to run `em till they die! Does ancient mean 18 to 20 years?? If so, & it is the ...
|
| Air Conditioner Fan blows but no air comes through the vents | 5/13/2007 |
Q: I have a Heil air conditioner. When it cycles on, the fan is running, but no air comes through the ... A: You need to spin the blower manually with the power off to test the bearings. If it spins freely it ...
|
| Goodman CK42-1C condensate pan | 5/12/2007 |
Q: The condensate pan in my unit appears to be rusted out because I have a puddle of water from under ... A: Condensate water leaks can come from dirt on the coil or a rusted drain pan. Either one, the coil ...
|
| Goodman CK42-1C | 5/12/2007 |
Q: fan will come on but the unit will not cool. unit sits outside with the heating unit in the attic ... A: I see the desert is heating up, time for cooling, huh? Sounds like you are low on freon assuming the ...
|
| air filters | 5/11/2007 |
Q: How often should air condition filters be changed? Thank you A: Good question. My usual answer is: whenever they need it.Mark the time for a new filter & say check ...
|
| ac furnace runs only on "ON" position | 5/11/2007 |
Q: Howard I have a problem with my ac furnace, It will turn on and stay running only, when I set the ... A: I`ll bet you have a digital thermostat?? Hear this problem quite often. First, you need to prove ...
|
| Air Conditioner Fan blows but no air comes through the vents | 5/11/2007 |
Q: I have a Heil air conditioner. When it cycles on, the fan is running, but no air comes through the ... A: Hey Jeff, I presume this is a new problem?? So let`s see how many things can cause this. First, is ...
|
| central air | 5/5/2007 |
Q: I have a Janitrol model GMP100-5. The fan will not turn off. What do I need to do to get it to turn ... A: I presume you`re talking about the inside fan??? Thermostat switch off??? Find the fan relay & tap ...
|
| heat pump with air handler | 5/5/2007 |
Q: Howard I love to read your guys experts opinion I have a heat pump that won't work has 24V to the ... A: You need some freon. Normal low side pressures are about 70 psi at 85 to 90 ambient.Always indicates ...
|
| units needed | 5/5/2007 |
Q: how many units or size of unit is needed to cool a two story home A: 500 sq/ ft. per ton is a good rule of thumb. A 2 story home DEFINITERLY needs 1 unit upstairs & 1 ...
|
| Central A/C condensor freezing up | 5/4/2007 |
Q: I live in FL and have a Janitrol central A/C system, 8 years old, that has an outside condensing ... A: Ice forms from lack of freon or too low airflow.Filter clean?? Good airflow from the supply air ...
|
| Heat pump problem | 5/4/2007 |
Q: Howard, I have a 5 year old Comfortmaker heat pump (2 ton 10 SEER) that has stopped working. When ... A: That sweating compressor does show it is running too cold. Now you would know that the cold air ...
|
| Heat pump problem | 5/3/2007 |
Q: Howard, I have a 5 year old Comfortmaker heat pump (2 ton 10 SEER) that has stopped working. When ... A: I`d say it`s definitely the rotor is locked in the compressor.No doubt the compressor is a Copeland. ...
|
| digital thermostat | 5/2/2007 |
Q: I installed a new hunter digital thermostat.. everything seems to be working just fine .. except ... A: Hey Cheri, I congratulate you for changing out the t`stat yourself. I`m a do-it-yourselfer too & get ...
|
| heat pump with air handler | 5/2/2007 |
Q: Howard I love to read your guys experts opinion I have a heat pump that won't work has 24V to the ... A: Lets go thru some "could be`s" for you to test. You have a control circuit problem for sure. Could ...
|
| HVAC - A/C | 5/1/2007 |
Q: Howard, I turned on my A/C for the first time last night. The outside unit turned on and copper ... A: That is a different circuit for the heat fan than the cool fan. Sounds like the fan relay. Cool fan ...
|
| THERMOSTAT | 4/30/2007 |
Q: HAD A SIMPLE COMFORT 2200 THAT HAD BATTERIES / REPLACE WITH A S C 2201 / PROBLEM / DISPLAY GOES OUT ... A: Shoot, Edward, attics are a big part of the business.A transformer cost about $10 so check out the ...
|
| Replacing Compressor Contactor | 4/29/2007 |
Q: I have a RUUD A/C unit where the outdoor fan motor will not start. I checked voltages at the fuse ... A: Maybe. Some a/c supply houses will sell COD to anyone. Others not. You have to know exactly what you ...
|
| ac blower | 4/28/2007 |
Q: I have a goodman 3 ton heatpump model# ph036-10 that heats and cools fine but sometimes the blower ... A: Hey Robert, Check the thermostat next. If you have it in auto & cool,the thermostat turns on the ...
|
| DICO Thermostat | 4/27/2007 |
Q: When in cool/auto mode, the thermostat will not allow setting below 73. It goes uu fine, but stops ... A: I`m not acquainted with that brand of thermostat. I presume it is a mercury bulb controlled ...
|
| Heil split unit central air conditioner | 4/26/2007 |
Q: Howard: My air conditioner quit blowing cold air last night. I removed the side panel of the inside ... A: Hey Frank, Not enough freon. Where did it go?? Most likely the leak is in the evaporator coil. Look ...
|
| Rheem outside package unit heat pump | 4/26/2007 |
Q: Howard, The unit is about 15 yrs. old and installed in 1992 new. When the AC is on, sometimes ... A: The blower motor(inside air) is controlled by the thermostat for cool thru the green wire at the ...
|
| Thermostats dying one by one | 4/25/2007 |
Q: We have hot water heat and had absolutely no problems until we had our boiler cleaned at the end of ... A: Down here they were primarily in apartment buildings & those people never did pay on time. So I will ...
|
| Rheem HVAC | 4/24/2007 |
Q: Howard, I have an 18 yr old Carrier Gas Furnace and Central Air system for my 3-level townhouse in ... A: Hey Brant, Sounds like the contractor needs money for his new car? Why not replace the evaporator ...
|
| Cold/Hot Rooms | 4/24/2007 |
Q: We purchased a "new" home this past fall and have continuing problems with hot/cold rooms no matter ... A: Air distribution is so critical for the longevity of a system & you have hit it head on. The method ...
|
| Start capacitor? | 4/22/2007 |
Q: I have a 10 year old trane xl 1100 split system. A few months ago the outside unit quit running, as ... A: That is a typical failure of a grounded compressor. But first the capacitor need testing, even ...
|
| air conditioning unit | 4/22/2007 |
Q: my comercial a/c uit will not turn on. a new thermostat was installed a month ago. It worked fine , ... A: First lesson to diagnose is start at the power source. Both 220/120 & 24 volt. Maybe a bad ...
|
| A/C vent locations | 4/20/2007 |
Q: I am selecting a vendor to install a/c - 2nd floor central system through attic, air handler in ... A: Hey Brian, The practice I followed all these years is select a place on the ceiling, not more than 2 ...
|
| Will a faster condenser fan speed hurt? | 4/20/2007 |
Q: I need to replace a condenser fan on a heatpump. The old OEM motor is an A.O. Smith with three ... A: Don`t recall ever seeing a motor running at 665 rpm. Usually is 825. You need to match that ...
|
| OK to install a mixed system? | 4/19/2007 |
Q: I need to replace my Air handler. The coil has a BIG leak. 1500 Sq ft, current system is a 3 to ... A: Why not just replacing the leaking coil?? I would stay with Lennox. Trane stuff is very expensive to ...
|
| burnt boards | 4/17/2007 |
Q: Howard, My gf has a carrier 395. the inducer bd burnt up and damaged the connector, replaced it ... A: Two things to check. First, is the gas valve & main gas turned on? Second, remove the flame sensor, ...
|
| Split ductless air conditioners (thru wall) | 4/17/2007 |
Q: I have a very small house with no ductwork, it is all electric heat through either baseboards or ... A: Sorta expensive but a sleeve unit, like motels use would work for you.Or you could cut a hole in a ...
|
| Central AC Blower | 4/15/2007 |
Q: I have a whirlpool package unit aprox 20yrs old. Can't find a model#. The blower runs ok when I put ... A: The thermostat controls the blower when in auto position & cooling. If the stat is digital, they can ...
|
| burnt boards | 4/14/2007 |
Q: Howard, My gf has a carrier 395. the inducer bd burnt up and damaged the connector, replaced it ... A: WOW, never heard of such repairs to a cb before.We just replace them. Ya know it takes a computer ...
|
| coil leak | 4/14/2007 |
Q: I want to know the guidelines on checking a coil leak. My repaireman said i could have a coil leak. ... A: Sounds like he doesn`t know what he`s doing! The only noise on the outside unit that can be caused ...
|
| air is cool @ blower but not @ vents | 4/12/2007 |
Q: Mr. Livingston I live in a double wide mobile home, when i turn on the intertherm ac the outside ... A: Sounds like a duct problem somewhere. I presume you have an attic in the MHome containing the supply ...
|
| Schematic - Fan Relay for Electric Furnace | 4/11/2007 |
Q: I have an adobe attachment of a scan of the schematic for my electric furnace. I can't find where in ... A: Let`s see if this helps.There are 2 kinds of relays, but in the same case. They are about 1" x 2". ...
|
| Afue ratings | 4/7/2007 |
Q: I have two Janitrol (Goodman) natural gas forced air furnaces in my house that are roughly 17 years ... A: I don`t have access to that AFUE rating. What`s wrong with the old furnaces?? 17 years is not old ...
|
| coil leak | 4/7/2007 |
Q: I want to know the guidelines on checking a coil leak. My repaireman said i could have a coil leak. ... A: YES. He`s right. In my working days I felt like I was working for Texaco I pumped so much ...
|
| Carrier aux heat lock out | 4/6/2007 |
Q: Has anyone encountered problems with lock out on new carrier units? I have two 2 ton carrier units ... A: You are the first I have heard from about this type problem. Not acquainted with that model Carrier ...
|
| Gas Pack Blower Reverses from Ait to Heat | 4/6/2007 |
Q: Howard, I have a 6 Ton Gas Pack unit outside the house. A month ago I had to change the blower ... A: I call a blower motor the one that supplies air to the house. Is this the one you changed?? Also, is ...
|
| HVAC Fin Comb | 4/3/2007 |
Q: My fins need combed, is this typically something a home owner can do themselves if they buy a comb? ... A: You need a fin comb that matches the spacing on the coils. Go to a supply house for a/c to get one. ...
|
| Thermostat / Condenser Wire connection | 4/2/2007 |
Q: The wire has been cut from the thermostat to the condenser in the exterior brick wall cavity... We ... A: 24 volts won`t cause a fire, no problem. The easiest way, unfortunately, is to knock out a brick or ...
|
| NO BLOWER IN AC MODE | 4/1/2007 |
Q: The heating works fine, but when I set the t-stat to COOL the outside unit comes on and I can hear ... A: The fan(blower, we call it) doesn`t work in auto or on? A blower relay has failed.Now, if you have ...
|
| Thermostat Power | 4/1/2007 |
Q: I just moved into a house that has been vacant for awhile. the compressor won't come on unless i ... A: I would go to the furnace terminals for low voltage wiring to confirm the wire colors. The blue & ...
|
| home a/c | 3/31/2007 |
Q: My home is 9 years old and I have a service contract on the furnace-a/c unit since new. The a/c was ... A: No, there is about a quart of oil in the compressor. Wonder why there was a bit more oil in the ...
|
| upright freezer burning smell | 3/31/2007 |
Q: "My upright freezer that I keep in the garage has a burning smell coming from the back side. ... A: I`m not in the freezer dept., only HVAC but can say you probably have a fan motor that smoked. ...
|
| Will Booster Fan solve my problem | 3/30/2007 |
Q: I recently had about 50' of 8" duct ran from my plenium to my garage I converted to a room. I don't ... A: Too much resistance in 50 ft. If the duct was flexible, is the run pretty straight? Lots of ...
|
| Hvac contactor | 3/29/2007 |
Q: I would like to know can contactor energize to pass 220 power but not be passing 24 volts to the ... A: The reversing valve is controlled by the thermostat with 24 volts. You can have a 110/220 coil on ...
|
| Cental A/C kicking on and off rapidly | 3/29/2007 |
Q: 1994 mobile home with Coleman/Evcon.at end of cooling cycle it will try to turn off,but will kick on ... A: Sounds like a thermostat problem. Mobile homes should have a mechanical switch thermostat. Yours ...
|
| bad smell from air vents | 3/28/2007 |
Q: We turned on our air for the first time about 4 days ago. About day 2 I noticed a bad smell, like ... A: I`ve seen dead snakes in a third floor furnace = electrocuted! You must have a return air grille ...
|
| Sears model 867.816940 AC Condensing Unit has loud buzz, won't run | 3/27/2007 |
Q: Just activated my AC unit for the season. Inside blower runs when moving thermostat down to ... A: AllExperts weree supposed to send my answer to you to test my problem with them. Sorry `bout that. ...
|
| Sears model 867.816940 AC Condensing Unit has loud buzz, won't run | 3/26/2007 |
Q: Just activated my AC unit for the season. Inside blower runs when moving thermostat down to ... A: Yo Jason, I presume neither the compressor AND the fan motor not working from your description. I ...
|
| need help with ac/thermostat | 3/26/2007 |
Q: My ac quit working a few days ago, after a little searching I found a blown fuse (5a) on a small ... A: Probably you had a short in the low voltage control circuit wires & didn`t need another thermostat. ...
|
| discrepancy between upstairs and downstairs temp | 3/26/2007 |
Q: We have a two story house and the first floor gets cool but the second floor stays hot. With the ... A: Heat rises, cold air sinks. The problem will reverse in the Winter. Open the downstairs vents just a ...
|
| HVAC | 3/25/2007 |
Q: We had a new heating and air unit put in around Nov. of last year. The heating works great, but ... A: Need to test the freon. Got a gauge? Maybe had a leak & lost it all & a low pressure switch has it ...
|
| No power to thermostat | 3/25/2007 |
Q: 2 days ago my downstairs thermostat appeared to simply stop working..i have a goodman AC unit and ... A: Sounds like a dead transformer. Test the voltage output on BOTH sides of the transformer with the ...
|
| Heat Pump/Diagnosis/Reccomendation | 3/24/2007 |
Q: Extremely informative (but he's on vacation) so Im writing you. My heat pump failed, and I think Im ... A: Les, You didn`t receive my previous seething reply about AHS ?? My second reply was the "software ...
|
| icing | 3/24/2007 |
Q: i have 3 unit 5TR floor mounted split type aircondition the problem is the compressor was icing ... A: correct diagnosis on your filter. So if the icing is occurring at the compressor there must be a ...
|
| amana gas furnace electical diagram. | 3/22/2007 |
Q: I have an older model that has run well for 15 years. I just moved in and am renovating the house ... A: I a charter member of the transformer smoke club! Here are the standard colors & places. R = ...
|
| HVAC WHISTLE | 3/22/2007 |
Q: When my whole house a/c cycles off, I get a high pitched whistle coming from inside the air handler ... A: Got to be an air leak. Can someone be at the furnace & another at the thermostat? If so, turn "cool" ...
|
| Heat Pump auto reset device? | 3/22/2007 |
Q: I live in a large condominium with water chillers on the roof and air handlers in my unit. They are ... A: Yes, I am sure there are digital or analog timers that will do that. The HVAC commercial equipment ...
|
| looking for circuit board | 3/21/2007 |
Q: I have a forced air with cooling unit. The name on the side is Concord, let me get to the question ... A: I have never heard of that brand. I would check the nameplate for a location & try to contact them. ...
|
| electronic ignition gas furnace | 3/21/2007 |
Q: the hot-surface gas ignitor on my furnace comes on and glows. the burners will light but will not ... A: The most common flaw in these furnaces. The flame sensor needs cleaning. It is a small metal rod ...
|
| no heat | 3/20/2007 |
Q: my questin is,,the fan will run but no fire to the burners...its a relatively new furqnce,,, with ... A: Does the combustion air blower motor run? Does the igniter glow? Need to know if these events are ...
|
| Ruud Heat Pump | 3/20/2007 |
Q: I have 24 volts at the outside unit but the unit only comes on when I push down on the 220 volt ... A: Wire colors can be different on different brands so I would be helpless seeing a circuit board. You ...
|
| HVAC air handler question | 3/20/2007 |
Q: Howard, My compressor on my unit is not turning on. I had a HVAC tech look at my unit and he said ... A: Oh boy, Charlie, too common a problem on evaporator coils. True that only 10 SEER stuff is ...
|
| a/c wont cool down my house | 3/20/2007 |
Q: i have 850 sq foot second story room, w/ a 3ton furnace and a 1.5 coil and ac. temp inside 74, out ... A: Not quite enough information George for a positive diagnosis but I`ll do my best. If all is OK with ...
|
| Gas furnace | 3/19/2007 |
Q: I have a 1996 Gas Rheem furnace sometimes it takes 30 minutes to come on after the thermostat sends ... A: You need to read the voltage between R & W at the circuit board on the furnace to test if the ...
|
| new residential A/C & furnace... | 3/19/2007 |
Q: My mother is looking to replace her A/C and furnace and she has been quoted the following: Rheem, ... A: 3 1/2 ton, 75k btu is OK for 1800 sq.ft. IF, she hasn`t had problems in being comfortable in every ...
|
| outside A/C unit problems | 3/19/2007 |
Q: My husband and I live in a rental house with electric heating/cooling units. The one inside works ... A: You have a common problem having an electric furnace. A heat relay is stuck closed, causing an ...
|
| Ruud Heat Pump | 3/19/2007 |
Q: I have 24 volts at the outside unit but the unit only comes on when I push down on the 220 volt ... A: Yo Steve, You have a control circuit problem diagnosed by what you did. Now, it may be simple, maybe ...
|
| a/c lines to heat pump | 3/19/2007 |
Q: i have started a prject of removing an lp furnace and installing an electric furnacein the process i ... A: You are right about the freon flow. But it`s like "you do what ya gotta do" to install this ...
|
| Gas furnace | 3/18/2007 |
Q: I have a 1996 Gas Rheem furnace sometimes it takes 30 minutes to come on after the thermostat sends ... A: I need to know more about your furnace to try & give you an answer. If it is a high efficiency ...
|
| Honeywell RTH 7000 Thermostat | 3/17/2007 |
Q: I hope you can help me because it's going to be 95 here in AZ today! I have a RTH 7000 Thermostat ... A: Let`s check the wiring in the thermostat first. Electric stuff is hard to return. Usually won`t. Did ...
|
| new HVAC install | 3/17/2007 |
Q: My question is regarding choosing a HVAC system for a house that has no existing system. My main ... A: You amaze me with your knowledge !!! I never get that much info on a question either.There can be a ...
|
| Cross Reference for Wiring a remote Thermostat | 3/14/2007 |
Q: Good Day... I have finaly got around to my office in the barn. I purchased a PTHP Sanyo STW-2 and ... A: Reasonably sure these terminals are the match between the 2 thermostats. I assume the FDC is for the ...
|
| central air system | 3/12/2007 |
Q: central air system gets frozen and does not htrow enough air flow to the inside of the house. what ... A: You have a freon leak OR your air filter needs changing. Two things that cause a cooling system to ...
|
| empire propane room heater | 3/11/2007 |
Q: I e-mailed you about the pilot light going out.I thought the wind was blowing it out but I was ... A: The pilot flame is not hitting the thermocouple when the burners shut off. I would even guess that ...
|
| Furnance won't work | 3/8/2007 |
Q: I have a question about my 4 years old Rheem Criterion II Gas furnance serial no. 49875. It does not ... A: Got some diagnosing to do. Those red LED`s blinking can give you a clue to the problem by counting ...
|
| furnace | 3/5/2007 |
Q: I have gas furnace, the blower motor is making grinding noise. I wonder if i can oil it and how can ... A: Run another test for bearings. Turn off the power, reach in & spin the wheel by hand after shaking ...
|
| Propane leak in my furnace? | 3/2/2007 |
Q: So I believe i have a propane leak in my home furnace. So I turned off the inside gas line and my ... A: The soot problem needs fixing before you fire up the furnace again due to the CO emissions emitted ...
|
| Wireing new thermostat | 3/1/2007 |
Q: white,blue and yellow is extra but now what I did is hooked up the red to R the white to W and the ... A: Standard colors used are: R for red, power, G for green for the fan switch, W for White, heat, Y for ...
|
| Rheem heater | 2/27/2007 |
Q: My rheem gas heater lights but when it comes time for the fan to turn on there is a loud hum and the ... A: Does the motor run when you turn the fan switch on at the thermostat? If so, the motor is bad & need ...
|
| Goodan Furnance doesn't reset | 2/25/2007 |
Q: I have a Goodman (Janitrol) Furnace Model GMP125-4 serial # 9404117191 apx 12 years old Honeywell ... A: Hey Sandi, Your problem description can only lead me to that 25 cent door power switch! But ...
|
| burner limit | 2/25/2007 |
Q: I have a 90% upflow gas furnace approx. 5 yrs. old with a honeywell 406650 control board. The ... A: I suspect the flame sensor is not sensing a flame & shuts off the gas. The sensor is a small metal ...
|
| Why would cause one loud vent? | 2/25/2007 |
Q: I was looking for some help. We have a 3 ton HVAC unit with 5 ducts sending air. Two of them are 8", ... A: Let`s start with "system requirements" A 3 ton furnace produces about 1200 cu.ft./min air at a ...
|
| rudd heater model # UGDD-O6NC-ER | 2/24/2007 |
Q: EVERYTHING SEEMS TO BE WORKING EXCEPT DOESNT SEEM LIKE THE GAS IS GETTING OUT TO WHERE THE IGNITOR ... A: Sounds like there is no gas beyond the gas valve ??? Correct ?? To start, is the gas valve knob in ...
|
| HVAC | 2/22/2007 |
Q: I have a Carrier furnace model 58mxa located in the crawl space of my home. It has a exhaust pipe ... A: I figured my answer would be a problem re leveling the flue pipe from the furnace to the foundation ...
|
| HVAC | 2/21/2007 |
Q: I have a Carrier furnace model 58mxa located in the crawl space of my home. It has a exhaust pipe ... A: Tricky problem there. Flue gas contains water vapor which condenses into water when the gas hits ...
|
| condensation in 6.5 type B gas vent | 2/20/2007 |
Q: How can I eliminate the excessive condensation in this area which is leaking and coming thru the ... A: Sounds like there is a single wall pipe section somewhere in the flue pipe.Maybe on the roof ?? The ...
|
| AC/Heat Pump | 2/19/2007 |
Q: I have a split all electric AC/Heat pump system. The blower is running continuously. I observed the ... A: Sorry about the delay, David. Didn`t get an email notice with your question. When you say "the coils ...
|
| FURNACE MAKES CLICKING NOISE | 2/12/2007 |
Q: My furnace is approximately 3-5 yrs old (from what the seller told me) and it started making a ... A: I`m Howard, picking up your question from the pool. I`m recovering from surgery & don`t have ...
|
| Possible thermostat sensor problem | 1/30/2007 |
Q: Well you helped me with something already...I did take the cover off the thermostat and found that ... A: Only other thing I can think to try is cleaning the flame sensor. It`s the small metal rod sticking ...
|
| Luxaire outside unit frost and icies over | 1/30/2007 |
Q: I have a older Luxaire Model : ECHP-F024AA unit. The outside unit will have frost on the inside and ... A: That HP sounds like a heat pump. the freon needs to be checked & if OK this is a normal occurance ...
|
| I think I have a blower problem | 1/29/2007 |
Q: I did everything, and nothing went wrong, I believe it to be the blower motor, it was very loud. As ... A: The blower motors sometimes are sealed & sometimes not. Look for a small oil hole in the visible end ...
|
| furnace | 1/29/2007 |
Q: I am really trying to narrow this down here. The therm idea seems ok, but the fact that it will work ... A: The exhaust fan runs on 110 volts. The transformer also feeds parts of the circuit board & the ...
|
| HVAC system | 1/28/2007 |
Q: I am having a central air and heat pump system installed. I wanted to know about the run on my ... A: 24 + feet is OK. The lines,at best, should slope downward a bit from the inside coil to the outside ...
|
| furnace | 1/28/2007 |
Q: ------------------------------------------- Ok so I have figured something else out. I can control ... A: Somewhat Kevin. Do you have a digital thermostat? I have found faulty ones with the fan switch on ...
|
| Possible thermostat sensor problem | 1/27/2007 |
Q: I have a gas powered furnace that is approx 13 years old. I have never serviced it in the 6 years I ... A: let`s see where to start testing for the problem. How about at the thermostat.Check the level of the ...
|
| 3 amp fuse, circuit board | 1/27/2007 |
Q: I've been having trouble with my heater ( furnace with air conditioner) It blows out the three amp ... A: You have a low voltage wiring short between a red, white,green,or blue(maybe yellow) wire & common. ...
|
| furnace | 1/27/2007 |
Q: I have an armstrong furn eg8g Gas model I am a new home owner who has been trying to solve alot of ... A: There are no silly questions ! Sure sounds like a bad circuit board. I`m not acquainted with the ...
|
| Heat Pump - Defrost Board/Compressor | 1/26/2007 |
Q: Howard, I have had some problems on & off with my Heat Pump w/ nat. gas furnace. A few days ago, ... A: Hey Stan, lets run a few tests & check out their diagnosis. First off,the defrost board. Have you ...
|
| I think I have a blower problem | 1/26/2007 |
Q: My furnace will try to start and then stop. It does this about 3-5 times before finally kicking on, ... A: I am assuming you have a circuit board controlled furnace. If that is correct it sounds like you ...
|
| new programmable thermostat problems | 1/26/2007 |
Q: I just installed a programmable thermostat. I labeled wires correctly, double-checked my work, ... A: Do you have one problem or two ?? "stayed on all night...house getting colder" sort of tells me the ...
|
| Poor air flow when heating | 1/24/2007 |
Q: My home is 7 yrs old and approx 1900 sq feet, two story. We have an attic mounted Rheem furnace ... A: Oh what a familiar problem!! Builders like to save money & install only one unit when there should ...
|
| Furnace Problem | 1/24/2007 |
Q: We have a furnace in our home that is about 10 years old. There is some piping that drains water ... A: The pipes are to drain condensate water from the cooling system.Don`t think that water problem ...
|
| new Goodman furnace noise | 1/24/2007 |
Q: I recently had a Goodman high efficiency furnace (Model #GMV90703BXA) installed to replace my old ... A: Not good. I would turn off the furnace & turn on the blower only. This is high speed. Still hear the ...
|
| furnace + thermost | 1/23/2007 |
Q: YOU MEAN TO TURN ON THE STAT AND JUMP THE CABLES ON THE STAT RED AND WHITE TO SEE IF THE MOTOR ... A: Pull the cover off the thermostat, remove the subbase then jump the red & white wires. If the ...
|
| furnace + thermost | 1/21/2007 |
Q: I few days ago I made the attent to replace my thermostate for a digital one, it just jappen that I ... A: There was a short between one of those 4 wires & common to blow the fuse. Check the wires carefully ...
|
| Furnace fan won't work on "auto" | 1/20/2007 |
Q: The other day, the house started to get cold, and there was no air coming out of the vents. I went ... A: it keeps my brain active after retiring. You most likely have a faulty heat fan switch.ON at the ...
|
| "Cyclematic" | 1/20/2007 |
Q: Mounted on my cold air return plenum is a small black box labeled with the word "Cyclematic." It is ... A: These questions keep my brain active since retiring. I really liked service work. I sure have no ...
|
| Wiring & Controls | 1/19/2007 |
Q: I need to run my waterfurnace geo unit with a back up generator but how would i be able to eliminate ... A: Going to have to add a switching relay to the electric element to have a "generator" & a "normal" ...
|
| Propane furnace & adding air conditioning | 1/19/2007 |
Q: Howard We just replaced an addition on our home. we have the old propane furnace for the main part ... A: Not worth it,Carol. A blower on a heat only furnace is too small for a/c & the wiring has to be ...
|
| BRYANT FURNACE (HEAT AND AIR) | 1/19/2007 |
Q: THE SMALL FAN DOES NOT STAY ON FOR NO MORE THEN 10 SECONDS AND THE BLOWER COMES ON (THE PILOT IS ON ... A: I am assuming Jay, you have a high efficiency furnace controlled by a circuit board. The sequence of ...
|
| SEER 13 | 1/18/2007 |
Q: I want to get a new heat pump that has a SEER of 13.Is this considered to be very efficient?Thanks! A: Yes, but you can get up to a 23 SEER nowdays!! A 13 SEER is as low a rating there is today. Compared ...
|
| Heating in 2 story | 1/18/2007 |
Q: I have a 2 story built in 77. we put in a new trane system 3 years ago. in the winter we set our ... A: Tough answer since you can`t stop heat from rising. 2 story homes really need 2 units, 1 up, 1 down ...
|
| Bad Contactor? | 1/16/2007 |
Q: This question is in regards to a SmarTemp Model T-1000 swimming pool heatpump. Here is my ... A: Good diagnosis ! The contactor either has burned points or an ant under the points. If the contactor ...
|
| Forced Air Heating | 1/16/2007 |
Q: I live in a double wide manufactured home, and one side of the heater vents have warm air coming out ... A: Are you up to crawling under the home? There is a duct interconnecting the 2 sides that I would ...
|
| Cold air return, etc. | 1/15/2007 |
Q: Two part question. I am making living space in my basement. The finished part is approx. 900 sq ft, ... A: 1.The paper faces inside & is suffice for a barrier. 2. Air diverted to the basement is lost to the ...
|
| Is turning into block of ice normal, or a design flaw ? | 1/15/2007 |
Q: Is outdoor compressor unit turning into block of ice normal, or a design flaw ? My American ... A: Iced over outdoor coils is a NORMAL state for heat pumps. The sensor & defrost control is designed ...
|
| air flow | 1/14/2007 |
Q: I have a brand new home and siting on my couch i feel cold air flowing out of my register. I have 9' ... A: Air doesn`t flow unless there is a pressure differential. For cold air to drop 9 ft. through hot ...
|
| NO Heat or heat start. All else, Fan, cooling works | 1/12/2007 |
Q: We have residential Carrier 376BAW036075AABA @1988 with control board HH84AA009. No heating occurs ... A: I presume your exhaust fan is the combustion air blower motor & that it runs when you call for heat? ...
|
| gas furnace | 1/11/2007 |
Q: I have a gravity direct vent wall furnace in my office and it has a little problem. We lite the ... A: There is a thermocouple that the pilot flame hits to generate a small current to keep the gas valve ...
|
| heating | 1/10/2007 |
Q: Have armstrong furnace not quite 4 years old when you turn up heat can hear burners kick on but go ... A: First I would clean the flame sensor. Ought to be a small steel rod between burner & igniter. Use ...
|
| I need help! | 1/10/2007 |
Q: I have Central Air And Heat. My pilot light on heater will not stay on. I think the controller on ... A: First, make sure the pilot light is striking the thermocouple at least 1/2". If not, strike the ...
|
| New 3 ton a/c suction line sweating | 1/8/2007 |
Q: The suction line is insulated with the proper insulation but it drips on the inside panel the runs ... A: Somehow, somewhere there is a suction line exposed to the air, however small. There is an ...
|
| Rheem furnace still out | 1/8/2007 |
Q: Howard, you are correct about the IDM. Rheem calls it the Induced Draft Motor. I checked the ... A: I would remove the IDM (got it!) (power OFF) & check the blower wheel & tightness on the shaft. ...
|
| condensation | 1/8/2007 |
Q: I have a new Rudd 3 ton a/c central unit my suction line sweats exsessivley cound there be somthing ... A: The suction line should be insulated. Sweating is normal when the temp/humidity is just right. Add ...
|
| Rheem furnace stops after purge | 1/7/2007 |
Q: I have a Rheem gas furnace about 10yrs old. It was running through the start up cycle up to the ... A: First let me say that when you need a flame sensor try lightly cleaning the rod with steel wool or ...
|
| Cold Finished Basement | 1/6/2007 |
Q: I had my basement redone, have gas heat (ducts are in the ceiling, forced hot hair, only one zone. ... A: A rule of physics: Hot air rises. I would install a supply air grille in the ducts on the side of ...
|
| Rudd heat pump: Airflow does not stop | 1/5/2007 |
Q: First, thank you for your time! We have a 5-year-old Rudd electric heat pump, with an intermittent ... A: Sounds like there may be 2 problems going on. One is the fan switch is stuck on. The circuit board ...
|
| RUUD Silhouette Nat. Gas Furnace Problem | 1/4/2007 |
Q: I am in central Alabama and I have a RUUD Silhouette Mod. # UGDG 07EAUER Furnace w/ natural gas ... A: Let`s start at the thermostat for a simple test. Turn the fan switch to on. Does the fan run? If so ...
|
| Reventing chimney | 1/2/2007 |
Q: Howard, I want to replace our 17yr.old 70% gas furnace w/ a 94%+. I've had 2 guys say I need to ... A: There are a lot of rigid rules about flue piping.But I`ll give you my opinion based on my ...
|
| Noma Programable themostat 52-2570-6 | 1/2/2007 |
Q: I recently tried to replace a standard Honeywell thermostat connected to a Lennox furnace with the ... A: Something fishy here. The thermostat is just a on - off switch.The instructions with a new ...
|
| hitachi minisplit | 1/1/2007 |
Q: i have a hitachi 9000 heatpump the ac works great the tstat in heat mode gets it to hot and then it ... A: Need to check your thermostat for a "heat anticipator".That is a manually adjusted small lever on a ...
|
| heating problem unit model 383kay036055 | 12/31/2006 |
Q: I have problem with the heating, I call HVAC service technician and he diagnosed and he said so ... A: Little bit high on the circuit board price, Salvador. I assume the board has been changed already? ...
|
| condensor fan motor | 12/30/2006 |
Q: I need a new fan motor. But I cannot find one exactly like the one I have.I found several very ... A: NO,NO. Use the 1075 rpm & change the run capacitor. How about direction of rotation?? Amperage ...
|
| rheem gas furnace | 12/30/2006 |
Q: I have a Rheem RGDG furnace about ten years old the furnace works fine goes through all startup and ... A: I am not acquainted with that model furnace.One answer for both kinds can be a stuck fan relay. The ...
|
| variable speed blowers | 12/29/2006 |
Q: I have 2 York 90+ furnaces with variable speed blowers.After the furnaces are running for a while ... A: Several options: One is to reduce the max speed of the blower by resettings the blower speed ...
|
| heat seems to work but no air circulation | 12/29/2006 |
Q: I have a heat pump that seems to be working (outside fan is running, coils into the house are hot, ... A: Let`s see whether it`s a control circuit problem or a power supply one. Quick test on the blower ...
|
| Heating | 12/28/2006 |
Q: Hey, It's winter here in Toronto. It's really cold in the solarium (solarium is in the apartment). I ... A: I hate to give you my quick answer but that is go buy an electric heater with a good fan as part of ...
|
| Fan Motor cuts off burner when energized | 12/28/2006 |
Q: The Luxaire Hi-Efficency gas furnace I have in my shop (2 months old) that I installed myself was ... A: I gather your furnace is controlled by a circuit board? For all my experience I cannot connect any ...
|
| Clicking noise when combustion air motor running. | 12/27/2006 |
Q: The noise definitely isn't related to the negative pressure switch or the blower fan part of the ... A: Well, when a tech has that kind of weird problem you get a new combustion air blower motor. But, ...
|
| Hot upstairs cold downstairs | 12/27/2006 |
Q: I got a new Trane split system installed on 11/24. House is 1718 sf, two story. I got a 5 ton split ... A: I assume the furnace blower is downstairs. You can`t beat the laws of physics that heat rises! Does ...
|
| Rudd Furnace Troubleshooting | 12/27/2006 |
Q: What should I do on a Limit Switch Open in my Furnace. My model is (UGPH-10NAMER) and it's a Rudd. ... A: There are probably 3 or 4 limit switches on your furnace hiding here & there around the burners & ...
|
| Coleman furnace | 12/26/2006 |
Q: I have a Coleman furnace model # 7956-856 and I am having problems with it. When I turn the ... A: Lets start checking the pilot flame & thermocouple. Is the thermocouple line to the gas valve snug ...
|
| Flame Sensor | 12/26/2006 |
Q: I have a Frigidaire packaged unit (3.5 ton). I have had to have three flame sensors replace. ... A: Not a good situation for a new furnace. I imagine your flame sensor is a small steel rod? Usually ...
|
| comfortmaker furnace | 12/26/2006 |
Q: My electric ignitor isn't working, probably has a crack. How do I remove it and replace it? I have ... A: You probably have the black, flat curved kind. This kind is way too sensitive & probably cracks from ...
|
| Rheem criterion furnace - no heat... pls help | 12/25/2006 |
Q: as it's blank (it's a honeywell t8601D chronotherm... I hired a tech to come out, he tested the ... A: The circuit boards are tied to the furnace brand. I would shop among the local dealers for the best ...
|
| Rheem criterion furnace - no heat... pls help | 12/25/2006 |
Q: as it's blank (it's a honeywell t8601D chronotherm... I hired a tech to come out, he tested the ... A: Just finished answering a question about circuit board problems.That final answer was, we techs hate ...
|
| Furnace flame sensor | 12/25/2006 |
Q: I have a Goodman GMP400-1. It will only intermittently start the burner. I disassembled it and got ... A: Good question with excellent information I usually don`t get. Have to do too much guessing. But the ...
|
| Furnace Humdifier | 12/24/2006 |
Q: It was very helpful. My follow-up question is a general one. Do furnaces typically have (for the ... A: No safety cutoff provided for continuous running other that the thermostat. The stop & go cycle you ...
|
| lennox heat pump icing up | 12/24/2006 |
Q: We live in Wa state, and our heat pump just became a block of ice. The fan can't turn because the ... A: That ice formation is a natural state for heat pumps. It occurs when the temperature & humidity are ...
|
| Thermocoupler | 12/24/2006 |
Q: How do I replace my thermocoupler in my furnace? It says to take the nut off and It won't come off. A: The nut referred to is screwed into the gas valve. If you can unscrew it, then the other end needs ...
|
| Furnace Humdifier | 12/23/2006 |
Q: I'm having a problem with my furnace when the outside temp drops down around 20 deg. or below. The ... A: You have proven the supply air to the house was reduced by the humidifier air. The ONLY control you ...
|
| heating problem | 12/23/2006 |
Q: i replace the thermostat and the heat come on but it don't blow out it come on for 2 minutes then ... A: Interesting that you don`t use capitals. A couple of my friends do that.As is usual there may be ...
|
| Clicking noise when combustion air motor running. | 12/22/2006 |
Q: I've done some more looking and testing and still haven't found anything but your suggestion to just ... A: OK, let`s dig a little deeper! Since the noise disappears when you pull the motor away from the ...
|
| trouble heat pump | 12/21/2006 |
Q: my goodman heat pump model cplt30-1 not working .when i test the contactor i have the 220v put no ... A: Control circuit problem. Heat pump control circuits can be complex so can only suggest a few things ...
|
| Distance from Air Handler to Condenser? | 12/21/2006 |
Q: Howard, Do AC systems lose efficiency of the condenser is too far away from the air handler? ... A: Hey Stephen, Yes, yes. Technically that 30 + foot elevation & 100 foot length of liquid freon is ...
|
| nordyne gas furnace | 12/20/2006 |
Q: my gas furnace is giving me fits the red light is blinking twice .if i blow on the little hose on ... A: that blinking is a signal some thing is going wrong. Check your manual or the sticker maybe on the ...
|
| no Power to Thermostat | 12/19/2006 |
Q: Came home today and there was no display on my Totaline p474-0100 digital thermostat. Went to ... A: Some of the digitals need batteries for the display. Would imagine you would have checked this out. ...
|
| Janitrol furnace | 12/19/2006 |
Q: lost pressure in the hose between pressure switch and venting fan. What can I do? A: I presume the combustion air motor is running but will not close the air pressure switch ? If that ...
|
| RUUD propane furnaces | 12/18/2006 |
Q: 10% of the time my furnace comes on with a bang. This has been going on since it was installed 17 ... A: Delayed ignition is the cause. Typically that is caused by the "flame runner" that carries the flame ...
|
| Clicking noise when combustion air motor running. | 12/18/2006 |
Q: I have a Rudd Deluxe 90+ furnace that is 18 years old. Starting recently when the combustion air ... A: Those motors are pretty darned expensive too! Did you notice ANY wobble in the blower wheel when you ...
|
| Noisy dampers in heating registers | 12/17/2006 |
Q: A new home in CA has gas-fired forced hot air heating. The system is not balanced, so we are closing ... A: A balanced airflow means that the ducts are properly sized & properly installed for the spaces they ...
|
| electric furnace trouble | 12/17/2006 |
Q: We have a Coleman furnace ,about 5 yrs old .Four weeks ago , the Blower motor burned up .So I went ... A: A good question & I think the best way to try to help is ask you a series of questions since the ...
|
| Fan problems old Holly Furnance-GE Air | 12/16/2006 |
Q: Lately when it gets cold, below 40F outside, the fan/electronics have been flaky. For a while if I ... A: Please don`t run furnace without the blower. I have seen overheat switches malfunction & almost ...
|
| william wall furnance not working properly | 12/16/2006 |
Q: my wall furnace not working properly. i bought new simple mechanically operation wall thermostat and ... A: Well lets see. There are 2 kinds of wall furnaces. A transformer powered one with 24 volt control or ...
|
| Thermostat - Mobile home | 12/15/2006 |
Q: I live in a mobile home that I have done a lot of upgrades and renovations to. I would like to ... A: Yes. Go to Home Depot or Lowes & get a programmable Honeywell.The digital ones nowdays handle gas or ...
|
| rheem criterion ll blower | 12/15/2006 |
Q: the question i have, when i turn the heater on, and after the top fan comes on, then the ignitor ... A: Several things can be the problem: 1.Reach in and spin the blower wheel to test for bad bearings ...
|
| White Powder buildup on Heating unit & blows through vents | 12/14/2006 |
Q: This is actually the second winter I spent in my house (moved in January this year) so this is not ... A: The products of combustion of natural gas are primarily water, carbon monoxide, non combustibles. To ...
|
| White Powder buildup on Heating unit & blows through vents | 12/13/2006 |
Q: The powder was found inside and outside the furnace, and no, the powder has not shown up on the air ... A: I noticed that the powder problem only happened when you turned on the heat for the first time. Also ...
|
| White Powder buildup on Heating unit & blows through vents | 12/12/2006 |
Q: I have a gas pack heating/air unit. When I switched from air to heat in November, a white powdery ... A: I don`t think I have ever encountered this problem before but give me more information & I`ll give ...
|
| Furnace maintanance | 12/11/2006 |
Q: Howard, I recently bought a house and became a proud owner :-).. And then started problems..:-( ... A: Good question, Sree. Lack of simple maintenance causes a lot of problems. You should see the rent ...
|
| W1,W2 WIRNG ON TRANE BWH742P100A1 | 12/11/2006 |
Q: TRANE BWH 742 HANDLER ,HW CT3611 THERMOSTAT,PAYNE PH10 HEAT PUMP. HAD TRANE HEAT PUMP W/THIS SYSTEM ... A: Sounds like some techs that installed the Trane were lost & left you without defrost heat.It can be ...
|