Heating, Air Conditioning, Fridge, HVAC/Questions Answered by Expert Howard Livingston

SubjectDate Asked
electric central heat3/6/2011
  Q: my central heat does not work on auto, the ac does but not the heater, it has to stay on constant to ...
  A: The auto & heat position is a function of only the thermostat. I would imagine you have a digital ...
Ducane Heating Problem3/4/2011
  Q: I have a Ducane MPGA100B4B gas furnace. The furnace only runs for about a minute then shut off. It ...
  A: Gremlins Dan, I'm still stuck on identifying the code flashes & voltage to the gas valve.Rig up a 24 ...
Carrier Model 58GFA/DFA2/26/2011
  Q: Howard- We've been having an issue with our furnace not keeping the set temp on the thermostat. It ...
  A: Helo Nick, Those intermittent problems are difficult to solve. Changing the power switch was just a ...
Heat Pumps were installed on dirt2/22/2011
  Q: I recently purchased a 4 year old home and had a home inspection. I contacted a HVAC company to set ...
  A: There are drain holes in the bottom of the outside units but I'll bet they can't drain on the ...
Rheem Furnace Burner Problem?2/22/2011
  Q: Expert, I have a Rheem Low Boy furnace (model# AC-080A). When the furnace tries to ignite, 10% of ...
  A: Main thing that kills a gas furnace is a hole in the heat exchanger. How much rust is there laying ...
Why does the heat stop and turn on all of a sudden?2/20/2011
  Q: The Inducer Motor turns on, but all of a sudden it doesn't go on to the next phase, it doesn't turn ...
  A: The next event after the induced draft motor is the air pressure switch closes. Thats the round ...
outside electrical issue2/8/2011
  Q: ruud UPNE- 036JBZ 2 years old (outside unit) Ruud Acheiver air handler 1 year old inside unit... ...
  A: I presume this is a heat pump ?? The voltage at the contactor supposed to 240v. But if it runs ...
AC Defrost / Aux Defrost1/25/2011
  Q: I recently had a York dual fuel system installed (YHJF48 heat pump, YP9C furnace running propane). ...
  A: Think you have an idea that won't work. The defrost cycle is a reversal of the heat of the ...
pam342kooa11/22/2011
  Q: Outside breaker tripped, reset, fan and aux heater strip came on for two minutes or so and the ...
  A: The sign of a dead short in the unit Some where. Does this breaker that tripped control the inside ...
burning smell from heater vents1/20/2011
  Q: Since November 2010 their has been a burning smell in the bathroom downstairs. Very strong. Have had ...
  A: Bet you have a keen sense of smell Alice. Mine is really dull. And that causes a problem tracking ...
Vexar Electric Heater (furnace)1/19/2011
  Q: My Vexar heating unit (mobile home) continously clicks during operation. I am pretty sure that it is ...
  A: Best thing to click in an electric furnace is the sequencers. They operate the switch by a 24v ...
UNIT NOT HEATING WELL1/14/2011
  Q: I live in Florida, and have a heat pump system. It's been blowing hot/cold air intermittently, and ...
  A: Ho Roberta, First off the freon needs testing in the cooling mode. Soumds like that has been done. ...
HVAC Problem1/13/2011
  Q: I have a comfortmaker furnace (NTG9125FKA3) that is about 12 yrs old. The thermostat is a maple ...
  A: The burners should fire after the igniter. Gas valve not opening. If both gas valves are open, need ...
Furnance Rumble & Cycling on/off before reaching temp1/11/2011
  Q: We have a Coleman/Evcon HVAC (DGRT075AUA) in our 1993 manufactured home (propane furnace - electric ...
  A: The prpane conversion kit includes something(different shapes) that "plugs" off the gas valve ...
Furnance Rumble & Cycling on/off before reaching temp1/10/2011
  Q: We have a Coleman/Evcon HVAC (DGRT075AUA) in our 1993 manufactured home (propane furnace - electric ...
  A: The propane pressure is set by the regulator on the tank. It is 12" water. The gas valve has a kit ...
Gas Smell1/9/2011
  Q: I have a duel fuel all in one furnace that is outside. It is only 2 1/2 yrs old. When the furnace ...
  A: Not acquainted with all those types of furnaces but I can take a try at the problem. And that would ...
air handler does not cut off after reaching temp1/7/2011
  Q: Livingston my Air handler runs after the thermostat reaches the set temp. I have replace the ...
  A: That blower is controlled by a relay on the circuit board. Its sticking. Try tapping on the little ...
220v generator1/2/2011
  Q: how can i use a 220v generator to check the hvac system on properties that have no power supply? how ...
  A: Connect the 2 hot leads to the two terminals at the contactor in the outside unit. Be sure to ...
inside fan not working properly12/31/2010
  Q: i have an all in one rheem outside ac/heat(LP) unit with honeywell electrical components ...
  A: The heat fan control is completely separate from the cool fan control circuit. Your problem is with ...
Goodman GMP 100-412/30/2010
  Q: The ignitor glows,but the burners don't light up. What do I need to do?
  A: Make sure the gas valve is turned on. Also the main gas valve to the furnace is open. Measure the ...
bryant fa4anf048 fan running 24/712/30/2010
  Q: have bryant fa4anf048 heat pump- fan runs 24/7 and strip heat is also running- unit will not turn ...
  A: Sounds like you have a stuck relay on the heat strip. Access the heat strips & each element has a ...
cooling booster for refrigerator12/29/2010
  Q: I have an outdoor snack van which has a glass display fridge at the front facing outward. Problem i ...
  A: Now thats an interesting question, Barry. Lets see, you could add some styofoam slabe glued to the ...
Propane furnace will not light, pilot goes out.12/28/2010
  Q: I have a propane furnace that after it tries to start a heat cycle, the pilot goes out. The pilot ...
  A: There is a pilot adjustment on the gas valve. It is hiding under a little cap. Need a small ...
insulation12/28/2010
  Q: We bought an older home 8 years ago that is all electric, so there's no furnace in the basement. ...
  A: You could sure benefit from the heat from the basement stove by removing SOME of the insulation. I ...
Baseboard registers12/25/2010
  Q: The baseboard heat registers in my home (triangular type) are 24" wide and 4.5" high, but the floor ...
  A: My lowest ratings is always the same - clarity. We speak a different language in the a/c business & ...
Youk gas furnace 17 years old12/24/2010
  Q: The furnace thinks there is an electrical problem with the supply electricity. This is at the ...
  A: Reverse the black wire(hot) & the white wire (ground) & retry. These circuit boards need the correct ...
No heat12/22/2010
  Q: I have a Lennox 80MGF heater & no heat. I cannot find the ignitor. Do you know how i can get to it ? ...
  A: The draft fan runs first on a call for heat. The flashing LED is a code for what the problem may be. ...
Lennox inducer motor bracket12/22/2010
  Q: I have a Lennox G16q3-75-5 furnace, and two of the thin, metal pieces - brackets, I assume - that ...
  A: Those brackets are for a larger motor, like aa 1/3rd hp blower motor. Won't work for the draft ...
Heil Quaker Heater12/17/2010
  Q: I have an old heil quaker heater that I have had for years. I let it set for about a year and the ...
  A: Some easy jobs are not too easy. Not to good to not have a pilot flame & the main burner is spewing ...
How to make an old furnace fan come on intermittently12/16/2010
  Q: We have recently installed a wood stove in our trailer and would like to make the fan on our old oil ...
  A: minus 40 deg I'd just rollover & die !!! OK, follow this: Get a double throw switch with center ...
Heil Quaker Heater12/16/2010
  Q: I have an old heil quaker heater that I have had for years. I let it set for about a year and the ...
  A: No problem Chris. Need to remove the pilot line & take off the pilot orifice tip & clean out the ...
Furnace12/15/2010
  Q: We have a Carrier furnace which is 8 years old, and we do have a thermostat. Suddenly a couple of ...
  A: May have a faulty thermostat if it is digital. Access the wires behind the tstat & jump across the ...
aux heat won't drop out properly12/15/2010
  Q: I have a heat pump and when it is cold the aux heat kicks on and brings the temp up to set point, ...
  A: That ought to be caused by a control circuit. Since the aux heat is controlled by an outside circuit ...
Janitrol GMP 100-3 Wont ignite12/14/2010
  Q: Service tech inspected and said needed new pressure switch. Obtained and installed and the vent ...
  A: After the pressure swich closes the ignitor will glow(or pilot flame will light) Jump across the ...
Carrier Weathermaker 920012/13/2010
  Q: I have a Carrier Weathermaker 9200 in the past couple of winters I get a code 31, this is an ...
  A: Have you tested the hose or tube between the draft motor & presure switch ?? Dirt can foul up the ...
Thermal zone furnace12/13/2010
  Q: I have a thermal zone furnace model number GU120M20C-S. I keep getting a code that says the pressure ...
  A: The codes are usually good on the problem.So I gather the ignitor never lights up ? Thats next ...
Old Trane heat pump (about 20 years?)12/11/2010
  Q: I have an old Trane (Weathertron?) heatpump - maybe about 20 years old - not sure - not the first ...
  A: 1. Need to test the heat elements. The relays that turn them on can be faulty. R to W can be first ...
vents12/11/2010
  Q: I have a 5 ton electric heat pump.I am only heating the back part of my home/about 600 sq.ft.could I ...
  A: A 5 ton system produces about 2000 cfm. To keep the velocity under control so it won't whistle you ...
hard wiring frigidaire electric furnace12/10/2010
  Q: Just bought a frigidaire electric furnace trying to hard wire but can not find anything on web to do ...
  A: Must have 4 heat elements with 2 60 a breaker. I would think just connecting 2 elements(36k btu's) ...
noise from residential gas forced air furnace12/7/2010
  Q: Recently,a fire at the home next door damaged the wall of my home on which the thermostat is ...
  A: That off/.on switch seems to have been a "Summer" switch that would circulate air. The buzz could be ...
Burner randomly does not light.12/6/2010
  Q: I have a Comfortmaker Enviroplus 90 furnace. Every so often the ignitor lights the pilot but the gas ...
  A: Not sure what your furnace has for proof that the pilot is lit but that would be the problem. If it ...
american standard gas furnace12/5/2010
  Q: Howard I have an American Standard CDB060A-D attic mounted downflow heating unit. New in 2003. The ...
  A: So if all the tests points to the circuit board thats nextto replace unfortuneately. Takes a ...
american standard gas furnace12/4/2010
  Q: Howard I have an American Standard CDB060A-D attic mounted downflow heating unit. New in 2003. The ...
  A: I would remove the hose or tube between the draft motor & pressure switch & check for crud. Check ...
blower will not turn off11/20/2010
  Q: I have a Coleman heating unit model #EB12B and the blower will not turn off. When I turn the power ...
  A: Turn the ohm meter to its highest setting. Then disconnect all the wires (incl caopacitor) at their ...
blower will not turn off11/20/2010
  Q: I have a Coleman heating unit model #EB12B and the blower will not turn off. When I turn the power ...
  A: Could be a short in the motor winding since the motor is running slower than the heat low speed. ...
20kw strip heaters11/20/2010
  Q: I have a Bryant heat pump system. I have observed the output temperature swinging abruptly when the ...
  A: So you are wanting to reduce the heat output when defrosting? You can cut out 1 element at a time & ...
american standard heater follow up question11/19/2010
  Q: i have an 18yr old American Standard Freedom 78 heater in my attic. this season it's not getting hot ...
  A: Takes a computer to test those boards Bob. You just have to thoroughly test everything to know it ...
american standard heater question11/19/2010
  Q: i have an 18yr old American Standard Freedom 78 heater in my attic. this season it's not getting hot ...
  A: $139 !! Never. Thats about a $10 part. If the flame sensor is a metal rod with a single wire to it, ...
dripping sound in wall11/19/2010
  Q: I own a bryant model 340MAV gas furnace that is 14 years old. It is located in the basement of a ...
  A: Oh memories of basic training ! I did it in '44 in Amarillo, TX in the Summer. 30 mile hikes witha ...
Uneven Temperature11/19/2010
  Q: I have a 4 bedroom, 2 bath 2000 sq. ft. home. All rooms pretty much heat & cool the same (central ...
  A: Messed up ducts, huh?? Best way to start is adjusting the supply air grilles. Begin closing them ...
HEATING11/18/2010
  Q: I live in a 3 story home with a basement that i finished. I want to know if i can add a damper in ...
  A: You can always tap onto a supply plenum & "steal" air for another run. That just robs air for the ...
Air handler11/17/2010
  Q: I have a York 3 1/2 ton heat pump in which the 15kw auxiliary heat does not work properly. All ...
  A: You have encountered the trouble with new heat pump thermostats installed on older heat pumps. Saw ...
definition11/17/2010
  Q: What is exactly meant by "free air" return ANSWER: Hi William, Don't think I really know what that ...
  A: Ah ha ! A draft hood hangs over the exhaust of the heat exchanger on a gas furnace. It guides the ...
Air handler11/17/2010
  Q: I have a York 3 1/2 ton heat pump in which the 15kw auxiliary heat does not work properly. All ...
  A: Heat pumps btu output generally need additional heat at about 32 deg. Its possibe yours may have 2 ...
Air handler11/16/2010
  Q: I have a York 3 1/2 ton heat pump in which the 15kw auxiliary heat does not work properly. All ...
  A: I'm speculating Jack that the 2 elements are not connected to the power supply, or maybe even to the ...
definition11/16/2010
  Q: What is exactly meant by "free air" return
  A: Don't think I really know what that means either ! Only context I can think it being used is in ...
furnace not working11/15/2010
  Q: I came across an answer you provided for the exact same furnace (4yr old Frigidare) back in 2008. ...
  A: So you have a faulty air pressure switch. Remove the hose or tube from the motor & switch & make ...
heater may or may not lite11/15/2010
  Q: I have an older unit it is an Acroaire Model#GUI075A012IN. The thermostat seems to work fine, and ...
  A: I would say the combustion air motor is not running full rpm , getting hot & turning off, stopping ...
york diamond 8011/14/2010
  Q: .i have a york diamond 80 furnace, which is over 22 years old. the repair guy said the circuit board ...
  A: Some of those boards can cost well over a hundred bucks, some far less. If you can buy one from the ...
SP80 Furnace won't start circ fan (AC Does)11/13/2010
  Q: This is long, but I hope in a helpful way. Generic “SP80 High Efficiency” gas furnace sold under ...
  A: Gee whiz, Steve, I NEVER get that much info !! I have never seen a wireless thermostat before !! ...
Programmable Thermostat11/13/2010
  Q: Purchased the RTH111 programmable thermostat. Is this compatable with electric baseboard. If so what ...
  A: I'm not acquainted with that thermostat. But electric heater operate off 240 volts ya know. So if ...
propane heater during power failure11/9/2010
  Q: I have an all electric house-but I do have a propane wall heater that is started with an electric ...
  A: So I presume you have 120 volts to the wall furnace ?? The gas valve would have to have a setting ...
furnace wont stay lit11/8/2010
  Q: model#ncc100bhal serial #L931475038 sears 80 persent ng gas furnace the spark ingnighter lights the ...
  A: A flame sensor is acting up. Is there a small metal rod sticking in the flame ?? Or it could be the ...
furnace11/7/2010
  Q: when i turn my heat on with my gas furnace it may heat for a few minutes or not at all before it ...
  A: Yo George, Sounds like a dirty flame sensor. Do you have a small metal rod in the flame of a burner ...
Furnace won't stay on11/7/2010
  Q: I recently had a furnace installed. It worked fine for a while, but now it seems to not want to ...
  A: If input is 88k your output is around 75k. NOT NEAR ENOUGH for 2700 sq ft. The furnace of a 88k btu ...
Furnace won't stay on11/6/2010
  Q: I recently had a furnace installed. It worked fine for a while, but now it seems to not want to ...
  A: Wow Rachel, you sound desparate !! Need to get this thing going. One thing missing is it gas or ...
Air Handler and Thermostat11/6/2010
  Q: I have a heat pump and a thermostat with 7 wires. I made the mistake of trying to change it to a ...
  A: Heat pump tstats have changed in the last few years. They have combined several terminals to one. ...
t-stat hookup11/4/2010
  Q: I have a forced air natural gas furnace and central air controlled with a digital t-stat. I am ...
  A: How are you controlling water temperature from the boiler if the pump runs constantly ? Also where ...
Furnace Issue10/30/2010
  Q: I have a Armstrong SX90 furnace that won't fire up. The ignitor will not start to glow. Have ...
  A: Need to test the hose between combustion air motor & pressure/vacuum switch as well as the openings ...
heat pump10/30/2010
  Q: my heat pump is not coming on when I ask for heat. I noticed under the wire panel on heat pump at ...
  A: Now thats it Tim !! You.ve got to get 24 volts across the side terminals. You've got a bad wire from ...
HVAC10/29/2010
  Q: I have a 9 year old International Comfort Products Corp. HVAC package unit. Model PH5548AKA4 .I live ...
  A: Need to determine which side of the transformer is opening. A good clue. Generally its the low volt ...
Ruud Deluxe 90 gas furnace not igniting electronic ign10/29/2010
  Q: I have a Ruud Deluxe 90 Plus gas furnace model UGEB-12EE-JS, 125,000 btu, just over 10-11 yrs old. ...
  A: Got to be the pressure switch not closing/opening when the ignitor won't glow. But when it does & no ...
heat pump10/29/2010
  Q: my heat pump is not coming on when I ask for heat. I noticed under the wire panel on heat pump at ...
  A: Hey Tim, thanks for the extra info. I'm still not acquainted with that connection to the unit. But I ...
Unit won't go into cooling mode!10/28/2010
  Q: I have a ruud a/c unit. I had a bad fan motor as well as a bad contactor.How ever I can not get the ...
  A: Making it run OK pushing in the contactor indicares the problem is in the control circuit. Somwtimes ...
rheem criterion2 fan wheel bearings10/23/2010
  Q: i have a rheem criterion2 furnace, model rgph. it is 8 years old. it has started to make a bad ...
  A: The noise can be from a loose setscrew that hold the wheel on the motor shaft. Check that out first. ...
Burners will not ignite10/20/2010
  Q: I have a comfortmaker LP gas pack. I had it installed in the year 2000. The LP tank is full. When ...
  A: I would test the voltage to the gas valve coil 1st.May be a switch holding it off.If no voltage, ...
Armstrong gas furnace10/19/2010
  Q: I have approximate 10 year old Armstrong forced air furnace. Had to have blower motor replaced last ...
  A: Don't have code info. Can say the sequence for heat is: Combustion air motor runs, closes air ...
AC Flow10/19/2010
  Q: I have a brick ranch house with a Rheem AC air handler unit in the attic with AC vents in the ...
  A: Running a bit late answering Mike. Been out of town (OK) & experienced an earthquake while there. ...
furnace blowing only cold air10/8/2010
  Q: I have a nordyne rc 92 upflow condensing furnace. It is only blowing cold air. The yellow flame ...
  A: The gas valve relay is built in the gas valve. Need to remove all the wires on the gas valve & ohm ...
replacing an existing central heating/cooling system10/8/2010
  Q: "I live in Kansas, AC season lasts about 6 months, have a ranch house of 1780 SQFT, average pitch ...
  A: Got any high ceilings ?? If so, I would go for a 4 ton furnace on a 3.5 ton cool system.Lots of ...
coleman heater10/8/2010
  Q: i have a coleman gas heater and all of a sudden the blower just came on and it wont shut off the ...
  A: Must have a short in the 2 wires somewhere. With the ignitor on there was a call for heat, which ...
fan will not cut off/air conditioning10/7/2010
  Q: I have a carrier 28rd036000 gas furnace/electric air unit. In air condition mode the house fan unit ...
  A: Tap on the little black boxes on the circuit board to see if one is stuck.Also, there can be wires ...
Furnace Won't Ignite10/7/2010
  Q: I have a Coleman G9D-UP high efficiency furnace with a hot surface ignitor ignition. The HSI does ...
  A: The only thing not happening is the gas valve not operating. Make sure the gas valve is turned on as ...
amana heating and air systems10/4/2010
  Q: Are there any known problems with these 15 seer ac and heating units (new)? I had one that worked ...
  A: Evaporator coils have become the major problem in a/c equipment.Way too much service work is ...
Split ac unit9/30/2010
  Q: Just found out my home in Fla has an AC problem.The compressor(outside) is running,the fan on top of ...
  A: You have the symptoms of no freon at all. Does the inside blower run when fan switch is ON ?? It ...
ac/heater fan won't go to high rpm9/30/2010
  Q: Can you help me with this problem. I have a/c unit in the garage Carrier model 58gsc065. Fan is ...
  A: You may have bad windings in the motor. I would replace the black hi speed wire on the circuit board ...
Central Air conditioning durability9/26/2010
  Q: just to how for how long A Carrier air conditioning will last, independently that a mechanical ...
  A: 12 to 15 years possible. It can be a function of a really good installation too.That is, it never ...
Wall furnace causes adjoining wall to get extremely hot9/24/2010
  Q: I purchased a home that has LP wall furnaces, Prefection by Schwank,35000 BTU, millivolt type. When ...
  A: I've installed a few of those but cannot imagine what would cause that much heat. You sure the heat ...
Using Nitrogen to do Leak chk9/23/2010
  Q: I have a question about performing a leak check by using nitrogen. My experience primarily has been ...
  A: good questions. I have been in the business since R22 was .69 cents/lb !! Used it to pump up tires, ...
furnace brand and duct configuration9/23/2010
  Q: I have a 1922 819 sq foot brick duplex in Denver Co with r-39 insulation in attic and a full ...
  A: There are computer programs that can calculate heat loads & equipment sizing but after years of ...
wiring of UV disinfection9/22/2010
  Q: I recently installed a Swordfish residential UV air disinfection unit on the cold air return plenum ...
  A: Better way Jeff involves a relay that the coil is 24v. connect the coil across jumper wires to the ...
New furnace sizing9/21/2010
  Q: I am trying to decide how to determine the correct furnace size for my parents 1939 block home. The ...
  A: I'm not a super tech kind of guy, just rely on 30 yrs experience. The super tech use computer ...
HVAC9/21/2010
  Q: I have a residential carrier HVAC (model 38YCC). In NC september have a fresh climate, so I switched ...
  A: You need to do several things to diagnos the problem. Make sure there is 240v powewr to the outside ...
install9/18/2010
  Q: im installing a 2 ton condenser and it was working fine now i found out there is a hole in tha ...
  A: Tell me what you are meaning when you state "return". Is that the suction line ?? Now I'm sure you ...
Upflow Ruud Achiever Super 80 air flow9/15/2010
  Q: I purchased a house in August of 2009, in which a new Ruud Achiever Super 80 upflow was installed ...
  A: All your heat is up in the ceilings Joe ! Yes, houses with cathedral ceilings need more airflow than ...
Air flow on furnace/a/c unit very low9/14/2010
  Q: I have a Rheem Imperial glass lined furnace that is about 20 years old, not for sure. I have ...
  A: Getting better Jane. A plenum is just a box. You have a return air & a supply air. But I'm getting a ...
Air flow on furnace/a/c unit very low9/13/2010
  Q: I have a Rheem Imperial glass lined furnace that is about 20 years old, not for sure. I have ...
  A: I'm sorta confused by your description of your furnace. I assume you have a cooling system on your ...
replacing HVAC9/9/2010
  Q: Hey Howard, u r told to change your oil in the car every 3000 miles right? Does there come a ...
  A: Your question poses an answer that is mainly an opinion, not from experiences. So my opinion from 35 ...
Rheem furnice problem9/7/2010
  Q: I have a Rheem furnice that was working fine for heat.I wanted to have the ability to run the fan ...
  A: It would be dificult to say what the problem is since you never know what can happen when a wrong ...
Coleman AC Unit9/6/2010
  Q: I have a Coleman AC and heating unit. When I run the AC, it makes that thumping sound when it first ...
  A: I presume the sound is coming from the furnace ?? I thats correct, there is nothing moving except ...
Armstrong SX 80 blower won't stop9/4/2010
  Q: Pulled off panels on front of furnace after unit front was sprayed (hose blew on iron filter sys.) ...
  A: Sounds like a relay is stuck. Tap on the black boxes on the circuit board to see if that stops the ...
a/c working intermittently9/3/2010
  Q: I have a 1989 Amana a/c unit Mod # CA7030QKA1 that works intermittently. My furnace is only 5 years ...
  A: Did the green LED keep on flashing ?? Thats the best clue to the problem since the flashing will ...
r-4109/3/2010
  Q: 3 ton 410 system installers set blower on med speed i put on high adjusted charge worked for a week ...
  A: Listen to the sound of the high side line near the TXV. Use a screwdriver touching the line & in ...
a/c working intermittently9/1/2010
  Q: I have a 1989 Amana a/c unit Mod # CA7030QKA1 that works intermittently. My furnace is only 5 years ...
  A: When you manually close the contactor & the fan AND compressor run it is a control circuit problem. ...
DUCT SIZING?8/31/2010
  Q: How do I know what size duct to resize. I have put in a heat pump and evaporator coil to my ...
  A: ALL of the ducts need redoing. The cfm difference requires larger ducts for good distribution. Thats ...
dual run capacitor8/30/2010
  Q: Why would a service technician jumper the "herm" side to the "fan" side of a dual run capacitor. ...
  A: Hang on Jeff, we gotta get this straight ! Good foto but it didn't quite show enough to me. I see ...
dual run capacitor8/30/2010
  Q: Why would a service technician jumper the "herm" side to the "fan" side of a dual run capacitor. ...
  A: I'm not clear on your using the "jumper" word. Did you mean "move"? I think of a jumper as a wire ...
HVAC question8/26/2010
  Q: I had a brand new system installed. Specs are as follows: > Goodman Furnace GMVC950905DX > A/C ...
  A: Your numbers indicate this is a 4 ton unit, right ?? That size ought to draw about 12 amps plus or ...
Supply Outlet Placement8/25/2010
  Q: Howard, I am in the process of building a new home and I disagree with the placement and ...
  A: Big potential trouble Jeff. Put it this way: A a/c system is only as good as the distribution ...
water in flexible duct mobile home8/25/2010
  Q: i live in florida , i have a mobile home with a heat pump last week on pipe broke in one of the ...
  A: Need to remove the top of the unit & inspect the drain pan under the evaporator coil. May be stopped ...
Low Flow A/C8/24/2010
  Q: I have central air conditioning in my home. Upon recently turning it on, I noticed that most of the ...
  A: Duct problems Jeff. The master bedroom is the farthest from the furnace & that duct run is ...
Condenser quits running8/24/2010
  Q: I have a 5 year old ton Luxaire AC. The complete condenser (fan and compressor) quits running after ...
  A: Since both fan & compressor stop the only thing that can do that is either a power loss or the ...
a/c drain8/23/2010
  Q: Originally my attic a/c had no secondary drain. After a few years the primary did get clogged but ...
  A: Isn't the drain pan bigger than the furnace ?? Sure should be.If you have an electric furnace is ...
a/c drain8/22/2010
  Q: Originally my attic a/c had no secondary drain. After a few years the primary did get clogged but ...
  A: The secondary drain difference in height is set by the evaporator coil drain pan. No can change. So ...
Heil Air Handler8/22/2010
  Q: I have a Hiel heat pump system which recently developed a leak in the coils on the air handler, the ...
  A: Once a coil starts leaking it needs replacing. There are so many places a coil can leak another one ...
Water leaking from ducts8/22/2010
  Q: new unit put in 2007 did not change ducts. water leaking from air ducts in almost all rooms. What ...
  A: 2 things joushlyn, overflowing drain pan & the blower is blowing the water down the ducts or ...
AC air distribution8/21/2010
  Q: Howard, I have a Carrier two part central ac system. The living room cools off very nice and the ...
  A: Someone that installed the ducts didn't know how to do it right. That duct at the end of the plenum ...
HELP8/19/2010
  Q: We are replacing the compressor in a Chrysler Air Temp unit model # 140 40GB 011 serial # GM440312 ...
  A: There's one thing you learn early in the a/c business & that is NEVER guess at the tonnage of a ...
Why is it hotter inside my apartment than out?8/19/2010
  Q: I recently moved into a 4th floor apartment, approximately 750 square feet. It's August, so it is ...
  A: Are you on the top floor on the 4th floor ?? If so, the roof is providing the heat. And I suspect ...
Condensation buildup on my indoor air handler8/17/2010
  Q: I had 2 new units (inside & Outside) installed about 5 years ago. I noticed a funky smell coming ...
  A: If you need to you can apply insulation on the outside of the furnace. But every open bit will allow ...
HVAC8/16/2010
  Q: I bought my house 21/2 years ago & seller installed a new gas pack all-in-one unit, which is ...
  A: Wow, Eliabeth that brought tears to my eyes !! What a tradgedy ! You said this is a gas pack outside ...
Air-conditioner not coming on8/14/2010
  Q: We have a Weather King just installed 4 months ago. Two days ago we had the cool going off for 10 ...
  A: Wonder where they put the drain line ?? These things produce a lot of water & maybe tripped the ...
emergency drain8/13/2010
  Q: I had my entire A/C unit changed about 1.5 years ago. I have been having an ongoing problem. Water ...
  A: Do you live in a 2 story house ?? Favorite place for drain line problems. Got to solve the problem ...
Compressor8/12/2010
  Q: My compressor fan has started making a scraping (as opposed to squealing) noise when the fan stops. ...
  A: Spin the blade & watch it for coasting to a stop. Then shake the blade for ANY play of the bearings. ...
Replace Heat Pump8/10/2010
  Q: Your question was Mr. Livingston: I am planning to replace a 22 year old York split system heat ...
  A: A heat pump in Maryland ?? Never heard of such. Every time its 32 or below your heat strips are on ...
Thermostat Not Controlling Heat Pump8/9/2010
  Q: I have a Heil heat pump that is 5 to 10 years old. A couple of weeks ago, it stopped responding to ...
  A: Thats strange. I would say that the contactor is sticking to keep cool on but the fact it could be ...
Water heater inducer motor pressure problem8/8/2010
  Q: I have a GSW direct vent water tank that has been operating flawlessly since installed new 2 yrs ...
  A: Have had questions about pressure switches & folks have found dust or dirt in the vacuum tube or in ...
New Thermostat8/7/2010
  Q: AC worked this morning. Installed a ritetemp 6036 digital according to instructions. Electric ...
  A: If anbody tells you a capacitor can be the cause of lack of cooling kick them in the a-- & get rid ...
New Thermostat8/6/2010
  Q: AC worked this morning. Installed a ritetemp 6036 digital according to instructions. Electric ...
  A: Jumed across Rc & RH ?? Whatcolor was on Y ? Can be either blue or yellow. You can't dead short ...
Goodman A/C purge cycle8/5/2010
  Q: Equipment: Goodman Modle GMP075-3 Gas furnace with HSI Module B18099-13. Sometimes when the t'stat ...
  A: If that was my former answer that was all wrong !! You really need to separate the wires behind the ...
Payne PA-10 unit suddenly stopped8/4/2010
  Q: I am not sure how old the unit is or where my dad bought it from, but he had a used Payne PA-10 unit ...
  A: Good idea, Kristopher, electricity is really dangerous. Not acquainted with that PA-10 unit but ...
Clicking8/1/2010
  Q: Heater or AC unit both acts like it wants to come on then starts clicking. If you turn the ...
  A: Thats a head scratcher, Elizabeth. I would suspect the thermostat IF you have mercury controlled ...
Air Conditioning Unit only cooling half the house7/31/2010
  Q: We have lived in our house 3 years this past June New Built 2 floors 2900 sq ft. If you were looking ...
  A: Duct systems nake or break a good unit. Are there dampners on the ducts at the supply plenum ?? ...
How manyA/C outlets/vents ?7/29/2010
  Q: How many vents/outlets can a 3.5 ton A/C ( 1/4 horsepower blower- 1900 sq. ft)unit support? Is there ...
  A: Wow, 15 drops !! How many rooms will you be cooling ?? How many "spaces "?? You will encounter ...
central air7/28/2010
  Q: why is the discharge line leaving the outside unit cold instead of hot or warm? thanks.
  A: First thing to test is the amount of freon in the system. If it is too low the freon is cooled by ...
Can low voltage damage refrigerator compressor7/27/2010
  Q: My voltage often drops about 10% to around 108 volts. Can this cause damage to the compressor on my ...
  A: Sure won't do it any good trying to start with low voltage.It will get hot trying to start, then the ...
A/C unit not cooling enough?7/25/2010
  Q: Our A/C unit doesn't seem to be cooling enough. We recently had our capacitor replaced and someone ...
  A: I would expect you to say "well, it used to cool, now it doesn't" Correct ?? First thing to ask is ...
Water pooling7/24/2010
  Q: A/C & Natural Gas furnace in basement. At one time there was a humidifier attached to the furnace ...
  A: Sounds like a stopped up drain line from the evaporator coil. Very little water flow can be stopped ...
HVAC - blower control7/24/2010
  Q: I have an older Lennox HVAC system, thermostat is mercury switch type two stage. I want to install ...
  A: The green & red wires in the thermostat control the blower motor. If you take the greeen wire to a 2 ...
Convert my one AC zone home to two zones7/24/2010
  Q: My house is 2800 sq ft (1st and 2nd floors)plus a finished basement for total of 3700 sq ft. The ...
  A: Need to add zone control modules added in the duct system that respond to 2 individual thermostats. ...
AC not cooling during the day7/23/2010
  Q: I have a two story Florida home built in 2001 with the original Bryant, split unit, gas furnace, 4.0 ...
  A: Something wrong. Way too much heat load. That 77 & 80 degree supply should be about 60 +/-. What ...
AC compressor kicking in and out7/22/2010
  Q: I have a 3 ton R22 Goodman compressor and a 3 ton R22 TXV Heil air handler. Brand new. We have 42' ...
  A: That 55 psi is way too low. Should be about 70psi for a 40 deg evaporator coil. The 55 is below ...
AC not cooling during the day7/22/2010
  Q: I have a two story Florida home built in 2001 with the original Bryant, split unit, gas furnace, 4.0 ...
  A: Time for a capacity test. With an accurate thermoneter in hand, run the cooling a 1/2 hr or so & ...
HVAC7/21/2010
  Q: Howard, My girlfriend and I are purchasing our first home and we have a lot of questions, but I'll ...
  A: The usual place an a/c leaks is in the evaporator coil. If the guy that looks at it knows anything ...
Ac not cooling very well7/20/2010
  Q: we recently moved to our new house and turn on the AC when the summer starts. Though the AC runs ...
  A: Sounds like the duct system is not too good. Maybe even the size of the a/c is too small. Should ...
Bryant A/C capacitor re[lacement7/19/2010
  Q: My old capacitor is a cylinder w/3 terminals. The new one is a 2 terminal. I have a yellow, black ...
  A: Well I'm running late & like to help fast when someone is sick. Yellow & black are for the motor. If ...
correct way to read gauges-R227/16/2010
  Q: I have only serviced A/C on my cars.I completed HVAC/Home study/certificate so no hands on ...
  A: Those readings on the unit are test pressures. An evaporator coil works at 40 deg. Look on the R22 ...
Central Air - Air Duct Cleaning Question7/14/2010
  Q: I purchased a home 2 years ago and it has a very good central air system in it approx 5 years old. ...
  A: I never have believed the value of duct cleaning. I have been in a lot of attics where the ducts ...
Split A/C Units.7/11/2010
  Q: I have three split Samsung A/C units. One went bad and I eventually replaced the control circuit ...
  A: Never know if there is a pressure switch on these units Mike. If there is, you can trace the control ...
goodman 4 ton return air7/11/2010
  Q: I have a goodman 4 ton split unit heat pump 16 seer rating. It's a two stage compressor and blower. ...
  A: That is amazing that the installer located the furnace way at the end of the house to make it close ...
Wiring Single Zone Gas Furnace7/10/2010
  Q: Can you tell me if I am right in the wiring of a single zone gas furnace? Come out of the furnace ...
  A: Sounds good Adam, except for "...above the furnace another 4" sq. receives the feed ...& is spliced ...
singer ac blowing hot air7/8/2010
  Q: We live in an apartment complex in a brick building on the 3rd floor. The older singer comfortmaker ...
  A: You are getting all the heat load from the units below you. Can't do anything about that. Plus you ...
Air Stratification with new Carrier Infinity A/C system7/8/2010
  Q: I have an "A" Frame house with three levels. The main part of the house (on this new system) has a ...
  A: Thats a good name, I'm Howard too ! Your just in a big battle with the laws of physics with hot & ...
Blower Fan in attic unit7/7/2010
  Q: Have zoned units in attic and downstairs. When temp in attic goes >90F unit blower fan will not come ...
  A: It appears to be the thermostat.There is a time delay on a call for cool. Usually 4 to 5 min.No ...
Blower fan in attic unit7/5/2010
  Q: Have “identical” zoned units in attic and downstairs. When temp in attic goes >90F unit blower fan ...
  A: Boy, Steve that's a good one ! I'm just going wild to guess that one. Do you have a powered attic ...
compressor runs intermittently7/4/2010
  Q: I have a heat pump, not sure what make or model, that i know is good on freon, since it was just ...
  A: Doesn't it always happen when you really need it ?? If the capacitor fails the comp. won't run. I ...
2 ton goodman package heat pump7/2/2010
  Q: I am looking to purchase a used goodman 2 ton package unit model GPH 1324H to replace an existing ...
  A: How old is the used package ? Is it pretty clean ?? I don't think too much about used a/c ...
Run Capacitor Replacement7/1/2010
  Q: I recently had my Lennox air conditioner serviced. The technician pulled the run capacity from the ...
  A: Get out your shotgun & run the guy off .HE IS A CROOK !!! First, capacitors don't slosh. They are ...
hvac wont shut off6/30/2010
  Q: i have tenants complaining about the ac costing them a fortune because it won't shut off. They say ...
  A: Sounds familiar. I service a lot of rental units & this sounds awful familiar. They NEVER change an ...
Noisy Furnace System6/27/2010
  Q: I live in a small house (1033 square feet) with a noisy 20-year old Ruud furnace/AC system. The ...
  A: This is noisy furnace day for questions !! A 3 ton cooling systen needs a return air(RA) opening of ...
New HVAC- Very loud at vents6/27/2010
  Q: I just had a new HVAC system installed. It is a high efficiency (95%) system with ECM motor. I am ...
  A: Those variable speed motors move a lot of air. They supposed to adjust it for the tonnage & they ...
AC blower6/26/2010
  Q: My AC stopped working yesterday. checked everything. electric company put us on conserve energy so ...
  A: What happens when you turn the fan switch to ON only ?? Cooling can't function without a blower. ...
Multi-Zone or Single / 1 or 2 Stage AC ???6/26/2010
  Q: I am looking at three proposals and two differences stand out - whether a single or two stage AC ...
  A: If the ducts are designed properly every living space will be comfortable regardless of certain ...
Multi-Zone or Single / 1 or 2 Stage AC ???6/25/2010
  Q: I am looking at three proposals and two differences stand out - whether a single or two stage AC ...
  A: Thats almst a TMI,San. Really need a floor plan for an accurate assessment.I would not recommend a 2 ...
Flex Duct Issues6/24/2010
  Q: Howard, Thanks for taking the time to read my question. My home is 7 years old and we have always ...
  A: The 6" lines should not be too long, maybe 6 ft or so. Sure need to correct those juntions with ...
Flex Duct Issues6/23/2010
  Q: Howard, Thanks for taking the time to read my question. My home is 7 years old and we have always ...
  A: you are on the right track. You got a lousy duct job. Starting off, do you have ducts wrapped with ...
new equipment install6/23/2010
  Q: Mr. Livingston, thanks for taking the time to look at my question. I'm building a new house in a ...
  A: well you've pinched a nerve of mine to ask about prices. I'm from the old school where we doubled ...
Blower Fan in attic unit6/19/2010
  Q: Have zoned units in attic and downstairs. When temp in attic goes >90F unit blower fan will not come ...
  A: Would be interestiug to know if the blower will come on when the attic is hot by jumping across the ...
Gas Furnace6/19/2010
  Q: We are putting a gas furnace in a closet. Where does the cold air return go and do you have to use a ...
  A: Need to build a platform 12" high for the furnace. Then the return air grilleS (plural) cut into the ...
ac compressor6/18/2010
  Q: Why the liquid line is not hot and the compressor is sweating? What is going on? ANSWER: Compressor ...
  A: No, the condenser coils can't handle that many more freon. Think that if you have an electric ...
New Furnace/Air Conditioner6/17/2010
  Q: I am replacing my 35 year old furnace and air conditioner. I've had several bids and have narrowed ...
  A: Annie, Don't forget the R410 ! Carrier is good stuff but parts are rather expensive. Glad you went ...
New Furnace/Air Conditioner6/17/2010
  Q: I am replacing my 35 year old furnace and air conditioner. I've had several bids and have narrowed ...
  A: Two brands of a wide variety. One expensive one cheap. Maybe not but the Goodman should be the ...
ac compressor6/16/2010
  Q: Why the liquid line is not hot and the compressor is sweating? What is going on?
  A: Compressor sweat indicates too much freon is coming back from the evaporator coil. Nothing but gas ...
HVAC Service Cost6/16/2010
  Q: We currently have a Carrier air conditioner in our home that is 26 years old. It still operates ...
  A: It takes all kinds & the a/c service techs have them. I'm in Texas & the service fees are about $80 ...
noisy inside unit6/14/2010
  Q: I have a Trane xr-80 that was installed in 2003. It is still working GREAT ... except that it ...
  A: Fan switch on the thermostat runs a high speed fan, the same as for cooling. I would look around ...
Furnace6/14/2010
  Q: I have a two story 3600 sq ft house with two 4-Ton units, one for upstairs and one for downstairs. ...
  A: After rereading your initial question you never say which kind of furnace you have, gas or electric ...
noisy inside unit6/14/2010
  Q: I have a Trane xr-80 that was installed in 2003. It is still working GREAT ... except that it ...
  A: Wel, thats a good one Elmer. So you have pretty well isolated the noise within the furnace case ?? ...
bedroom ceiling vents6/14/2010
  Q: My husband and I bought our home 2 years ago. It's a quad level home with ceiling vents for heat ...
  A: Need to do an inspection to check my diagnosis first. If insulation is needed you need some 1.5" or ...
Furnace6/13/2010
  Q: I have a two story 3600 sq ft house with two 4-Ton units, one for upstairs and one for downstairs. ...
  A: Thats strange since you are suffering from not enough cooling & those guys were going to just add ...
bedroom ceiling vents6/13/2010
  Q: My husband and I bought our home 2 years ago. It's a quad level home with ceiling vents for heat ...
  A: looks like there is none or little insulation around the grilles in the attic. There is a metal box ...
HVAC repair6/12/2010
  Q: When my AC unit has been running for a while during the day, it cuts off about 8pm each night. A ...
  A: I wouldn't deal with this tech. He's way off base I'm pretty sure in his diagnosis. If a capacitor ...
carrier heat & air6/11/2010
  Q: My central heat/air system was not working and when I checked it I found that the run capicitor was ...
  A: Those are strange happenings Robert. The amps increase goes along with the high head but I fail to ...
HRV wiring6/7/2010
  Q: .i am installing a venmar hepa 3000 hrv that is ducted into my furnace ducting. I have it on a timer ...
  A: All I can see Ron is a single poledouble throw relay with a 10 volt coil, normally open. Relay ...
AC vents and airflow6/6/2010
  Q: My home has a finished basement that gets VERY cold when the AC is running.There is one 9 1/2" x ...
  A: Is there an open stair well to the basement ?? Cold air falls & can get into the basement that way. ...
HVAC6/2/2010
  Q: "I have an evaporator leak from my bryant system. to me it appears to be just condensation. the leak ...
  A: Really not acquainted with the drain pans on your model. Too many different kinds. I can say tho ...
Thermostat Install Cause Freeze6/1/2010
  Q: I just installed a Lennox x4146 to replace a Trane Bay 239 on my TWN036C100B1 heat pump unit. I ...
  A: Was the inside blower working OK during the run tests ?? The outside coils frozen over is a puzzle ...
Central ac blowing fuse6/1/2010
  Q: I have changed the compressor fan motor. Unit runs for approx 30-40 mins. Compressor continues to ...
  A: Make sure the fam motor is turning the correct direction. Then check all the power supply terminals ...
AC filter-clarified5/31/2010
  Q: I previously may have asked you a question about our A/C filter. This is a clarification of my ...
  A: If the LR grilles are just flat they don't accept filters. Got to have a flat frame area. So if they ...
Lennox Whisper Heat5/30/2010
  Q: I purchased a 1993 home last year with the G20 furnace. It has the 30W33 igniter module installed ...
  A: You don't have a code manual for the flashes you see? That is a aluable tool for diagnosing the ...
A/C Units5/30/2010
  Q: I had my AC replace with Gibbson AC units last summer. Also the Thermostat with Honeywell. Just ...
  A: Yes it happens on any system, old or new. These leaks can be repaired easily, finding the leak can ...
R22 Air Handling Unit5/28/2010
  Q: Had a Trane 410 inside air handling unit installed about 3 weeks ago. Valve changed to convert to ...
  A: I think your R16 is really R410. Never heard of R16. Anyway, Its not really recommended to have a ...
HVAC Troubleshooting5/28/2010
  Q: I have a 6 year old Goodman Heat Pump that is not cooling the house properly. I checked the high and ...
  A: Appears that you need a couple of pounds of freon. Some systems can lose a lot of capacity with just ...
Replace HVAC or wait? Probable cost?5/13/2010
  Q: My HVAC is a split unit -- 5 ton AC (installed outdoors in 1992) and ~95,000 BTU heater (installed ...
  A: Day & night is a downgraded unit of Carrier. For your minimum useage I would service it at the ...
Replace HVAC or wait? Probable cost?5/13/2010
  Q: My HVAC is a split unit -- 5 ton AC (installed outdoors in 1992) and ~95,000 BTU heater (installed ...
  A: You will have about $3000 equipment cost for 13 SEER stuff. Add Lennox plus Elite add ons & that ...
zoneline 3500 no heat, ac okay5/12/2010
  Q: Got a zoneline 3500 on remote thermostat. I caused the problem, I am sure. Replaced thermostat ...
  A: Usually heat is considered more important than cooling. Therefore the reversing valve is actuated ...
13 Seer cost with installation5/7/2010
  Q: I am getting quotes to have an XB13 HP 13 SEER Single Speed Compressor, HVAC system (heat pump w/AC) ...
  A: I assume the new stuff uses R 410a freon ?? It should be. I was just looking at the prices (mine) ...
secondary heating coils won't shut off5/6/2010
  Q: i have a trane heat pump with an american standard air handler in the attic. this winter the fan ...
  A: Need to test the relays that control each heat element. If they are open with no call for emergency ...
Contactor5/5/2010
  Q: I need some help troubleshooting my TempStar 2000 heat pump. The outside unit stopped working ...
  A: Some more possibilities are the low pressure switch has been tripped since the freon has leaked so ...
fan speed adjustment on heater/ac5/5/2010
  Q: I have two 12 year old Trane heating/ac units in my home. The fan speed on one is much faster and ...
  A: Cool speed could be changed to blue, heat could go to red. Need to watch the cool since the airflow ...
Compressor failed on OLD unit4/26/2010
  Q: The 3 ton unit at my restaurant is about 50 years old or so. The compressor is on the roof and the ...
  A: Was the 8" duct capturing ALL the air from the blower ?? If so that could have restricted the ...
Room Air Conditioner4/26/2010
  Q: We have a 2 story house in the south and our HVAC does really well for the downstairs. However, the ...
  A: Got good attic insulation ?? There is no insulation in interior walls so other rooms not cooled can ...
Trane XL1200 Super Efficiency Weathertron Heat Pump4/25/2010
  Q: I asked this question earlier to Frank A. and got a response (perhaps automated?) that he doesn't ...
  A: the Emergency light being on may indicate that the electical heat elements MAY be on. Not good. Need ...
Service Manual4/24/2010
  Q: Could you help me find a service manual for my Tempstar SP80 Nat gas furnace/AC unit? I need to ...
  A: This is strange since a bad capacitor is usually the cause when the motor turns the wrong direstion. ...
Service Manual4/24/2010
  Q: Could you help me find a service manual for my Tempstar SP80 Nat gas furnace/AC unit? I need to ...
  A: could be the hi speed windings are bad. But first, test the run capacitor with your ohm meter. Then ...
dirt around ceiling vents4/24/2010
  Q: my mom has dirt around most all her ceiling a/c vents.it started in the kitchen area which is ...
  A: Dirt comes from dirt bypassing the air filter plus the evaporator coil being excessively dirty. ...
Combustion Air Venting in to-be finished bsmt4/22/2010
  Q: I'm planning to finish a roughly 400 sqft area of my basement once I close on my house next month - ...
  A: A fresh air intake needs to be 1 sq in./1000 btu boiler. A motorized vent can connect to the heat ...
freon gas container4/21/2010
  Q: Our company in Mongolia is a mining company. There are many heavy duty equipment and we do ...
  A: We just turn the empty ones in for scrap metal. Our usual sizes are generally 30 or 50 #.The valve ...
Furnace error codes4/19/2010
  Q: I have an American Standard series 80 Furnace that has a red error code light that is flashing 4 ...
  A: The temp limit circuits are the little red buttons located near the burners.There may be 2 to 4 of ...
Air handler coil leak 3 years in row4/15/2010
  Q: I completed construction on my home in March 2007. In June 2007 my second floor system stopped ...
  A: Boy.ike I NEVER had that happen before !! I have had a very few get leaks in the coil after about 2 ...
variable speed vs single speed airflow4/10/2010
  Q: We are in the process of replacing our existing 4 ton unit with an Amana 4 ton. We received quotes ...
  A: A variable speed senses air pressure & changes speed according ly. Ih has a larger blower wheel than ...
Blowing Cold Air from vent4/8/2010
  Q: my aircondition unit blows cold air. Reapir people told me that Motor that blows air is bad. He ...
  A: Does the motor still run ?? That motor cost about $60, you need to get another bid. Also, some ...
new air install has never worked4/7/2010
  Q: may of 2005 we had central air added to cool our upstairs in our new cape cod house. it has never ...
  A: Sorry, after the 1st year thats it. Seems that there may have been a freon leak all along that was ...
blower works but no air is comming from vents4/6/2010
  Q: however there was cold air blowing out of the unit itself around the exhaust vent. Is there a ...
  A: Usually there is no valve ned s to be opened from heat to cool. Something is blocking the air. Now ...
rheem RGDA-100A-AR gas furnace4/3/2010
  Q: I recently turned off my furnace via the thermostat control switch to do some duct work. When I ...
  A: Got the diagram. I don't have the regulation codes anymore on venting to see what they say.But I ...
rheem RGDA-100A-AR gas furnace4/2/2010
  Q: I recently turned off my furnace via the thermostat control switch to do some duct work. When I ...
  A: I would ask if the inline fan you installed was blowing the wrong way ?? There are tight rules as ...
Hunter 443603/28/2010
  Q: I have recently installed the Hunter 44360 thermostat, but I have had a problem with it. It will ...
  A: You must have a heat pump. The new thermostats for heat pumps will not work with old heat pumps.I ...
AC motor - windings?3/25/2010
  Q: Just had a routine AC maintenance call. The technician measured amp from one of the motor wires, ...
  A: It is true that the rated amps on a motor can't exceed but by 0.1 amps to overheat the motor which ...
Attic Ventilation3/18/2010
  Q: I live in Santa Barbara, CA in a single-story house with no A/C. My attic space gets hot in the ...
  A: Sorry about the delay Don. Been sick & should have applied for a vacation. One rule in physics ...
HVAC3/17/2010
  Q: I have motor rated @ 16 amps. when I put a clamp meter on it it reads 7.5 to 8.2 without the belt, ...
  A: The motor rating is the max draw it can handle. 16 amps.The work load on the mtor is defined by the ...
gas furnace heater3/16/2010
  Q: We have a Carrier 58PAV gas furnace. It stopped working recently. I used multimeter to test the ...
  A: Is there a screw in fuse in the power box ?? That is standard in certain areas. Also, the power ...
gas furnace no light3/16/2010
  Q: My carrier model number 28rc030010 is not working when i go to turn the heat on. the a/c unit runs ...
  A: On a call for heat a draft motor should run first on a board controlled furnace. Soon after an ...
Rheem Thermostate3/15/2010
  Q: I am replaceing a Rheem #41-20804-15 thermostate with a honeywell RTH7500. The wiring on the Rheem ...
  A: I presume you have a heat pump - right ?? Maybe not? There is a difference ya know. The Rheem ...
Noisy old gas furnace3/15/2010
  Q: I have an "Airco AH-115" gas forced-air furnace, which is probably 30 years old. It makes a loud ...
  A: Time for a little overhaul. With the power off, cut the wires to the blower motor at a concenient ...
hvac3/1/2010
  Q: am am basically a qs now in an mep project.can u please explain to me how the hvac system works in a ...
  A: I''ll try. Here goes: The freon is R 11. A compressor pumps it to a high pressure & turns it into ...
air condition2/28/2010
  Q: My air-con is not blowing cool air..The compressor fan runs for a minute or so before it stops. I ...
  A: There are too many things that can go wrong with this stuff to really know why it quit. I would feel ...
fan not working2/25/2010
  Q: Nothing works, I have replaced the thermostat, still nothing. I have 240 vac to the outside unit, ...
  A: The source of the control circuit is a transformer in the furnace. Turn the fan switch only to ON. ...
goodman phkj036-1f heat strip2/25/2010
  Q: i have a goodmans phkj/phk 036-1f packaged unit, it didnt come with a heat strip i went and bought ...
  A: Sure a lot of wires to those connectors. All you need to power a 5kw element is 240 volts(2 wires) & ...
Cold Air Return2/22/2010
  Q: I have a cole air return built into the steps going from kitchen up to my living room and when the ...
  A: Is this a new problem, or been there awhile ?? Air moves because of a different pressure or weight. ...
Install Fan Timer Control Circuit Board2/21/2010
  Q: I have a couple of questions regarding installing the Fan Timer control circuit board (Model Number: ...
  A: Holy mackeral Jonathon, that wiring is waaaay beyond me ! I can't imagine removing circuits from ...
Heil package unit2/19/2010
  Q: When the heat runs, I am getting a very bad electrical smell out of the vents. The wires all around ...
  A: Me again. Just thinking of the possibilities & thought that a stopped up flue,( even on the roof ...
Led code 6 + 1 flashes HELP ME PLEASE!!!2/19/2010
  Q: I came home from work about an hour ago and my house is freezing. Thermostat is on and set but my ...
  A: The lockout after 4 tries can be about anything in the sequence of events that has to take place ...
Heil package unit2/19/2010
  Q: When the heat runs, I am getting a very bad electrical smell out of the vents. The wires all around ...
  A: back online after a bit of oral surgery. Thanks for asking me. Is the combustion motor running full ...
where is the reset button?2/13/2010
  Q: I have a Bryant compressor model 561CJ030-D and I cannot find the reset button. The furnace/AC will ...
  A: If the furnace won't turn on there is no reset button to punch, maybe. Tell me what knd of furnace ...
no aux heat when in defrost2/12/2010
  Q: I have a heat pump. The indoor unit is Bryant 517EN030 with electric aux heat. I have noticed that ...
  A: That 49 amps is the rating for 2 5 kw heat elements. So they are turning on in defrost cycle. The ...
furnace#ff792/11/2010
  Q: I can't find the electric shutoff switch?? Have been all thought the house?? Is it posible it dosent ...
  A: This is a gas furnace ? A code requirement is to have a switch near the furnace somewhere. The ...
Furnace runs but control goes to lockout2/11/2010
  Q: I have a Johnson controls G779lha-1 control that goes into lockout about every 12 hours. According ...
  A: these darned solid stae stuff is a pain.The ONLY thing contolling the heat is the ignition module. ...
floor furnace2/10/2010
  Q: I have a suburbun floor furnuce #ff79 for one I can't find the electric cutoff switch? Is there a ...
  A: Insure that the pilot flame is impinging on the top 3/4" of the thermocouple. You may have a clogged ...
Weathermaker 9200 Flashing Code Lights2/9/2010
  Q: With the thermostat in the on position, there is no response at the furnace. There is a standard ...
  A: Sory Richard I don't have the codes meaning. Check on the inside of the lower furnace door or on the ...
Strange noise from gas pack2/8/2010
  Q: Recently when our 9 year old Trane gas pack starts it makes a strange buzzing noise. The noise is ...
  A: Is this an auto ignition pack ?? If so, you have a combustion air motor running as soon as a call ...
Combustion or Ventor Motor operation2/8/2010
  Q: I have a York Diamond 80 Ultra (2 stage) furnace. Lately we have notices a slight burning smell from ...
  A: Can't believe the circuit board would not detect no draft motor. The air from that is what operates ...
Carrier Heat Pump Issues2/7/2010
  Q: Howard, I have a Carrier Heat Pump System. It’s about 5 years old and has functioned ok until this ...
  A: You must be Waaaaay out in the country ??? Ther buzzing transformer is emmitting a 60 cycle hum & ...
Trane XE-70 - No heat.2/7/2010
  Q: I have a Trane xe 70. The Heat is not turning on. The igniter will glow but NO gas or blower. I turn ...
  A: The next event after the igniter is the gas valve opening. Need to check the voltage across the gas ...
Carrier Heat Pump Issues2/7/2010
  Q: Howard, I have a Carrier Heat Pump System. It’s about 5 years old and has functioned ok until this ...
  A: what a lot of trouble you have had. First thing, the 5 amp fuse blew from a short in the 24v circuit ...
weak air flow2/6/2010
  Q: I have three vents in my bedroom and the air blowing out seems to be very weak. the temperature is ...
  A: The airflow canbe adjusted by adjusting the supply air grilles, starting near the furnace & working ...
New Honeywell RTH 7600 Thermostat not working2/5/2010
  Q: Having problems getting a new Honeywell RTH 7600 thermostat to work properly. My System: - Nordyne ...
  A: Alex, you have run nto a problem since the new heat pump thermostats don't seem to be compatible ...
ac/heatpump compatibility2/5/2010
  Q: My outside unit was stolen and an outside unit of unknown capacity is available. My assumption is ...
  A: You can have a 6000 bty (1/2 ton) difference with no problem. Nameplates may not indicate whether a ...
Bard Furnace2/2/2010
  Q: I have a Bard electric furnace that came with the house. It is 13 years old. The problem is that ...
  A: Electric furnaces have sequencers that control a heating element & the fan.Also have overheat ...
Circuit Board Replacement2/2/2010
  Q: I have a 13 yr. old Trane XL 1100 combination unit. Recently when the heater would go on, the ...
  A: You can do it easily Michael. Even my son-in-law that is an Indian on thr eservation did it. One ...
iced over heat pump1/31/2010
  Q: We have a heat pump in Maryland in a unit that we just purchased (I am in New York). In January the ...
  A: The iced over senser is not working. Needs a repair job. Meanwhile you have an emergency switch on ...
Convert 90% furnace to 80%1/31/2010
  Q: can you convert a 90% furnace to an 80%. I can not run pvc pipe for the vent and need to use the ...
  A: Don't have a clue what physically makes the difference between the 2 efficiencies. But a flue is a ...
Rheem Criterion II furnace will not start1/30/2010
  Q: I have a Rheem Criterion II furnace that was bought in 2004 with a Honeywell thermostat that we ...
  A: Just reviewedthe question & answer for a similar problem. Need to determine the flashing light code ...
UV Treatement1/29/2010
  Q: I just had a company take a look at our HVAC systems. They indicated that we need to clean the ...
  A: If you have kept a clean air filter in the furnace you shouldn't need the coils cleaned after 5 ...
Superior fireplace burner problem1/28/2010
  Q: we bought this house last summer that has a Superior DR 500 CMN fireplace insert. The pilot light ...
  A: So you have a gas valve controlled by a thermocouple. The thing that usually is bad is the ...
HVAC Fan won't turn on...1/27/2010
  Q: I just replaced the thermostat and it is doing the same thing the last one did where it clicks to ...
  A: No fan either when the fan switch is turned on ?? Could be a dead fan motor? Jump across the red & ...
York HVAC transformer heat-up1/26/2010
  Q: The blower motor and run capacitor on my 20-year-old York gas furnace were replaced earlier in the ...
  A: Sure can't find any rtelationship between the transformer & the blower motor. But electricity can do ...
furnace shuts off1/24/2010
  Q: the amana 90 furnace will start and run for about 2 seconds than shut off. the red light will blink ...
  A: A quick shutdown ussually is a faulty flame senser. I'd try cleaning it with a rag first & then ...
heat pump1/23/2010
  Q: I have a 2 ton, split system heat pump (Goodman) unit that is about 3 years old. My home is new ...
  A: Wow, what a mess ! If you have a 2200 sq ft, 2 story condo with a 2 ton heat pump system you.ve ...
home heating problem1/23/2010
  Q: The master bedroom and adjoining ensuite in my home don't seem to heat up as well as the rest of my ...
  A: This is a duct system problem. If you have dampners in all the ducts at the supply plenum you can ...
central eletric furnace1/23/2010
  Q: My neighbors heat wont come on. She has a, colman central electric furnace.For manufactured modular ...
  A: There are control circuit sequencers that control the heat, one for each element.Probably have the ...
HVAC emergency heat?1/22/2010
  Q: I have all electric power and a heat pump. I have figured out that the fan blades on the pump are ...
  A: Whatever temp you set for heat the compressor will TRY to supply that temp. If the 1st stage (the ...
Intertherm gas furnace flue replacement1/21/2010
  Q: You mentioned that replacing the flue on my Intertherm furnace[model MGHA-066AAFC-01] was doable and ...
  A: I've had a telephone wire break & was down for 5 days. When that happens on U Verse, you lose fone, ...
Intertherm gas furnace burner1/13/2010
  Q: my Intertherm gas furnace{model MGHA-075AAFC-01} has a flame from the burner that acts as if a ...
  A: You can replace the flue but get ready for some labor. All the screws that hold the flue pipe to the ...
furnace1/13/2010
  Q: Is there a special setting for the air shutter on my furnace in the winter time. It runs for a while ...
  A: Could be a high temp switch turning it off. You have a new air filter in the furnace ?? Could be a ...
Intertherm gas furnace burner1/12/2010
  Q: my Intertherm gas furnace{model MGHA-075AAFC-01} has a flame from the burner that acts as if a ...
  A: OK Joe, so much for that !Good job checking that out. All the symptons of a hole. Next is that the ...
Armstrong Ultra V tech 911/11/2010
  Q: I just got back from a week on the road. My thermostat was set at 60 while gone. When I returned I ...
  A: These furnaces diagnose the problem with a blinking LED. Count the number of flashes & find the code ...
Coleman Package Unit Wiring1/9/2010
  Q: Well it's getting too cold here in Florida - We own a Coleman Mobile Home Model PHP036H1321A and ...
  A: Can give you general info only.The white wire control circuit connects the the bottom terminals on ...
nordyne furnace melted wire1/8/2010
  Q: I have a nordyne e2eb-015hb and the wire that runs from the relay to the fusible link attached ...
  A: Its not the insulation on the wire, it is the wire size for the current load. That wire is carrying ...
HVAC ductwork...critter proof?1/8/2010
  Q: Have been waking up in the middle of the night the past 6 months to the sound of a critter ...
  A: I'll guarantee those critters are INSIDE your ducts. Hardly nothing to stop them & they love that ...
squirl cage1/7/2010
  Q: how to remove and clean on a ducane #cmpb100u4
  A: Cut the wires to the motor at a convenient place they can be spliced again with wire nuts. Find the ...
nordyne furnace melted wire1/7/2010
  Q: I have a nordyne e2eb-015hb and the wire that runs from the relay to the fusible link attached ...
  A: The wires are melting from a rusted terminal. Clean the terminals with a wire brush or anything ...
aux. heat1/7/2010
  Q: i have a heil phf048k000a single package heat pump. auxiliary and emergency are not working. has ...
  A: A tricky question. Try manually pushing in the contactor. If it runs OK it is a control circuit ...
Heil Gas Furnace starting problem1/6/2010
  Q: I have a Heil gas forced air furnace Model NTC5075BFC1 in my home and this is my problem: When the ...
  A: Thats why I don't like electronics to control furnaces. It takes remove & replace to diagnose a ...
ac/heater unit noise1/6/2010
  Q: I have a new comfort maker ac unit. It whistles. Louder as it starts and stops and but a constant ...
  A: The whistle is from an air leak somewhere around the blower case. Air pressure is increasing as the ...
Intertherm gas furnace burner1/6/2010
  Q: my Intertherm gas furnace{model MGHA-075AAFC-01} has a flame from the burner that acts as if a ...
  A: You have a hole in the heat exchanger. Best NOT USE IT until it is confirmed a hole since carbon ...
American Standard Freedom 801/5/2010
  Q: I have an American Standard Freedom 80 that has been blowing cold air. The light is blinking 2 ...
  A: He isn't being too honest charging that much for a senser. Coarse it was Sunday though. You need to ...
york gas furnace1/4/2010
  Q: My york gas furnace burner shut off before the blower kicks in. The ignition is fine and the burner ...
  A: Missed on that one, Charley. That is a perplexing problem without a definite solution. Have had ...
tempstar1/4/2010
  Q: The unit has been knocking a middle breaker on it out side. I can put the breaker in and it seems ...
  A: circuit breakers can have a loose terminal that can cause it to open, or it can be a bad breaker, or ...
cold air returns1/4/2010
  Q: I had a payne furnace and all new duct work put in this summer, winter is here in Mich. and my ...
  A: Wonder what thickness insulation was used for the flex ducts. Up there, it ought to be 2" at least ...
Ruud Silhouette II Cycles1/3/2010
  Q: I have a Ruud Silhouette II that is just over 5 years old. It will kick on for a few minutes, then ...
  A: First, the blower is on a separate timed circuit. I've see this problem before Kris & found it a ...
gas furnace12/31/2009
  Q: I have a 10 year old Bryant gas furnace that keeps locking out. Then I shut it off for a few hours ...
  A: is this a circuit board controlled furnace ?? Or just a ignition module only ?? A board control has ...
Model E2EB-015HB12/29/2009
  Q: I am helping a neighbor out with his furnace. The unit will turn the indoor fan motor on(in auto on ...
  A: The heating an motor is turned on by a heat sensing reay If this is a standing pilot type furnace ...
Gas furnace wont' ignite12/29/2009
  Q: I have an American Standard Freedom 80 gas furnace. When I try to get it to kick on the blower fan ...
  A: There is a sequence of events that has to happen before the gas lights. Can you tell me which of ...
gas furnace issues12/28/2009
  Q: The pilot light turns on but the burners do not ignite (sometimes)it is a Coleman furnace ...
  A: If the pilot tight stays on the thermocouple is OK. Is the gas valve knob turned to ON ?? Is the ...
Forced hot air natural gas furnace w/AC12/27/2009
  Q: I am building a full basement 2-story colonial (2600 sq ft located 1500' from the ocean. Receiving ...
  A: Now thats GOOD info, Kevin. Thanks. You will regret not having 2 units. I get complaints all the ...
Furnace fan run continuous12/26/2009
  Q: Livingston~ I have a new goodman furnace with a honeywell stat. The problem is that the heat ...
  A: John. Our blizzard has passed thank you. You are "resetting" the circuit board John, disconnecting ...
Forced hot air natural gas furnace w/AC12/26/2009
  Q: I am building a full basement 2-story colonial (2600 sq ft located 1500' from the ocean. Receiving ...
  A: Need clarification Kevin being a Texan not having basements. Is this a 3 story house( 1 story ...
A./C noise12/25/2009
  Q: When A/C is running, there is a loud whooshing / slurping type noise in wall(bedroom wall where ...
  A: Need to tet the freon first. You may have a valve control of freon to the evaporator coil & it could ...
wall furnace inop.12/24/2009
  Q: I am attempting to put back into service a fan type wall natural gas wall furnace. It is made by ...
  A: Usually there is a manual reset high temp. switch that will trip on overheat, like you had when the ...
HVAC12/24/2009
  Q: I have an all electric condo in NY, GE forced hot air heat and a.c. It is the original system from ...
  A: There is a liquid you can inject into the system that can stop a leaking evaporator coil, lke you ...
GMP furnace--Induced draft motor will not fully start12/23/2009
  Q: I have two Goodman GMP series furnaces (about 1995 models)installed at the same time in 1996 and ...
  A: Usually don't get enough for a decent answer. The black modules are relays. One is for the blower ...
Ruud Deluxe 90 furnace issue12/23/2009
  Q: I have a Ruud Deluxe 90 furnace. I'm in Wisconsin, so it's a bit cold outside. I keep the temp at ...
  A: The list of events that have to occur before the furnace lights is a bunch & ya know anyone thing ...
Cold air flow through intake vent12/22/2009
  Q: My 2007 home has a metal elbow connected to a vent from outside to allow air intake for the furnace ...
  A: Combustion air to sustain fire is an unbelievable amount.So cold air is being sucked into the vent. ...
humidifier12/22/2009
  Q: Just changed the water panel in my 1 year old Aprilaire 700 humidifier. Followed all the directions ...
  A: Is there a float in this model ?? Can it be stuck ?? Or maybe the solenoid valve is stuck ?? ...
Heat Strip installation when Gas is shut off!12/21/2009
  Q: It's not overly-ambitious, I am doing it right now. Because I owe the gas company about $1500, ...
  A: 10 gauge is good for 30 amps. Go directly from the 60amp double pole breaker to the elements in ...
Heat Strip installation when Gas is shut off!12/20/2009
  Q: It's not overly-ambitious, I am doing it right now. Because I owe the gas company about $1500, ...
  A: Now I see the strips. And see you have altready mounted the strip on the plenum So you have 3 5kw ...
Heat Strip installation when Gas is shut off!12/20/2009
  Q: It's not overly-ambitious, I am doing it right now. Because I owe the gas company about $1500, ...
  A: Do I see 2 electric elements on that plate ?? I can see 2 high temp switches. If that is true, the ...
Heat Strip installation when Gas is shut off!12/19/2009
  Q: It's not overly-ambitious, I am doing it right now. Because I owe the gas company about $1500, ...
  A: Man, you got problems. Does the 15 kw strip mounted on a metal plate ? If so, there will be a limit ...
Heat Pump Size12/19/2009
  Q: We have split style home, 1800 sq feet above ground level with a 300 sq feet of additional living ...
  A: Since you don't need any cooling all you need is a gas furnace, not a heat pump. That uses a ...
Payne Heat Pump12/18/2009
  Q: I have a Payne Split System Heat Pump 13 SEER R-22 that's about 3 years old. While it seems to be ...
  A: Thats condensate water from the evaporator coil, which the outside unit is when on heat. That ...
13 seer vs 1412/18/2009
  Q: Is a 14 seer a better choice evn if the $1500 fed credit does not amtter? The quote for the 13 is ...
  A: Best judge is to compare the run amps between the 2. Look at the nameplate for the answer. You ...
heating furnace, forced air12/17/2009
  Q: Trying to figure out correct BTU size for purchasing new furnace. Total living space of my 15 year ...
  A: Well, you just can't guess heat loads. If the guy has run a heat load analysis go for it. If not, ...
Thermostat / Gas Furnace quits at night12/17/2009
  Q: I have a Honeywell RTH230B thermostat - under a year old- and a Rheem Criterion II gas furnace- ...
  A: Need to verify the accuracy of the thermostat. Jump across the red & white wire for heat & see if it ...
Furnace will not light burners12/16/2009
  Q: My furnace is 26 years old. I just spent $700 a few months ago. My problem now is when the heater ...
  A: Any burned looking terminals on the wire ?? A .oo1 " gap is enough to disconnect a current. The ...
Rheem furnace doesnt cycle right12/15/2009
  Q: I have a Rheem Criterion furnace. It is not cycling correctly. When the the thermostat calls for ...
  A: NOT the flame senser, Brian. Difficult to not have suspicions about the thermostat since all the ...
goodman furnace wont fire off12/15/2009
  Q: I recently got a call about a furnace that would'nt fire so It seemed to me that the gas control ...
  A: Does the fan motor run when thermostat switch for fan is tuened on ?? If it still hums, manually ...
heating a townhouse12/15/2009
  Q: We have a heat pump and a three-story townhouse. The basement (1st floor) is very cold. There are ...
  A: Is the furnace in the basement ?? If so you can open up the supply air plenum with an adjustable ...
elec. heaters central thermostat control12/13/2009
  Q: Greetings Howard: I recently returned to using the baseboard elec. heaters that have been in my ...
  A: Can be done with contactors controlled by a 24volt control but you are still limited by the current ...
forced air seems half speed after new blower motor installed12/13/2009
  Q: My system is a heat pump with electric back-up unit. The blower motor was going out and I had it ...
  A: There are maybe 4 wires on the motor. For a 240 v motor the high speed is black & white. Or could be ...
Furnace not working12/11/2009
  Q: I have a Janitrol GMP075 that has a heat pump that snitches to propane at a pre-selected ...
  A: How;s the voltage to the gas valve ?? Is the gas pressure at the valve about 12" water ?? The ...
heat pump/gas furnace combo12/10/2009
  Q: I have a Johnson furnace/heat pump combo. the heat pump does all right but I would rather the gas ...
  A: A heat pump ya know, uses the compressor heat ad 1st stage, the furnace the 2nd. When the ...
travel trailer furnace12/10/2009
  Q: fan comes on,ignitor begins clicking,and I actually seen it sparking,it tries to inite,but then goes ...
  A: So the pilot gas must be on but maybe the pilot orifice is stopped up or the spark is not jumping ...
Air Intake Pipe Freezing Shut12/9/2009
  Q: Our Air intake pipe for the HVAC keeps freezing shut each night. Once this happens the gas to the ...
  A: Hey, move to Florida ! Gotta have heat to stop this. Is there any inside room the fresh air could ...
payne heater pressure release valve12/9/2009
  Q: , recomends to check vent and if there are high winds.. where is the pressure valve located and ...
  A: The pressure valve is located at the end of the tube from the combustion air draft motor. When it ...
heat sequencers12/8/2009
  Q: Good Morning, I have been working one season on the heating so far. I have been getting ...
  A: Sorry I don't have any schematics. But its not that hard. A call for heat activates several ...
No Heat on a Gaffers and Sattlers Furnace12/8/2009
  Q: It's an old G&S Model U60 that will not fire. I got the problem narrow down to the Pilot/Flame ...
  A: Not sure about that "flame switch" But for sure the pilot flame has to activate the switch to supply ...
Air circulation12/8/2009
  Q: I appreciate it. I have a small home in the foothills West of Denver, CO. I have recently installed ...
  A: Ought to be a thermostat available for heat only with a fan switch on it. You'll have to add a green ...
Duct size for 5 ton12/7/2009
  Q: for a 5 ton unit what size duct should i run from the unit. The house is 45 feet long what size ...
  A: An extended plenum starts off the same size as the supply air opening is from the furnace. But ...
heater doesn't work when it's cold12/7/2009
  Q: Numerous "heater guys" came by and none of them know what to do. I am desperate. My heater works ...
  A: is this a heat pump ?? I'm in Arlington. Have just learned today about a heat pump is doing what ...
Losing Flame!?12/7/2009
  Q: There are three HVAC units and two gas fire places in my home. They were all installed in 2006 ...
  A: Sounds like you have solved the problem yourself. Need to run gas pressure tests at the downstream ...
New Furnace Problem12/6/2009
  Q: Furnace Model: American Standard Freedom 80 Single Stage ADD1B100A9451A 100000 BTU Thermostat: ...
  A: A heater requires 1 sq in per 1000 btu's. Got that much ?? I so it could be in the return air ducts ...
Ruud furnace blower continues to run12/5/2009
  Q: Howard, I have a Ruud Silhouette furnace - model # UGDG-07EAUER. It is 15 years old. The system ...
  A: If the flame senser was not working right the flame would go out in seconds, not minutes. Where is ...
over amping12/5/2009
  Q: I'm working on a magnaflow airhandler,( 2 ton, 24b hffx model) twice the blower motors burned ...
  A: SEVEN AMPS !!! No wonder it fried. How's the run caacitor ?? The correct size for the motor ?? ...
New Furnace Problem12/4/2009
  Q: Furnace Model: American Standard Freedom 80 Single Stage ADD1B100A9451A 100000 BTU Thermostat: ...
  A: You have a good thermostat but I would question it from what's going on with the furnace ...
"OOOOH" sound at end of cycle in evening12/3/2009
  Q: Heat Pump HP22-411 (1992) makes an "oooooh" sound at end of cycle--heating or cooling late in ...
  A: I gotta make a educated guess on this one. Never heard a sound like that. Bet it is freon rushing ...
5 ton heat pump popping breaker12/2/2009
  Q: We have a 5 ton heat pump package unit in a car repair shop that we recently purchased. The unit is ...
  A: Just sent an answer to your reply. Still say now need a larger breaker. Look on the nameplate for ...
heat pump12/2/2009
  Q: I have a 2-1/2 ton Luxaire made by York I think. Heat pump runs and operates ok but does not stay ...
  A: Thinking more about feeling the compressor with your hand open ,layit on top of the pot. If it is ...
5 ton heat pump popping breaker12/1/2009
  Q: We have a 5 ton heat pump package unit in a car repair shop that we recently purchased. The unit is ...
  A: Start off tightening the terminals on the breaker & on the outside unit at the contacto & the ...
Summer switch - furnace fan.11/24/2009
  Q: We had a new gas furnace installed a few months back and the installer added a "summer switch" to ...
  A: About 35 years ago a Summer fan switch was standard on a furnce. Not any more. All you need to do is ...
Rheem furnace control board problem11/23/2009
  Q: I live in Houston and have a 17yr old Rheem furnace in the attic. Last winter I had problems and it ...
  A: The trouble seems to be caused by a flame senser but you have replaced it already.Are there any ...
Call for Heat11/23/2009
  Q: I have a (mid 1990s) Heil NUGS100BH03 furnace which stopped working a few weeks ago. As I am new to ...
  A: The missing link is the air pressure switch. That has to close from the air(or vacuum) from the ...
American Standard Furnace11/22/2009
  Q: AS Freedom 80 Furnace - Blowing Cold Air - Warning light flashing 9 times. Just purchased house a ...
  A: Dang David,you pulled all those wire s?? I can see the brown around the resistors but usually when ...
American Standard 500011/21/2009
  Q: my 16 year old AS 5000 upflow heating unit quit heating during the night. I have performed the ...
  A: The draft motor closes an air pressure switch, THEN the igniter glows. Got to be the pressure switch ...
Pilot won't stay on11/21/2009
  Q: I have a Trane XE60 that the pilot light will go out after running heat for a little while. I have ...
  A: Try adjusting the pilot flame at the pilot adjutment screw on the gas valve to be a bit stronger.Be ...
American Standard Furnace11/20/2009
  Q: AS Freedom 80 Furnace - Blowing Cold Air - Warning light flashing 9 times. Just purchased house a ...
  A: Somebody got ripped off bad on the igniter !! Glad you didn't. Those darned circuit boards do ...
Gaffers & Sattler Furnace Doesn't Fire-up11/19/2009
  Q: We had the digital thermostat set to "Off" over the summer. After setting it back to "Heat," when ...
  A: This is a goofy question but the place to start. Is the gas valve turned to ON ?? Need to test the ...
Squirrel cage and circuit board11/19/2009
  Q: We recently had a company clean our Lennox G20 series furnace and ducts. The next day, our furnace ...
  A: I do not recommend duct cleaning. Have seen damage done while cleaning too many times. Did the ...
Old furnace with possible electrical problems11/18/2009
  Q: Livingston, We just moved into a house with a 20 year old furnace (model NUGE100AG01 - not sure of ...
  A: Well hello Adam. Now lets see whats going on here.Start with #1.Could be worn bearings. Are there ...
residential gas furnace11/17/2009
  Q: I have a Gaffers & Sattler's furnace which keeps popping everytime it lights up the burners. ...
  A: The flame runner needs cleaning. Plus the leftburner probably has a hole stopped up right at the ...
Fraser-Johnson HVAC fan system11/17/2009
  Q: My heater fan motor oscillates on and off while the gas burner stays on when I increase the ...
  A: The capacitor may be in the electrical area by the burners or look at the moroe wires & there will ...
American Standard Gas Furnace Issues11/16/2009
  Q: Howard, I have a Amer. Standard furnace with a White Rodgers board in it. Service tech told me that ...
  A: Sounds like the 2nd thing on the heat sequence is faulty, the air pressure switch. The blower auto ...
american standard freedom 70 propane furnace11/14/2009
  Q: our furnace is 9 years old. It is american standard freedom 70 propane with one zone. Recently, ...
  A: The blower is on a separate circuit & will activate the fan when you call for heat. Main problem is ...
ac ducts cleaning11/14/2009
  Q: We lived in our home for 32 years when it was built. The AC ducts have never been cleaned. I have ...
  A: I don't think duct cleaning does any good. You have 3 filters that removes most of the dust. The air ...
Coleman Furnace Model 7680B Series 85611/13/2009
  Q: My gas furnace will bring the temperature up to the thermostat's temperature setting but then it ...
  A: I presume the furnace is controlled by a circuit board. Correct ?? Is just the fan doing the ...
AC Turns On by Itself11/11/2009
  Q: Our 4 ton central AC turns on by itself, even though the temperature does not warrant it. For ...
  A: The thermostat controls the blower when on cooling. If you have a digital thermostat it has the ...
AC Unit.... what to do???11/10/2009
  Q: I'm very confused about a problem with my outside AC Unit and would be really grateful to hear your ...
  A: Best be fixed Juliet.It won't last too long with bad bearings. What happens when you spin the blades ...
AC blower turns on by itself11/8/2009
  Q: With the fan switched to auto, heating and cooling in off position. the fan intermittently turns on ...
  A: Wow, Ralh, thats really weird. A circuit board controlled furnace has a timed circuit for blower ...
Trane XR90 Will not turn on.11/7/2009
  Q: I recently installed a programable thermostat for my Trane XR90 furnace. Once it was installed, I ...
  A: And here you thought you were improving the tstat, huh ?? It happens, Michael. You need to test ...
Gaffers Sattler furnance model ACD12-U10011/6/2009
  Q: The pilot had blown out during a Santa Ana wind without me knowing it. When I tried to turn on the ...
  A: Well Steve, the favorite question is : Did you turn the gas valve knob to "ON" after lighting the ...
Furnace burner not lighting11/6/2009
  Q: I have a Carrier 58PAV/RAV upflow HVAC unit...when I adjust the thermostat, the unit kicks on, the ...
  A: Don't have knowledge of those codes Derrick. Could be a failed igniter or a pressure switch. Try ...
nordyne heater E2EB015HA11/5/2009
  Q: The elements are getting hot but part of the time the blower will not come on. What controls the ...
  A: Something fishy here. Need to test just the motor. Remove the motor & blower case. I just cut the ...
contaminated heat pump11/4/2009
  Q: wife and i purchased a new rhemm central heating and air system back in febuary of this year(2009), ...
  A: Wow, Glenn, that is a terrible mmess !! How did that water get in the system ?? A teaspoon will ...
leaking condensate.10/28/2009
  Q: I have a Heil DC90 furnace mounted horizontally in a crawl space. I have water driping from the ...
  A: Is there not any crawl space vents around the foundation ?? So all your combustion air supply is ...
Aux Heat On10/25/2009
  Q: I have a Honeywell Vision Pro TH8320U thermostat controlling a heat pump and oil fired furnace (as ...
  A: First stage heat is from the outside unit. It is sensing that unit is not running. Check that out on ...
Gas Furnance Issues10/23/2009
  Q: Before I begin, I want to thank you Mr. Howard for answering my question. Well, I have a gas ...
  A: That kind of furnace, controlled by a circuit board, starts thre heat cycle with the induced draft ...
Gas space heater10/23/2009
  Q: I have a vintage "Brilliant Fire" gas space heater in my log cabin that has been there for many ...
  A: Know what you're saying about the backfire at shutdown. I'm not really sure but think it is a gas ...
propane furnace problem10/22/2009
  Q: I have a Carrier Weathermaker 9200 that will not work, it is my secondary heat source with a new air ...
  A: Transformer is OK.I would pull the wires on the inducer motor & test it with 120v.That motor ought ...
Rheem Gas Furnace10/21/2009
  Q: I am having an issue with my Rheem Gas furnace #80PJ07EAR01 4yrs old. My issue is this: the inducer ...
  A: Wow, Josh. The things gone wild !! All I could add is test the voltage at the gas valve & see if ...
fan motors blowing circuits10/21/2009
  Q: We have installed 4 2hp motors with trunking in our church attic to ensure ventalation, ALL on ...
  A: I can imagine there is something wrong with the start windings from manufacture. Can you get ...
R22 hvac10/20/2009
  Q: I am building a house. The builder charged me to put in an unspecified hvac unit. After the fact, ...
  A: I am not up on prices these days since I have retired for several years. R22 units are being phased ...
inverter10/20/2009
  Q: I have a small print shop of 12,00m2; there is no heating in it. I bought an inverter air condition ...
  A: Don't think the pipe size difference would do anything. The heating watts sure is small for the size ...
HVAC10/19/2009
  Q: We have a house built in 2003 with a second floor and central heat / AC, full basement, and 2 return ...
  A: Ni Randy, good thinking ! Best to have 2 units for 2 story houses but gotta live with what you ...
Bryant Plus 90 Upflow gas furnace10/19/2009
  Q: When my 1990's Bryant Plus 90 gas furnace starts up, only three out of four burners light. If I ...
  A: Check the flame runner that carries the fire to all burners. It can clog easily with dust, etc. ...
central heating10/19/2009
  Q: When I cut my central heat on it blows cool air out and constantly runs until I shut the system off ...
  A: Check for shorted wires between red & green wires behind the thermostat. If, OK,there is a stuck fan ...
HEIL NTC6125KJA1 gas furnace10/18/2009
  Q: I just turned my furnace on and... the flue fan comes on, the ignition system seems to work (the ...
  A: Each burner is 25,000 btu. 75k is good for a 3 ton cooling & a 1500 sq. ft. house. Short cycling can ...
Gas Furnace Cycling10/17/2009
  Q: Miller LP furnace model M3RL-080-ABWT-will go through a heat cycle of igniting followed by fan ...
  A: I would start by jumping across the red & white wires behind the thermostat to test it out. If it ...
Lennox G51MP furnace not responding to thermostat call for heat10/15/2009
  Q: We just switched our Lennox G51MP furnace to heat this morning, but it will not operate. The two ...
  A: The rollout switched usually have a red button that pops out. If not, it's not them. I'm not ...
Lennox G61MPV trips breaker10/14/2009
  Q: Note: I'm traveling on business so the information I'm getting is from the wife and I'm trying to ...
  A: A tripped breaker sez there is a dead short somewhere.From what I gather this breaker controls the ...
burners are cycling on and off10/14/2009
  Q: I am having a problem with the burners on my furnace. When the thermostat is calling for heat the ...
  A: Sounds like you have an older furnace without any of the solid state stuff. Right ?? If so, the ...
hvac10/13/2009
  Q: We have a 992 sq ft home with a no day light basement also 992 sq ft. I am installing a wood stove ...
  A: You really can just turn on the fan switch on the thermostat to circulate hot air thru the existing ...
furnace won't stay lit10/11/2009
  Q: My Trane XE80 gas furnace won't stay lit. I believe it was installed in 1994. It will run for about ...
  A: need to know which kind of furnace that is. Does it have standing pilot or is it controlled by a ...
return air filter sizing10/11/2009
  Q: My question is "I know that it is bad to undersize your return air filter, but is it possible to ...
  A: I'm thinking a 4" will cut down the airflow too much. You can do a good job on the dust if you get a ...
Fan will not shut off10/10/2009
  Q: I have a Heat Pump/Ac and electric furnace.....International Comfort brand I believe. Unit/House is ...
  A: Not good Paul. That black box on the board is the fan relay. But it is controlled by the time delay ...
Burners won't stay lit10/2/2009
  Q: Single mom needs your help! I own a Dayton gas fired furnace, eight years old. Once again, when I ...
  A: got to help these Mom's. You have a flame sensor that need cleaning, It is a small metal rod that ...
Sears wall furnace, low heat output.10/2/2009
  Q: I have a very old Sears Wall furnace(867.73342). It doesn't seam to have the proper heat output ...
  A: That carbon buil up is dangerous. That means improper combustion. The heat exchanger is probably ...
RHEEM 80 Imperial10/1/2009
  Q: I have just purchased a house and the HVAC unit is a RHEEM 80 Imperial. It has worked well all ...
  A: Well, we wouldn't want a killing now, George ?? You're going to have to do some diagnosing George ...
check valve v expansion valve9/30/2009
  Q: Howard, Is there a difference between an expansion valve and a check valve in the air handler part ...
  A: A check valve is necessary for the reverse flow of freon when calling for heat. Expansion valve ...
wall furnace9/29/2009
  Q: The small cabin I recently purchased has a Sears Series 600 - Model 867 - wall furnace.. Pilot and ...
  A: Yo Tom, I'm not acquainted with that Sears model but can say those snap disc switches can be the ...
heatpumpFreeon9/28/2009
  Q: Howard, Thanks for your reply. I don't think they would dare come on to the property again. What ...
  A: Have to have a chemical analysis run to find out about the freon. Still don't think that is your ...
HeatPumpHumidity9/28/2009
  Q: Our ac, trane heat pump, was working great until a company came over to do a yearly maintenance. ...
  A: Humidity too high is usually caused by the cooling not running long enough per cycle to remove the ...
Furnace wont reach desired temperature9/27/2009
  Q: I am having trouble with furnace. I turn furnace on with thermostat set at 68 degrees. The furnace ...
  A: Is this a digital t=stat ?? Sounds like the stat is way too sensitive. Usually are + or- 1 deg.but ...
lites dim when A/C comes on9/26/2009
  Q: New house, 2.5 ton central air. Trane 13 seer condensor. When the condensor comes on, the lights in ...
  A: An option is to install a start capacitor on the compressor. That costs about $75. Will help some, ...
HVAC9/25/2009
  Q: my husband has been trying fix the a/c and first the thermostat went out and he got and new one and ...
  A: Now thats the first time I have ever heard that name !! Interesting I get a LOT of questions ...
lites dim when A/C comes on9/25/2009
  Q: New house, 2.5 ton central air. Trane 13 seer condensor. When the condensor comes on, the lights in ...
  A: Circuit to condenser not big enough. Is it on a separate circuit ? Should be. Read the nameplate ...
HVAC9/24/2009
  Q: We have a York "Packaged" Heating and Cooling System, that is tripping the breakers at the main ...
  A: Hate to say it but that symptom usually indicates a shorted compressor. Easiest test to confirm is ...
heil propane hot air furnace9/24/2009
  Q: i have a heil propane hot air furnace ,direct vent and it will not open the gas valve to let the gas ...
  A: The famous answer is "is the gas valve knob turned to on "? Does the igniter light a pilot light or ...
Heating/AC Unit9/23/2009
  Q: I'm looking for general direction and advice as I try to help my parents who are interested in ...
  A: let's see what we can do for your folks. First thing is to run off the guy that bid $18,900 ! He's ...
GE Zoneline Heat Pump9/22/2009
  Q: We've had this through the wall unit for about 15 years. It now sounds as if the compressor is ...
  A: I'm the kind that will try to get anything running again so you know my answer. If thats one of ...
Condenser Fan Motor9/21/2009
  Q: My ac went out last night. I suspected the condenser fan motor, and I had that confirmed by a HVAC ...
  A: Good for you. See, you can do it. Everythibg OK since it runs. Only one thing, the capacitors need ...
Condenser Fan Motor9/20/2009
  Q: My ac went out last night. I suspected the condenser fan motor, and I had that confirmed by a HVAC ...
  A: NEVER hammer on the end of the shaft. Sand the exposed shaft clean & add WD 40. With a crescent ...
central air9/20/2009
  Q: I was told that it cost's more money to turn your central air off and on then it does to just adjust ...
  A: hope I don't start a tussle between you two by my answer ! Cooling the air does 2 things, first it ...
Condenser Fan Motor9/20/2009
  Q: My ac went out last night. I suspected the condenser fan motor, and I had that confirmed by a HVAC ...
  A: $800 my God thats terrible. Tell him to bug off. Remove the motor & tajke it to the motor shop to ...
Propane Heating System and Utility Room Smell?9/19/2009
  Q: We have moved into a home that is heated by a propane heating system. The heating system is located ...
  A: Tell ya its dificult to diagnose smells & stuff coming from the grille problems. Thanks for the ...
heat pump defrost affecting ac function9/18/2009
  Q: I have a 3-ton Rheem hpne heat pump system. The outside cabinet is shutting off while the air ...
  A: Only reason I can imagine for the 5 min stop is a defrost signal. But the unit should reverse, or ...
Ruud heat pump9/18/2009
  Q: We have an all electric Ruud Heat Pump. I saw someone else has white powder coming out of the vents, ...
  A: I know I've had that powder question before but can't remember the answer - if I had one ! The ...
contol problem9/15/2009
  Q: I am a 2nd year HVAC student at a local community college. My neighbor ask me to look at her A/C ...
  A: 2nd try, Terry. I would test the output from the transformer in the furnace while running & stopped. ...
Trane model BCHA - 90 fan assembly removal9/15/2009
  Q: During construction of this fairly new facility(1994), the Trane Air Handlers were all installed ...
  A: Another reason I don't care for Trane. I am not acquainted with that problem but doing service work ...
contol problem9/14/2009
  Q: I am a 2nd year HVAC student at a local community college. My neighbor ask me to look at her A/C ...
  A: First thing I would do is put my open hand on top of the compressor after it runs & stops. I'll bet ...
wireing on a coleman evcon EB12B9/13/2009
  Q: I replaced a HW 4700 with a HW RTH3100C. The old one had a wire labeled X, neither thermostat has ...
  A: Thermostas for heat pumps have changed terminal designations. I do not have wire circuits for ...
Compressor run state9/13/2009
  Q: I have a package unit with a single compressor, controlled by a mercoid style t-stat. With the unit ...
  A: The contactor points may be burnt & not making good contact on first try. Check out the points & see ...
Air ducts9/12/2009
  Q: I recently cleaned my air ducts professionally but this didn't solve my problem. The problem is not ...
  A: Air duct cleaning NEVER solves any problem. They usually create one. My humble opinion. Apparently ...
lack of moisture9/11/2009
  Q: I live in Ontario,Canada mwhere the winters get cold and the house gets very dry.I had installed a ...
  A: I could be a wise guy & say move to Houston, TX ! Surprised that the floor heating dries out the ...
AC unit not efficient9/1/2009
  Q: I have 2 AC units, one covering the first floor, the other for the second. Despite this, the house ...
  A: Sounds like the upstairs unit duct system is not too good. A good size unit in FL ought to be 1 ton ...
AC unit not efficient9/1/2009
  Q: I have 2 AC units, one covering the first floor, the other for the second. Despite this, the house ...
  A: 2 story houses not too efficient due to the open stairway. High ceilings add to it also. Since cold ...
Trane a/cs8/31/2009
  Q: A technician came out to check my 2 units. He said I had a leaking capacitor, show me a clear oily ...
  A: Not acquainted at all that there is another king of supply air plenum ?? To distribute air to the ...
Bad Flame Sensor?8/31/2009
  Q: I have an Armstrong Air upflow gas furnace (model #G1N80BU075D16B) and it stopped working at the end ...
  A: Whoa, thats interesting ! You have a thermostat with a heat anticiator dial on it ?? Other than the ...
Bad Flame Sensor?8/30/2009
  Q: I have an Armstrong Air upflow gas furnace (model #G1N80BU075D16B) and it stopped working at the end ...
  A: Nice to hear somewhere its getting cold again. Still Summer down here in Texas.This is my first ...
Rheem RRKA-0368/29/2009
  Q: I have a 10 yr old Rheem RRKA-A036jk06X A/C+heat unit on my roof. My problem is that I do not get ...
  A: Most al circuit boards have a 3 amo auto type fuse in a plug in socket. That is protecting the 24 v ...
Approximate cost for coolant leak8/28/2009
  Q: Here's myOne of the pipes leaving our outdoor central AC unit and the pipe entering the blower are ...
  A: Anyone tried to locate the leak, Michael ?? There is a liquid you can inject that will seal small ...
upstairs shut down8/28/2009
  Q: My boys are now sent off to college. I want to shut down the upstairs (which consists of 2 bedrooms ...
  A: I presume you have only one unit for 2 floors ?? If so, that return will suck in the hot air from ...
Keeping heat pump; replacing furnace8/27/2009
  Q: I have a 25 year old Trane electric furnace that has been needing a lot of maintenance in the past ...
  A: Not really. Different brands heat pumps can be complex or impossible to wire the control circuit ...
air handler wiring8/25/2009
  Q: My drain pan overflow turned into a float switch replacement that has become a wiring problem ...
  A: A 2 wire thermostat is only for heat. The ah for air handler refers to all the wire connections AT ...
Armstromg Ultra V A/C blower and compressor will not run at same time8/25/2009
  Q: Our A/C stopped working yesterday. I've gone through a lot of on-line troubleshooting and here is ...
  A: Sounds lke a resistance problem.With a small load its OK, big load red, yellow, green too big. Seems ...
air handler wiring8/25/2009
  Q: My drain pan overflow turned into a float switch replacement that has become a wiring problem ...
  A: Wel, Kevin lets see. I'll just give you what wires go where for C<R<G<Y<W from the air handler..C= ...
cent air system8/24/2009
  Q: In a 40 yr old Payne heat/air can the cooling coil be replaced or repaired if there is a slight ...
  A: FOURTY YEARS OLD !!!! Good gosh, thats amazing. Once the evaporator coil starts leaking it needs ...
ac problem8/23/2009
  Q: would my ac unit freeze up if it was one pound low on freon? does the cap on the freon fill valve ...
  A: I wouldn't be happy with that call either. Is it still making ice ?? That evapoator coil should be ...
Zone control problem8/23/2009
  Q: I recently had a zone control setup installed on my Carrier AC unit/ furnace which is about 5 years ...
  A: I'm still at loss to figure this one out, Brian. Do yu have a variable speed blower ?? If not, I'm ...
Zone control problem8/23/2009
  Q: I recently had a zone control setup installed on my Carrier AC unit/ furnace which is about 5 years ...
  A: A clunking fan on startup can be a loose setscrew. Ever checked that ? I am at loss to connect the ...
Low voltage short8/23/2009
  Q: Son installed digital thermostat without pulling curcuit breaker......nothing comes on.....I assume ...
  A: The wires at the thermostat can't be shorted, all on the same side of the transformer.The fuse is ...
replacement HVAC system8/22/2009
  Q: Howard, Thanks for your time. We are replacing our 15 year old split A/C and furnace as the E coil ...
  A: A varible speed blower used to COST $600 several years ago ! A 16 SEER probably adds $300 to 400 ...
replacement HVAC system8/22/2009
  Q: Howard, Thanks for your time. We are replacing our 15 year old split A/C and furnace as the E coil ...
  A: Can't believe you had 2 foks using laptops to figure heat loads ! That eliminates all the opinions ...
Amana Refrigerator8/20/2009
  Q: I just moved into a new house and have an Amana refrigerator. It has always worked but does not get ...
  A: I'm not an expert on refrigerators but undestand your problem. The freezer side vents cold air to ...
Condenser replacement8/20/2009
  Q: I am installing a 3.5 ton 12 SEER condensing unit and I replaced the orfice in the evaporator coil ...
  A: The difference n orifice size between 3.5 & 4 ton is negligble. Just a few thousands. Don;t think ...
Evaporator ices, compressor keeps running when control temp reached8/19/2009
  Q: I have a Trane XE 800 A/C with a new filter. When I turn on air at the thermostat, I get good air ...
  A: Check the freon in the heat of the afternoon. Feel the copper, big suction line outside. It should ...
AC sizing8/19/2009
  Q: I have received bids back on new construction AC unit. The sizes of the units suggested vary fro 3.5 ...
  A: Have any of the bidders used a software heat load design ?? They have software duct design also. ...
Should I replace system before it breaks?8/18/2009
  Q: My Trane system is 14 years old. My compressor stopped working last night but when I flipped the ...
  A: Can be the beginning of the end for the compressor when they trip the breaker. Usually worn bearings ...
Vents & Filter8/18/2009
  Q: I am a asthmatic. The vents in my apartment keep attracting black stuff on the vents and on the ...
  A: This kind of stuff coming from the vents is hard to really diagnose. Have reports a lot of smells, ...
Evaporator ices, compressor keeps running when control temp reached8/18/2009
  Q: I have a Trane XE 800 A/C with a new filter. When I turn on air at the thermostat, I get good air ...
  A: Don't dig why the thermostat is not turning off the cooling? Must be stopping the inside blower ...
a/c noise8/17/2009
  Q: we live in a condo. When someone's or our a/c's compressor kicks on right before it go on it makes a ...
  A: Boy, Dee thats a new one ! Only thing I can imagine is the copper lines are touching a stud in the ...
gas furnace pilot light8/17/2009
  Q: The pilot can be lit as per normal lighting procedures. When control is set to ON position the ...
  A: Wow, wish it was time for pilot lights down here in Texas !! 102 today. IF the pilot flame is ...
airflow problem8/17/2009
  Q: Last year we had central Ac installed on the second floor (3 bedrooms). The first 2 rooms cool very ...
  A: I'm sure getting a lot of questions like yours. Bad duct sizing. Proper duct sizing comes from ...
AC not working. Air handler seems ok8/16/2009
  Q: I live in FL in a 2 story home with 2 AC units, one for each story. All units seems to function ...
  A: Need to test the freon first off. Even without it running you can tell if the freon is needed. But ...
moving air from woodstove8/16/2009
  Q: We have just built a new cottage. It is still all open walls so now is the time I would like to add ...
  A: If you could capture the heat from the stove directly above it, or close to, think it would be ...
uneven A/C cooling in house8/15/2009
  Q: Three years ago I purchased a modified split level, 3 bedroom house (30 yo)- on the first floor, ...
  A: Difficult problem to solve, John. Have to tear apart the house to correct the duct system. Obviously ...
condensation blowing out transformer8/14/2009
  Q: Replaced entire ac system w/ new carrier downflow system.The repairman just left again. He states ...
  A: Something wrong here. A counterflow system with the blower at the top, coil at the bottom would not ...
Outside coils erroding8/13/2009
  Q: The coils on my outside unit Tempstar 2200 12 + Seer Heat Pump installed 12/12/02 have deteriorated ...
  A: I've seen these coils disapear but it was due to dog urine. Once they started using it it was their ...
AIR RETURNS8/11/2009
  Q: My house is 1752 sq. ft 1 level. I am located Port St.Lucie Fl. My ac unit is a 4 ton. We had a leak ...
  A: How old is the system being replaced ? 12 to 15 years ? Time to replace. Be sure & replace with ...
A/C won't turn off and I have ice build up8/11/2009
  Q: After experiencing a brown out power reduction in my area recently, my air conditioner now won't ...
  A: You have a stuck contactor in the outside unit. Probably from burned points. If you pull on the ...
power failure oil furnace8/10/2009
  Q: while pulling staples i shorted the wire that feeds the round red outlet ( box ) @ furnace . the ...
  A: I'mnot acquainted with the round red outlet box. Usually just a spark won't do any more than trip a ...
24v at contactor8/10/2009
  Q: Have a rental unit that was giving intermittent starting problems but by the time my HVAC guy would ...
  A: Gotcha. You have a dog in the backyard ?? They love to chew on the wires to the outside unit. Not ...
Trane XE808/9/2009
  Q: I have a Trane XE80. In the cooling mode, the condensing unit outside does not turn on. The ...
  A: The thermostat closes a switch to send a 24v signal to the condensing unit. Also, in auto fan turns ...
24v at contactor8/9/2009
  Q: Have a rental unit that was giving intermittent starting problems but by the time my HVAC guy would ...
  A: The first question is was the fan switch turned to ON ?? If the blower was still running & ...
Reset wont stay8/7/2009
  Q: Heil 5000 Model CA5024 VKB1 air conditioning fan and compressor inop. (fan inside the house unit ok) ...
  A: A transformer in the outside unit ??? That's unusual. Isn't there a transformer in the furnace ...
Reset wont stay8/7/2009
  Q: Heil 5000 Model CA5024 VKB1 air conditioning fan and compressor inop. (fan inside the house unit ok) ...
  A: That reset button generally a high pressure reset. Several things can cause a trip. Fan motor ...
Rheem A/C Problem8/6/2009
  Q: my husband and I bought a Rheem A/C unit with heat pump, allegedly high-efficiency, 16 seer 4-ton, ...
  A: hate to hear problems like you are having. That 4 to should be doing a good job cooling your size ...
Air Conditioner8/6/2009
  Q: My air conditioner is clicking like crazy. The air is not really cool, but that's not as bad the ...
  A: A difficult question Joy. Have you tried to locate the sound. Got to be associated with the blower. ...
Home HVAC8/5/2009
  Q: What is the difference between pleated and fiberglass (usually blue with aluminun-looking frame with ...
  A: I have never seen any figures concerning pressure drop across a pleated filter. There would be more ...
Flipping Inside unit upside down8/4/2009
  Q: I am replacing AC & gas furnace into all electric AC/heat. I found a used 2.5 ton Goodman complete ...
  A: The main problem is the evaopator coil drain. The fan will also blow hot air directly onto the ...
Condensing Unit/// Lennox 10ACC8/4/2009
  Q: Fan in the garage works fine, blows air,. My outside unit does not come on. You can hear the power ...
  A: Look for burned wires in the electriv\cal box in the unit. Need to test the compressor run capacitor ...
how to install thermostst8/2/2009
  Q: i just bought a new mobile home had to install the a-coil and condencer the home had a thermostat ...
  A: No, you use the transformer in the furnace. Now the problem, you will need 4 wire control wire from ...
Mini Splits8/2/2009
  Q: We are ready to choose HVAC for a total rehab of brick home, converted to 3 family units (on 3 ...
  A: Carol. Yes I am suggesting the sleeve units for all 3 levels. Add to the benefits is no thermostats ...
water in air conditioning ducts in mobile home8/2/2009
  Q: We just found water in the ducts on the back side of our double wide (same side as the unit is ...
  A: If you have a package unit outside(includes both cool & heat) remove the whole top. That should ...
HVAC tonnage8/1/2009
  Q: I installed a new air handler and outdoor unit on my home a couple of years ago. My home is about ...
  A: Bet your neighbor has a correct sized duct system. These things are no better than the air ...
Mini Splits8/1/2009
  Q: We are ready to choose HVAC for a total rehab of brick home, converted to 3 family units (on 3 ...
  A: I was aboutfinished with my answer & was interrupted & lost it ! My answer was to use sleeve ...
residential hvac systems7/31/2009
  Q: What are the best rated 4 ton HVAC units? How does Amana rate ANSWER: I'm not really acquainted ...
  A: If Amana is owned by Goodman its a NO. Goodman puts a compressor in their units that is 6000 btu ...
residential hvac systems7/31/2009
  Q: What are the best rated 4 ton HVAC units? How does Amana rate
  A: I'm not really acquainted with Amana. There are a few differnent compressors made today so need to ...
tampering7/31/2009
  Q: Can someone tamper with your central air unit
  A: If you wouldn't pay me I'll puncture a hole in your condensing unit. Or open the service valve ...
hvac7/30/2009
  Q: I have been having air problems for a while now & was told it probably due to air flow. I only have ...
  A: Well, no nee to just do patch work for a duct system. Best to go for the right SIZED ducts with a 5 ...
Isolation relay.7/29/2009
  Q: .. ...hope you can shed some light on my problem. I installed a whole-house dehumdifier. ...
  A: Its only Thursday but hees the answer. Get a "contactor" type relay with a 24 v coil. Hook the 24v ...
AC stops working after power blackout7/29/2009
  Q: Today we had a brief power blackout period. The power off lasted 2 minutes then on again. However, ...
  A: Lennox has a switch inside the outside unit near the compressor. its red. Push on it & if you feel a ...
Isolation relay.7/28/2009
  Q: .. ...hope you can shed some light on my problem. I installed a whole-house dehumdifier. ...
  A: let's see now, when you call for cool, the thermostat circuit turns on the blower, but also turns on ...
why my 5 year old air conditioner needs so much freon yearly!7/27/2009
  Q: In 2004, I put a 4 ton trane in my 'cottage-like", 1600 square foot office. In September and ...
  A: Got rain today. Shoot, your problem is simple: YOU HAVE A LEAK ! Never saw so much over a leak. Just ...
copperlines from compressor to condensor7/26/2009
  Q: I have an Arcoaire AC (3.5 ton for 11oo sq ft, yeah too big I know) 12 seers system that was ...
  A: The liquid line size is the most important. A 3.5 will run OK with a 3/4 & 3/8 lines. Usually the ...
Brands of air conditioners7/26/2009
  Q: Is there any major differences in brands of air conditioners when the specs are the same? The ...
  A: Very little difference.The major difference is in add on features. Like high & low pressure ...
Musty smell from ceiling vents7/25/2009
  Q: I have dual zone goodman unit. The up stair unit has has the coil inside the attic which has easy ...
  A: Condensate water standing in the drain pan can cause the smells. Need to access the opening to the ...
moving warm air7/24/2009
  Q: we have a wood burning insert in the bottom level of our tri level home.that room gets very warm, ...
  A: A duct booster fan doesn't blow much air. About like a bathroom fan. You have a Grainger Supply ...
Furnace / AC size?7/23/2009
  Q: We have a 14 yo unit in our home in Indiana. Currently heated with a Goodman furnace, I seriously ...
  A: A 5 ton, Andrew. You need lots of oir moving with vaulted ceilings. But for good distribution the ...
LG Deluxe Dual-zone airconditioner7/22/2009
  Q: I live on the third floor of a house and had the above installed two years ago and two months ago. ...
  A: Don't know what tonnage your cooling is but if its a 3 ton or bigger, $600 is a fair price. ...
AC unit w/ Heat pump option, AC not running7/22/2009
  Q: I switched on my ac option on my unit last night. Everything inside the house ran. I noticed I didnt ...
  A: No, the fan runs the same for both modes. Only difference is the reversing valve. It is reversed on ...
Central Air Conditioner not cooling7/20/2009
  Q: I tried to run my a/c today for the first time this year. After 3.5 hours of running the unit I ...
  A: Hate those meters John since you can't tell why the cooling stopped. The ambient air test was for ...
Central Air Conditioner not cooling7/20/2009
  Q: I tried to run my a/c today for the first time this year. After 3.5 hours of running the unit I ...
  A: Usual problem John is it needs freon. But check to see if the outside unit is running at all. \ Is ...
Custom Air Filter Size for Carrier 58GP100-3 Series 3117/19/2009
  Q: I live in a house built in Dallas FOrt Worth in 1968. It's a two-story house with a simple return ...
  A: Carrier is famous for requiring special size filter ! Any a/c supply house can order a specila ...
rooftop ac7/18/2009
  Q: this deli was having problems with rooftop 5 to 10 ton unit (not sure of size) it was going off and ...
  A: Sounds familiar for commercial rooftop stuff. Is the nameplate still visible ?? That ought to give ...
hermetic compressor amperage7/17/2009
  Q: Howard, I've got a three ton residential condensing unit that I am having problems with wires ...
  A: Burned wires are caused by bad or rusty connections. Every compressor is different & there are ...
Lux programmable thermostat7/15/2009
  Q: I am a little experienced in HVAC/electrical but I need some help with this one. I bought a Lux ...
  A: Best one is don't buy any more Lux stuff !! I'm sure not acquainted with any of the programmables to ...
a/c exterior fan not moving7/14/2009
  Q: I noticed recently one of the two exterior fans is not moving and hums. I dont know what to call ...
  A: Sounds like the bearings are worn for what happened. I'd suggest getting some oil on the bearings ...
a/c exterior fan not moving7/14/2009
  Q: I noticed recently one of the two exterior fans is not moving and hums. I dont know what to call ...
  A: both of the fans are needed for the cooling. The trouble may be just a capacitor for the dead motor. ...
A/C Question - Goodman CK-42-1B7/12/2009
  Q: when that satisfying sound of the compressor springing to life stopped happening and just the fan ...
  A: Well hello again Don. I have been in this business since 1973 & it has always been fun(well most of ...
AC fan stays on after AC is off7/12/2009
  Q: Replaced an old t-stat recently with a new programmable t-stat (ritetemp model 6025). Initially had ...
  A: The O is not to be connected to O. Is this a heat pump ? Doesn't seem to be. The white is for heat, ...
A/C Question - Goodman CK-42-1B7/12/2009
  Q: when that satisfying sound of the compressor springing to life stopped happening and just the fan ...
  A: nice to have good info like yours. Need to test the run capacitor for the compressor first.May be a ...
Raindown furnace flu7/11/2009
  Q: Howard. I'm having a problem with rain coming down the "inside" of my Gas furnace flu. I have tried ...
  A: wishyou would send the rain over here in TX. We are 106 every day, no rain, Only thing I can imagine ...
air running (not continuous) - apt humid!7/9/2009
  Q: Livingston, Thank you so much for being there for all of us who are out here (literally)sweating ...
  A: Gladto "try" to help your not=to=good situation. Hope for your comfort & recovery. I have ...
attic fan7/9/2009
  Q: I am planning installing an attic fan in my 2-story house. My attic size is approximately 1200 ...
  A: The soffits vents will work === but if you remove one you will probably see a much smaller hole has ...
Air Conditioner kicks off breaker7/6/2009
  Q: As the weather warmed we noticed our AC was not working on the main floor (we have a separate unit ...
  A: Could be a bad capacitor on the outside unit fan. Have you watched the unit while it was running ?? ...
No Cool Air After PG&E Smart AC Program7/5/2009
  Q: My question is... My central AC worked great until last Tues. afternoon when during the sweltering ...
  A: Oh Jennifer, never saw so much ineptitude in one place !! The guesswork on the 50 amp breaker shows ...
carrier unit condensor valve cores7/5/2009
  Q: Do older Carrier units have a valve core on the suction side that cannot be removed if they are ...
  A: Been at it since 1973 & have never seen a unit without removeable schrader valve. What can happen is ...
Roof top AC7/4/2009
  Q: I have a 1976 Coleman rooftop AC unit on my Motorhome, It runs OK, not the coldest, but after a ...
  A: sually there is not a service valve on those things. But you can buy a clamp made for the diameter ...
Roof top AC7/4/2009
  Q: I have a 1976 Coleman rooftop AC unit on my Motorhome, It runs OK, not the coldest, but after a ...
  A: 33 years old !!!! They made good stuff then. Not anymore. Fan motors is the favorite thing to ...
Goodman GMP07-37/3/2009
  Q: my Goodman unit's inside fan is running constantly. The outside unit will not turn at all, no fan, ...
  A: Manually press in the contactor in the outside unit & see if it runs. Test the freon to see if has ...
tapping into air ducts7/1/2009
  Q: I finished our basement a few years ago and did not think we needed to tap into the ducts for air. ...
  A: you can do it. Whatever size duct you tap into you would need a Y fitting with a 45 deg side outlet ...
Carrrier Furnace 58XTS070 placement7/1/2009
  Q: We got this Carrrier Furnace 58XTS070 last year when it was installed in downflow format. We are ...
  A: I presume the furnace is electric heat ?? The coil drain pan & drain lines is the problem. I don't ...
New AC Unit tripping breaker6/30/2009
  Q: We have a 14 seer Goodman unit that is 13 months old. On Saturday we noticed there was no cold air ...
  A: I would start off replacing the circuit breaker. They can fail like everything else. Did the tech ...
Iced Pipe on Trane Unit6/29/2009
  Q: We have a Trane XL19i Super High Efficiency heat pump that was installed in 2004 that doesn't seem ...
  A: Hate to say it but these evaporator coils they make nowdays can start leaking in a couple of ...
SWAMPED PACKAGE UNIT6/29/2009
  Q: I probably have a wild question, but I'm looking at 2 International Comfort Package units: ...
  A: Look at the serial number for a year date in it. Like 184702432. See the 02 ?? I'd think if they are ...
AC variations6/28/2009
  Q: My wife has a problem with the bedroom temperature in the summer. She is complaining that our AC ...
  A: I would suggest a new thermostat, like a Honeywell gold round one from Home Depot or elsewhere. They ...
Central air6/26/2009
  Q: Help! On house is on the market and we just realized our central air isn't working. We want to fix ...
  A: Got my email ?? Its a control circuit problem. !!! So lets carry on with the diagnosis. It can be ...
low voltage problem6/26/2009
  Q: okay let me start by saying i am a residential/commercial service tech. my question is one, more for ...
  A: Are you getting 24 v between Y & C on the board WITH THE RED & WHITE wires to the outside unit ...
Evaporator Coil/Furnace6/25/2009
  Q: I had and two ton condenser installed last year. When I turned the air on this year, the thermostat ...
  A: 1. Only if enough oil has leaked out with the freon. Generally does. 2. Look below the burners for ...
hvac6/25/2009
  Q: Our air handler is (Friedrich) over 22 years old and the compressor is dated 1991, very few problems ...
  A: Florida is the best place in the country for heat pumps. You hardly EVER use the electric heaat. Its ...
Evaporator Coil/Furnace6/25/2009
  Q: I had and two ton condenser installed last year. When I turned the air on this year, the thermostat ...
  A: 1. Yes just find one that fits the case. 2. Not unless the heat exchanger is rusting out. 3. Usually ...
Heating, Air Conditioning HVAC - Rheem Classic 10, fuse6/25/2009
  Q: Everything (heating or AC) was working before. I turn on AC this year, control board fuse always ...
  A: Now its getting wilder Steve. I would disconnect the 2 wires to the outside unit at BOTH ends. With ...
hvac6/23/2009
  Q: We installed a new frigidaire hvac unit in 2004. We have had nothing but trouble w/ the temperature ...
  A: Reminds me of a problem with 2 heat pumps 2 friends had installed themselves. Both had compressors ...
GMC Furnance6/22/2009
  Q: Last year the AC tubing(copper)had ice on it. Had it checked to see what was causing the freeze up. ...
  A: It's 103 down here in Texas now Ramona, cooling is valuable, right ? The place to start on the unit ...
HVAC Dual Zone6/22/2009
  Q: My father-in-law has a dual zone system in his house. The house is about 1500-1600 square feet on ...
  A: Common problem with 2 story houses & an open stairwell. Difficult to fix since the cool air upstairs ...
hacv6/19/2009
  Q: Had my system repaired,condensing coil,blower motor and fin,charged system. -This is a slit system ...
  A: New repair parts work as good as old parts. If you have an electric furnace the elements can ...
HVAC6/17/2009
  Q: I have a model: E2EB-017HA 4ton unit. Ihave had the inside and outside coils cleaned, the technician ...
  A: Have you tested he run capacitor for the blower motor ?? How about the current draw when the motor ...
A/C cooling but home is hot6/15/2009
  Q: ! We have a Coleman blend air system - 4 ton in a 1782 sq ft mobile home built in 1996. Over the ...
  A: This sorta IM, right ? I'm retired so check in often. Keeps my brain active. The return is onthe ...
A/C cooling but home is hot6/15/2009
  Q: ! We have a Coleman blend air system - 4 ton in a 1782 sq ft mobile home built in 1996. Over the ...
  A: That phrase "it's doing all it can" is familiar. I've used it myself so I would accept that it is ...
Condensation pan shut off6/14/2009
  Q: Our AC shut off because the condensation pan was full. I emptied the pan, found and (hopefully) ...
  A: You have an emergency float switch on the drain line ??? Either that or a condensate pump are the ...
HVAC air distribution6/13/2009
  Q: I have a RUUD system in my house (Heat pump model # RPKA-031JAZ and air handler # RBHA-17J11NFDAI). ...
  A: You have an "extended plenum" duct system now. They work if, after each drop to a room the size ...
Circuit Breakers6/12/2009
  Q: In general, can a "defective" circuit breaker fail to pass electricity while in the "on" position ...
  A: good question. These things can be deceiving.hey will not reset to the ON position. Maybe a little ...
Split AC Not Cooling6/11/2009
  Q: I have a 1 ton videocon split air conditioner at my home. Most of the time it does not cool i.e. the ...
  A: You need to go see if the outside unit is running when the thermostat is calling for cool. Hold your ...
P traps6/9/2009
  Q: We have an inspector that is telling us that we HAVE to install P traps on A coils on top of ...
  A: Well I'm not much on codes. They are different in different places. I agree with you after 30 yrs ...
heat pump blower quits sometimes6/8/2009
  Q: I'm running my air conditioner, and I noticed that the blower is quiting at times and sometimes not ...
  A: The blower is triggered to run by the thermostat on a call for cooling. Check behind the tstat for a ...
Hight pitch noise on the A/C furnace, only on summer6/6/2009
  Q: is my second summer in a row with a high pitch noise coming from the A/C furnace. It only happens ...
  A: Well, I was going to say air noise but not ! There has o be a restriction in the high side liquid ...
Commercial AC Temp Control6/6/2009
  Q: I work in a 4 story building, 40,000 sq ft/floor. We are working hard to be green. We are in the ...
  A: Keep the fans running all the time & set the temps up to about 81 - 82. That is comfortable with air ...
Corroded coils on furnace6/5/2009
  Q: An HVAC technician just left after inspecting my upstairs unit, Carrier 38YCC, which is a little ...
  A: I presume you are referring to the evaporator coils ?? They are normally made from aluminum fins & ...
problem with control circuits6/5/2009
  Q: I have an HVAC degree and i am pretty decent with troubling shooting until it comes to double wides ...
  A: Electrical skills in this A/c business determines whether you are good or not. I worked with a guy ...
American Standard Freedom 90 blower problem6/5/2009
  Q: I have an American Standard Freedom 90 furnace with a brand new (yesterday) American Standard ...
  A: When in cool mode the thermostat activates the inside fan when cooling is activated. If you have a ...
Multivolt gas valve6/4/2009
  Q: My son has a gas pool heater that has a White Rodgers Multivolt gas valve with a 250 milivolt pilot ...
  A: The generator does hold the knob down on the gas valve. Its not producing the 750 millivolts to do ...
Snyder General Fan Won't Stop Running6/2/2009
  Q: Howard, I have a Snyder General Comfortmaker model # GUF100A012AN. The AC and Heating systems seem ...
  A: all those folks are correct. Your problem is "most likely" a stuck fan relay. You have a circuit ...
evaporator water problem6/1/2009
  Q: I have a trane vertical air handler with the coil at about a 60 degree angle. This system is about ...
  A: The fins are spaced to retain water. Your fins may look clean but have collected crud over the years ...
AC Unit Float Switch question5/29/2009
  Q: I have a Goodman air conditioner that was installed brand new in my condo in May 2005, when it was ...
  A: I don't dig the 2 pipes coming from the evaporator coil ? Something different here. Anyway, the ...
Frozen AC pipes and AC runs as heat pump5/28/2009
  Q: I got a new Goodman 5 ton heat pump system in Dec 2006. The system worked well until Jan 2009, at ...
  A: Looks like a stuck closed contactor in the outside unit. Running with out an inside blower causes ...
AC Unit Float Switch question5/27/2009
  Q: I have a Goodman air conditioner that was installed brand new in my condo in May 2005, when it was ...
  A: Ah, those float switches are there as an emergency only. Don;'t need them if the drain line for the ...
air conditioner output air temp5/27/2009
  Q: what should the temperature of the air coming out of the room register while the air conditioner is ...
  A: Good question, Jim but tricky. An eveporator coil operates at 70 deg. BUT, from there a bunch of ...
rotten egg smell5/26/2009
  Q: HOWARD---THIS IS NOT A QUESTION BUT THIS SAME SMELL HAPPENED TO US WHEN WE GOT OUR NEW HEAT PUMP ...
  A: Are you the one that reported the smell a few days ago ??? I had another question about that & don't ...
Luxaire a/c unit loses all freon 4 years in a row5/25/2009
  Q: The short of the story is this: I had 2 Luxaire Outdoor Split-System air conditioners installed in ...
  A: Freon leaks can occur ANYWHERE !! A 7 day leak should be able to be heard 100 ft away. But I have ...
No Power5/25/2009
  Q: we have a Heil DC 90 Ultra High Efficiency with model # beginning with NTGM. We have not used our ...
  A: Wait to call a tech. This is for free. Look for a 3 amp fuse, automobile type, plugged in to the ...
restart eletronic furance5/24/2009
  Q: windy weather,so the gas furance and water heater went out. started the water heater,no problem. ...
  A: How about 85 in Texas.Gas pilot lights are blown out by high winds bacck pressure down the flue ...
Somewhat of a rotten egg smell emitted out of a brand new system5/24/2009
  Q: Howdy sir. I will try to use to use all the technical lingo I can, and what I have tried so far to ...
  A: Jon, I have the answer !!! Just got a reply from "Shirley" that solves the problem. The rotten egg ...
Central Air Install/Quotes5/23/2009
  Q: I have been getting estimates for central air install w/duct for my old colonial home in northern ...
  A: The only advantage I've seen for variable speed blowers is quiet. If a return air grille faces a ...
Janitrol compressor trips breaker5/21/2009
  Q: I have a Janitrol compressor that occasionally trips the breaker. If I reset the breaker (off and ...
  A: Good question, difficult to answer. Many things can be the fault. First try tightening all the ...
A/C charge5/19/2009
  Q: should refrigerant be added until the sight glass shows no bubbles?Does this work on all systems?No ...
  A: It's better than nothing Gregg. But it can show bubbles & be over/under charged. The type of ...
mold in air duct system5/19/2009
  Q: Cladosporiium and another non flower mold was identified to be in my flexible air duct system ...
  A: Duct cleaning in flexible ducts is no good. Probably will tear them up with that plastic tube. ...
smell of natural gas5/18/2009
  Q: Mr. Livingston, I am hoping you can give me some direction concerning a problem with my Central A/C ...
  A: Glad its not CO are you'd be a goner. Couldn't smell it anyway. Is the furnace a gas unit ?? You ...
noise from Lennox G40UH xseries5/17/2009
  Q: Howard, thought I might need to change a fan belt or oil a motor but now I see no belt...squealing ...
  A: Belt driven blower motors stopped many years ago. Sure had to keep many, many sizes on the truck. No ...
Rheem heat pump indoor motor does not run5/17/2009
  Q: Howard, I have a 1991 Rheem 2.5 ton all electric heat pump system. In cool mode, the indoor motor ...
  A: If the furnace controls is a solid state circuit board the fan replay is a little black box on the ...
Rheem heat pump indoor motor does not run5/16/2009
  Q: Howard, I have a 1991 Rheem 2.5 ton all electric heat pump system. In cool mode, the indoor motor ...
  A: In cool mode & fan in auto, the thermostat turns on the fan. If you have a digital tstat, have had ...
CO Level5/16/2009
  Q: What level of CO is acceptable in the airstream heating the living area?
  A: Good question, difficult answer. That's because everybody has different tolerence to CO. Thats why a ...
AC question5/15/2009
  Q: I own a condo with roughly 1500 sq ft of livign space (2 stories). The AC unit (which is a heating ...
  A: WOW !!!! 10 grand !! Must be awful hungry.Talk to your neighbors or friends for recommendations of ...
temps5/15/2009
  Q: Is there a standard for temp differences from outside to inside to determine how well insulated a ...
  A: Good question. There is a rule of thumb that is surprising. Here it is. With a good accurate ...
Cold Room Air Flow5/12/2009
  Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ...
  A: From the installations I have done a 6' line can only cool a small bathroom !! And a 4"ine to a ...
Cold Room Air Flow5/11/2009
  Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ...
  A: Got a chance to respond today. 20 ft for a 6 " ?? Does the "extended supply air plenum" it's called ...
Cold Room Air Flow5/10/2009
  Q: Firstly thanks for any help in advance. I have a upstairs bedroom that is partially over a garage ...
  A: A 6" duct will not supply very much air more than 10 feet length.Was that room added or is the 6" ...
One room hotter than the rest5/8/2009
  Q: I’m sure you hear this one a lot. I bought my house last summer. It was built in 1995 and is about ...
  A: It's a shame the duct systems are installed so badly.Air distrubition is so important. It adds to ...
Compressor terminal prong corroded5/7/2009
  Q: I have a Bryant split AC system installed in 1997 (Model # 561CJ030-C). It tripped the circuit ...
  A: Hope thats all it wasn the burned terminal. Is there ANY stub left on the compressor terminal?? If ...
fan doesnt always come on5/6/2009
  Q: Big fan doesnt always come on when air condition is running on outside gas heat and air? Is this ...
  A: Whoa ! A different picture ! It's icing over the evaporator coil, blocking the air flow. Probable ...
Carrier Infinity 96, 40000 BTU5/5/2009
  Q: We've just had this unit installed after our old oil furnace went kaput, using the same duct work ...
  A: Fans has speed adjustments but the increase from one to another is 50 rpm. Not much but can help. ...
A/C Brands5/5/2009
  Q: I think we're going to replace our central air unit this summer. Do you have any preference on ...
  A: How much money you have ??? I'm a "conservative" ie tightwad. Make sure the new stuff uses R 410a ...
Outside Unit - Fan & Compressor not turning on - electrical?5/4/2009
  Q: I'm hoping you can help me out with my Bryant Air Conditioner outside unit. The outside unit won't ...
  A: Start off testing for power supply to the outside unit by pressing in the start relay manually. If ...
Coile and duct work needed5/3/2009
  Q: I have a 5 year old 4 ton system that continues to freeze up. I am constantly told the Freon is ...
  A: You need more bids. At least 2 more. Ask your neighbors for their recommendation or co workers. Your ...
wiring for 24 volt transformer4/29/2009
  Q: I put a new control or mother board on a goodman heat/air unti, wiring a 110/230 24 volt transformer ...
  A: Well, the control circuit board controls the heating unit, so the transformer has to connect to ...
Trane XT500C heat pump wiring4/29/2009
  Q: I have a trane heat pump xt500c thermo. and am trying to find out what each wire goes to so I can ...
  A: Heat pump tstats have changed lately. Have had trouble myself matching the combination terminals ...
HVAC Duel System4/27/2009
  Q: I just bought a home with a Duel zone system, one for upstairs and one down. My question is: when I ...
  A: hat's a good one, Michael ! Maybe there is a diverter in the ducts somewhere is all I could imagine. ...
Home A\C compressor4/26/2009
  Q: I have a Lennox outside unit and a Comfort air inside unit. The comfort air furnace and evaporator ...
  A: Sounds familiar. They were welding freon lines on the changeout & a weld is leaking all the freon - ...
weather king AC unit4/26/2009
  Q: My puppy was chewing and yanking on the wires coming from our house to the AC unit. The thermostat ...
  A: Need to enclose those wires in fence wire. Once the dog chews on them it will not stop. Consequences ...
outside fan want turn on but inside blower want stop running4/25/2009
  Q: when i turn t-stat to cool auto or on the outside fan want turn on you can hear a click in the ...
  A: Check the circuit breaker for he outside unit first.If OK, manually close the start relay with a ...
Size and distance intake line from unit4/24/2009
  Q: Our exterior 3 1/2 ton heating/air condition unit is current located on the southern exposure, which ...
  A: Need some clarification. That 16" line is a round duct 16" in diameter ?? That is the return air ...
Rheem RPKA-037JAZ4/22/2009
  Q: The heat pump will not turn on. On the outside of the unit is a reset button. The schematic calls it ...
  A: That's a high pressure switch. Main cause to trip it is a bad condenser fan motor. Does he fan run ...
venting three dryers in line thru flat roof4/22/2009
  Q: Howard we are renovating a three family house with washers and dryers on each floor to vent the ...
  A: W hen the 3 vent lines merge, the diameter of the duct should increase to 3 times the area of one 3" ...
air conditioning4/21/2009
  Q: What is the correct way to measure super heat in an a.c. system, wet bulb temp and dry bulb temp?
  A: The old fashioned way, like me. It is: measure the suction pressure & convert it to temperature. ...
AC unit age and warranty4/19/2009
  Q: I have a Rheem CriterionII. The inside fan stopped working. Is there a way I can find out how old ...
  A: Nice to have a rough idea of its age to find the date. for 1990 it may read 1469047.hat motor is ...
replace EVAP coil4/15/2009
  Q: Howard, I have a 5 yr old Goodman split heat pump. Two yrs ago i had to add refrigerant an now I am ...
  A: Where do you live, California ?? Run the guy off with a stick. Try this, there is a liquid you can ...
Split System Central AC4/15/2009
  Q: I have a split system central AC in my condo. Compressor unit is on roof of three story building ...
  A: Upthere all you need is a block of ice & a fan for cooling ! No problem for the distance between the ...
Split System Central AC4/14/2009
  Q: I have a split system central AC in my condo. Compressor unit is on roof of three story building ...
  A: Big expensive problem for a 3 story roof! Sometime a crane is necessary to access the roof. Could be ...
a/c installation4/13/2009
  Q: I had a Trane split system installed last week.The outdoor unit is 1 1/4" out of level.The ...
  A: There is about a qt of oil in the compressor that is oiling the bearings. There is some tolerance on ...
Leaking Evaporator Coil4/13/2009
  Q: I currently have a split Lenox Unit (11 years old) and the Evaporator Coil has a leak. The company ...
  A: That point of a matching SEER system, in & out can bring about a HUGE discussion! Some brands say ...
seer versus tons4/9/2009
  Q: What is the difference between seer and ton? We are getting ready to get a new system for the house ...
  A: 1980 !!!! Cheez, that's great ! You can't ever tell how long these things will run. But one thing ...
seer versus tons4/8/2009
  Q: What is the difference between seer and ton? We are getting ready to get a new system for the house ...
  A: Seasonal Energy efficiency rating = watts/ hours. one ton = 12,00btu.@95 deg. Bet you've heard a LOT ...
bathroom exhausts:energy efficient?4/8/2009
  Q: do bathroom exhausts suck the heat/air out of your house. i always turn them on for white noise in ...
  A: Uh oh, a family discussion ?? A bathroom exhaust fan moves about 50 cfm.A 1500 sq. ft house has ...
central heat unit4/7/2009
  Q: I have an American Standard central heat and air unit. I am unsure of the size. The air works great ...
  A: Those switches are around the burners & are small red switches. Sopme have a reset button that pops ...
24v control wiring to outdoor unit.4/6/2009
  Q: I am having a problem getting 24v to my outdoor unit. there was two transformers on the system one ...
  A: You have a dog in the backyard that has chewed on the wire ?? Common problem. Can be a mouse in ...
Digital thermostat for Mobile Home4/1/2009
  Q: I live in a 1994 mobile home 16x80 & want to change to a digital thermostat (Honeywell RTH230B) my ...
  A: The red & white wire was for heat ONLY. Moving the red wire to Rc is OK but the white wire to Y is ...
HEAT PUMPS3/31/2009
  Q: Sir, I would like to ask you if you think a heat pump is recommended for my area for a new AC and ...
  A: Florida is the best state for heat pumps. Go for it. Just check the run amps comparison between the ...
Proper HVAC size for house3/30/2009
  Q: Howard: we bought a 750 sf, one level, circa 1935 cottage on Va's eastern shore. Crawl space newly ...
  A: Heat pumps are for Florida, NOT Virginia ! You would be running electric elements most of the Winter ...
Air return sizing3/30/2009
  Q: I have discovered that whoever installed my HVAC system did it in a strange way. There are filters ...
  A: I have a 3 ton cooling system & have 400 sq. in. grille.But I could use any number of RA grilles as ...
Proper HVAC size for house3/30/2009
  Q: Howard: we bought a 750 sf, one level, circa 1935 cottage on Va's eastern shore. Crawl space newly ...
  A: Ducts nowadays are flexible stuff but with good insulation(1.5")But would you have any space for a ...
Air return sizing3/30/2009
  Q: I have discovered that whoever installed my HVAC system did it in a strange way. There are filters ...
  A: Are these returns near the floor in several places around the house ?? There should not be any ...
Furnace problems3/28/2009
  Q: I'm currently having some trouble with my furnace. The Thermostat seems to be working fine. I can ...
  A: Those switches are pretty standard among most brands. First tho, detremine whether the switch is NO ...
Gas Furnace/White powder buildup3/27/2009
  Q: Yesterday my carbon monoxide detector went off. I had someone from the gas company come out and ...
  A: Is this a standing pilot type furnace ? Some kind of powder is typical for this type, but not very ...
Furnace problems3/27/2009
  Q: I'm currently having some trouble with my furnace. The Thermostat seems to be working fine. I can ...
  A: The key here is " it won't even light up".If the draft motro runs on a call for heat, the air ...
Zone vs. Variable Speed Heat and AC3/26/2009
  Q: I have a 3-story house and installing central air. I have been told to get a 2-zone system in order ...
  A: A 2.5 cooling system will produce only 1000 cfm. Not very much air. Since cold air falls you need 2 ...
Furnace problem with ignition3/26/2009
  Q: My daughter has a Rheem Criterion Gas furnace Model RGDJ 07EAUER Serial # EB50302F400001836. It ...
  A: Does the igniter glow ? If so, several events are OK. If it does, & there is 24v at the gas valve it ...
HVAC3/26/2009
  Q: I am involved with a Temple, and I am not sure if we are getting the run-around. We replaced all the ...
  A: Wow, Rick, never heard of that kind of problem. An a/c unit will run in 20 deg weather.Can't think ...
thermostat3/17/2009
  Q: Six month old digital Honeywell thermostat keeps going from "heat on" to "aux heat on" but heat ...
  A: So your aux heat is for the electrical heat elements.If the tstat is auto shifting to aux heat I ...
Heat Pump3/17/2009
  Q: I have a trane xb10 heat pump, standard airhandler with 1/2 HP motor heat strip BAYHTR 1415 backup ...
  A: Heat pump in Maryland noi good. That system can only provide enough heat down to about 32 deg in ...
Payne Furnace...no heat3/15/2009
  Q: We have a 14 yr old Payne downdraft furnace up in the attic. It was forking fine until this morning. ...
  A: Getting closer Albert. Some of those igniters are ceramic & they can develop a small crack from the ...
rheem home central heating & cooling unit3/14/2009
  Q: gas burner on unit wont lite. put new gas valve on but stll no burnner. piolt does stay lit
  A: An old style furnace, I gather that has a standing pilot ?? Is there any high temperature switches ...
heating3/13/2009
  Q: My emergency heat light will not go off when the heat is running. It worked fine earlier in the ...
  A: Your elecric bill is up since emergency heat is only electric elements are operating. Does every ...
condensing unit lowside and high side fluctuate3/12/2009
  Q: Please! Help. Last summer I had four units the same problem. 1st Weather King, 2nd Ruud, 3rd ...
  A: You in the a/c business, nuoc ?? The description you give sounds typical for a dreaded disease ...
thermostat replacment3/11/2009
  Q: i wanted to replace my central ac thermostat with a digital one when i did sparks flared up and it ...
  A: Something funny here since "normally" those 4 wires are from the same side of the transformer. So ...
Payne Furnace...no heat3/11/2009
  Q: We have a 14 yr old Payne downdraft furnace up in the attic. It was forking fine until this morning. ...
  A: If the draft motor runs & no igniter glows, it the air pressure switch that's bad. Insure the hose ...
Heating3/8/2009
  Q: I have a Carrier forced air unit for our heating and air conditioning. Everything works fine but ...
  A: You must have an older gas furnace. If so, the fan/limit switch needs adjusting to control the fan ...
3600 sq ft ranch in nh-size of furnace needed3/5/2009
  Q: We just put a 1600 sq ft addition on to our ranch to bring total sq ft to 3600 (existing on slab, ...
  A: Like blowing in a bottle, when the pressure is maxed, no more pressure is possible, So when the ...
Question about HVAC (Gas heat)3/5/2009
  Q: Where can I find the fuse for a tempstar Dc90 ultra high efficiency gas heating system? The system ...
  A: If there is a fuse on the module it is a plug in auto type, 3 amp. That is only a protection for the ...
3600 sq ft ranch in nh-size of furnace needed3/4/2009
  Q: We just put a 1600 sq ft addition on to our ranch to bring total sq ft to 3600 (existing on slab, ...
  A: Easy question Bonnie, difficult to answer. The new way to run a heat load analysis is with a ...
payne furnace3/4/2009
  Q: The furnace was working last nite now over nite it will not come on. Checked thermostat when it was ...
  A: Does the lighting sequence of: Draft motor runs, air pressure switch closes, igniter glows, burners ...
AC forced air unit leaks freon3/3/2009
  Q: I had to have my outdoor AC unit completely charged w/ freon last spring. My HVAC guy told me that I ...
  A: 90% of freon leaks are in the evaporator coil.Sometimes a sealer can be added in the system that ...
Furnace working (or not) intermittently3/3/2009
  Q: 3 year old American Standard Freedom 90 Single Stage locks out intermittently (usually at night). ...
  A: Been at it 30 yrs never heard of "backfeeding" !! Have you tried reversing the power supply to the ...
Furnace3/2/2009
  Q: I have a Lennox G21 pulse furnace. Last night the furnace didn't fire up. There was a humming sound ...
  A: Sounds like a lemon to me ! I would call the local Lennox sales manager for your area & tell them ...
A/C tonnage rating3/2/2009
  Q: As best as I can determine from the internet, all the manufacturers have a/c in half-ton increments ...
  A: I did throw you a curve. Yes, you are correct about the Goodman. That is; a 3 ton condensing ...
Furnace3/1/2009
  Q: I have a Lennox G21 pulse furnace. Last night the furnace didn't fire up. There was a humming sound ...
  A: The last thing you want to do is replace the module. You are resetting the module with the off/on ...
A/C tonnage rating3/1/2009
  Q: As best as I can determine from the internet, all the manufacturers have a/c in half-ton increments ...
  A: Sometimes the evaporator coils are the same, the expansion device(which is a hole)is just a bit ...
Gaffer & Slatter furnace2/23/2009
  Q: My condo has a G & S furnace. I replaced the old dial style of thermostat with a Honeywell digital ...
  A: Again. One more clarification. Are the burners still fired up or is it just the blower still running ...
Rudd Silhouhette II Gas Furnace 4 Blinks2/22/2009
  Q: My Rudd Silhouhette II Gas Furnace will not start and the Normal green light is flashing 4 Blinks ...
  A: Check the air hose from the draft motor to the switch, blowing thru it for blockage. Check the ...
Options for oversized A/C2/21/2009
  Q: Howard, My family just moved into a 3200 sqft house in Houston, which was built in 1993. It has a ...
  A: Good thinking Bill. In Houston you will need everything you can afford to cut the big electric ...
New construction HVAC2/19/2009
  Q: Is a gas heat/elec AC outside package system less costly than a split system? It seems like a ...
  A: A package unit is more costly.The unit is more costly & the ducting connecions is more difficult ...
heater not working2/19/2009
  Q: When i turn the thermostat to heat/auto the furnace tries to kick in for a couple mintues then shuts ...
  A: You've got to do some diagnosing yourself before I can help you. Namely, open the furnace to watch ...
Return size2/18/2009
  Q: I have a 5-ton York split system. My installer put in a 20" x 20" return with a 16" duct. I have ...
  A: The return air duct is sized to produce an air velocity of 400 cfm or less. I do not have the chart ...
code requirement for supply air filter2/18/2009
  Q: What is the code requirement for installing filters on the return air ducts serving the heating and ...
  A: Every state probably has there own codes. But there is a Universal Mechanical Code that all states ...
Heil DC90 Ultra High Efficiency Furnace2/16/2009
  Q: I have a Heil DC90 Ultra High Efficiency Furnace which stopped working over the weekend. My Direct ...
  A: CO can affect different people different ways. Some can die when others are barely affected. Also, a ...
furnace air flow with bigger pulley2/15/2009
  Q: Last summer I had ac installed in my house that did not work properly. My furnace is a Lennox that ...
  A: Sure can't see the air volume increase will affect the furnace for heat. You may see more affect on ...
furnace won't stop running and sometimes won't fire2/15/2009
  Q: I have a Goodman Gas Furnace. It is about 5 years old. The other day my husband and I noticed that ...
  A: Replaced in warranty only keeps the original warranty length in place. Some can be expensive, some ...
AC Unit Hard Start Kit for Dimming Lights2/13/2009
  Q: This is the second home that I have had on this property. The first home I went through two ...
  A: Powersupply to the house is inadequate. Somewhere in the electrical power circuit the wire is too ...
Location of Filter for RUUD AC Model UENB 1008 BDS2/12/2009
  Q: I am visiting my 96 year old mother in Florida and opened up her AC unit to replace the filter. I ...
  A: I presume the furnace is NOT in the attic ?? If it is an uplow in a closet the filter would be at ...
Residential Gas Furnace2/11/2009
  Q: Is it ok to continuously run the fan on a residential gas furnace? We have a large expanse of ...
  A: Continuous fan is good for circulation for large homes. If you have a 2 story house the hot air ...
obsolete circuit board replacement2/10/2009
  Q: Livingston, I am getting a bit of a run around from various HVAC guys and am looking for some ...
  A: Good for you, Elaine. You will have to rely on the schenatic posted somewqhere on the furnace.Use ...
Furnace to coming on2/9/2009
  Q: I do home repairs for a living and have a little experience with heating and I'm pretty good with ...
  A: Sure don't have an idea what's going wrong.Those code flashes on the led's sre generally OK for ...
Thermostat2/8/2009
  Q: I am changing from a Chronotherm III to an Emerson 1F95-1277 thermostat. Current wires on ...
  A: New kinds of thermostats for heat pumps can be difficult. Can only say what is "normal" for the ...
Kenmore Heating and air unit2/8/2009
  Q: i have a Kenmore model NTC6100GFA1 system that was installed 9 years ago.I recently have lost heat ...
  A: Several problems at once. The fan circuit is on a timed cycle with the heat. Think the fan relay on ...
ac air return2/7/2009
  Q: I live in the Northeast. My AC is in the attic, (heat is baseboard so no connection)Home is 5 years ...
  A: Air doesn't move withou a pressure differential. Most likely that is occuring between the return air ...
Gaffer & Slatter furnace2/6/2009
  Q: My condo has a G & S furnace. I replaced the old dial style of thermostat with a Honeywell digital ...
  A: Steven. When the furnace is set to run on the thermostat, let it stabilize for a bit. Then urn the ...
carrier gas furnace2/3/2009
  Q: I have a carrier gas furnace plus 90 that was installed in 1993. The furnace is a sealed system so ...
  A: Doesn't that furnace have an led trouble light that flashes codes that can tell you where the ...
obsolete circuit board replacement2/3/2009
  Q: Livingston, I am getting a bit of a run around from various HVAC guys and am looking for some ...
  A: Don't know about D & L Supply, but I would relay on the local RUUD supply house to sell me the ...
No Heat.1/16/2009
  Q: I came home tonight to find no electricity in my apartment. After I fixed that I noticed that my ...
  A: Turn on the fan to"on". Does the fan run ?? That's a test for power, low & high. Is there a pilot ...
furnace exhaust blower condensation1/16/2009
  Q: This is about 18 years old Heil furnace.I've replaced noisy exhaust blower, cleaned all drain tubes. ...
  A: This condensate problem is a difficult issue.A hot exhaust moving thru a cold pipe is hard to stop ...
heating and air1/14/2009
  Q: i got a loud noise from my ac unit outside, i have electric central heating and air, i went outside ...
  A: You must have a heat pump. The ice formation is natural & is thawed by a defrost cycle in the ...
wiring1/12/2009
  Q: i have zone heating. 2 stats. need to know how to wire control board. red. white wire coming from ...
  A: the heat contro; wires are red & white. The rest are for cooling & a fan.If each stat uses a red & ...
Air Handler Fan Will Not Run1/10/2009
  Q: I have a 1990 Amana Heat Pump. The inside unit blower fan stops running intermittently..... about ...
  A: I did not respond about the delay knnob since an ajustable knob would be a coil of wire with a ...
no power to furnace1/6/2009
  Q: My reheem furnace (model rgdg07eauer)is all of a sudden powerless, I check the circuit breaker,no ...
  A: There is a fuse on the board, generally. Its like an auto fuse & just plugs in. Usually a 3 amp. If ...
Central heat/ac unit that cools from a well?1/5/2009
  Q: I am looking at purchasing a house, that has a central heat/ac unit that cools from a well. I think ...
  A: The model number hides the tonnage, like ABC3602516. That 60 is 60k btu & a 5 ton.A 1600 sq ft may ...
Payne Force Air System1/5/2009
  Q: Fan is set on auto but when the unit is set to HEAT, the blower does not turn on. Angela
  A: The circuit for the heat fan is different from cool fan.Now, if you have a circuit board controlled ...
error code on armstrong furnace1/3/2009
  Q: My 8 year old furnace will not fire up by thermostat, unless i go to the side of the furnace turn ...
  A: Pull off the 2 wires at the pressure switch & ohm across the terminals to test.Thats a reset you're ...
Resize central hvac system1/2/2009
  Q: been awhile since I've talked to you.I installed a 3ton.Goodman 13 seer straight cool matched system ...
  A: The reversing valve is the question. Since heat is more important than cooling for people, the ...
Electric Baseboard/Thermostat12/31/2008
  Q: Howard: I just installed 220 volt hydronic baseboard units (TPI)in an atrium (the rest of the home ...
  A: Running late due to the holidays. The green ground wire goes to a bare ground wire, or to a water ...
Loud "bang" from air handler on Heat pump12/30/2008
  Q: I have a 1 1/2 yr old 4 ton Rheem seer 13 classic heat pump coupled with a rheem prestige air ...
  A: Could it be the blower motor inside ??? Quick test, turn on fan to on only, when up to speed turn it ...
Ignition Failure, Gas Forced Air Furnace12/29/2008
  Q: I have a Frigidaire FG6RA 072C-12A - Nordyne. There is a red light that blinks 4 times. The ...
  A: Ground wires screwed to a metal surface can corrode. Sand off the metal at contact. Just watch the ...
refrigerated air conditioners12/28/2008
  Q: I want to start investigating refrigerated air conditioners. I have searched the Internet and can't ...
  A: Happy New Year Sharon!Hope your Christmas was great. A rule of thumb to size is 500 sq ft /ton ...
Direct vent propane wall heater12/27/2008
  Q: I have a 1 yr old Cozy direct vent propane wall heater. It works well, but only stays on for about 3 ...
  A: There is a hidden overheat switch somewhere near the top of the heat exchanger that may be tripping. ...
hi howard12/27/2008
  Q: i have a clare megasave furnace. the motor went on in las t night. go figure huh christmas and all. ...
  A: This furnace has spark ignition to a pilot light ?? If so, you may have a stopped up pilot orifice ...
no heat jus air from roofmount fau12/26/2008
  Q: MERRY CHRISTMAS HOWARD. I have a roof mounted fau the fan comes on but no heat . I looked and ...
  A: Test the air pressure switch by jumping across the 2 terminals. The ignitor lights after the ...
T-1250 pool heater12/25/2008
  Q: I bought this unit used and the person who had it never used it. I got the unit hooked up and the ...
  A: There is an axiom in the service business, Werner, "if you touch it you're married to it " That's ...
Thermostat OFF, heat still ON12/25/2008
  Q: This senior citizen is ignorant when it comes to heating. Have 3-year-old Weil-McLain Series 3 ...
  A: Well, Santa Claus may be watching if you strip !! Turn off the power at the boiler to kill the heat. ...
Propane furnace gas surge12/25/2008
  Q: I have a Conquest 90 furnace (installed 1995) that started surging the flow of gas tonight. The ...
  A: Yes, there is a filter at the inlet to the gas valve. You know that condensate is possible in the ...
Heat Pumps12/24/2008
  Q: How can I tell if I have a bad reversing valve or a compressor issue.or maybe check valves The head ...
  A: It could be an electric heat element on, leaking seals in the reversing valve. Does a test of the ...
Furnace has to ignite several times to light12/24/2008
  Q: I have a Nordyne model#M3RL080ABW furnace that tries to ignite up to 4 times, which then shuts ...
  A: Is the ignitor glowing red ? And if the gas ignites on the main burner just a bit the flame sensor ...
goodman air handler and heat pump12/22/2008
  Q: Howard, My wife and I recentley purchased a older farm house. It was built in 1942. It has the cape ...
  A: Hope you live in Florida, or the South considering a heat pump. The heat from the compressor(1st ...
13 Seers vs 14 Seers12/21/2008
  Q: Howard, First off thanks for your time and making yourself available. I've got what i hope is a ...
  A: WOW, $480 !! No way. Know the formula for SEER ?? Its btu's per season divided by watts per ...
heatpump12/21/2008
  Q: I have a split heatpump when I turn the t'stat to heat and fan to auto only the indoor blower is ...
  A: Good info Phil. Has the freon been tested?? First thing to do on a heat pump. May be off from a low ...
Rheem Gas Furnance - Blower won't start12/18/2008
  Q: My Rheem furnance goes thru the start cycle and ignites but the blower wont come on...20 seconds ...
  A: Test the motor run capaictor first. You know how with an ohm meter ?? Then if it's OK, test the ...
Internal fan won't turn on unless U hard wire it/.12/18/2008
  Q: I have a Coleman downdraft furnace, the internal fan won't turn on, I tested the wires and there is ...
  A: Sorry, can't help you on those code signals. Are they not indicated on the manuals? Maybe on the ...
limit switch12/16/2008
  Q: My furnace is 11 years old, and i had to replace my limit switch because the electric pilot light ...
  A: Guess you are talking about the high temperature limit switches ?? Are those manually resets ?? If ...
Heat pump/electric furnace12/16/2008
  Q: Have older TempStar Heat pump w/electric furnace. Fan on heat pump working ok (but is running ...
  A: Generally. the output of the compressor heat(first stage) poops out around 32 deg. At that time the ...
heating12/16/2008
  Q: We have a newer two story home, but half of the 'second story' is a vaulted ceiling from the first ...
  A: The best answer, Matt is to have had 2 units installed, 1 up,1 down. Your on track to have ceiling ...
Furnace Operates Correctly in All Ways Except...12/15/2008
  Q: ... the heat output is low. [LIST] [*]Centurion Gas Furnace, 75,000 btu., with AC [*]Thermostat ...
  A: Wow, never got such detailed info in my 1860 questions I've answered !! Good for you.My big surprise ...
Electric HVAC12/14/2008
  Q: i recently had service done on my Electric furnance. The tech said that i am using only half(5 KW) ...
  A: If there are wires running to the elements & is connected to 240 volts you are getting full power. ...
gas furnace12/14/2008
  Q: have gas furnace with electric start-appears that it takes 5 or 6 times for furnace to light(Clicks ...
  A: Maybe needs a little cleaning around the spark ignition. Or can be a partially blocked pilot gas ...
No heat when it gets below 30 outside12/13/2008
  Q: Let us begin with, we have an Amer. Standard heat pump and for the 10 years we have been here, we ...
  A: Wow, Stephanie, you ought to go into a/c service work after all that good info !! Now let's see if I ...
Moving burners on York 4 burner unit12/13/2008
  Q: I have an York package unit, the heating component has four heat exchanger ports but only uses two ...
  A: So the top burners heat exchanger is good ?? Yes, move the burners & block off both top & bottorm ...
Furnace12/12/2008
  Q: I have a York Furnace about ten years old,it blows out cool air when it first starts.Is there ...
  A: That fan needs a delay to stop that. You may have little switches on the circuit board that can be ...
HVAC tandem units12/12/2008
  Q: A friend has a large open loft space in a seaside community. The building is brick and concrete. The ...
  A: Well, ya know the humidity is 100% all the time on the seashore. Every crack needs to be sealed. ...
Auxiliary Heat12/10/2008
  Q: I have an electric heat pump. My auxiliary heat keeps kicking on. I have my temp set at 65 degrees ...
  A: Some heat pumps have a thermostat in the outside unit which turns on the aux heat. Some are ...
heating12/9/2008
  Q: ..I have a furnace that is at least 20 years old. I had it checked out last winter and it checked ...
  A: Probably have a thermostat with a heat anticipator in it that needs adjusting to a "longer" cyle ...
Rudd Forced Air Gas Furnace12/9/2008
  Q: Having a problem with my furnace turning on. The system seems to work properly when I flip the ...
  A: You are resetting the circuit board that is acting up killing the power. Do you get the LED trouble ...
heating schematic12/9/2008
  Q: I have a very old package unit gas heat that the fan will not turn on inheat mode. There is no name ...
  A: You have a thermostat with a heat anticipator ?? Maybe it needs adjusting. It is a dial with an ...
Guardian furnace Pressure Control Switch12/8/2008
  Q: My pressure control switch on my new 95.5 efficiency gas furnace keeps filling with ...
  A: Well well. found the problem! You need a "P" trap, (not "S") on that horizontil run to catch the ...
trane induction fan12/7/2008
  Q: I have a trane 2.5 ton unit with gas pack that is about 12 years old not sure about the model ...
  A: Yes there is John.Locate the transformer & press on it & see if it changes sound. They develop a 60 ...
Guardian furnace Pressure Control Switch12/7/2008
  Q: My pressure control switch on my new 95.5 efficiency gas furnace keeps filling with ...
  A: That moisture would only come through the induced draft motor. That water may come from the flue ...
Rudd 5 ton heat12/6/2008
  Q: Howard: It's 4 years old. Have replaced compressor, 2-3 fans, it freezes up and quits, just recently ...
  A: Gather all you're service orders plus any other happenings. Call you're local Ruud supply house & ...
Heater blowing cold air12/6/2008
  Q: I have an electric heater, I noticed today that the house seemed cooler then normal. I was in and ...
  A: Those elements can drop off one at a time & you won't notice it till it gets real cold. Each element ...
Heater Problem12/6/2008
  Q: I have a Day & Night split unit with the fan coils in the attic and the condenser outside. The unit ...
  A: It could be caused by a digital thermostat. Also the heat fan is a separate circuit & for an old ...
A/C12/5/2008
  Q: I have a 28 year old Lenox central A/C system in a 1400 square foot Townhome. The outside condensing ...
  A: Let the buyer beware! Caveat Emptor. This equipment usually does not like to work in a different ...
heat pump compressor noise12/5/2008
  Q: Our"Thermal Zone" heat pump works fine in the summer ,but as soon as it turns cold out 40 degrees or ...
  A: Wonder you're still alive !! Must be good neighbors.Main thing differemce between heat & cool for a ...
Ducane12/4/2008
  Q: We have a Ducane heater. When it is super cold out side it completely turns off. The heater heats ...
  A: some of these heaters have several rollout switches.Some can be manually reset by resetting a button ...
PGCJAA/MAA cycling on-off in heat mode12/4/2008
  Q: in the heat mode, the unit cycles on and off, will not stay on to reach the temp needed to shut off, ...
  A: I presume this is a gas furnace. Don't recognize those letters.If this is a pretty old furnace ...
Furnace inducer problem12/3/2008
  Q: I have a 4 year old new construction house with an 80+ single furnance. The inducer had been making ...
  A: Naw, that's like stockpiling a compressor. You have one spotted so I'd keep oiling the shaft end ...
Furnace inducer problem12/2/2008
  Q: I have a 4 year old new construction house with an 80+ single furnance. The inducer had been making ...
  A: the bearings in those motors are just sleeve bearings. Was there oil ports on the motor?? Both ends ...
heating unit12/2/2008
  Q: My heat unit outside doesnt always run with the fan going, is this normal? But the thermostat, it ...
  A: Sounds like this is an electric furnace ?? If so the hea fan is run on a time delay relay & that ...
Comfortmaker gas pack issue12/1/2008
  Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ...
  A: We did have a good Thanksgiving with the family at a lake house owned by my daughter & husband. ...
AC blower cycling on and off11/30/2008
  Q: Ruud model UCBA100C, Propane furnace, Age not sure but if it is original it's pushing 30 years. ...
  A: A 10% allowance for a capacitor is the limit. So replace it with a 10 mfd size. Sounds like the ...
Booster Fan11/30/2008
  Q: I have a Carrier furnace with a Tjernlund duct booster fan on one of the branches. Previously, ...
  A: The booster fan ought to be 120v. Follow the 2 wires from the fan & see if they are not connected t ...
fan blowing, but no gas or ignition11/28/2008
  Q: I have a 10-15 year old Amana furnace. About a year ago, it started blowing cold air. The heating ...
  A: Could be the flame sensor, Roger. Needs cleaning. Remove it & clean with a rag. Could be the air ...
Gas Valve question11/28/2008
  Q: My Gas valve went bad on my Payne central unit. PY1PNBO30060AAAA series B LP converted Unit! I ...
  A: Does the flames look all blue, Jeff?? That's the sign of complete combustion on LP. And as you know ...
Comfortmaker gas pack issue11/28/2008
  Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ...
  A: That would be OK to plug the 2 bad bays in the heat exchanger. Gas pressure not affected.I would ...
Comfortmaker gas pack issue11/27/2008
  Q: I have a 9 year old Comfortmaker gas pack model PGAD30D1K5 that I am almost positive has a bad heat ...
  A: I'm not sure which model that is. You have 4 burners on that model? Does sound like a hole in the ...
Payne gas hot air heater11/26/2008
  Q: I have a Payne gas hot air heater. When heat is called for the exhaust blower starts for 15 seconds ...
  A: Gosh, Fran that's a crud problem, maybe. ! Let's see,you could have dirt or something clogging the ...
wiring for new thermostats11/26/2008
  Q: I bought the Honeywell rth6300b thermostat to replace the old mercury thermo that I'm sure came with ...
  A: Well, Don this proves that the heat pump thermostats will not work with an older model heat pump. As ...
Goodman Heat Pump11/25/2008
  Q: Howard, I have a 7 year old Goodman PHK024-1 heat pump. Last night the heat stopped running. The ...
  A: Yes, the compressor is supposed to run for first stage heat, as is the outside fan. Sounds like that ...
Condensation on Ceiling11/25/2008
  Q: I bought a house in April and it is on a concrete slab. At closing the seller told me he gets ...
  A: You're plumbing is under the slab & can leak anywhere. They find it by listening with headphones on ...
elctronic fan timer control board replacement11/25/2008
  Q: My System is keeping the fan on constantly. Both the heater and the AC will not engage....I suspect ...
  A: Sounds familiar. Try tapping on the little black boxes on the circuit board to see if you can ...
Carrier Gas Furnace short cycle11/24/2008
  Q: I am a novice and will try to explain what is going on and see if you can help me out. I just bought ...
  A: los of good info. I'll take it on one at a time. Don't understand what's the connection between the ...
wiring for new thermostats11/24/2008
  Q: I bought the Honeywell rth6300b thermostat to replace the old mercury thermo that I'm sure came with ...
  A: The wires used on the old tstat do not indicate a heat pump.W2 was used for heat.Don't lnow why C ...
Condensation on Ceiling11/23/2008
  Q: I bought a house in April and it is on a concrete slab. At closing the seller told me he gets ...
  A: Wow, Denise something funny here ! The condensation pump is to drain the condensate water generated ...
how to wire a honeywell fan and limit switch11/22/2008
  Q: i need to know how to wire a fan and limit switch to the blower
  A: A limit switch is usually a high temperature device & it is connected to the gas valve, in series. ...
heil model nuge080kg0111/21/2008
  Q: if I start the unit up the pilot lights and the unit will run till it reaches the set temp then when ...
  A: Not a place to have furnace problems ! Check the voltage across the gasvalve 24v terminals & see if ...
caloric LP range11/19/2008
  Q: we bought it used, converted to LP. The burners work fine, however the oven and broiler do not. ...
  A: Usually not involved with stoves but I think you're problem may be is the pilot orifice is stopped ...
pulse 21 furnace 6 years old horizontal unit with moisture in blower compartment11/18/2008
  Q: pulse 21 furnace 6 years old horizontal unit with moisture in blower compartment. The furnace runs ...
  A: Sounds like condensate problems.Was the filter pretty dirty when you changed it ?? I would check the ...
furnace11/18/2008
  Q: I have a 3yr old Tempstar upright furnace.The 5amps fuse on the circuit board keeps on blowing. Any ...
  A: You have a dead short in the low voltage control circuit. Got to find it. Sometimes can be in the ...
Heating Airflow problem11/16/2008
  Q: My parents live in a townhouse that was constructed poorly because when they turn on the central ...
  A: Town houses are notoriously bad for a/c installations. Most likely there are too many jigs & jogs in ...
Electric Furnace Sequencer/fan control problem11/15/2008
  Q: I'd like to start with thanking you for your time in advance. Now, help me impress my new wife with ...
  A: I better move fast Mark to keep you out of trouble with all those kids, wife too. You really have ...
Transformer got burned11/15/2008
  Q: I cleaned the blower, burners and heat exchanger for my furnace and in order to do so I took out ...
  A: That was caused by a dead short in the 24v control circuit.You need a 40 VA with 120/24 ...
lennox g40uh(x) series furnace gas11/13/2008
  Q: both led lights on furnace blink slow together when furnace is turned on the led lights blingk fast ...
  A: You should have in you're instruction a list of codes that tells what the problem is. If you don't, ...
My Ruud heater11/13/2008
  Q: I have a Ruud Heater/ac unit in my house I just bought. It runs fine in the summer and the ac unit ...
  A: Now,you need to check & see if the outside unit is turning off when the cold air starts.Or is the ...
lennox gas heat and air unit11/13/2008
  Q: I have a lennox gas heat and air furnace model gsc16. its a 93 model. Anyway when it started cooling ...
  A: That blower motor only draws about 3 amps, or it should. You have a clamp on amp meter ?? With the ...
Ignitor fires early or gas valve turns on too late...11/12/2008
  Q: Here is the sequence I see. I ask for heat. The combustion exhaust fan comes on. The ignighter ...
  A: I think the problem is low propane pressure. The gas valve ought to open pretty fast after the ...
heating and cooling workshop11/10/2008
  Q: I am converting a 14 x 20 freestanding potting shed into a craft studio. I'm adding insulation and ...
  A: Been on vacation so running late on my answers. I suggest a window unit with heat. I could be a heat ...
question on furnace10/30/2008
  Q: I went to a friends house and the furnace was in a flood. No LED lights came on whe I turn on the ...
  A: The blower motor is on a timed circuit & will delay AFTER the burners are on. Try jumping across the ...
Carrier Robertshaw Unitrol Valve10/29/2008
  Q: I have an older furnace, I'd say approx. 20 yrs old. It say 1985 as the year on it, but I'm not sure ...
  A: You have a 60 cycle hum from a 24v coil. I'm not sure what the part is as a "regulator valve" or " ...
Thermostat Replacement10/29/2008
  Q: Have a Trane electric forced air heat pump and air conditioning system with a Trane Baystat 239 ...
  A: Head for Home Depot & look at the round Honeywell tstats with a lcd screen on it. I think those are ...
gas furnace10/27/2008
  Q: My gas furnace is not lighting. In checking the electronic gas valve I see that the solinoids are ...
  A: A sensor needs to detect the igniter before the gas valve will open. So it seems the circuit board ...
Furnace won't ignite10/27/2008
  Q: I have a residential gas furnace g6rl 90+ downflow, it tries but won't ignite. This is my first yr ...
  A: Follow this cycle to check what is NOT happening. On a call for heat with the gas valve turned to ...
Heating10/26/2008
  Q: I have a Rheem RGRA series heater. The gas valve is not opening, when the furnace should be calling ...
  A: I'm not sure what all those acronyms mean. I don't know what the LED flashes mean, not having any ...
gas pipe10/25/2008
  Q: we have a huge vibration in our gas pipes in our home specially in one room where the pipes go on ...
  A: Gas pressure in the line is so low you may have a problem in the regulator at the gas meter to cause ...
heating unit filters10/24/2008
  Q: I have a Carrier 2800 gas heating furnace. It heats very well, but there are no air filter on any of ...
  A: Look at the return end of the furnace case.If there is a small door there that is the place for the ...
American Standard Freedom 90 - 4 Flash Code10/24/2008
  Q: It looks like I need to press the reset burner box temperature limit switch which is located at the ...
  A: That is a strange name for a heat exchanger. I think that is what that term means. There usually are ...
no power to furnace10/24/2008
  Q: I recently moved my thermostat from one side of the room to the other side,but I did,not turn off ...
  A: Wow, no wonder no power ! That 3 amp protects the 24v control circuit. The 20 amp should not have ...
heil model nuge080kg0110/23/2008
  Q: if I start the unit up the pilot lights and the unit will run till it reaches the set temp then when ...
  A: Since you have replaced the pilot sensor it indicates the module is not responding to open the gas ...
Carrier PAV 58 - Fan won't turn off10/22/2008
  Q: The furnace heats and everything else works..no failure codes, however the fan stays on. It turns ...
  A: Are there any small switches on the circuit board that sets the fan on time ?? They are called dip ...
furnace repair10/22/2008
  Q: I have an Empire direct vent wall furnace, propane, no fan 5 years old. The pilot went out, but now ...
  A: Is this a millivolt unit ? Sounds like it is. If so, need to test the voltage output with a strong ...
the basement10/14/2008
  Q: Sir, I am renting the pretty garden flat in the most prestigious location in London...but, alas, it ...
  A: I'm still here till Friday Jimmy. Fire away.
burners won't ignite on older ruud furnace with a gas pilot10/14/2008
  Q: I lit the pilot,turn on the heat but the burners did not ignite OK so i installed a new pressure ...
  A: Is the draft motor air flow blocked ? The air pressure switch is activated by positive air pressure, ...
HEATER NOT WORKING10/11/2008
  Q: I HAVE AN EVCON HEATER/AC THAT DOES NOT PUT OUT HEAT NOW. BLOWER WORKS, BUT NO HEAT. SOMETIMES IT ...
  A: Not enough info, Bill but I can make a guess. Main thing to know if this is a circuit board ...
trane gaspack furnace10/11/2008
  Q: unit has been cleaned and inspected but yet in am when it is not too cold out the heat seems to fire ...
  A: Wonder if you have low gas pressure ?? The flame sensor may not be sensing flames that are too weak. ...
Airflow into center of finished basement.10/11/2008
  Q: I don't think I have enough air getting into the room which houses 2 H/W/H, and a 100k btu furnace. ...
  A: A stopped up flue pipe can cause this, Nick. Don't run it with yellow flames. That creates soot, ...
Air Conditioning10/10/2008
  Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ...
  A: You do it with a garden hose & an oil can using about 5 drops of oil at the start of every Summer. ...
Tempstar DC90 - Thermal Limits switch trips10/10/2008
  Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ...
  A: If dirt or soot has accumulated to plug up the heat exchanger or the flue pipe, the flame, or too ...
Tempstar DC90 - Thermal Limits switch trips10/9/2008
  Q: My thermal limit switch trips and the burner turns off. When I remove my filter the furnace runs ...
  A: Is there any flames rolling from the burners ?? Is this switch one of those little red manual reset ...
HVAC / Evap Cooler Lockout Circuit10/9/2008
  Q: Does anyone make a "lock-out" circuit for an HVAC unit, such that it will not come on if an evap ...
  A: Boy, Don, that's a good one ! Swamp cooler & a/c going at the same time !! Don't know of anything on ...
Furnace10/8/2008
  Q: I currently have a Thermopride 1995 oil furnace and am thinking of switching to natural gas. I have ...
  A: Variable speed motors are quiet, but blow the same amount of air as a common motor. They do ramp up ...
Air Conditioning10/8/2008
  Q: I had my coil replaced about a year ago. I did not replace my outside ac unit yet, but it is pretty ...
  A: Not yet. R22 is phasing out in 2010, R410 replacing it. BUT, recycled R22 will be around awhile yet ...
AC control10/7/2008
  Q: I have a control problem that I could solve with an embedded controller, a small Visual Basic ...
  A: Interesting point, John. Just think that startup load is about 175% of run load & I could imagine ...
furnace wont light10/5/2008
  Q: The furnace will not ignite. It has electronic ignition and you can hear it click to try to ignite ...
  A: Most likely the pilot line is plugged. Can you try to light it with a match while clicking ?? ...
Bypass Humidifier Installation10/3/2008
  Q: I am installing an Aprilaire 600A unit on my Lenox Furnace and am wondering if the bypass ducting ...
  A: Is this an electrical furnace ?? The heat from that is only about 90 deg & not hot enough to ...
HARD START10/3/2008
  Q: You had asked me a couple of questions so as that you could better understand the problem. I ...
  A: FOURTEEN POUNDS !!! WOW !!! Do you have a 100 ft liquid line ?? The amount of the charge is based ...
gaffers and sattler forced air furnace model # S80FEF9/30/2008
  Q: my forced air furnace is located on the second floor in the closet. when i had the gasman come to ...
  A: Presume you use natural gas. Typical problem. The gas man was wrong. Soot doesn't mean a cracked ...
HVAC9/30/2008
  Q: we have a 4ton rooftop carrier unit, evaporator is clean condenser is clean condenser fan is running ...
  A: Sounds familiar.The compressor bearings are wearing causing a bit of heat. Then on a cold start the ...
Lennox Furnace on a Generator ?9/26/2008
  Q: Can I run my newer (2004) NG Lennox Furnace on the Generator?? Sorry I don't have the model # but I ...
  A: Not acquainted what a "Manual Transfer Switch"does. I wouldnt use the generator with a solid state ...
Heating9/25/2008
  Q: My furnace HEIL DC90, model NTGM 100 EHA2 runs a small fan continuously. The fan does not stop even ...
  A: Could be a short in the control circuit for heat.Remove the thermostat wires. Fan still run ?? Look ...
Lennox Furnace on a Generator ?9/25/2008
  Q: Can I run my newer (2004) NG Lennox Furnace on the Generator?? Sorry I don't have the model # but I ...
  A: You didn't say cooling. Just the furnace ?? If it's electric, probably not. One element is too much ...
gas furnace won't start9/25/2008
  Q: I have a gas furnace that has what my husband calls an electric start pilot light. The furnace was ...
  A: Aw, don't need model numbers, they are all alike. $180 !!!!! Wow. I'd ask the neighbors who they ...
no return register, stale air9/24/2008
  Q: I have a 3 story house. on the third floor, there are four floor registers but no return register, ...
  A: Where is the nearest register ?? I would say the return air was expected to be thru the open ...
match condensing unit w/ gas furnace9/23/2008
  Q: Right now I have a Lennox G26Q3/4-100-1 model gas furnace matched to a Lennox condensing unit ...
  A: Either inside or outside can be changed separately. Just has to match tons of cooling to provide the ...
condenser fan9/23/2008
  Q: two bladed fan slaps air and makes to much noise..uaka036jaz ruud, tried a three bladed 27degree but ...
  A: You are correct, cheaper. A shop that sells blades will have cfm values for blades.But the amp draw ...
No power to AC9/22/2008
  Q: The ac was running normally this morning when it stopped just as if it had reached the set point. I ...
  A: Go outside & remove the control area panel. With a screwdriver press in the contactor points.If it ...
HARD START9/21/2008
  Q: I HAD JUST PURCHASED AND INSTALLED A 14 SEER GOODMAN ALONG WITH NEW GAS FURNACE. I SAVE CONSIDERABLY ...
  A: He ain't worth $75/hr.R22 Freon sells for $7/lb so go figger.Or was this R410? Wonder what the sound ...
york furnace9/20/2008
  Q: ..I recently bought a house without central air/heat. Central air is going to be too pricey for us ...
  A: Sounds good way to go Justin, except for the York. Try a Comfortmaker, American Standard or similar ...
air handler/heaters9/19/2008
  Q: do you have to match the seer ratings of the handlers to the compressors (ac) eg can i replace a ...
  A: Wow, that is a arguable subject Jack.I have polled a bunch of the experts on this site & the ...
york ac unit9/17/2008
  Q: I recently bought a house with a York unit that was manufactured and installed in 1993. It ran fine ...
  A: First, install a good surge protector on the furnace power supply. Next, I think it may be the ...
Air vent noise9/15/2008
  Q: recently, I have notices a dripping/clicking noise in our upstairs air vents. At first, I thought I ...
  A: Sounds like condensate on the humid days is backing up water in the drain pan & maybe the fan is ...
thermostats9/15/2008
  Q: I have what is probally a dumb question. I was looking to buy a 7-day programable...it has 3 stage ...
  A: There are no dumb question, Nick. A heat pump has 2 stages for heat. 1st is the compressor heat,2nd ...
compressor problems???????9/14/2008
  Q: What could cause a compressor to operate under the conditions listed below? Liquid line pressure ...
  A: Is there a liquid line filter installed inside the outside unit ?? Or one outside the unit on the ...
New Air Unit9/13/2008
  Q: i just bought a home that was made in 1982. The air conditioning unit has went out. I found a nice ...
  A: Yes, you can change either in or outside separately. There is a "situation" happening about SEER ...
NEW HVAC SYSTEM9/12/2008
  Q: I have a home that was built in 1977 in southern California. There is a 5 ton Original Lennox ...
  A: Hey Ike, You remind me of a hurricane I knew! Sure is slamming Galveston right now. 22ft surge ...
Carrier Furnace9/12/2008
  Q: my fan won't kick on (buzzing at me) on my Carrier furnace. The LED light kicks on and is one solid. ...
  A: Spin the blower wheel to test the motor bearings. Test the motor run capacitor. If both OK,tap on ...
ticking noises coming from heating ducts9/11/2008
  Q: I have a 2 yr old trane system. In the last 2 months I have started to hear snapping noises coming ...
  A: I am really puzzled with this one based on the fact that it occurs even when the unit is not ...
hvac9/11/2008
  Q: My son has a 13 seer a/c unit, a payne, that is 1.5 years old and is no longer working. He had ...
  A: Sounds like bull to me, Jim. Current is current. Small difference between the power needed between ...
Central air frigidaire B4VM-X36K-B9/7/2008
  Q: I added a 6in duct booster and got a Packard PR293Q relay but I can't figure out how to wire it to ...
  A: Get a 24v coil, single pole, double throw relay.( NO)I assume the fan motor is 120v. Find a 120v ...
HVAC9/6/2008
  Q: I REMOVED A LEAKING R-22 EVAPORATOR "A" COIL AND I WAS GIVEN A CARRIER "N" COIL FOR REPLACEMENT. I ...
  A: I would use the old ear trick to set the charge on the TXV. Place a screw driver end on the liquid ...
a/c unit does not turn on9/6/2008
  Q: Goodman AH1826-1 Last week, the unit responded properly, but now the unit no longer functioned. ...
  A: OK, you've got a dead short in the 24v control circuit somewhere. Have a dog in the backyard ?? ...
Central air unit impacted by rain.9/6/2008
  Q: Howard, We live in a 6 year old condominium building with separate central air/heating units. Each ...
  A: After 30 years I thought I had heard everything !!! Not so, that's the strangest thing I have EVER ...
Yearly Cleaning on Regency Gas Fireplace9/4/2008
  Q: Wow... this is the first time I've been to this site! What a fabulous idea! People, such as ...
  A: Pat for the very kind words. I have semi retired after 35 yrs & this sure keeps my mind ...
Condo Wiring Issue?9/4/2008
  Q: We appear to be having an electrical issue in our condo. Awhile back our AC was icing up, freon was ...
  A: When it rains it pours is true, right ?? Icing is caused by several things: dirty filter, stopped up ...
variable speed furnace/motors9/3/2008
  Q: I am purchasing a new furnace and like the idea of a variable speed motor for comfort and savings. ...
  A: The variable speed motor ramps up from 50 rpm to about 1100 rpm for cooling, the common speed. So ...
Tripping CB in afternoon on start9/1/2008
  Q: My AC has been tripping the CB only in the afternoons during start up. I can reset the CB and it ...
  A: Where do you live in Phoenix ?? Your problems can often occur when the circuit breaker box is on a ...
Bryant 90 plus RED LIGHT and NO AC9/1/2008
  Q: My A/AC was working fine until today. The outside A/AC just stops running and upon opening the ...
  A: Insure there is power outside, check both breakers. Then check the contactor after calling for ...
Blown 50 amp fuse8/30/2008
  Q: Came home from store found A/C not running first thing I did was check the A/C disconnect,but could ...
  A: When that happens, Eric, it's usually the compressor shorting to ground. Disconnect all 3 wires to ...
A/C problem8/29/2008
  Q: Residential 3 ton R-22 A/C unit about 13 years old in Dallas. T'stat calls for cooling. 24V and ...
  A: Sounds like(my favorite term) the compressor has a locked rotor. Have you measured the locked rotor ...
Air conditioning8/27/2008
  Q: I have a two story home in FL my kids have moved out to school and we do not use the 2nd floor. I ...
  A: If it's possible to shut down the upstairs I would. The heat load from upstairs moving down stairs ...
noisy air conditioner inside8/22/2008
  Q: my ac makes a bit of a loud noise when it turns on - it blows loudly while it's on - it makes a loud ...
  A: Try this, with a pair of needle nose pliers, bend each fin on the return air grille open a bit ...
Lemon A/C???8/22/2008
  Q: I closed on my home 12/31/2003 (brand new, 2 story, 1600 sqft). Since then, at least twice per year ...
  A: Candice,Not a good deal at all. You need to push real hard on the manufacture of the equipment. Talk ...
poor air flow with newer home8/20/2008
  Q: I just moved into a new home. It is about a year and a half old. The builder lived in it for about ...
  A: Just a bad installation, Tim. If those are flex ducts the air resistance is high so the ducts need ...
Installation of Honeywell Programmable Thermostat with Bryant Puron HVAC Syster8/19/2008
  Q: I have purchased the Honeywell 7-day Programmable Thermostat, Model # RTH7500, to install for my ...
  A: Wow, Mary Sue, that's mind boggling!Let's go back to the basics, then rebuild the thermostat. The ...
AC issues8/16/2008
  Q: I noticed that my ac unit was blowing warm air so I looked downstairs and noticed that the fan was ...
  A: RIP OFF, RIP OFF! That's probably an $8 relay. Well, that thing being a heat pump I'm not sure how ...
running fan on central air8/15/2008
  Q: I live in FL and use A/AC all year. I'd like to be as efficient as possible. I recently had to ...
  A: Only need to run the blower all the time if you live in a great big house with high ceilings. Better ...
Carrier compressor noise8/15/2008
  Q: We recently purchased a home that is 2 years old that has 2 Carrier AC units. The model numbers ...
  A: Have the compressor mounting bolts been checked for tightness ?? The rubber mounting pads been ...
AC not working with fan in auto8/14/2008
  Q: Central home AC does not start with fan on auto mode. When fan is set to on mode, blower starts but ...
  A: Insure that the wires to the thermostat are not shorted. Carefully separate them & retry.If this ...
Air Handler Replacement8/14/2008
  Q: First, thanks for taking the time to answer the readers' questions. It is appreciated. Is it OK to ...
  A: Well thank you Al, I really enjoy helping you all with your questions. Keeps my brain active. Is it ...
Ductless Air Conditioners8/13/2008
  Q: I have two 9,000 btu air conditioners connected to a compressor outside for which is for up to ...
  A: An air conditioning unit requires a blower fan to transfer heat to the evaporator coil.So I would ...
trane compressor8/13/2008
  Q: When my a/c shuts down, it makes a loud, vibrating noise. Was told that compressor is shot. My unit ...
  A: Having a Trane unit changes the answer on a compressor. Trane's are about 3 times the cost over all ...
HVAC Design-best control system?8/12/2008
  Q: I am planning to replace my Apollo furnace/AC system with a Goodman heat pump/gas furnace system. ...
  A: A Trane compressor is about 3 times as expensive as all others.The tubing in the coils is aluminum, ...
duct size8/12/2008
  Q: I don't think my duct is sized right please help me. I recently added on to my house and up sized ...
  A: Duct sizing is based on Bernoullis Equation for airflow.This is converted to a circular sliderule. ...
a/c not blowing very cold8/11/2008
  Q: i have a 4.5 ton a/c split system that is not blowing very cold. the unit runs all the time and has ...
  A: Looks like you have a restriction in the system. Too low, & too high. pressures. First thing, was ...
freon vs puron system - effect of reusing lines?8/9/2008
  Q: I need a total Heat pump HVAC system. The compressor is in the back of my townhouse,which is on a ...
  A: R-22 will no longer be made after 2010. So now is the time for R-410 for you. There is a flushing ...
Variable speed furnace operating with standard AC Unit?8/7/2008
  Q: I am in the process of doing a complete HVAC install on both my existing units that are 21 years ...
  A: First off, you ought to be installing systems using R-410a. Thats the new, high pressure stuff ...
Garage door opener8/7/2008
  Q: Recently my wife plugged in my large air compressor to inflate a raft! Well she heard a loud pop at ...
  A: WOW, what a blast ! No telling what happened with the breakers being rearranged ! Going to have to ...
Heat pump problem.8/7/2008
  Q: My home has three heat pump sytems which are about 15 years old - Seer 11. Recently, the MBR unit ...
  A: Sounds familiar for a compressor getting too hot over a period of time & shutting down, till it ...
Payne PA10 central air conditioner8/6/2008
  Q: My Payne PA10 air conditioner has suddenly quit working. The problem seems to be at the outside ...
  A: On the capacitor the 3 terminal are marked C, HERM, FAN.Cut the power, pull the wires off. With an ...
no a/c8/5/2008
  Q: the house is reading 85.no cold air.repairman was out 2 weeks ago.said i was low on freon.put some ...
  A: How much freon is "some" That sealer is best for a small leak. Say not more than 2# added to fill ...
carrier condenser motor replacement8/5/2008
  Q: outside condenser unit 38CKC036-340 says 1/5 hp 1.4a what my a/c repair man put in is an Emerson ...
  A: 69 avg days above 100 !! Couldn't handle that. I live in arlington,tx & we are having a string of ...
evaporator fan inop8/5/2008
  Q: This is trane airhandler a couple of years old with variable speed. If I turn on power to it, after ...
  A: Hey Paul, sounds just like a bad run capacitor on the evap motor. Test it with an ohm meter on the ...
Thermostat problem or . . .8/4/2008
  Q: In North Texas we are experiencing a significant heat wave of over 100 degrees for several days now. ...
  A: Need a freon test for capacity check. Just feel the suction line outside or inside in the afternoon ...
Circuit breaker keeps triping8/2/2008
  Q: I have a Central Lennox airconditioner installed in my home about eight years ago. I recently ...
  A: Running late on answering, sorry. It could be as simple as a loose terminal on the power circuit. Or ...
Dual Zone - Electronic vs manaul8/1/2008
  Q: We currently have a Electronic Dual Zone system that seems to have went bad after 12 years the other ...
  A: Zone control is sure good for multiple level homes.Being able to set 2 thermometers different in ...
White Rogers Thermostat7/30/2008
  Q: I recently purchased a property that I am renting out. There was an old white-rodgers thermostat ...
  A: An inexpensive thermostat can be a magnetic switch control.The White Rogers is good, mercury ...
mold in air handler7/29/2008
  Q: About 4 years ago I had a new ac system put in my 13 year old home. The old system failed and mold ...
  A: I'd say if you have a family with breathing difficulties get a UV light. I wouldn't pay $1800 for ...
HVAC Design-best control system?7/29/2008
  Q: I am planning to replace my Apollo furnace/AC system with a Goodman heat pump/gas furnace system. ...
  A: Hate to tell you but Goodman used to be Janitrol & we nicknamed it "Junkatrol" Used to be named GMC. ...
Air conditioner7/29/2008
  Q: We just had a power outage of 1-2 seconds. Our thermostat is working as is the blower. The A/C unit ...
  A: That outage is hard on compressor's. Refrigerator compressors too. If it is running when that ...
Time delay relay on outside Compressor7/28/2008
  Q: I have a Carrier 38CK036320 split unit hvac system. After having different issues with the air ...
  A: From adding freon last year, that's where I would start testing. That Carrier probably has a low ...
Freon/Puron Conversion Kits7/27/2008
  Q: I have a 6 yr old freon-based heat pump that needs replacing. In the process of getting quotes, one ...
  A: Sounds like he's blowing smoke at you, Mike. Never heard of a "conversion kit" before.It may be wise ...
AC not working7/27/2008
  Q: Mr. Livingston, I am hoping you can give me some guidance. Our home is only 2 years old, a modular ...
  A: 2 105 days ahead. That was very nicely worded question. Thank you. These things can break at any ...
AC Mold/mildew smell from ductwork7/26/2008
  Q: We live in South Florida and have a moldy smell in our house, which is probably originating from the ...
  A: Vacuum out the dust & dirt all you can from the supply air plenum. Then vacuum around the evaporator ...
AC Blower won't stop before & after New Blower Relay7/24/2008
  Q: 30+ y old Singer AC - The Blower motor turns on & after the compressor cycles off the Blower turns ...
  A: The cool fan circuit is different from the heat circuit, that you may know. Also, with the ...
thermostat swing7/23/2008
  Q: I have a question about the frequency of cycling of a Lux TX500 programmable thermostat which I ...
  A: I can't imagine you can satisfy both settings of cycle time & temperature !! A well balanced cooling ...
Goodman Heat Pump7/23/2008
  Q: I have a Goodman Heatpump and 2 days ago I started smelling a smell like the heat had kick on. I ...
  A: Don't know whether that Goodman has this but some heat pumps auto turn on heat elements on a defrost ...
Broken compressor7/21/2008
  Q: I would like to ask you a question. We have lived in an apartment 9 months and have one cat. Our ...
  A: Usually don't answer questions about friidges, but yours is easy.When the coils are pretty clogged & ...
ac not blowing but compressor runs7/20/2008
  Q: we have ac/heating unit lenox g-26 series.few days ago we noticed that the compressor runs outside ...
  A: Women are sure a target, Janet.I hate that.Fan control on "auto" comes from the thermostat. Do you ...
Gas Heater7/20/2008
  Q: I have a problem with my upstairs HVAC system in my house. The house was built in 1994 and has the ...
  A: Tricky question, Mike.I know of nothing that would interrupt power to the thermostat. There ...
crack combustion chamber7/19/2008
  Q: I just bought a house and had the oil furnace serviced for the winter and the person who conducted ...
  A: Cracked heat exchanger usually condemns it. But if he sees a crack so can you. That's an easy way to ...
A/C Capacitor7/18/2008
  Q: We had a service call (on our 2.5 ton Trane) a month or so ago (because only warm air was blowing ...
  A: WOW, $139 for a service call !!! $75 would be better.There is a 10% allowance from the capacitance ...
Central air units7/17/2008
  Q: Just returned from Iraq to find that the basin for one of two HVAC units in my house is full of ...
  A: The open one is a secondary drain line, needed when the primary drain plugs up. Someone was lazy.If ...
Air conditioner and water heater7/16/2008
  Q: When my air conditioner is running and the hot water heater turns on the exhaust from the hot water ...
  A: OOnly other thing I can think of is the heat exchanger in the furnace has a big hole in it. When the ...
a/c is blowing warm air.7/15/2008
  Q: I live in a mobile home. I have a "split system" ( a/c outside, electric furnace and blower ...
  A: Anything can happen anytime to this stuff, Anthony ! Warm air indicates the compressor is not ...
Gibson Furnace7/15/2008
  Q: Howard, I am attempting to solve two minor problems on a heat only central system located in a ...
  A: Wayne, Metal ducts I presume ?? #1. A multiple speed motor can have 2 brown wires for a capacitor,2 ...
Two Stage AC Wiring7/14/2008
  Q: I have a two stage 5-Ton Goodman condensing unit, single stage variable speed Goodman furnace/air ...
  A: the most complex circuitry I have ever seen is on a 2 stage compressor.Lennox has had those 2 stage ...
Question about Purely-Radiant Cooling?7/13/2008
  Q: I thinking of a cooling mechanism for houses and buildings in which the cooling -- in the direct ...
  A: I like you're thinking, Green! My counter to that idea is one of the laws of physics, heat flows ...
York heat pump not running7/13/2008
  Q: I have a york heat pump at home and it has stopped running. If I force the breaker in the unit ie. ...
  A: A control circuit problem.Can be a bunch of things to cause that. Low on freon,broken wire ,24v, to ...
SEER7/12/2008
  Q: The condenser on my split system failed (fifteen years old - we bought the house eight months ago). ...
  A: You touched a raw nerve, Bob about a mismatched SEER equipment.There is a lot of disagreement about ...
trane a/c compressor stops, will start backup7/12/2008
  Q: Our Trane is about 10 years old. It did this last year and stopped. The compressor will stop and ...
  A: Better test the compressor. After the unit stops, lay your hand on top of the compressor. Is is too ...
Leaking AC needs freeon??7/11/2008
  Q: About a year ago my AC was not getting cold. The company came and added freeon and it was fine. ...
  A: Lack of freon can cause lots of ice on the evaporator coil. As it melts you can have a flood. But if ...
York Heat Pump Error code 47/11/2008
  Q: I have a York heat pump that is functioning properly for about an hour (starts to cool down the ...
  A: Sounds like a hot compressor. Need to let it run until it stops, then open the top & lay your hand ...
pricing/labor7/9/2008
  Q: My AC was not working properly and water was leaking around the outside unit. I called a repair man ...
  A: DON'T EVER PAY UP FRONT SHELLY. I changed a 4 ton coil & it was $875 total. Tell the guy to give you ...
fan problem7/9/2008
  Q: i have a ten yr old heat pump/ac it's a 3.5ton janitrol/goodman the problem is spuratic? maybe 2X's ...
  A: With the fan in the "auto" mode on the thermostat, the thermostat turns on the fan when cool is ...
Janitrol compressor problems7/8/2008
  Q: I have a 13 year old goodman janitrol heat pump with a bad compressor. It shorts out inside and blow ...
  A: That's a problem nowdays. The a/c supply houses require a license to buy parts. You might call a ...
pulled small wire from outside a/c unit7/6/2008
  Q: I accidentally pulled a small wire from my outside a/c unit while weedeating. It contains 2 smaller ...
  A: Oh, how much money have I made fixing those wires !! Best thing is to splice those wires back where ...
Return Air Vents7/6/2008
  Q: I am considering purchasing a new home still under construction, but we have concerns over return ...
  A: Did your current house have only 1 unit ?? Bet it did with multiple RA grilles.Now, the new house is ...
AC7/5/2008
  Q: We moved recently- Have a -Trane I believe- from an old bill- "Unit- ICPC- Model NFCX480062" , "ICPC ...
  A: Sorry about the delay, Fred. A busy weekend. Back to the contactor. Check the points to see if they ...
Air Flow7/5/2008
  Q: I recently ran an 8" air duct from the main duct of our swamp cooler to the master bedroom. ...
  A: If there is a supply air plenum with other ducts of various sizes connected to it & you add a duct ...
Mystery Duct7/3/2008
  Q: This is a receipt for a question you recently asked at allexperts.com of Craig HVAC Expert. You ...
  A: Did Craig answer your question ? Your link to the drawings is invalid.I will just make a guess about ...
Leak in the Compressor Area7/2/2008
  Q: "Hi, We have a Carrier 5 ton AC that's manufactured in 2001 for our home. We had an AC technician ...
  A: All good service folks have a H-10 leak detector which can measure leaks down to 1/2 ounce PER YEAR ...
24-V / 3 amp fuse7/2/2008
  Q: Having issues with my HVAC. At the forced air unit, there is a 3 amp fuse that blew, which caused a ...
  A: Right, Ken, you have a dead short in the 24v control circuit. You can fins it. It can be in the ...
air flow6/30/2008
  Q: I have a dual HVAC system and had the upstairs system replaced. i contracted a guy who was to ...
  A: Air flow can be affected by the evaporator coil only if it is making ice & blocking the air flow. 17 ...
A/C UNIT WILL NOT TURN ON6/28/2008
  Q: Two days ago I shut my a/c unit off(while running) from the Main circuit breaker and tried to turn ...
  A: Those breakers can be ornery. Once you've tripped them they may not reset, even tho you moved the ...
Rheem Criterion 2 cooling problem6/27/2008
  Q: I can feel the sheetmetal become ice cold but the fan blower motor is not spinning. Is that a bad ...
  A: Turn on the fan only. No cool. Does it run ?? Test the run capacitor first. OK, bad motor. But next ...
4 speed to 3 speed conversion6/26/2008
  Q: I have an older Frigidaire (Heil?) furnace with a 4 speed blower motor (low, med-low, med-high, ...
  A: little late responding. Phone has been down for 3 days. For heat & cool you need low & high speed ...
A/C compressor not always starting6/23/2008
  Q: I have a brand new Rheem Classic 90 (410A refrigerant) split system that works great 90% of the ...
  A: Sounds like you have a "sticky" compressor.How long is the warranty on it ?? 5 or 10 yrs ? Need to ...
Control Panel Wiring6/23/2008
  Q: My outside unit had water on the ground and iced up tubing leading into house. I opened express ...
  A: Can't see any missing wires in the photo, Dereck. That's a piece of the wire laying in the box ? ...
Carrier Heat Pump6/22/2008
  Q: Sir, I have a Carrier 38YMA which is 14 years old. The unit has been working extremely well. Last ...
  A: I would like to hire you to do my service work ! You good !!Fan motor windings do not have start ...
A/C system in Florida6/22/2008
  Q: I had an A/C system changed out in my Florida 1920's bungalow in 2002. I am embarrassingly young and ...
  A: Well, your question comes to a person that hasn't had a license for at least 10 years !!! I work ...
central heat/air6/21/2008
  Q: we bought a house last year-it's about 10yrs old- and the central air return is under the house in ...
  A: I live in North Texas. You too?? That's the way houses were built way back in the 50's & 60's here. ...
Furnace Clearance6/19/2008
  Q: I want to rearrange a few things in my basement and as part of that i want to put a door for access ...
  A: is this a gas or electric furnace.?? For gas you need 6" from the front to the door. The door needs ...
Need help on HVAC usage costs.6/19/2008
  Q: I have an an interior room in my house with no exterior walls. The central A/C for the house cools ...
  A: I'll get out my slide rule & figure that out ! Wish we had electricity that cheap in Texas. ...
Lennox heat pump (10HPB48-10P)6/18/2008
  Q: I have almost the same question as what was posted in the post "Trane heat pump xl1200". I turned ...
  A: Easy test for capacitors is with an ohm meter set on it's highest reading. With no wires attached, ...
air condioning6/18/2008
  Q: With air-conditioning season starting so has the debate as to leaving the air on and doors and ...
  A: The first thing cooling does is remove humidity, 2nd is the temperature of EVERY OBJECT in your ...
Heil heat pump6/17/2008
  Q: I have a Heil system that does not cool. The capicitor, reverse valve and compressor are good. It ...
  A: The service valve on the suction line has a Schrader valve in it. Sometimes the hose connection ...
wiring6/17/2008
  Q: I replaced the condenser fan motor on our churches a/ac package unit. It's running the correct ...
  A: Capacitors are NOT directional. Either way. Maybe test the capacitor. There sorta cheap these ...
Trane heat pump xl12006/16/2008
  Q: I suspect that the cooling fan in the condenser unit is bad.I had ac on all night and awoke to warm ...
  A: Test the run capacitor first. If OK, it's the fan motor.2 speed condenser fan motors went out a long ...
Honeywell Vision Pro 8000 wiring6/16/2008
  Q: I am installing a totally self-contained heatpump system in a trailer, and want to hook up a vision ...
  A: Yes, remove the jumper from R & Rc. What I don't know is the use of E for that tstat.It is usual for ...
Heat pump size/efficiency6/15/2008
  Q: I have a 5 y/o, 1300 sq. ft ranch. It came with a 2.5 ton heat pump. I live in NC where the high ...
  A: Used a/c stuff has little market. They are good for garage cooling or a landlord looking for cheap. ...
Weird Smell From Air Conditioner6/14/2008
  Q: There is a weird smell coming from the air vents - I would like to say it smells like a super ...
  A: Not too uncommon to smell something from the vents. Main that that could create a smell is the ...
Electrical Problem (?) with Bryant AC Unit6/10/2008
  Q: On very warm days when my AC unit has to run for ~90 or more minutes in order to get/keep the house ...
  A: First, I would test the accuracy of the thermostat. Got another thermometer to lay on the thermostat ...
fan relay6/9/2008
  Q: 95 year trane unit, air handler fans runs non-stop, can the orignal relay#9100211Q132 be replaced ...
  A: I don't have catalogs to know what those numbers mean for a fan relay.I can say the coil voltage ...
Residential AC6/9/2008
  Q: I have 2 zones with a 3 ton air conditioning unit. The bottom zone is Central air with a propane ...
  A: Oscar. I'm a little late responding as fast as I like. Got to admit we had our 60th anniversary ...
a/c not real cool6/8/2008
  Q: I HAVE A TRANE WEATHERTON XE1000 WHEN WE MOVED INTO THE HOUSE THE AIR WAS REAL COLD NOW 3 YEARS ...
  A: It's possible but... Does the compressor still run ?? Sounds like the problem may be just needs ...
AC not blowing cold6/7/2008
  Q: I have a Raheem HVAC system. After noticing that the air is not blowing cold, I went outside to find ...
  A: Without that outside fan running the freon pressure goes nuts & kills the pressure switch. First, ...
Lennox Central Home Air Conditioner No Cool6/5/2008
  Q: Almost identical to another current question on this site. My system turns the distribution fan on, ...
  A: The breakers are only one of many causes for nor cooling. More are a burned contactor points. Or low ...
HVAC split unit6/1/2008
  Q: I have an HVAC where the compressor is on the roof and the heater is in the hallway. The model of ...
  A: Are you using the green horsehair media ?? Some horizontal furnaces just lay the filter against the ...
Rheem Split Unit6/1/2008
  Q: I have recently purchased a rehabbed home that was built in the 40's. The seller claimed that the ...
  A: These things cab act up at any time !! Usually on the weekends in Summer. Does the inside fan run ...
heating5/31/2008
  Q: I was having a talk with a friend and we discussing heating and how to save money this coming ...
  A: A chart I have compares the amount needed to produce 1 mil btu's. It says it takes 293 kwh & 10.9gal ...
help5/30/2008
  Q: heater work great all winter.except had to replace thermostate.turn on air cond. and blower would ...
  A: Where did you find all those bad people ?? Starts off with a bad motor & ends up changing a ...
question on appropriate heat pump size5/29/2008
  Q: I have a 3200 sq ft home in Washington state (pretty mild weather). My furnace is a Rheem Criterion ...
  A: A couple of questions first. Is this a replacement deal or a new house?? (Replacement would give a ...
Hard start kit question5/29/2008
  Q: Recently my a/c company installed a new evaporator coil with a TXV. Later they realized the coil was ...
  A: That lesson about using a start capacitor on a TXV valve coil is learned early on in this business. ...
Neither AC nor fan will come on5/27/2008
  Q: We tried to turn our AC on last night for the first time this season. I set the thermostat to cool ...
  A: Check the wires behind the thermostat. red wire on R, green wire to G, white wire to W, blue or ...
a/c compressor5/24/2008
  Q: I have a Bryant package unit, keeps blowing breaker. I think it could be compressor, removed black, ...
  A: Burned out motor windings for common & run windings. The freon ought to smell burned also.Add liquid ...
TRANE XE1000 HEAT PUMP THERMOSTAT5/24/2008
  Q: EVERY ONCE IN A WHILE, OUR A.C. AUXILIARY HEAT "LIGHT" GOES ON WHEN WE LOWER THE COOLING SET POINT, ...
  A: Some control circuit wires crossed up for that to happen. Suggest checking the wires behind the ...
Heil Air Conditioning Unit5/23/2008
  Q: My unit is 6 years old and I have had an issue with it eery summer for the past 4 years. The most ...
  A: I've experienced that problem before & was totally unable to stop it ! It was a small, short wire ...
2 year old Carrier evaporators are leaking5/22/2008
  Q: In May of 2006 we replaced our entire hvac system with all Carroer equipment. Recently the system ...
  A: Different vents will have different temps due to the heat load in the attic & different length runs. ...
noise in Luxaire 12 EER5/22/2008
  Q: About a year after we got it, our outside unit started making a loud noise when it kicks on, ...
  A: If you have a mercury controlled thermostat & it is not level on the wall the mercury can roll back ...
Thermostat5/22/2008
  Q: My AC quit working. The thermostat is not showing any readings. I checked the transformer voltage ...
  A: That thermostat use batteries ?? Test for 24v from red to all other connection on the thermostat. ...
A/C age + compatability ?5/21/2008
  Q: My current a/c unit is as old as my home (1976) and is still hanging on by a thread, but just ...
  A: That is a 1992 model
2 year old Carrier evaporators are leaking5/21/2008
  Q: In May of 2006 we replaced our entire hvac system with all Carroer equipment. Recently the system ...
  A: Hey Jennifer, You said "both evaporators". You have 2 systems ?? Both leaking ?? I have not heard ...
motor replacement to air conditioning unit5/21/2008
  Q: Our unit is 25 years old. Within the last month it would work for an hour and then the blower would ...
  A: Makes me sick for someone to charge a fee like that !!I am assuming that the "blower" is usually the ...
YORK MODEL SJ - Not as cool as it should be5/20/2008
  Q: We just installed a YORK Model SJ unit in our mobile home: Latitude Series, R-22, 13 Seer, ...
  A: Mobile homes are not known for good insulation. 1# of freon shouln't make much difference in ...
Lawnmower Sound From Heat Pump5/19/2008
  Q: Okay, I have had my installer out four times to evaluate this problem. I have a 4 ton American ...
  A: Only thing on the inside unit possible is the blower wheel & motor. Sometimes the freon rushing in ...
hvac5/18/2008
  Q: I am getting ready to install a new HVAC (air conditioner and air handler) in my ten-year old, ...
  A: Always a good question, Don. This tho is only my opinion of coarse. Scroll compressors are good ...
Payne Warranty on Compressor5/16/2008
  Q: We bought a new house that came with a Payne A/C unit. The unit was serviced because it was not ...
  A: WOW ! You was ripped ! $60 OK. 2.75 hrs OK. $165 filter NOT OK. That's a $35 filter !!.No ...
Carrier motor problem?5/16/2008
  Q: The tech wants to replace my blower motor for $450, but I'm not convinced that it's the problem. ...
  A: Never heard of condemning a motor for those causes in 35 years !! If one piece of the continuous ...
Frozen AC5/14/2008
  Q: We live in TX where our Summers are always above 90. We just moved into a home with a central ac ...
  A: Ice forms when these things happen to the cooling system: Dirty filter, dirty blower wheel, dirty ...
need heat pump advice5/12/2008
  Q: I need some advice about heat pumps. My parents home is in West Central Florida ( Hudson ) where the ...
  A: Nw that's some good info, Ken. Usually the other way.Bet the R value od cinder blocks ain't too good ...
question about the fan5/12/2008
  Q: my question is about the fan. I noticed it was on this morning, even though it was on auto and the ...
  A: No need to worry, Angelique. There's lots of safety stuff on this equipment, plus circuit breakers. ...
Payne Interior unit problem5/12/2008
  Q: The distribution fan in the interior unit is receiving voltage in all locations except one. I ...
  A: Capacitor test: With ohm setting on the highest, remove all the wires & test across 2 terminals. The ...
A/C unit is freezing up5/11/2008
  Q: I have pretty fair knowledge of electrical and some a/c components. Limited on funds and down in ...
  A: Wow, a Chrysler still running !!! Those were really good units. Worse thing happened a freon leak ...
replacing a Condenser Fan Motor5/10/2008
  Q: I have a Ruud Acheiver 10 High Efficiency air conditioning unit. I've been watching this motor go ...
  A: No problem. Kill the power & remove the motor. Propeller is first tho. Just cut the wires in a ...
Inside Fan Motor stays on - Carrier AC with heat strip5/9/2008
  Q: Issue is blower motor stays on. Even with AC/Off/Heat set to Off, blower motor stays on, regardless ...
  A: One of the heat element sequencer disks on an electric heater can lock closed & keep the fan ...
Trane XE 805/8/2008
  Q: We had a recent power surge come through our house as a result of some tornadoes. It took out 2 ...
  A: If you don;t have a fried circuit board you're lucky. The 3 amp fuse is an auto type plugged into a ...
Carrier furnace 58ES5/8/2008
  Q: WHERE IS THE FAN LIMIT SWITCH LOCATED? AND IS IT EASY ENOUGH TO REPLACE? IF I HAD AN ACCURATE ...
  A: Don't have info that you have sent me a question before ?? Anyway, on the old style furnaces(NOT ...
Air Conditioner Brands5/8/2008
  Q: We are looking to replace our AC units. I see information about trane/american standard and ...
  A: York makes their own compressors & they are way more expensive than other brands. Lennox is good ...
Goodman air/furnace5/7/2008
  Q: I have a HVAC system that is two years old. I went to turn the air on the other day and the system ...
  A: Sounds like you've lost the control circuit. Turn only the fan switch on to test for fan. If none ...
air handlers5/7/2008
  Q: Are variable speed air-handlers for Central AC worth the extra cost? How has their reliability been ...
  A: Good question, Steve.The best place to use a VS blower is where you need a quiet fan. Best example: ...
Replacement Coil5/6/2008
  Q: I have a friend who had his air conditioner go out yesterday. He called a repairman, and he said ...
  A: Replacing the coil indicates it is leaking freon. If this is an "A" coil upflow, there are coils ...
Black specks from air ducts5/5/2008
  Q: Black specks fall from the air duct in the room that is directly below the heating/AC unit in my ...
  A: This is a difficult question to answer. But not an uncommon question. Only thing I can imagine is ...
2 HEAT PUMPS 1 THERMOSTAT5/5/2008
  Q: At our church we have a very large room that has 2 separate heat pumps with 2 separate ...
  A: Yes. Use one of the units transformers to supply control voltage to both of them.So use the 24v ...
e-coil cleaning5/2/2008
  Q: I have some experiance with various hvac repairs. I want to inspect and clean a Rheem evap coil. The ...
  A: Some coils have end plates screwed in that you can take loose that may give you a peek to the ...
Why did my scroll compressor lock?5/2/2008
  Q: The HVAC man diagnosed a "tightly locked" Benchmark brand 3.5 ton compressor in my heat pump/air ...
  A: DON'T GIVE UP JARED !!!! 4 to 5 hours !!! 10# freon !!!! I can do those by myself in 2 hrs. No, ...
Carrier heatpump5/1/2008
  Q: Howard, I have a carrier one piece electrical 2 1/2 ton heatpump, 11 years old. The cooling works, ...
  A: Something fishy here, Ron. When you call for heat, doesn't the heat from the heat pump turn on ?? ...
Quotes, New Purchase5/1/2008
  Q: Right now I have radiant heat and am looking at upgrading to a heat pump system. So far I have ...
  A: Is that "air purifier" a true electrostatic filter ?? If so, those things are a lot of trouble. I'd ...
Compact Room AC for 12v Mobile Use4/30/2008
  Q: I would like to apply a small room, 115v AC Air Conditioning unit to a 12v DC mobile environment ...
  A: Don't think they ever made window units smaller than 5000 btu. The compressor start up is usually at ...
HVAC4/29/2008
  Q: Can you replace a 10 ser condensing unit w/ a 13 and not change the a coil, and if so what is the ...
  A: Yes you can, Bob. Some places cancel the warranty if the coil not replaced but most of us have ...
Lennox 10ACB24-9P4/29/2008
  Q: I was reading one of your suggestions about a hidden switch on my unit. I don't seem to be able to ...
  A: I was referring to a switch on the outside unit that trips on a fan motor failure - i.e. high ...
Payne Central Unit4/28/2008
  Q: I had a guy come out and look at my unit it was installed in 2001 . Propane heat split unit Payne ...
  A: I'd replace the gas valve. A familiar story.Furnaces can last 35yrs or more. He was hungry I guess. ...
gunk in a/c condensate line?4/27/2008
  Q: I noticed our unit- which normally cools to whatever temperature we set it at- was not cooling. The ...
  A: (that's an interesting name !)Ice is caused by several things, like; low on freon, dirty filter, & ...
new Hi eff furnace purchase4/26/2008
  Q: Have quotes on the lennoxG71p, bryant plus 90i, Ruud ultra hi eff furnaces with vs fans, wondering ...
  A: Best advice is move to Texas, where I live.Those variable speed fans are really expensive but good ...
a/c4/25/2008
  Q: Our a/c unit kicks on and runs for 3 minutes then kicks off for 3 minutes and keeps this steady 3 ...
  A: First thing to test is the freon amount. May have electrical problems also if freon OK. Could be the ...
short cycling heat pump4/23/2008
  Q: I have a Rheem RPKB heat pump that was installed almost two years ago. It now appears that the ...
  A: Lack of air across the coils will short cyle on a low pressure switch. If your system is operated by ...
Trying to understand HVAC repair and replacement.4/22/2008
  Q: I am an investor and I’m trying to understand the AC repair and replacement market. I would be ...
  A: Personal opinions can vary all over the place Robert. Here's mine. I used to have about 700 ...
Lennox A/c issue...4/22/2008
  Q: 2 months ago mid Feb. you helped me solve a heating problem. Your diagnosis was spot on! Now need ...
  A: The compressor is cooled by the returning freon.But it can also get hot from worn bearings & drawing ...
short cycling heat pump4/22/2008
  Q: I have a Rheem RPKB heat pump that was installed almost two years ago. It now appears that the ...
  A: Looks like you have lost some freon & it is short cycling from a low pressure switch. Got gauges to ...
Compressor runs but fan doesn't4/20/2008
  Q: My gas ac unit will run for how ever long it takes to get to programmed temp.but during process the ...
  A: Terry. Now the main thing to test is the run capacitor for the fan motor.You can test it with an ohm ...
Replacing an AC fan motor4/19/2008
  Q: Just wanted to get an idea of how difficult it would be to replace the AC fan motor on a residential ...
  A: OK, here goes, Wayne. Kill the power. Access the motor & remove the propeller.And that task can be ...
RUUD Filters4/18/2008
  Q: We have a RUUD UBHC 17J11SFF, manufactured 2/04. We're looking for HEPA-like air filters but ...
  A: Yo J. I like short names ! Don't be fooled by "electrostatic" filters. They are not. It takes ...
Lennox A/c issue...4/18/2008
  Q: 2 months ago mid Feb. you helped me solve a heating problem. Your diagnosis was spot on! Now need ...
  A: Well hello again Dave! You have been tricked by a typical problem. The outside fan masks the fact ...
blower on furnace will not stop4/17/2008
  Q: Heil gas furnace model EPD5536DC1, then it has another line under it that says d36pa15a1 but not ...
  A: I presume your furnace is controlled by a circuit board ?? Two things I can think of, Kim. One is ...
Pressure switch in furnace4/16/2008
  Q: My furnace runs too many times at night. Each time it runs less than 10 minutes. Could it be the ...
  A: The pressure switch closes to tell the circuit board the combustion air blower is working. Actually, ...
Trane XE800 High and low Pressure4/8/2008
  Q: I had noticed the Air Handler running almost constantly in the last month (Outside Temp 30-40 F). I ...
  A: Heat pumps are tested for freon only on the cooling cycle.The buzzing sound is typically the ...
a/c no start4/8/2008
  Q: I have a Goodman air unit. When I turn the thermostat I hear a click on from the unit and a hum as ...
  A: Yo Joe, Sounds like the contactor points are burned a bit & won't make good contact. With the ...
liquid cool assist for residential A/C4/7/2008
  Q: I'm trying to detemine if there is some kind of geothermal assist available for a/c units. I don't ...
  A: Well.Tom, you could dig a deep well in the backyard & run a loop of pipe in & out of it to precool ...
Lennox AC/Heat Pump4/5/2008
  Q: Thermostat lost power...outside unit has power, air handler has power... replaced defrost circuit ...
  A: Does the fan run when the fan switch on the thermostat is "on"? Thats a control & power circuit ...
Luxaire Evaporator Coil Access4/4/2008
  Q: I have an older home with a 1995ish a/c and furnace unit inside. I am having difficulty getting to ...
  A: It`s difficult to clean a coil. To do a good job, you have to remove the coils & the difficulty is ...
Duo Therm Roof RV AC4/2/2008
  Q: My '76 GMC motorhome has two roof mount Duo Therm AC units model# 54615-035 and 54515-036 one has ...
  A: gosh, after 30 years you ought to be used to the vibration !! That is just a flaw in the compressor ...
Carrier AC Problem4/1/2008
  Q: Howard, my AC system is a Carrier for a 2-story 1500 sqft townhouse and is less than 2 yrs old. A ...
  A: Best guess Tom, the transformer is heating up from a bad coil. A test would be read voltage on both ...
air handler circuit breaker3/30/2008
  Q: I just moved into a really nice townhouse. The air works but I noticed that the air handler switch ...
  A: Circuit breakers can be an ornery as any electrical device.Also can cause fires too. So when they ...
Rudd Furnace yr19913/30/2008
  Q: Furnace starts up with induction motor first and then cycles without the hot surface ignition ...
  A: Tricky stuff it appears. You can eliminate the thermostat by jumping across the red & white wires at ...
AC/heat pump problem3/29/2008
  Q: Heat runs fine. When you cut the AC on the fan runs but the pump does not run. It does work with the ...
  A: The one thing that makes the heat/cool for a heat pump is the reversing valve.The inside fan runs ...
Low Flame Sensor Signal3/29/2008
  Q: My Frigidiare 90+ downdraft natural gas has a "low flame sensor signal" indication. Which some times ...
  A: That ought to mean the electrical signal sent to the flame sensor from the circuit board that there ...
Return Air Flow - Gas Furnace3/29/2008
  Q: Bought this house two years ago. We have been slowly renovating and I just pulled a return air vent ...
  A: That is a pretty good way to have good circulation, is to use the wall as a return air duct. Return ...
Heat pump not starting up3/26/2008
  Q: I have a Carrier heat pump that stopped working all of a sudden. Even if you put the fan switch to ...
  A: That's a first, Mohammad, to get a picture ! Circuit board can be identified by the part number of ...
Heating/A/C thermostat3/26/2008
  Q: I live in North Texas ( DFW) area. I have a single story 3000 sq Foot house with two A?c's/ ...
  A: The digital thermostats have taken over the market & there are a lot of varieties.Stay away from ...
home furnace/ac3/23/2008
  Q: Furnace switches on when thermostat says area is too cool. Runs as it is supposed to, but when ...
  A: This sounds like a fan running(no heat)since the temperature switch is not satisfied, Ron.If this is ...
American Standard Furnace3/19/2008
  Q: I've had ongoing problems with my 21/2 year old American Standard furnace. The most recent problem ...
  A: The pilot light or the ignitor has to be proven before ignition, then the flames proven by the flame ...
limit switch settings3/19/2008
  Q: I have a keeprite furnace, it has an intermittent switch I think it's about 10yrs old, anyway the ...
  A: Ought to shut off the fan at about 90 deg.But, if the furnace is controlled by a circuit board, the ...
Heil DC90 Model# NTGM100EHA2 intermittently blows cold3/15/2008
  Q: I am having the problem in which the draft inducer comes on but the pilot fails to go to full ...
  A: The flame sensor sanding may have screwed up the sensor. Just need to rub it with a rag to polish ...
Carrier Infinity3/13/2008
  Q: Howard, A Manual J was done on my home and determined that I need: 16,524 BTU's for cooling the 2nd ...
  A: Well, Brian I am a conservative & over the 35 yrs in the a/c business my opinion goes that way. ...
1 A/C or 2 ?3/12/2008
  Q: i am in central CA in a 2,000 sq.ft house. half of the house is open plan (almost one big room) ...
  A: Think the best approach, Rick, would be a separate system in the attic for the 3 br, 2 bath side. ...
frigidaire3/11/2008
  Q: I have a frigidaire model # FG6RA 096C 16B and was moving humidifier wires. The cap came off a wire ...
  A: Little trouble, huh? Ya never know what happens on a ground fault like that.Do you have a 120v ...
Furnace blower motors3/9/2008
  Q: I am about to upgrade my furnace to a 95% efficient one and add AC at the same time. Is there an ...
  A: The only advantage that I would see adding a variable speed blower is the quietness. I you have a ...
Goodman GMP100-33/6/2008
  Q: I just replaced the blower motor and fan wheel.After I hooked everything up the blower works for the ...
  A: A blue wire to the gas valve is puzzling since a blue wire usually is the control wire from the ...
Won't keep running NUG9075FGB1/GUM075N12A3/5/2008
  Q: I have an old Keeprite/Comfortmaker which heats my house for the last 10 years very well. It's a ...
  A: Your`e a good fixer, Bruce.I like do-it-yourselfers, as long as they don`t take too much apart that ...
Concord gas furnace CG80UB150D20D3/4/2008
  Q: Install furnace in November. I notice burner cycling on/off. Works when bypassed. Original limit ...
  A: There`s no air shutters at the ends of the burners ?? Maybe not with combustion air regulated by the ...
Heater troubles3/4/2008
  Q: I am not sure of brand of heater...It has a diagnostic light on board that flashes three ...
  A: Wow,John, that`s a killer problem. Does the igniter ever light ?? I presume the LED code is still ...
Concord gas furnace CG80UB150D20D3/3/2008
  Q: Install furnace in November. I notice burner cycling on/off. Works when bypassed. Original limit ...
  A: Yo Edward,3.5 " water good. Those flames need more air if they are yellowish.You`re on natural gas, ...
Heater troubles3/3/2008
  Q: I am not sure of brand of heater...It has a diagnostic light on board that flashes three ...
  A: need to remove the hose & insure its not obstructed, nor the opening at the induced draft motor. ...
Comfortmaker high efficiency furnace problem3/1/2008
  Q: I have a 12yo Comfortmaker gas furnace model# NUG9075FGB1/GUM075N12A - For the past month, on ...
  A: In Texas we draw air from the attic into a sealed closet.The induced draft motor provides the air ...
Comfortmaker high efficiency furnace problem2/29/2008
  Q: I have a 12yo Comfortmaker gas furnace model# NUG9075FGB1/GUM075N12A - For the past month, on ...
  A: Test for gas leaks with a soap & water mix. Stir it up to make bubbles & wipe across the gas joints. ...
Installing Humidifier2/29/2008
  Q: I have a Trane Forced Air Furnace Model: GUCDA-10-A Type: 174-470-2-A I want to install the ...
  A: The air flow will only be from the high pressure supply side. So you can mount on the high side ...
Trane XE 902/28/2008
  Q: I have a 1995 Trane XE 90 Heat Pump. The diagnostic light blinks 2X, "System Lockout, No Flame, ...
  A: That is just turning the power plug around to reverse the polarity. No plug, will have to splice the ...
Installing Humidifier2/28/2008
  Q: I have a Trane Forced Air Furnace Model: GUCDA-10-A Type: 174-470-2-A I want to install the ...
  A: Black is hot, white is ground.Ground is anything that is grounded, so the case, or copper pipes are ...
Gas Forced Air Furnace2/27/2008
  Q: The furnace is an Armstrong Air Ultra V unit. The blower motor starts, but ignition does not ...
  A: Remove the tube between the induced draft motor & pressure switch. Blow thru it to test for ...
heater will not ignite2/26/2008
  Q: My York diamond try to ignite three times and then goes into lockout mode. The seven flashes of the ...
  A: Aha, you have an electric ignition for the pilot only,After sensing the pilot, the gas valve opens ...
Rheem Criterion II2/26/2008
  Q: My heater is of electronic ignition control.. When commanded on by thermostat, initial sparking ...
  A: There is a flame sensor that CAN cause that to happen, Richard. The sensor is usually a metal rod ...
American Standard Freedom 782/25/2008
  Q: Howard, I've got a American Standard Freedom 78 in my home that blows cold air from time to time, ...
  A: So you must have a variable speed blower ?? Assume the furnace is circuit board controlled also ?? ...
Tempstar condensing propane furnace2/25/2008
  Q: Late this past week I noticed sounds from our Tempstar furnace that sounded like the air from the ...
  A: Furnace problems can echo throughout the house! Open the door to access the blower & feel the blower ...
furnace filter2/25/2008
  Q: sorry if this is a stupid question but i recently moved into my new home and there is a heil ps80 ...
  A: There are no stupid question, only stupid answersKim. Normally, the filetr is behind the lower door ...
heater will not ignite2/24/2008
  Q: My York diamond try to ignite three times and then goes into lockout mode. The seven flashes of the ...
  A: Put on a coat, first.Does the igniter glow ?? Does this model light a pilot flame, then the burners ...
miller furnace2/24/2008
  Q: This is my mom's furnace. It is an '89 in a doublewide trailer. If properly working, I see it ...
  A: Pretty) sure I have seen this on trailers. As the "inferno: (I like that name) starts, it sucks the ...
Lennox heat pump2/23/2008
  Q: we had an issue with the a/c system not blowing cool air we called out a tech who said the system ...
  A: Adding freon means you have a leak somewhere. Favorite place is the evaporator coil. Need to sniff ...
Powered Humidifier wiring2/22/2008
  Q: How should my new powered humidifier be wired? My brother in law installed it for me. He ran a new ...
  A: Humidifier only runs when the blower is on. So if the board has an H terminal that ought to do it. ...
induced draft motor2/22/2008
  Q: i have a tempstar 90% furnace that wont run. its only 18 months old. the stat will call for heat ...
  A: Whoa ! not good, Tony. Typical electronics, acting up so soon.Those code LED flashes are usually ...
Maytag heat pumps2/21/2008
  Q: I am shopping around to replace my existing 15 year old lennox heat pump system. Most of the ...
  A: A salt water creek ?? Interesting. That explains the stainless steel.First thing, what`s wrong with ...
Furnace Draft Inducer Blower Replacement2/21/2008
  Q: I need to replace the blower, the wheel is wobbling and getting stuck. The gas-pak unit is a: Inter ...
  A: Hey George, Don`t think I have the answer either.I think the main thing to deal with is the shaft ...
Heater not blowing heat2/20/2008
  Q: I have a dual heat pump. The heating in the attic is working but the unit unit (big fan thingy) ...
  A: I`m sorta confused, Susan. I`ll quote you as " the heating in the attic is working..." & " the fan ...
TAPPAN FORCED AIR GAS FURNACE2/19/2008
  Q: I have a 30 year old Tappan Forced Air Gas Furnace (Model SGUF 140842 E-7 Series). It has a ...
  A: NOW your talking good when you said the flames are HUGE> Thats a very good tip that the regulator in ...
intake air vent2/18/2008
  Q: We have a big intake vent which is right next to our tv in our family room (basement of house.) It ...
  A: No,No. Find some thick, heavy shag carpeting. Glue a piece on the floor behind the grille. Find some ...
Am Std Freedom2/18/2008
  Q: read following question here...We have a Freedom 78 American Standard furnace in our 13 year old ...
  A: This is sorta a common problem.Has the LED trouble lights flashed? O r does your furnace have a led ...
Setting the thermostats2/17/2008
  Q: We are having trouble learning how to set the thermostats in our just built home (not programming, ...
  A: Start off by adding a LOT of ceiling fans.Particularly, one in the 2 story foyer.Then another in the ...
TAPPAN FORCED AIR GAS FURNACE2/15/2008
  Q: I have a 30 year old Tappan Forced Air Gas Furnace (Model SGUF 140842 E-7 Series). It has a ...
  A: Your question, Karen were the burners supposed to do that ? I said no. So now here is possibly your ...
Furnace2/14/2008
  Q: 8 yr. old Bryant heats to temp on stat and then cuts off. A qwik flip of the circut breaker restarts ...
  A: Could be a bunch of things.Was the circuit breaker tripped, or just reset?? There are several over ...
15 Year old WaterFurnace2/13/2008
  Q: I have a 15-year old WaterFurnace brand GeoThermal unit that has been diagnosed with a Freon leak ...
  A: Rush to the local a/c supply house & get a can of "leak sealer". That has hit the market about a ...
Lennox Propane Heater2/13/2008
  Q: I recently had a two-year old Lennox Direct-Vent propane heating unit replaced with a new one. The ...
  A: Yes, yes, yes you should be concerned with the soot.Not good. Those flames better be all blue, but a ...
Air purifier giving off a smell, may be motor2/10/2008
  Q: Testing your DC motor experience. I have just bought a second hand Sharp Plasmacluster air ...
  A: I`m not familiar with that kind purifier so I can only guess. My gues would be that thing was ...
HVAC Question2/10/2008
  Q: I'm loosing a ton of warm air generated by my HVAC system this winter because the only return ...
  A: A return air is sized so the airflow is about 400cfm/min across the grille(s). This ensure the ...
Lennox G60 error codes2/8/2008
  Q: I am having the same problem as Joanne is. Alternating LED's. It happens intermittently, maybe ...
  A: Didn`t check my answer to Joanne. I`ll just shoot you with what can be wrong with your furnace. It`s ...
Split system approaching its usefull life2/8/2008
  Q: I purchased a used house in S.W.Fla. 4 yrs ago.Came with a 1998 Lennox heat pump 13 seer 3.5 ton ...
  A: Sort of a common question. I have been an independent for 30 yrs, & a conservative type.So my ...
HVAC residential Compressor related2/7/2008
  Q: ... Generally speaking, if I had a symptom of a tripped 100 amp breaker, a burnt smell, how long do ...
  A: depending on the locked rotor amps of your compressor it could kick a 100 amp breaker. The locked ...
drain pan and drain pipe2/7/2008
  Q: I have 2 questions: #1 I have a Carrier Model # FX4ANF048 that was installed in late 2001. The ...
  A: You forgot what material the pan is ! I will presume it is plastic. Puron does not crack ...
Air Quality2/5/2008
  Q: We have an air quality problem I hope you can help me with. When our furnace clicks on we ...
  A: Thing of it is different people have different smell sensitivity. I have had bad experiences with ...
Furnace Control Board2/5/2008
  Q: Furnace Model # P1UKD12N0401A Problem is the ignitor stays lit all the time, only goes off when ...
  A: That`s a heck of a problem, Chuck. All of the problems seem to point to the board.It has the control ...
Gas furnace not blowing very hot air1/31/2008
  Q: I have a gas furnace (comfortmaker FBF050B12AA, serial # L002729897)that is 7 years old. When the ...
  A: I would check the duct system to see if they are OK. With all the burners working that amount of ...
hear pump1/30/2008
  Q: I have a Lennox heat pump that the compressor will kick off about every sixteen hours. I will have ...
  A: What you really need is a recording amp meter to follow what`s going on with the compressor (if ...
thermal fuse (or what)1/29/2008
  Q: I have a Trane Air Handler and need to replace some old, rusted fuses-took one out and it says ...
  A: I had the wrong fuse in mind.That`s a second fuse protecting against an overheat situation.Don`t ...
Emergency Heat Inoperative1/28/2008
  Q: Howard, I have a two and a half year old Carrier heat pump system with an electric emergency heat ...
  A: Wow, Chad that`s a good one !! Have to eliminate things one at a time to arrive at some kind of ...
noma 52-2570-6 thermostat1/26/2008
  Q: Good evening. I've never posted to this forum before but I thought I'd try... I just bought a ...
  A: You have a heat pump. Is the new one for a heat pump ?? I`m not familiar with that H designation. I ...
burners sometimes don't light on AS Freedom 781/25/2008
  Q: We have a Freedom 78 American Standard furnace in our 13 year old home. I assume it's the original. ...
  A: The blower works on a time delay only. Does the igniter glow each call for heat ?? If so, the flame ...
I think Heat pump?1/25/2008
  Q: I have a carrier model # 38Ycc. The problem has happe three or four times. The outside uit shuts off ...
  A: Could be several things, Mike. One is the point on the contactor are burned & not making contact. ...
Lennox G60 gas furnace will not maintain heat set on thermostat1/24/2008
  Q: I have a Lennox G60UH-070-02 (2002)gas furnace which has been fine until now. At night or when I ...
  A: Check the thermostat to be level. Check the heat anticipator behind the front to be set about at .4 ...
Thermostat1/24/2008
  Q: Should you set the heat and leave it alone or adjust it at night. This is a 2 story house. Upstair ...
  A: Typical problem for 2 story houses with 1 unit ! If all the bedrooms are upstairs I would turn off ...
Heating problem1/21/2008
  Q: We just moved in to a new house that has a fairly new Heil H9MPD heater. It seems to work fine when ...
  A: Need to run a test on the thermostat.Wonder if it is a mercury or digital ?? If mercury controlled, ...
RE: Tappan furnace wire question1/20/2008
  Q: Howard, I have a Tappan model 100-16, and the product literature that comes with it says that it ...
  A: There`s only about 50 rpm difference between adjacent speeds. Hi speeds for heating can produce ...
Help me build a ground source geothermal please!1/20/2008
  Q: I am looking for help with building a ground source geothermal this spring. I own a tractor and a ...
  A: Google it, Jessica. I have worked on them is all the experience I have. Most different thing is the ...
rheem criterion 2 gas furnace1/19/2008
  Q: My furnace fails to start, and I most of the time move the filters around to get it to start again. ...
  A: My wife used to call me at the office(1 hr away) that the washing machine flooded the place! Sounds ...
Bard Furnace1/18/2008
  Q: My furnace will shut down every 2 or 3 days? when I turn it on and off it cycles again for anothe 2 ...
  A: Tricky to find source of a problem like that. Start off reversing the power supply to the furnace. ...
Induction gas furnace1/18/2008
  Q: Furnace starts to turn on blower for 30 seconds but cuts off and flashes 6 times for trouble code. ...
  A: Bet that water has been sucked into the hose from the draft motor to the air pressure switch. Dry ...
Air Conditioning System1/17/2008
  Q: I'm getting ready to build a 2600 sq foot house. R-14 insulation in walls and R-49 in attic. Also ...
  A: I live in Texas & here 500sq ft/ton is a rule of thumb.I gather this is a 1 story house. If so, it ...
gas furnace location1/17/2008
  Q: mr. livingston i believe i have recieved some bad advice on the location of my gas furnace when i ...
  A: That flex ducting should have 3" of insulation on it for your location.That attic is as cold as the ...
replacing heat pump1/15/2008
  Q: We are about to replace our heat pump here in Columbus Ohio. There are some differences of opinion ...
  A: Charlie. I`ll ask you why are you replacing the system ?? Age ?? Still running OK after 10 years ?? ...
new unit vs dehumidifier1/14/2008
  Q: Howard, I was talking with Fred about my problem but he went on vacation. Would you be so kind as ...
  A: Holy cow, Ed what a discussion ! What a nasty problem.Can`t believe someone screwed up a 1 story ...
Heat pump1/13/2008
  Q: I have had a new heat pump and central air unit installed and I thought my gas furnace was only for ...
  A: That gas furnace is the secondary source of heat. The compressors supplies the first stage.Look at ...
Gaffers and Sattler Gas Furnace1/12/2008
  Q: I have a wonderful G&S Model CF100-1 gas furnace that has run great in my home for the last 30 ...
  A: I can still get parts for 50 + year old wall furnaces.True, that parts prices rise for old furnaces ...
Lennox 15CHPX1/12/2008
  Q: The unit (Lennox 15CHPX)was installed September, 2007. This is a split system. We've been dealing ...
  A: Something fishy here, Malou.You paid high dollar for that Lennox & it no work ?? Is that circuit ...
Burning smell coming out through heater vents1/11/2008
  Q: About two days ago, we noticed a burning/maybe gas coming out through our heater vents. The smell ...
  A: Furnace smells occur mostly on electric furnaces when something hits the elements when its on. If it ...
Gaffers and Sattler Gas Furnace1/11/2008
  Q: I have a wonderful G&S Model CF100-1 gas furnace that has run great in my home for the last 30 ...
  A: Don`t mess with it. Let `er run.Those parts like each other & a new part would screw up the ...
aircon fires1/11/2008
  Q: We have an window type airconditioner. A technician says that it has a compressor problem, i.e. ...
  A: There was a dead short in the wiring, maybe at the compressor, but maybe not.The compressor is a ...
Gas Furnace1/9/2008
  Q: My upstairs furnace is not burning correctly. Spitting out small flames when the gas company turned ...
  A: If the gas trouble persists for 20 to 30 min.the line would be purged. Now, when a gas line is ...
Trane XE 80 Furnace1/9/2008
  Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ...
  A: It is a normally open switch. Ohm it when the IDMotor starts up.Have some reports of the hose ...
Trane XE 80 Furnace1/8/2008
  Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ...
  A: With a good induced draft motor, the next event is the air pressure switch closing completing the ...
lennox elite series cb29m1/6/2008
  Q: Livingston, I have a lennox elite series air conditioner/heating system. The fire damper is closed ...
  A: Lennox builds strange stuff, Gayle.Complex electronics are the rule.Good stuff tho when the kinks ...
Trane XE 80 Furnace1/6/2008
  Q: "I have a Trane XE80 that is doing the following: When call for heat is sent nothing happens. The ...
  A: Has the induced draft motor ever run in the tests ?? Is that motor good ?? I would separate it & ...
Heater1/6/2008
  Q: I have a Honeywell thermostat set at 68 degrees. I wake up every morning and it shows the heat is ...
  A: How old is that stat, James ?? No doubt it uses a mercury bulb. Take the cover off & check the roll ...
continually running furnace1/5/2008
  Q: We have an older Steel City standing pilot gas furnace, the problem seems to be is that it is either ...
  A: I wouldn`t have changed the fan/limit length.The fan settings should be set at about on at 110 & ...
fan running continally1/4/2008
  Q: Forced air, natural gas 18+ years old, had limit switch replaced last year. Unit kicks on, burners ...
  A: That is a symptom of a stopped up evaporator coil. The dirt accumulations are on the lower side of ...
Ruud Achiever 90 Plus12/21/2007
  Q: We have a 9 year old Ruud Achiever 90 Plus Furnace. Starting toward the end of last winter, I began ...
  A: You are right on Casey, that is a malfunctioning air pressure switch. Need to remove the hose from ...
part numbers12/21/2007
  Q: I'm looking for a parts number manual for a Goodman GMH950703BXA gas furnace. I emailed Goodman to ...
  A: Sorry Richard, can`t offer any help.Don`t particularly like this company when years ago they had a ...
Furnace won't Ignite and blower is constant12/20/2007
  Q: I have a 20-25 yr old Bryant furnace which will not ignite and the blower/fan constantly runs. The ...
  A: Ignition problems caused by several problems. One is a gas pressure problem .The backfire can be ...
carrier gas furnace12/20/2007
  Q: Howard I've been working on a 90 model gas furnace with a spark igniter, 1st problem could not get ...
  A: With a fan/limit control with a manual knob to pull for on, push for off with the knob missing maybe ...
Furnace won't Ignite and blower is constant12/19/2007
  Q: I have a 20-25 yr old Bryant furnace which will not ignite and the blower/fan constantly runs. The ...
  A: (that`s what I was called many years ago)The blower is controlled by a relay on the circuit board on ...
Thermostat12/17/2007
  Q: Livingston I just replaced two thermostats with programmable thermostats. I have a combined ...
  A: Well, well, John, you have the cooling wire from the thermostat in contact with the heating wire. ...
electric heat12/17/2007
  Q: My father has been really ill so I hope you can help me for we don't have much money to call someone ...
  A: hate to see anyone getting ripped off. I can see he didn`t do any good.Moving wire s wouldn`t solve ...
ID fan & Circ Air blower won't stop12/17/2007
  Q: OK, the equipment is a 1999 Heil DC 90 condensing nat gas furnace with honeywell ST9120C4057 ...
  A: Wow, Dave, never saw anyone pulling so many wires ! ! I think if I did that I would NEVER get it ...
Adding a central humidifier to an AC only (no heat) system12/16/2007
  Q: We just bought a 1 1/2 story home in Maine with first floor only AC (no air heat) installed in 2001. ...
  A: Will not do too much good. You need to measure the humidity in the Winter & Google a psychometric ...
Returns12/16/2007
  Q: What is the concern in not having a return in a bedroom. We are on a forced air system?
  A: The return air path from the house back to the return air grille(s)needs to be just so long. that ...
GMP075-4 no power12/15/2007
  Q: I've got a Goodman GMP075-4 gas furnace that is not getting power. I replaced the ignitor because it ...
  A: The induced draft motor runs on 120 v as you found out. The quick test for low & hi power is to turn ...
Heat not working12/15/2007
  Q: When we returned home this evening we noted that the thermostat was set for 69 degrees yet it was 64 ...
  A: I`m gathering Dan, 2 different problems. When the burners have flames & then it shuts off the flame ...
Furnace fan won't turn off12/15/2007
  Q: I have a Lennox natural gas heater that is at least 35 years old and works great. I replaced the ...
  A: Was the low fan speed used for the heat speed ?? Usually, the red wire is used for that speed. If ...
carrier furnace/air conditioner 1 piece unit12/14/2007
  Q: i have a carrier air/furnace combo, sits outside. my problem; sometimes when i turn the unit on i ...
  A: Must be a gas unit since you "can hear it running" but no fan. Not possible for an electric furnace ...
Comfortmaker RPJII Furnance12/14/2007
  Q: Symptom: Occasionally and with increasing frequency the temperature in the house drops below the set ...
  A: to begin with #1: That`s an indication of thermostat failure. If it is a mercury controlled stat, ...
propane supply12/13/2007
  Q: My neighbors propane ran out and when it was refilled the furnace will not restart.Went by ...
  A: I have seen that happening a lot when I worked on mobile home furnaces. I found that when a tank is ...
Rheem a/c not working12/13/2007
  Q: I am a snow bird and am back in Florida. The a/c was not working when I got back although I had left ...
  A: Monica, A factor is how old & in what shape is the unit ?? Pretty clean unit?? Works good ?? ...
Rheem a/c not working12/12/2007
  Q: I am a snow bird and am back in Florida. The a/c was not working when I got back although I had left ...
  A: Lots of things can just happen to this stuff, Monica.First thing is to test the freon, then the ...
Heating Airconditioning Unit has ice on it12/11/2007
  Q: I discovered our unit has ice on the outside of it...what causes this?
  A: If that is a heat pump that is normal to collect ice on the outside unit. BUT, at some point when ...
Garage electricity will not go back on12/10/2007
  Q: Livingston, Some of my rooms on my first floor bi-level had a short (basically the electricity cut ...
  A: Just switching breakers doesn`t do any damage. Here`s the catch tho, the breaker switch can be in ...
Carrier/Night&Day Furnaces12/9/2007
  Q: I have five Night and Day Furnaces in my house. Two repeatedly blow their HBC controller and one ...
  A: When the 3 amp fuses blow that shows there is a short in the low voltage control circuits some ...
Vent Motor12/7/2007
  Q: I have a GDPI series furnace and the vent motor never shuts off. How do I fix it? Please help
  A: The notor runs from a call for heat thru the circuit board. If the thermostat is not calling for ...
Goodmam gmp100_4 will not continue to run12/6/2007
  Q: The heater will start up and ignite, burners will come on and run for a short time. I have replace ...
  A: its not vacuum, its pressure. Remove the hose between the induced draft motor & pressure switch & ...
cfms12/5/2007
  Q: Can you tell me how to calculate cfms in flex air duct for a new construction side job.Two story ...
  A: I have installed only 2 variable speed blowers. Had trouble with one. Had to adjust the switches to ...
Electrical Furnace12/4/2007
  Q: I have a Coleman Central Electric Furnace model number 3500A816, the problem when I call for the a/c ...
  A: The heat fan circuit goes thru the fan /limit to turn on the fan. Replacing that switch should have ...
cfms12/4/2007
  Q: Can you tell me how to calculate cfms in flex air duct for a new construction side job.Two story ...
  A: easy question a long answer.You need to go buy a "ductalator" at a local a/c supply house. It`s a ...
heating problem12/3/2007
  Q: mr. livingston, last friday my heating at home abruptly stopped working. i live in a condo with a ...
  A: Could be a failure of the gas valve. When calling for heat, test for 24 volts at the gas valve. If ...
Problem with Freedom 8012/3/2007
  Q: Hey Howard. I have a American Standard Freedom 80 model # AUD140C96051 serial # R261WWH2G and I'm ...
  A: That`s an interesting name. Sure would like to know the interpretation of the LED flashing 4 times. ...
Propane furnace burner problem.12/2/2007
  Q: I have a Tempstar propane furnace. The problem is only one out of the three burners are burning when ...
  A: Now that`s something you discovered Terry. Somebody never installed the complete conversion kit for ...
colmen gas furnace12/1/2007
  Q: my furnace went out.they replaced the contol board and it ran good for 5 days and quit again.I set ...
  A: I would remove the tube from the air pressure switch & see if its clean, then check the outlet & ...
Propane furnace burner problem.12/1/2007
  Q: I have a Tempstar propane furnace. The problem is only one out of the three burners are burning when ...
  A: Wow, Terry, that`s a good one ! Never have experienced that problem. If no gas is coming from 2 ...
rheem heat pump, humidifier install12/1/2007
  Q: I have a rheem heat pump, installing a honeywell 365 powered humidifier, humidifier plugs into 120v, ...
  A: First off, Norm I wouldn`t recommend a humidifier on a heat pump. Only gas furnaces produce hot ...
Heat11/30/2007
  Q: We just bought our home in Indianapolis it has a Trane XE 78 unit it keeps shutting the heat off but ...
  A: How much dust was on the filter ?? And, in the area around the blower ?? I`ll bet the previous owner ...
3 year old 3 ton 12 seer Ruud Heat Pump11/30/2007
  Q: 1. the intesnity of warmth is lacking- milk-toast heating- so runs a long time. I have an April Aire ...
  A: I hate to see folks ripped off. Happens too often in this business/ Ask your friends & neighbors who ...
furnace...11/29/2007
  Q: I have a 3 yr old modular house in Central NY. It is heated by a 3 yr old Thermopride fuel oil ...
  A: I live in Texas & we would freeze at 67 deg ! Heard that fuel oil price really increased this year. ...
Furnace air temperture11/29/2007
  Q: How warm should the air be that comes out of the registers
  A: Easy question, difficult answer Ken. The answer depends on the heat load or loss of heat from the ...
Gas Heater/AC Unit11/28/2007
  Q: The A/C portion of the unit works. However, the heat portion does not. When the unit engages, ...
  A: Does the spark light a pilot light or light the main burners?? Later models have a glowing ignitor ...
ruud 80 plus intermittent no heat11/26/2007
  Q: I have a 1989 ruud 80 plus unit, model # UGDE-14 ERAJS upflow furnace. I have an intermittent ...
  A: What you said needs clarifying. "the pre purge sequence starts, the draft inducer motor does not ...
airflow management11/26/2007
  Q: I have a 25+ yr old Freidrich central unit in a house I just bought. Sucker runs like a champ. The ...
  A: Take care of that Freidrich. Probably have another 8 yrs on it! These service guys see that & all ...
American Standard Freedom 9011/25/2007
  Q: My furnace is now flashing 3 times (pressure switch problem)per my service paper work. Is there ...
  A: Running late today Jim. Hope you haven`t froze yet. Need to remove the hose between the induced ...
Rudd Super Achiever 80 series11/25/2007
  Q: According to instructions on outside cover there is supposed to be a Honeywell on/off gas control. ...
  A: Problem with answering these questions, Virgil is not knowing the details of all these furnaces. So ...
gas furnace filling with water, tripping pressure switch11/25/2007
  Q: Howard, I have a Goodman GMN080-4 90% gas hot air furnace, about 15 years old. When it comes on, it ...
  A: Boy, Brian, we got a weird one !! Just another wild thought. You have a humidifier on this furnace ...
gas furnace filling with water, tripping pressure switch11/24/2007
  Q: Howard, I have a Goodman GMN080-4 90% gas hot air furnace, about 15 years old. When it comes on, it ...
  A: Better stop that water quickly,Brian. Rust out the heat exchanger. That isn`t condensate but can`t ...
American Genaeral Freedom 78 furnace11/24/2007
  Q: Furnace heats the house properly ,however ,turns off and on all night and day without stop time in ...
  A: Usually, on a complaint like that Ken, you are "hearing" the fan noise short cycling, not the ...
breaker11/23/2007
  Q: I have a six year old house. A/c cools great and so does heating. But when i use heater, after ...
  A: Yea, Mike like last night at 3AM at 35 deg & snow!I live in Arlington. You must have electric heat ...
Carrier combo unit11/22/2007
  Q: Have a 15 year old Carrier combo unit. Last year tech replaced gas valve with new Honeywell unit. ...
  A: After you bled the air out & you had heat it usually will not have any more air in the lines from my ...
fuse keep blowing11/21/2007
  Q: when i turn my unit on it runs for about 5 Min then the fuse on the inside the air handler on the ...
  A: There is a short in the low voltage circuit. If you were trying to run the cooling, check the 24v ...
Heat unbearable upstairs in WINTER!!!11/20/2007
  Q: We recently bought house w/Lennox A/C-Heat Pump. Our master bedroom is upstairs over the garage. ...
  A: Can`t stop the physics law that hot air rises.Cold air sinks.I would close completely off all the ...
Is there a filter on a gas Armstrong 38HWC182-5A furnace/air conditioner?11/19/2007
  Q: .. I have moved into an apartment (first one in 35 years), and it is REALLY dusty. I have opened ...
  A: Sometimes there was no place provided for a filter in the furnace. It needs a place that can seal ...
Intake Vent11/19/2007
  Q: In the colder months, the first floor of our house seems to get cold as if there is a draft. I ...
  A: Hey Paul, Are there foundation vents around your house that allow cold air under the house ?? Air ...
goodman gas pack problem11/18/2007
  Q: I AM HAVING TROUBLE WITH A GOODMAN MODEL PGO-60150-1AB-REV E GAS PACK. AT FIRST IT WOULD NOT ...
  A: Boy, that is a crazy problem. I can think of several things to check out but they are just ...
TRAIN XE 1200 model TTP060C100A111/17/2007
  Q: What are some possible reasons that the outside compressor makes a loud humming noise when the heat ...
  A: Is this unit a heat pump, Yale?? Main thing that can hum in the outside unit is the coil in the ...
Cozy Floor Furnace11/17/2007
  Q: I have an older Cozy floor furnace. The pilot light is lit but I could not get the heater to kick ...
  A: Wow, Brad, you must feel like a mole! I am thinking the problem may be "resistance" Maybe in the ...
Diamond 80 P3HUA12N06401c Furnace no heat11/17/2007
  Q: I have a Diamond 80 P3HUA12N06401c, when the unit calls for heat the main blower is coming on, not ...
  A: I`m not acquainted with any particular control boards.The induced draft motor starts first on call ...
Central Heating and Air Unit11/16/2007
  Q: Yesterday my C/ h&a unit seemed to be working fine, minus the fact that my air unit quit blowing ...
  A: Cooling first: Wonder if the coil has a freon leak to cause the guy to say you need a new one.Now ...
HEAT PUMP11/16/2007
  Q: I HAVE A NORDYNE SPLIT SYSTEM HEAT PUMP #F3TBA 030KA WITH HEATER KIT B3BM 030K AB. MY SON PUT ON A ...
  A: The new thermostat is for a heaT Pump ??? Sorry, can not provide info to connect the wires since ...
pressure swithc11/14/2007
  Q: i have a question about a Rheem 90 imperail furnace.the heat doesnt appear to be working correctly. ...
  A: Are you referring to the round pressure switch that has a hose from the induced draft motor ...
Central A/C not responding11/13/2007
  Q: Our A/C is not responding when we turn it on. The outside fan unit does not start. There is no sound ...
  A: Does the inside fan run when calling for cool ?? Locate the contactor rely in the outside unit & ...
heating flow11/13/2007
  Q: my girl friend has lived in the double wide trailer for a year now and she has had this problem for ...
  A: Double wides have an interconnecting duct between the 2 sides. Does the cold air come from the same ...
American Standard furnace11/12/2007
  Q: My blower motor on my furnace (model lgf120e100 will not stop running after the house has reached ...
  A: The length of the probe inside the furnace needs to be matched. Then, does your fan control also ...
flame sensor11/12/2007
  Q: For the umpteen year my Weatherking gas furnace turns on and the ignitor heats up and starts the ...
  A: The sensor is the small rod sticking into the flame on the burner. Kill the power,remove the 2 wires ...
convert gas pack to heat pump11/11/2007
  Q: I live in Raleigh NC. I want to covert my 3 ton gas pack to a 3 ton heat pump. Is this possible ...
  A: Can`t convert, Mike. Too much to change.The lowest SEER is now 13. That`s good enough. Don`t get ...
American Standard furnace11/11/2007
  Q: My blower motor on my furnace (model lgf120e100 will not stop running after the house has reached ...
  A: I am assuming you have the standing pilot type furnace ?? Doesn`t that dial have other temperature ...
Main fan problem11/11/2007
  Q: Carrier model #58SX100-cc-1 circa 1987. When call for heat is made inducer fan works, furnace lights ...
  A: The fan circuit is different for heat & cool modes as are the fan speeds. Usually, the heat fan ...
Propane AC11/10/2007
  Q: Howard, Do you know of anyone that makes a propane AC unit? I am fortunate enough to have free ...
  A: Well, hello lucky.I`m paying $2.38/gal !!There used to be gas powered unit made by Arkla Servel that ...
PROPANE FURNACE11/10/2007
  Q: OUR HEIL 7000 FURNACE LIGHTS NORMALLY BUT WILL BACKFIRE UP THE BURNER JET OCCASIONALLY. IT SEEMS TO ...
  A: Tricky problem. I would test the incoming gas pressure to confirm it`s OK. Is the gas valve fully on ...
trouble starting new York gas furnace11/10/2007
  Q: Just installed a York gas furnace 120,000 btu's 90% downflow unit GY9S-DH. Can't get it to start. ...
  A: How frustrating !!! Test the induced draft motor & air pressure by removing the hose from the draft ...
lennox gas furnace11/9/2007
  Q: my furnace stays on for a few days then goes off again. i clicked the reset switch and it would ...
  A: You need to move to Texas. It`s 80 down here. I`m sorry but you didn`t supply enough info to help ...
janitrol gmn100-4 furnace circuit board blinks11/8/2007
  Q: Just installed new circuit board, igniter not turning on (glowing)which was installed a year ago, ...
  A: Wow, Diane we got to get you some heat, FAST. But sorry, I don`t have the blink codes for your ...
Attic humidity11/7/2007
  Q: I just recently had an thermostatically operated attic fan installed. I was advised afterwards that ...
  A: You don`t want to remove moisture in the Winter, you want to add humidity. The heat dries out the ...
Rheem furnace 1x200011/6/2007
  Q: My Rheem furnaces will trip out periodically and I have to reset one or more of the limit switches ...
  A: Now that`s an interesting name! Have you removed the flame sensor & drag over it with a rag ?? If ...
Induced draft blower cycling on and off11/6/2007
  Q: I have a 13 year old high efficiency natural gas furnace. I'm having no heating problems with it ...
  A: That motor turns on with a call for heat only.Sounds like there may be a short across the red & ...
Heat Pump fan operation11/5/2007
  Q: My fan works properly when the thermostat calls for heat, but it doesn't always stop when the ...
  A: A heat pump blower operates at only high speed. heat or cool. That fan is energized by a time delay ...
Heating balance.11/5/2007
  Q: I have recently moved into a newly built 2 story home. I have the HVAC unit on, at this time, to ...
  A: Hot air rises, cold air falls. 2 story house have an open stairway that allows that to happen in ...
no light from my smartvalve11/4/2007
  Q: I have a concord 80 plus gas furnace. I had a severe power spike in the neighborhood and the furnace ...
  A: Does the inside fan run when the fan switch on the thermostat is turned ON ??? The fuse on the ...
gas furnace11/3/2007
  Q: Maybe you can help me. I have a vented floor furnace. It is a Cozy brand. Model number 90P50A. I ...
  A: Insure the pilot flame is striking the top 1/2" or more of the thermocouple. Did you hold down the ...
Furnance11/2/2007
  Q: Sir: I have a new nat. gas fired furnance in my attic. It takes from 5-8 mins for the blower to come ...
  A: Gas lines for furnaces up to about 100,000 btu use 1/2" lines. 3/4" above that.The circuit board ...
Burnt electronics smell coming from my registers11/2/2007
  Q: I have a "burnt electronics/electrical" smell coming from my registers when using the heat. This ...
  A: Wow, Eric that`s a lot of amps for the blower motor!!That`s gotta be the cause of the smell but the ...
Wood Stove11/1/2007
  Q: No basement just a crawlspace. I run my propane forced air furnace blower on low 24/7 with my ...
  A: Not sure what the problem would be but if you could just install a flex duct from the ceiling of the ...
Furnace control problem11/1/2007
  Q: Howard, I've been having problems with my gas furnace the past few days. Furnace is American ...
  A: Think the place to start is with the "check line polarity" Turn off the power supply & reverse the ...
American Standard Trane furnace problem10/31/2007
  Q: My gas forced air furnace is not lighting. The fan blows cold, but that's it...it doesn't attempt to ...
  A: Well, that`s a first John, to get a photo of the furnace!!The 4 blinks for an open switch would be a ...
Gas Furnace10/31/2007
  Q: I got the pilot light lit and it stays on. When I first lit the pilot light the burners started as ...
  A: Is the gas valve on the gas line all the way on Bryan ??? How about the knob on the gas valve?? ...
white powder coming out of vents when ac unit on10/31/2007
  Q: I have white powder in my apartment when I run my ac unit. It is a very fine powder that covers ...
  A: The place you can find powder is inside the heat exchanger of the furnace.That`s a natural ...
blower fan for air circulation does not work10/30/2007
  Q: Blower fan for air circulation does not come on in auto or manual. I opened the door to the fan and ...
  A: Follow the 2 brown wires from the fan to the run capacitor. Need a volt-ohm meter to test it. If ...
centtral issue follow up button not working10/30/2007
  Q: Subject Central air/heat issues new installation Question Howard. My parents recently decided ...
  A: Well, Gregory what a deal !!! A 110,000btu furnace would have the cfm capacity for the size house. ...
Heil furnace blows cold air, SOMETIMES!!10/29/2007
  Q: Well if anyone can answer this then you did better then the contractor I had come over!! I have a ...
  A: The induced draft motor that starts the cycle has to blow enough air to close an air pressure ...
Ameristar Furnace10/29/2007
  Q: Can you tell me where to find information on a 2005 Ameristar Furnace? I just had the unit cleaned. ...
  A: By all means call the guy back.American Standard makes that furnace. Can`t find any info on it on ...
two stage furnace, one stage thermostat10/28/2007
  Q: I just bought a two stage furnace, how do I jumper the control board to still use my standard ...
  A: I presume your gas valve has high & low output of heat on the one gas valve ?? Or does it have a W1 ...
honeywell rth230b10/28/2007
  Q: I bought this house and when the temperature is really cold in the house, my Honeywell still reads ...
  A: Put an accurate thermometer on the thermostat for a good read of temperature. Take off the cover & ...
CLEARANCES FOR GAS FIRED HEATERS10/28/2007
  Q: I am rehabilitating an apartment complex in NJ. I am retro fitting each unit to have its own heating ...
  A: These high efficiency furnace nowadays are pretty small, about 42"high X 17" wide, about 28" deep, ...
gas furnance10/27/2007
  Q: I have a brand new gas furnace (KeepRite C8PN100F14B). It works well for a few days after it is ...
  A: Have you checked the blinking of the LED on the circuit board ?? It can diagnose the problem for ...
Central AC Fan Motor running at 1/2 speed or less10/26/2007
  Q: We have a 3 ton central unit in our home that is only a few years old. Its gotten kinda cold the ...
  A: Electric furnaces use 240 v power. One leg on the fan motor bad runs the motor on 120v at half ...
Frost on condenser pipes.10/26/2007
  Q: Howard, I live in dallas and have a Amana heat pump (AC & Heat), just today I noticed that my ...
  A: Could be several things wrong. Could be the defrost cycle was operating erroneously. You could the ...
Central air/heat issues new installation10/26/2007
  Q: Howard. My parents recently decided to get central a/c. They had their old heater and all duct work ...
  A: Wow, I hate to hear a story like that,Greg! Those high ceilings need a lot of airflow to circulate ...
replacing...10/25/2007
  Q: I am replacing the a/c heating system in my home in washington dc. the question i have is as ...
  A: Carrier repair parts are pretty darn expensive as is the equipment. The variable blower is an ...
HVAC Brands10/25/2007
  Q: What can you tell me about the Goodman brand? What brand would you recommend as a replacement unit?
  A: Goodman changed the brand name from Janitrol to Goodman. Maybe the reason was we used to call it ...
Question about home A/C10/24/2007
  Q: Problem: A/C starts cooling but quits. Have noticed that fan on outside unit starts but stops after ...
  A: Did the tech check the fan motor run capacitor ?? It could be just a $10 or less capacitor. If it ...
janitrol gmp100-310/24/2007
  Q: My furnace will come on the hot surface ignitor will light and the gas will come on there are 4 ...
  A: Sounds like the flame runner is clogged, or even the orifice on the flashing burner is clogged too. ...
Forced AIr Furnace "Gibson"10/24/2007
  Q: I had a new (Gibson)forced air furnace installed professional two months ago. It is a 90k BTU w/ a ...
  A: Insulate, insulate, Dave. Can to use duct insulation which is black & really fuzzy on one side, or ...
Heat Blower not comming on.10/23/2007
  Q: Well I went to turn on the heat on my 3 ton HVAC for the first time last night and nothing. The ...
  A: The blower has 2 speeds, one for heat, high speed for cool. The heat speed is controlled thru a ...
Furnace only buzzes when turned on10/23/2007
  Q: I recently bought a fixed up home with an upgraded brand new gas furnace and hot water heater. The ...
  A: Easy way to test for power, Anthony, is to turn on the fan switch only. That proves low & high ...
Heating Problem10/22/2007
  Q: This morning it was a little bit cold in my house so I decided to turn on my central electric ...
  A: During the Summer cooling season dust is bypassing your filter & hanging on the heat elements. Then ...
re:tenant tampering with air conditioner10/20/2007
  Q: I rent out my basement which contains the furnace/electrical box. I think my tenant is tampering ...
  A: Well, Kelly I could say evict the tenants & you`ll find out !Naw, just kidding. The tenants could ...
Mobile Home Furnace10/19/2007
  Q: I have a Intertherm propane fired furnace. It is about 8 years old and in very good condition. The ...
  A: Sounds like you have a mobile home model furnace, Jason ?? If that is correct I am unsure that an ...
Amana furnace10/18/2007
  Q: We moved into a house with an Amana Air Command furnace that we think was installed in 1974 or 95. ...
  A: The filters are somewhere in the return air, Carolyn.Start off looking at the base of the furnace ...
heatpump10/18/2007
  Q: What is proper way to hook up hoses on heatpump in both heating and cooling modes? Which is best way ...
  A: I presume your talking about the liquid & suction line, Chad.Those lines connect to the evaporator ...
AC won't stay on...10/18/2007
  Q: Our Bryant air conditioner blew it's capacitor (run/start). The repair guy replaced the capacitor, ...
  A: Sounds like you have a heat pump having an outside sensor.Either way I would run a test at the ...
Hardwiring Air Purifier to HVAC10/9/2007
  Q: I'm installing a UV air purifier in the return plenum of an Gas forced air heating system. The ...
  A: You could supply the power with a relay that has a single, normally open switch & a 24 volt ...
airflow/black furnace filter10/9/2007
  Q: I had a new Gibson electric furnace installed three months ago. It was adapted to my air ...
  A: that`s a good question.If your furnace is in a closet sitting on the return air plenum I would ...
Warm Basement??10/8/2007
  Q: Howard, My basement has been noticeably warmer than the main floor this summer. It use to be the ...
  A: There was one more thing that it could be. But only if you have an electric furnace down there. It ...
Heating not working on central ac unit10/7/2007
  Q: This morining the heat was turned on (and it worked) then it turned off automatically; but it did ...
  A: The inside fan works by a time delay, not by heat or the "on" switch.You must have a circuit board ...
Forced Air Heater Pilot Won't Ignite10/6/2007
  Q: When the thermostat asks for heat, the draft fan starts, the pilot light igniter starts arcing, but ...
  A: Sounds like Mark that the pilot orifice is stopped up.Common problem. Maybe run a test by holding a ...
circuit board short10/6/2007
  Q: "i have a bryant model AC1CN036B that was installed in 1995. my dog bit thru and broke thermostat ...
  A: If your unit is NOT a heat pump there was only 2 wires on the outside the dog broke. If those 2 ...
furnace not lighting in heat mode10/5/2007
  Q: The ignitor comes on, then after a few seconds it goes out and the blower comes on but the burner ...
  A: The blower is on a timed circuit so that`s OK.Doesn`t sound like the pilot comes on either. The ...
outside ac unit10/4/2007
  Q: I have noticed my outside unit runs continually. There is also ice on the outside of the unit. Can ...
  A: You need another contactor in the outside unit. The points are burned & are sticking closed. Your ...
HEIL DC90 not lighting10/3/2007
  Q: I have a HEIL DC90 gas furnace that has stopped lighting. It is about 9 years old. The small blower ...
  A: Good description of your problem. Thanks. Sounds like the pilot flame is not being proved by a ...
Heating - Furnace10/3/2007
  Q: We have a Rheem Classic 90 high efficiency furnace installed in a garage to heat a garage apartment. ...
  A: Most of the limit switches have a little button that pops out when tripped. If so, just push the ...
fried equipment10/2/2007
  Q: i recently replaced a tranformer on the indoor unit of a split system, aparently an electrician ...
  A: Holy cow, Richard !! What a mistake.Could be the contactor coil in the outside unit was fried ...
How to light furnace10/1/2007
  Q: Howard, I have a nineteen year old Lennox furnace. Am confused as to how to light it, although I ...
  A: The only other kind of pilot control I have ever seen has a separate valve for the pilot.Follow the ...
Furnace turns off too soon10/1/2007
  Q: our furnace turns itself off way before it has reached the desired room temperature. Furnace and ...
  A: A 3 yrs old furnace is controlled by a circuit board. Some boards have little dip switches that can ...
Transformer Brunt9/29/2007
  Q: I have a Rheem model RBHA 17J10SFAA furnace and heat pump. Yesterday the thermostat screen went ...
  A: A short in the low voltage power somewhere.Could be the coil on the contactor in the outside unit. ...
condensation pump safety switch9/29/2007
  Q: The compressor would not come but every thing else worked, went out to the compressor to see if the ...
  A: The condensate pump wiring is simple. There are 2- 24v wires to the condensing unit, usually a red & ...
Poor Dehumidification with Old Furnace9/28/2007
  Q: Howard - I have a Lenox G14 Pulse furnace with a multi-speed blower. Added a new Lenox 2 speed AC, ...
  A: This a heat pump ?? They run heat & cool at high speed blower. Were the coils replaced when you got ...
central air and heat unit maintenance - coils9/27/2007
  Q: I live in an apartment and it looks like the coils in my system (inside the apartment) are in pretty ...
  A: Christie, that is the typical rental unit coil you described! It`s all because tenants NEVER change ...
return air9/27/2007
  Q: Howard, I just relocated your answer to me about return in ceiling, but had already posted another ...
  A: Well, you are a sharp lady, Paula. Always happy to help you. I gave away a lot of time over the ...
Furnace upgrades9/26/2007
  Q: I have an older (1980) electric furnace/heat pump system with a single-speed blower and noise from ...
  A: Heat pump inside fans need to run on high speed for both heat & cool.That`s what you have.Best thing ...
return air9/26/2007
  Q: Howard, I just relocated your answer to me about return in ceiling, but had already posted another ...
  A: Now I recall your problem, Paula! That`s goooood info you sent. I live in Arlington, by the way.Did ...
Help! Need a new a/c unit9/26/2007
  Q: Howard. It's 4:30am and I haven't slept all nite worrying about this. I'm in your neck of the ...
  A: Van. R22 will be phased out in the next few years. The wholesale price has already tripled! BUT, ...
Help! Need a new a/c unit9/25/2007
  Q: Howard. It's 4:30am and I haven't slept all nite worrying about this. I'm in your neck of the ...
  A: Wow, Van, what a night !! I would stay away from Puron (R410) It`s pretty expensive stuff & higher ...
air handler9/24/2007
  Q: i have a old carrier air handler 230 volt and changed the old t-stat out ive been doing this for 15 ...
  A: Is there a separate fan/limit switch mounted on the furnace ?? If so, there is a knob on the front ...
Coil and refrigerant lines freezing up9/24/2007
  Q: I have had 4 service calls recently because the coil and refrig lines freeze up. They have tested ...
  A: Well, well Jamie lets see how many ways can cause these things to make ice! You have a tricky one ...
airconditioner9/23/2007
  Q: I had my two year old 3 ton 13 seer airconditioner fixed ,it had a small leak and now it is not ...
  A: With 92 ambient temp the suction line should Chilly & even sweating. Did he fix the leak ?? Was it ...
Float switch reset?9/22/2007
  Q: My attic-mounted air handler/evaporator has a switched condensate trap. At the suggestion of the ...
  A: Never heard of a reset switch on a condensate pump.There, usually, is just a microswitch tripped by ...
HVAC not working9/21/2007
  Q: I came home yesterday to find my a/c not running. I've checked the circuit breaker and confirmed ...
  A: If no inside fan runs when fan switch is turned on test for 110 volts thru the wall switch or ...
HEIL 90 propane furnace, doesn't ignite9/21/2007
  Q: I have a HEIL DC90 furnace, and just got the propane tank filled, but the furnace won't ignite. The ...
  A: All that is controlled by a circuit board Ken.Got to have a pilot light first to light the main ...
a/c unit9/19/2007
  Q: I am have an air conditioner unit that is not blowing through the vents in the house, the outside ...
  A: Yo Cindy,How about a collapsed duct?? Or a blower motor not running at rated speed?? Or an ...
older home hvac9/19/2007
  Q: I would like to know if I can replace my air handler with a smaller unit or get rid of it entirely. ...
  A: If you have lots of money you could rip out all that stuff & install 1 or 2 or more( 1 per floor) ...
Hvac Coils9/17/2007
  Q: Said i had to also clean the evaporator coils.Seeing how the coils is hard to get to he said about ...
  A: Yes, Brad. The hot air from the furnace also flows thru the evaporator coils. That`s way too much to ...
Heat pump problem9/16/2007
  Q: When I switched the thermostat from cool to heat, it made a clicking sound and then never came on. ...
  A: Dead short somewhere.With the breaker reset, turn on the fan only(no heat) at the thermostat. If the ...
Humidifier9/14/2007
  Q: A recent HVAC Rep suggested I install a humidifier as part of a new system (both furnace & A/C). I ...
  A: Somewhat, John. Heat always dries out the air. Humidifiers will help some. If your family has dry ...
heat......9/13/2007
  Q: I have a modular home in Northern Ind. where it gets to 0deg. in the winter( a summer home) Can you ...
  A: Modular houses are not known to be well insulated.You never know how much insulation is in the floor ...
c/a9/13/2007
  Q: The fan on my Bryant High eff. furnace won't turn on, on the heat cycle, but it works for the ...
  A: The fan for heat is controlled by a time delay on the furnace circuit board. Actuated after flame is ...
Electrostatic filters on HVAC9/12/2007
  Q: I have a Rheem AC that recently failed (6 months out of 5 year warrenty, figures) and I am getting ...
  A: Have to define "electrostatic" filters, Joe. Does this filter have wires connected to it ?? If not, ...
panel to furnace wiring for air handler9/11/2007
  Q: I just had a heat pump and air handler/electric furnace installed. I noticed that the furnace has a ...
  A: Those breakers are, most likely just disconnects, Joel. 60 amps for 3 - 5kw heat elements, 20 for ...
Compressor Not Turnig Off9/10/2007
  Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ...
  A: The points are still not making contact after the cleaning. What you said indicates the thermostat ...
High pitched noise from coolant line9/9/2007
  Q: I have 2 questions for you: 1) We have an ac unit in the attic and the coolant line runs from the ...
  A: You must be about ready for the funny farm with all those irritating noises ?? Noise #1: Usually, ...
airflow9/9/2007
  Q: the air from the vents is cool but the air is barley coming out had the t-stat replaced a month ago ...
  A: I presume the air flow has been good in the past ?? That is, this lack of flow is a change ?? Lack ...
New Puron system, not enough air, bad service and design9/8/2007
  Q: Need advice/info: I hired a well-known HVAC company to install central air in my oceanfront, ...
  A: How many tons cooling was that, Robin?? How many sq. ft. is your house.2 story ?? Big attic ?? High ...
THERMOSTAT WILL NOT COME ON9/8/2007
  Q: MY THERMOSTAT WILL NOT COME ON AT FIRST IT WAS SET 90 DEGREES AND WE COULD GET TO TURN DOWN OR UP. ...
  A: Now that`s an interesting name, Eboni! Does the inside fan run when the switch is turned on at the ...
Compressor Not Turnig Off9/8/2007
  Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ...
  A: Those are pretty standard Mike. Go to a local a/c supply house & get a 30amp, 2 pole, 24 volt coil ...
moved thermostat - HVAC won't work9/7/2007
  Q: I'm remodeling and cut the thermostat wire to move the thermostat. I reconnected the thermostat ...
  A: Is that a digital thermostat that would have both common & hot wires from the transformer ?? That`s ...
Dual wall-mount A/C thermostat9/6/2007
  Q: I have a radio building with dual 3-ton Bard wall-mount air conditioners. This is a 200SF building ...
  A: Wow, 6 tons for 200 sq. ft. !!! You could use it for a meat locker too. Each one of those units has ...
Compressor Not Turnig Off9/6/2007
  Q: I noticed a warmer than normal temperature in my house one day this week, so I went outside to check ...
  A: A common problem,Mike! The contactor in the outside unit has burned points & is stuck in the closed ...
Follow up9/4/2007
  Q: This is a follow-up from my previous question (below). The fix is a little above me, so we called ...
  A: Sorry I`m late Joe. Have been in the hospital for a overnight stay. That`s too much for a circuit ...
Blower fan problem9/4/2007
  Q: Howard. I have a blower fan problem. Originally I thought it was control board problem. Therefore, I ...
  A: Well done description of your problem, Bill. As I follow the description it seems like your ...
Inside Unit Freezing Up9/3/2007
  Q: "Hi, we recently started having problems with our inside evaporator coils freezing up and not ...
  A: Freezing is caused by a low amount of freon OR a dirty air filter.Weak suction valves in the ...
goodman heat pump9/2/2007
  Q: I have a goodman package heat pump and homneywell pro 3000 thermostat. I need help with the wiring. ...
  A: White should be on w1, your heat pump primary heat.I`m not familiar with that stat nor did you say ...
Thermal shutdown problem9/1/2007
  Q: I have a Amana 14 seer RCE, about 2 years new. In a nutshell, the problem is that the cooling fan ...
  A: After knowing that the motor run capacitor is OK (changing or testing) if the motor fails its the ...
AC Blower will not turn off8/30/2007
  Q: I have a gas furnace, with an AC unit outside the house. We have two separate thermostats, one ...
  A: Yo Joe, stuck fan relay. Sounds like the relay is a separate relay?? (Rather than having a solid ...
AC/ Coil identification8/30/2007
  Q: I have a carrier split system and have been told the inside and outside units don't match in size. ...
  A: How in the world did that happen, Jerry ?? That`s a 5 ton(060)inside & 3(036)outside!That evaporator ...
old air conditioner, odor8/30/2007
  Q: At some point the original owner of our circa 1929 house installed in-wall air conditioning units in ...
  A: Need a little cleaning, Meghan, Best way is to pull the innerds that may just slide out of the case ...
Air Cond. Compressor not Running8/29/2007
  Q: My Goodman A/C Compressor stopped running. Model CK24-1B Serial 951002322B. Furnace & Thermostat ...
  A: Does it trip the breakers to the outside unit when trying to start ?? But since nothing runs I would ...