Security & Fire Protection Systems/smoke detector in pump station wet well


Have found current smoke detectors are not rated for than 95% H. We have started to have false alarms due to high moisture. Is there a compensated detector on the market for high humidity and classified for hazardous location

No smoke detector should be used in this kind of environment, unless you go with a beam type detector.  Any areas involving high humidity strikes me as better suited for heat type detectors.  You have a number of options.  You can go with a rate-of-rise/fixed temperature unit that is environmentally sealed (like those manufactured by Fire Detection Devices), or go with linear heat detector cable that's manufactured by Protecto-wire.