We get OID out of sequence. Set [OID]Reset=1 after adding a tag.
Can you help us find clarity ?

Answer
Check Rules for using Parameters:

1.Parameters set in the CITECT.INI file take precedence over parameters set in the project database.

2.If you set (or change) parameters in the project database, you must re-compile the project before the parameter settings are used.

3.If you set (or change) parameters in the CITECT.INI file, you must restart CitectHMI/SCADA before the parameter settings are used.

4.Parameters set in the database are local to the specific Citect project.  Parameters set in the CITECT.INI file apply to all CitectHMI/SCADA projects (if you are using multiple CitectHMI/SCADA systems).